© 2020 Carrier Form 48-50P-11PD Rev. A
48/50P2,P3,P4,P5,P6,P7,P8,P9 030-100Single-Package Gas
Heating/Electric Cooling Rooftop Unitsand Electric Cooling Rooftop
Units with Optional Electric Heatwith ComfortLink Controls and
Puron® Refrigerant (R-410A)
Product Data
WeatherMaster®
Single-Package Rooftop Units30 to 100 Nominal Tons
-
2
Carrier’s 48/50P commercial packaged unit offers design
flexibility, quality, reliability, interoperability and ComfortLink
controls.Carrier’s 48/50P Series commercialpackaged rooftops
offer:• Puron® refrigerant (R-410A)• Novation® heat exchanger
technol-
ogy with microchannel coil• scroll compressors• variable
capacity digital scroll com-
pressor option• constant volume (CV)• staged air volume (SAV™)•
variable air volume (VAV)• vertical supply/return units• horizontal
supply/return units• flexible chassis and plenum options• optional
return fan or power exhaust• Greenspeed® Intelligence control
option• staged or modulating gas heat control• hydronic heat
option• high-capacity evaporator coil• optional airfoil fan•
Humidi-MiZer® adaptive dehumidifi-
cation optionComfortLink controlsFactory-installed ComfortLink
controlsprovide the capability for free standingoperation or may be
linked with a moreextensive system. Optional factory-installed and
programmed BACnet1communication capability provides sim-ple
integration with the building HVACsystem (e.g., terminal devices),
an i-Vu®Open control system or a BACnet build-ing automation
system.ComfortLink controls also have thecapability to communicate
with theCarrier Comfort Network® (CCN) sys-tem. This communication
flexibilityallows simple system integration as wellas data
collection, trending, monitoringand alarm displays.The 48/50P
Series may also be con-figured to communicate via MODBUS2or
LonWorks3 protocols, if required bythe application.The ComfortLink
controls can alsointerface directly with Carrier Open orCCN
controls on 35 and 45 SeriesVAV terminals to form a system
foroptimal efficiency and tenant comfort.
All units may also be applied to non-communicating building
control sys-tems via switch and/or 4 to 20 mA sig-nal to provide
remote occupancycontrol, fire shutdown and smoke con-trol modes,
IAQ (indoor air quality)modes, and demand limit sequences.In
addition, VAV units can interfacewith other control systems via a 4
to20 mA signal capability which permitscontrol of supply-air
temperature reset.Standard ComfortLink controls func-tions
include:• easy-to-use, plain English display• supply-fan control
based on occu-
pancy schedule• up to 6 steps of cooling capacity con-
trol with standard scroll compressors• digital scroll compressor
option that
allows variable control of compres-sor capacity to match load
require-ment of the space
• lead-lag circuit control to equalizethe operating hours
between thedual refrigeration circuits
• 2-stage heat control• adaptive optimal start/morning
warm-up• 2 stage thermostat control (SAV/CV
only)• head pressure control to 32°F ambi-
ent outdoor-air temperature• economizer and ventilation control•
economizer sequence enabled by
standard outside air enthalpy switch• adjustment of space set
point in the
occupied space on CV applications
• selectable supply air set point inboth CV, SAV™, and VAV
modes
• control of optional variable fre-quency supply-fan drives
• interface with 35 or 45 Series VAVterminals to create a
system
• IAQ and demand controlled ventila-tion control support
• space temperature reset (VAV applications)
• local or remote unit alarm and alertmonitoring
• filter maintenance alarm• building ventilation mode purge•
self-monitoring diagnostics• demand limiting• external input to
permit supply-air
temperature reset using a 4 to 20 mAsignal from another control
system
• easy replacement of select legacy30-100 ton Carrier rooftop
units
A self-diagnostic microprocessor man-ages all unit sequences,
includingstages of cooling and unit safety con-trols. The
microprocessor also con-trols stages of cooling and unit
safetycontrols. At start-up, the self-diagnostictest verifies
component operation andcalibration. Fault codes and expandedfault
descriptions reduce service trou-bleshooting time and
difficulty.Unique designA unique feature of these units
withComfortLink controls is that the con-trols will support both
CV, SAV, andVAV unit operations. The controls areconfigured in the
factory, based on theunit model and options installed.
1. BACnet is a registered trademark of ASHRAE (American Society
of Heating, Refrigerating, and Air-Conditioning Engineers).
