PROFIBUS PA Date 09/19/00, Page 1 PROFIBUS PA s PROFIBUS PA = PROFIBUS for P rocess A utomation PA is based on the DP and DP Extended protocol DP Master Class 1 controls both DP AND PA field devices Definitions for DP protocol also valid for PA: Parameterization Configuration Cyclic data exchange Diagnostic ...
18
Embed
PROFIBUS PA Date 09/19/00, Page 1 PROFIBUS PA s PROFIBUS PA = PROFIBUS for Process Automation PA is based on the DP and DP Extended protocol DP Master.
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
PROFIBUS PADate 09/19/00, Page 1
PROFIBUS PA
s
PROFIBUS PA = PROFIBUS for Process Automation
PA is based on the DP and DP Extended protocol
DP Master Class 1 controls both DP AND PA field devices
Definitions for DP protocol also valid for PA:
Parameterization
Configuration
Cyclic data exchange
Diagnostic
...
PROFIBUS PADate 09/19/00, Page 2
PROFIBUS PA
s
Physical Setup
Physical layer based on IEC 1158-2
Synchronous data transfer with Manchester coding
Power AND data are transferred via the same wire
Different components for the physical setup (cable, connectors, termination…)
Rules regarding topology and length according to IEC 1158-2
P: 16 Bit PreampleSD: Start DelimiterLE: Net Data Length (DU) + DA, SA , FC, DSAP, SSAPLEr: Length repeatedDA: Destination Address (Where the message goes to)SA: Source Address (Where the message comes from)FC: Function Code ( FC=Type & Priority of Message)DU: Data Unit (Up to 246 Bytes including 2 Bytes for SAP’s)FCS: Frame Checking SequenceCRC: 16 Bit Cyclic Redundancy CheckED: End DelimiterEOF: End Of Frame
SD LE LEr SD DA SA FC DU.. FCS ED
SD LE LEr SD DA SA FC DU.. CRC EOFP SOF
PROFIBUS PADate 09/19/00, Page 5
PROFIBUS PA
s
Character Format
10 0 1 0 0 1 1 0 0 1 1 0 0 0 1 0
Clock
Binary
NRZ(PROFIBUS)
„1“
„0“ 0
0
+
Manchester Bitphase L
(PROFIBUS-PA)
„1“
„0“ 0
0
-
+-
+
0
PROFIBUS PADate 09/19/00, Page 6
PROFIBUS PA
s
PROFIBUSup to 12Mbaud
24 V 24 V
PA Link PA Link
PACoupler
PACoupler
Network Addressing
PROFIBUS45.45kbaud
PROFIBUS PA 31.25kbaud
24 V 24 V
1
2
2
1
PACoupler
3 4 343
11PA
Coupler
XXXX
3
PROFIBUS PADate 09/19/00, Page 7
PROFIBUS PA
s
Network Topology
PROFIBUS
T Branch
(Main) Line
Star
PROFIBUS PA
24 V
Termination
Spur Line
PROFIBUS PADate 09/19/00, Page 8
PROFIBUS PA
s
Network Topology (continued)
+-
PROFIBUS PADate 09/19/00, Page 9
PROFIBUS PA
s
Network Setup - Rules (continued)
24 V
PACoupler
Up to 31 PA field devices can be
connected to ONE coupler
PROFIBUS PADate 09/19/00, Page 10
PROFIBUS PA
s
Network Setup - Rules
= PA Link = PA Coupler
Up to 5 couplers can be used with one link
PROFIBUS PADate 09/19/00, Page 11
PROFIBUS PA
s
Network Setup - Rules (continued)
24 V
PA Link PACoupler
Up to 31 PA field devices can be connected to ONE
link - INDEPENDENT of the number of couplers
PROFIBUS PADate 09/19/00, Page 12
PROFIBUS PA
s
Network Setup - Rules (continued)
PA Link PACoupler
Maximum current flow per coupler:
400mA for
110mA for EEx [ib] II C ignition protection
90mA for EEx [ia] II C ignition protection
24 V
I
x
PROFIBUS PADate 09/19/00, Page 13
PROFIBUS PA
s
Network Setup - Rules (continued)
24 V
Maximum segment length per coupler = 1,900m
PROFIBUS PADate 09/19/00, Page 14
PROFIBUS PA
s
Network Setup - Rules (continued) (Allowed Length PER Drop/Spur Line)
90
120
30
60
303030
0
20
40
60
80
100
120
140
1..12 13..14 15..18 19..24
[Number of Spur Lines]
Maximum Length(Non Ex) [m]
Maximum Length(Ex) [m]
PROFIBUS PADate 09/19/00, Page 15
PROFIBUS PA
s
PA Profile
Definition on the application layer level
Profile defines variables, function blocks, meaning of the data, mapping to communication services...
Devices with the same profile implemented can be exchanged
Current version of PA Profile is V3.0
Available as official PROFIBUS International document with order no. 3.042
Pre-defined GSD files for various PA field devices available
PROFIBUS PADate 09/19/00, Page 16
PROFIBUS PA
s
PA Profile (continued)
Measuring range
DP servicescyclic and
acyclic
DP Servicesacyclic
DP servicesacyclic
Profile B
Status
Measured value
Manufacturer-specificparameters
Filter time
Alarm/warning limits
Alarm summary
TAG
(e.g. forpressure
transmitters)
PROFIBUS PADate 09/19/00, Page 17
PROFIBUS PA
s
Electronic Data Sheets
GSD
GSD File for description of communication parameters