2. Modbus is a registered trademark of Schneider Electric.
3. LonWorks is a registered trademark of Echelon
corporation.
Features/Benefits
Table of contentsPage
Features/Benefits
......................................................................................
2Model Number Nomenclature
.....................................................................
6Ratings and Capacities
...............................................................................
7Physical
Data...........................................................................................
15Options and
Accessories...........................................................................
47Base Unit Dimension
Examples.................................................................
54Accessory
Dimensions..............................................................................
63Selection Procedure
.................................................................................
68Performance
Data....................................................................................
69Electrical Data
.......................................................................................
150Controls................................................................................................
151Application
Data....................................................................................
160Typical Piping and
Wiring.......................................................................
168Typical Wiring Schematics
......................................................................
169Guide
Specifications...............................................................................
176
-
3
System functions like adaptive optimalstart, nighttime free
cooling, buildingsmoke control modes, occupied heat-ing and IAQ
support are resident in thecontrols and can be easily
integratedinto the control system strategy.Environmentally
balancedPuron refrigerant (R-410A) is an HFCrefrigerant that does
not contain chlo-rine that is damaging to the ozone layer.This
refrigerant is a safe, efficient, andenvironmentally balanced
refrigerant.Quality and reliabilityExcellent full and part load
efficienciesare achieved by using multiple scrollcompressors and
indoor coils withintertwined dual refrigerant circuits.The
compressors are equipped withcrankcase heaters and protected
byelectronic sensors and logic to controlminimum on and off times
and reverserotation. The refrigerant circuits areboth electrically
and mechanically inde-pendent, to provide standby capabilityshould
one circuit require service.Novation® heat exchanger technologyThe
Novation heat exchanger designwith microchannel condenser coil is
arobust, cost effective alternative to tradi-tional coil design for
standard applica-tions. Microchannel coils are also sturdierthan
other coil types, making them eas-ier to clean without causing
damage tothe coil.Due to the compact, all-aluminumdesign,
microchannel coils reduce over-all unit operating weight. The
stream-lined microchannel coil also reducesrefrigerant charge by up
to 40%.Microchannel coils are not recom-mended by Carrier for
marine, coastal,or industrial environments, unless
aCarrier-approved coating is applied.
Variable capacity digital scroll compressorIn air conditioning
applications, theload may vary significantly, requiring ameans to
vary the system coolingcapacity for optimal system perfor-mance and
control. The 48/50P serieslarge rooftop units with digital
scrollcompression provide a highly efficientmeans of capacity
control using scrollcompressors. The digital compressortechnology
provides smooth, vibrationfree operation by axially unloading
thecompliant scrolls. By varying theamount of time that the scrolls
areunloaded, the unit is able to preciselymatch the system capacity
to the spaceload. This feature can reduce energyconsumption,
provide better dehumidi-fication, reduce compressor cycling,and
improve comfort in the space.Humidi-MiZer® adaptive
dehu-midification systemCarrier’s Humidi-MiZer adaptive
dehu-midification system is an all-inclusivefactory-installed
option that can beordered with any Weathermaster®commercial rooftop
unit.This system expands the envelope ofoperation of the rooftop to
provideunprecedented flexibility that will meetyear-round comfort
conditions. TheHumidi-MiZer adaptive dehumidificationsystem has the
industry’s only dual dehu-midification mode setting. The
Weather-master rooftop, coupled with theHumidi-MiZer adaptive
dehumidificationsystem, is capable of operating in normaldesign
cooling mode, subcooling mode,and hot gas reheat mode.Normal design
cooling mode will oper-ate under the normal sequence ofoperation.
Subcooling mode will oper-ate to satisfy part load type
conditions
by providing both cooling andenhanced dehumidification. Hot
GasReheat mode will operate when thereis a demand for
dehumidification butno demand for space cooling. Hot GasReheat mode
will provide neutral airfor maximum dehumidification opera-tion
without over-cooling the zone.The Weathermaster 48/50P Seriesnext
generation version of Carrier’sHumidi-MiZer system includes
refriger-ant modulating valves that provide vari-able flow bypass
around the condenser.This innovative feature ensures exactcontrol
of the supply-air temperatureas the unit lowers the evaporator
tem-perature to increase latent capacity.Additionally, when the
space requiresdehumidification only, the Humidi-MiZersystem can
increase hot discharge gasbypass to the Humidi-MiZer coil in
orderto heat the air to the exact neutral staterequired – no
overcooling or overheatingwith similar latent capacity as that
pro-vided in the full subcooling mode. Greenspeed intelligence
optionGreenspeed intelligence allows lowambient mechanical cooling
and maxi-mizes unit mechanical cooling efficiencyby continuously
monitoring refrigerantcircuit efficiency and ambient conditionsto
optimize condenser fan operation. Greenspeed also reduces the unit
acous-tic footprint through the condenser fanspeed modulation,
included low soundcondenser fans, and factory installedcompressor
sound blankets. Staged/modulating gas controlStaged and modulating
gas controloptions provide a supply air temperingheat function
during conditions of lowmixed air temperature while the systemis
still in Ventilation mode.
SPRING ISOLATION HINGED ACCESS DOORS
NOVATION® HEAT EXCHANGERTECHNOLOGY WITH
MICROCHANNEL COILS
TUBES
FINS
MICROCHANNELS
MANIFOLD
-
4
These low, mixed air conditions occurwhen the outdoor
temperature is lowand the outside-air damper is in its min-imum
position, so that the mixing ofcold outside air and return air
results inmixed-air temperatures below 50°F.Both staged and
modulating gas con-trol options will raise the air tempera-ture
leaving the unit up to thetempering mode set point. Modulatinggas
control option offers an enhancedcontrol of leaving air temperature
setpoint by continuously modulating theheat load. The modulating
gas controlreduces the burners on/off cycles intempering mode. The
staged gas control option also pro-vides additional control stages
of heat-ing operation during the normal spacedemand heating
function. The modu-lating gas control option provides con-tinuous
heating modulation to satisfythe space demand for heat. Design
flexibilityThe 48/50P Series rooftop units withComfortLink controls
are designed tomeet all customer requirements fornew construction,
replacement jobs, orspecial applications.The customer can choose
from thefollowing:• CV, SAV™ or VAV applications• variable capacity
digital scroll
compressors• 4 or more supply-fan motor sizes • 2 sizes of
natural gas heat (48 Series
units)• electric heat (50 Series units)• hydronic heat (50
Series units)• Novation® MCHX (microchannel
heat exchanger) condenser coils ore-coated MCHX condenser
coils
• integrated economizer with low-leakdampers and barometric
relief,return fan, or power exhaust
• ultra low leak economizer• Greenspeed intelligence control•
extended chassis units are provided
with space and mounting tracks for afactory or field-installed
heating coil
• standard 2-in. filter tracks are pro-vided but can be
field-modified toaccept 4-in. panel filters
• Humidi-MiZer® adaptive humidifica-tion system
Discharge optionsUnits can be used for vertical
discharge,discharge plenum vertical discharge, orspecial horizontal
applications, such asreplacement or sound-sensitive applica-tions.
The horizontal installation allowssound to be attenuated before the
ductpenetrates the roof.
Exhaust and return optionsFor applications requiring
mechanicalexhaust, all 48/50P series units withan economizer are
available with non-modulating (CV) or modulating powerexhaust. The
75-100 ton units are alsoavailable with high capacity powerexhaust
for higher airflow or staticrequirements. Multiple exhaust
fancontrol methods are available. For applications requiring high
returnduct static pressure (>0.5 in. static) afactory installed
return fan is availablefor all 48/50P units with an economizerand
vertical return. The return fan helpsovercome the return duct
static pres-sure, which allows a reduction in thesupply fan motor
capacity. The returnfan option includes a VFD for CFM off-set
control or building static pressurecontrol. Superior space pressure
control is pro-vided by specifying one of the modulat-ing power
exhaust or return fansystems. Modulating power exhaustand return
fan systems control exhaustfan airflow rates to maintain a
user-established space pressure set point.The ComfortID™
solutionThe 48/50P ComfortLink controls fullysupport the ComfortID
system. TheComfortID system is a completely inte-grated control
system that uses state-of-the-art Direct Digital Controls (DDC)
tocontinually monitor and communicatethe varying heating and
cooling condi-tions in each zone of the building.The ComfortID
system capabilities gowell beyond temperature control. Byadding
humidity, CO2, or other IAQ sen-sors, indoor air quality and
consistentcomfort conditions can be tailor-madefor each zone.
Proper ventilation basedon number of occupants can be
preciselymaintained. Using the ComfortID systemfor
demand-controlled ventilation (DCV)allows for compliance with
ASHRAE(American Society of Heating, Refriger-ating and
Air-Conditioning Engineers)standard 62 and helps keep energy
costsdown. The ComfortID system does notmerely monitor air quality
— it maintainsair quality, adjusting to promote
buildinghealth.Indoor air quality (IAQ)All units incorporate a
sloped, stainlesssteel condensate drain pan to preventstanding
water from accumulating insidethe rooftop air-conditioning unit.
Thecondensate pan has a recessed nonfer-rous condensate drain
connection.Interior cabinet surfaces (except insupply fan discharge
section) are insu-lated with a flexible fire-retardant dual-density
fiberglass blanket, coated on
the air side. The coating contains anEnvironmental Protection
Agency(EPA) registered immobilized anti-microbial agent to
effectively resist thegrowth of bacteria and fungi.Double wall
construction in the air-stream is available as an option. Dou-ble
wall construction with Agion1 anti-microbial coating can also be
provided.These units and controls have beendeveloped to provide the
design com-munity with the flexibility to meet indi-vidual job
needs for both comfort andIAQ. The design features include:•
Optional two position OA damper or
integral economizer for the introduc-tion of high quality
ventilation air.
• Optional OA station to control theeconomizer to meet the
requiredventilation airflow.
• Multiple filter options, including car-tridge filters and MERV
15 bag filters.
• Multiple cooling capacity options tohelp match the unit size
to thespace load.
• Multiple, small scroll compressorsprovide multiple steps of
coolingcapacity to help prevent over-cool-ing the space.
• Optional variable capacity compres-sor for more precise supply
air tem-perature control.
• Large diameter, low RPM supply fansfor reduced discharge sound
levels.
• SAV and VAV fan control providereduced discharge sound levels
tothe space at part load.
• Refrigeration system designed tooperate down to 32°F
outdoor-airtemperature.
• Multiple heat capacity options tomatch the application load
and helpprevent overheating.
• Multi-staged or modulating heat con-trol for precise supply
air temperaturecontrol.
• Humidi-MiZer adaptive dehumidifi-cation system.
Fan modulationSupply fan duct pressure control on VAVmodels is
accomplished via a variable fre-quency (inverter) drive (VFD). The
VFDcontrols supply fan airflow to maintain auser-established duct
pressure set point inthe unit’s supply duct. Supply duct pres-sure
control can be used for both multi-zone VAV systems with air
terminal unitsand single zone VAV systems with orwithout air
terminal units.
1. Agion is a trademark of Sciessent.
Features/Benefits (cont)
-
5
Installation and serviceabilityAccess panelsAll full-size access
panels are hinged foreasy access to serviceable components.No
fasteners need to be removed fromany units, which reduces servicing
timeand prevents roof leaks caused by dis-carded screws puncturing
the roof.Electrical connectionsSingle point electrical connections
arestandard on all units. Electrical serviceaccess can be made
through roof curbor side of unit. All 48P units provide asingle
point gas connection.Run testingTo ensure a successful start-up,
everyrooftop unit is factory run tested.Unit designUnit design is
ETL and ETL, Canada,listed according to UL (Underwriters
Lab-oratories) Standard 1995.Scrolling marqueeWhen using the
standard scrolling mar-quee, serviceability becomes even
easier,including:• local or remote alarm and alert
monitoring• self-diagnostic run testing to confirm
control and component operation• expedited troubleshooting and
unit
repair through self-diagnostic dis-play of unit troubleshooting
alertand alarm codes with expanded textdescriptions to immediately
identifyreason for unit outage
• filter maintenance alarm• monitoring of supply-air fan run
time, permitting easy service sched-ule planning
TransducersServiceability is further facilitated withsuction and
discharge pressure trans-ducers. These allow suction pressureand
discharge pressure to be monitoredremotely with alarm capability.
Thesetransducers also control condenser headpressure to maintain
the minimum dif-ferential pressure required across thethermostatic
expansion valve (TXV) forproper operation, which reduces
energyconsumption.Non-fused disconnectA factory-installed non-fused
discon-nect (NFD) option is available to simplifyunit installation
and improve unit ser-viceability. The location of the NFD in
the main control box simplifies fieldpower supply routing into
the unit. TheNFD incorporates an access panel inter-lock feature,
ensuring that all power tothe unit will be disconnected before
aservice person opens the control box.Gas heat units (48P units)The
48P units are gas heating units,using natural gas combustion, with
twoheat sizes available for every unit.The unit heating systems
employ multi-ple heat exchanger sections, with eachsection equipped
with a 2-stage redun-dant gas valve and independent igni-tion
control, with all sections operatingin parallel.Units with gas
modulating heating areequipped with an additional modulatinggas
valve installed downstream of the2-stage redundant gas valve.Heat
exchangerThe tubular steel heat exchanger designoptimizes heat
transfer for improved effi-ciency. The tubular design permits
multi-ple passes across the supply air path.Each tube has an
individual inshotburner, ensuring uniform combustion ineach tube of
the heat exchangers. Tubesare dimpled to create a turbulent gas
flowto maximize heat efficiency and toensure uniform surface
temperatures forreduced corrosion effects, improveddurability and
long-life service. Heatexchanger material is aluminized steel
orstainless steel, for improved corrosionresistance and
reliability.Integrated gas unit controllerThe IGC (integrated gas
unit controller)ignition and safety control system isused on each
heat exchanger section.The IGC, unique to Carrier rooftopunits,
simplifies system evaluation andtroubleshooting by providing
systemstatus and visual fault notification via anon-board LED
(light-emitting diode).Ignition is initiated by a direct
sparkignition system; flame status is deter-mined by flame
rectification process.Combustion fan operation is proven bya Hall
Effect speed sensor circuit forunits equipped with 2-stage or
stagedgas heat. For units equipped with mod-ulating gas heat,
combustion fan oper-ation is proven with a pressure switch.Safeties
include flame rollout and limitswitch. Auto reset with manual
lockoutis also provided for repeated limitswitch trips. The IGC
also preventsshort-cycling due to thermostat jiggle
by ensuring a full minute heating cycleoperation on each call
for heat.Gas heat systemThe induced draft fan system draws
hotcombustion gas through the heatexchanger tubes at the optimum
rate forthe most effective heat transfer and com-bustion process.
The heat exchangeroperates under a negative pressure, pre-venting
flue gas leakage into the indoorsupply air.Flue outlet hoods with
wind baffles arelocated on the side of the unit, to mini-mize the
effects of wind on heatingoperations.Standard units use 2-stage
control forunoccupied, morning warm-up andoccupied space
heating.Additional control stages for heatingoperation are
available by specifyingthe staged gas control option.Modulating
control option is availableby specifying the modulating gas
con-trol option.A single hinged panel gains access to thecomplete
heat exchanger assembly andcontrols, for improved serviceability.A
single point gas connection providesfor easy installation.An LP
(liquid propane) conversionaccessory can be field-installed on
gasunits without staged or modulating gascontrol option (sizes
030-070 for verti-cal low heat units and sizes 030-050for vertical
high heat units).Optional modulating gas heatThe modulating gas
heat option moni-tors unit supply-air temperature andcontrols the
unit heat exchanger toprovide first-stage demand heatingcontrol,
with modulation to maintainuser-configured heating supply air
tem-perature set point.The option also provides full-firedemand
heating on heating controlcommand and tempering heat control,based
on user-configured ventilationsupply air temperature set point,
toeliminate cold draft conditions with lowmixed-air
temperatures.The modulating gas control optionconsists of a
modulating controllercapable of ensuring the proper fuel airmixture
at operating firing rates, sup-ply air temperature thermistors
withduct-mounting base, a limit switch tem-perature thermistor, and
stainless steelheat exchanger tubes.
-
6
50 P2 D 030 6 1 Option Code
Factory Options50 – Cooling Unit with Electric Heat See note
below
ConfigurationDesign Revision Level
Voltage Options1 – 575-3-60
Heat and Chassis Options
2 – 380-3-60
- – No Heat
5 – 208/230-3-60
A – Low Electric Heat
6 – 460-3-60
B – Medium Electric HeatC – High Electric Heat
Unit Size – Nominal Tons030 – 30 060 – 60035 – 35 070 – 70040 –
40 075 – 75
J – No Heat with Discharge Plenum, Humidi-MiZer System
050 – 50 090 – 90055 – 55 100 – 100
P – No Heat with Discharge Plenum and Extended ChassisR – No
Heat with Extended ChassisS – Low Electric Heat with Extended
ChassisT – Medium Electric Heat with Extended ChassisV – High
Electric Heat with Extended ChassisW – No Electric Heat with
Extended Chassis and Hot Water CoilY – No Electric Heat with
Discharge Plenum, Extended Chassis
and Hot Water Coil
D – No Heat, Humidi-MiZer SystemE – Low Electric Heat,
Humidi-MiZer SystemF – Medium Electric Heat, Humidi-MiZer SystemG –
High Electric Heat, Humidi-MiZer SystemH – No Heat with Discharge
Plenum
Z – Low Electric Heat, Humidi-MiZer with SCR Control2 – Medium
Electric Heat, Humidi-MiZer with SCR Control3 – High Electric Heat,
Humidi-MiZer with SCR Control4 – Low Electric Heat, with Extended
Chassis with SCR Control5 – Medium Electric Heat, with Extended
Chassis with SCR Control6 – High Electric Heat, with Extended
Chassis with SCR Control
P2 – Vertical Supply/Return, CV/SAV ComfortLink ControlsP3 –
Vertical Supply/Return, VAV ComfortLink ControlsP4 – Horizontal
Supply/Return, CV/SAV ComfortLink ControlsP5 – Horizontal
Supply/Return, VAV ComfortLink ControlsP6 – Vertical Supply/Return,
CV/SAV ComfortLink Controls
with GreenspeedP7 – Vertical Supply/Return, VAV ComfortLink
Controls
with GreenspeedP8 – Horizontal Supply/Return, CV/SAV ComfortLink
Controls
with GreenspeedP9 – Horizontal Supply/Return, VAV ComfortLink
Controls
with Greenspeed
0 – Initial Release1 – First Revision2 – 35T Release3 – Third
Revision4 – Fourth Revision
48 P2 D 030 6 1 Option Code
Factory Options48 – Cooling Unit with Gas Heat See note
below
ConfigurationDesign Revision Level0 – Initial Release
Voltage Options1 – 575-3-60
Heat and Chassis Options
5 – 208/230-3-606 – 460-3-60
B – Low Gas Heat, Stainless Steel C – High Gas Heat, Stainless
Steel
Unit Size – Nominal Tons
D – Low Gas Heat
030 – 30 060 – 60
E – High Gas Heat
035 – 35 070 – 70040 – 40 075 – 75050 – 50 090 – 90
H – Low Staged Gas Heat, Stainless Steel
055 – 55 100 – 100
J – High Staged Gas Heat, Stainless Steel
P – Low Gas Heat, Stainless Steel, Extended ChassisQ – High Gas
Heat, Stainless Steel, Extended ChassisR – Low Gas Heat with
Extended ChassisS – High Gas Heat with Extended ChassisW – Low
Staged Gas Heat, Stainless Steel, with Extended ChassisX – High
Staged Gas Heat, Stainless Steel, with Extended Chassis
– – Low Gas Heat, Humidi-MiZer® System A – High Gas Heat,
Humidi-MiZer System
F – Low Staged Gas Heat, Stainless Steel, Humidi-MiZer SystemG –
High Staged Gas Heat, Stainless Steel, Humidi-MiZer System
M – Low Gas Heat, Stainless Steel, Humidi-MiZer SystemN – High
Gas Heat, Stainless Steel, Humidi-MiZer System
K – Low Modulating Gas Heat, Stainless SteelL – High Modulating
Gas Heat, Stainless Steel
Y – Low Modulating Gas Heat, Stainless Steel, Humidi-MiZer
SystemZ – High Modulating Gas Heat, Stainless Steel, Humidi-MiZer
System2 – Low Modulating Gas Heat, Stainless Steel, with Extended
Chassis3 – High Modulating Gas Heat, Stainless Steel, with Extended
Chassis
1 – First Revision2 – 35T Release3 – Third Revision4 – Fourth
Revision
P2 – Vertical Supply/Return, CV/SAV ComfortLink ControlsP3 –
Vertical Supply/Return, VAV ComfortLink ControlsP4 – Horizontal
Supply/Return, CV/SAV ComfortLink ControlsP5 – Horizontal
Supply/Return, VAV ComfortLink ControlsP6 – Vertical Supply/Return,
CV/SAV ComfortLink Controls
with GreenspeedP7 – Vertical Supply/Return, VAV ComfortLink
Controls
with GreenspeedP8 – Horizontal Supply/Return, CV/SAV ComfortLink
Controls
with GreenspeedP9 – Horizontal Supply/Return, VAV ComfortLink
Controls
with Greenspeed
NOTE: Because of the large number of options and the many
resultingcombinations, the Applied Rooftop Builder software must be
used togenerate the 8-digit option code for the unit model number.
Refer to thesoftware for the different choices for unit
factory-installed options. Onceall of the options have been
selected, the software will generate the cor-rect code. Unit
options and accessories are listed in the Options andAccessories
section on page 47.
NOTE: Because of the large number of options and the many
resultingcombinations, the Applied Rooftop Builder software must be
used togenerate the 8-digit option code for the unit model number.
Refer to thesoftware for the different choices for unit
factory-installed options. Onceall of the options have been
selected, the software will generate the cor-rect code. Unit
options and accessories are listed in the Options andAccessories
section on page 47.
50P2,P3,P4,P5,P6,P7,P8,P9 UNITS
48P2,P3,P4,P5,P6,P7,P8,P9 UNITS
LEGENDCV — Constant VolumeSAV — Staged Air VolumeSCR — Silicon
Controlled Rectifier Electric HeatVAV — Variable Air Volume
Quality AssuranceCertified to ISO 9001:2015
LEGENDCV — Constant VolumeSAV™ — Staged Air VolumeVAV — Variable
Air Volume
Model number nomenclature
-
7
UNIT DESIGN AIRFLOW LIMITS
NOTE: Refer to Application Data section for more information
concern-ing minimum operating airflow in Cooling mode.
TWO-STAGE GAS HEATING CAPACITIES — 48P2,P3,P6,P7 UNITS(NATURAL
GAS ON ALL UNITS AND LP GAS ON 030-070 UNITS)
LEGEND
LP — Liquid Propane
NOTES:1. Ratings are approved for altitudes to 2000 ft. At
altitudes over 2000
ft, ratings are 4% less for each 1000 ft above sea level.2. At
altitudes up to 2000 ft, the following formula may be used to
calcu-
late air temperature rise:
3. At altitudes above 2000 ft, the following formula may be
used:
4. Minimum allowable temperature of mixed air entering the
heatexchanger during half-rate (first stage) operation is 35°F.
There is nominimum mixture temperature limitation during full-rate
operation.
5. Temperature rise limits: see table.6. On VAV (variable air
volume) applications set the zone terminals to
provide minimum unit heating airflow as indicated in the table
uponcommand from Heat Interlock Relay (HIR) function.
UNIT SIZE UNIT TYPE MINIMUM COOLING CFM MAXIMUM CFM
03048P Low Heat 6,000 15,00048P High Heat 6,000 15,00050P 6,000
15,000
03548P Low Heat 7,000 15,00048P High Heat 7,000 15,00050P 7,000
15,000
04048P Low Heat 8,000 20,00048P High Heat 8,000 20,00050P 8,000
20,000
05048P Low Heat 9,000 20,00048P High Heat 9,000 19,50050P 9,000
20,000
05548P Low Heat 10,000 25,00048P High Heat 10,000 25,00050P
10,000 25,000
06048P Low Heat 12,000 30,00048P High Heat 12,000 30,00050P
12,000 30,000
07048P Low Heat 14,000 30,00048P High Heat 14,000 30,00050P
14,000 30,000
07548P Low Heat 15,000 30,00048P High Heat 15,000 30,00050P
15,000 30,000
09048P Low Heat 17,000 40,00048P High Heat 17,000 37,00050P
17,000 40,000
10048P Low Heat 20,000 44,00048P High Heat 20,000 37,00050P
20,000 44,000
UNIT48P2,P3,P6,P7
GAS INPUT (1000 Btuh) EFFICIENCY(%)
OUTPUT CAPACITY (1000 Btuh) TEMP RISE(F)
AIRFLOW (Cfm)Stage 1 Stage 2 Stage 1 Stage 2 Min Max
030-050 Low Heat 244 325 81.0% 197 263 10-40 6,094 20,000030-050
High Heat 488 650 81.0% 395 527 25-55 8,864 19,259055-070 Low Heat
488 650 80.0% 390 520 10-40 12,142 30,000055-070 High Heat 731 975
80.0% 585 780 20-50 14,571 30,000075-100 Low Heat 488 650 80.0% 390
520 10-40 12,172 44,000075-100 High Heat 731 975 80.0% 585 780
20-50 14,517 36,292
t =maximum output capacity
1.10 x air quantity
t =maximum output capacity
(.24 x specific weight of air x 60) (air quantity)
Ratings and capacities
-
8
TWO-STAGE GAS HEATING CAPACITIES — 48P4,P5,P8,P9 UNITS(NATURAL
GAS ON ALL UNITS AND LP GAS NOT AVAILABLE)
LEGEND
LP — Liquid Propane
NOTES:1. Ratings are approved for altitudes to 2000 ft. At
altitudes over 2000
ft, ratings are 4% less for each 1000 ft above sea level.2. At
altitudes up to 2000 ft, the following formula may be used to
calcu-
late air temperature rise:
3. At altitudes above 2000 ft, the following formula may be
used:
4. Minimum allowable temperature of mixed air entering the
heatexchanger during half-rate (first stage) operation is 35°F.
There is nominimum mixture temperature limitation during full-rate
operation.
5. Temperature rise limits: see table.6. On VAV (variable air
volume) applications set the zone terminals to
provide minimum unit heating airflow as indicated in the table
uponcommand from Heat Interlock Relay (HIR) function.
GAS HEATING CAPACITIES — UNITS WITH TWO-STAGE GAS CONTROL
OPTION
48P2,P3,P6,P7 030-050 LOW HEAT
48P4,P5,P8,P9 030-050 LOW HEAT
GAS HEATING CAPACITIES — UNITS WITH MULTI-STAGE GAS CONTROL
OPTION
48P2,P3,P6,P7 030-050 HIGH HEAT
48P4,P5,P8,P9 030-050 HIGH HEAT
UNIT48P4,P5,P8,P9
GAS INPUT (1000 Btuh) EFFICIENCY(%)
OUTPUT CAPACITY (1000 Btuh) TEMP RISE(F)
AIRFLOW (Cfm)Stage 1 Stage 2 Stage 1 Stage 2 Min Max
030-050 Low Heat 244 325 80.0% 195 260 10-40 6,019 20,000030-050
High Heat 488 650 80.0% 390 520 25-55 8,754 19,259055-070 Low Heat
488 650 80.0% 390 520 10-40 12,037 30,000055-070 High Heat 731 975
80.0% 585 780 20-50 14,444 30,000075-100 Low Heat 488 650 80.0% 390
520 10-40 12,037 44,000075-100 High Heat 731 975 80.0% 585 780
20-50 14,444 36,111
t =maximum output capacity
1.10 x air quantity
t =maximum output capacity
(.24 x specific weight of air x 60) (air quantity)
HEATINGSTAGES
INPUTCAPACITY(1000 Btuh)
% FULL FIRE THERMAL EFFICIENCY %
OUTPUT CAPACITY (1000 Btuh)
OUTPUT CAPACITY PER SECTION (1000 Btuh)
SECTION 1 SECTION 2 SECTION 3
1 244 75% 81.0% 197.4 197.4 N/A N/A2 325 100% 81.0% 263.3 263.3
N/A N/A
HEATINGSTAGES
INPUTCAPACITY(1000 Btuh)
% FULL FIRE THERMAL EFFICIENCY %
OUTPUT CAPACITY (1000 Btuh)
OUTPUT CAPACITY PER SECTION (1000 Btuh)
SECTION 1 SECTION 2 SECTION 3
1 244 75% 80.0% 195.0 195.0 N/A N/A2 325 100% 80.0% 260.0 260.0
N/A N/A
HEATINGSTAGES
INPUTCAPACITY(1000 Btuh)
% FULL FIRE THERMAL EFFICIENCY %
OUTPUT CAPACITY (1000 Btuh)
OUTPUT CAPACITY PER SECTION (1000 Btuh)
SECTION 1 SECTION 2 SECTION 3
1 244 38% 81.0% 197.4 197.4 0.0 N/A2 325 50% 81.0% 263.3 263.3
0.0 N/A3 488 75% 81.0% 394.9 197.4 197.4 N/A4 569 88% 81.0% 460.7
263.3 197.4 N/A5 650 100% 81.0% 526.5 263.3 263.3 N/A
HEATINGSTAGES
INPUTCAPACITY(1000 Btuh)
% FULL FIRE THERMAL EFFICIENCY %
OUTPUT CAPACITY (1000 Btuh)
OUTPUT CAPACITY PER SECTION (1000 Btuh)
SECTION 1 SECTION 2 SECTION 3
1 244 38% 80.0% 195.0 195.0 0.0 N/A2 325 50% 80.0% 260.0 260.0
0.0 N/A3 488 75% 80.0% 390.0 195.0 195.0 N/A4 569 88% 80.0% 455.0
260.0 195.0 N/A5 650 100% 80.0% 520.0 260.0 260.0 N/A
Ratings and capacities (cont)
-
9
GAS HEATING CAPACITIES — UNITS WITH STAGED GAS CONTROL OPTION
(CONT)
48P2,P3,P6,P7 055-070 LOW HEAT
48P4,P5,P8,P9 055-070 LOW HEAT
48P2,P3,P6,P7 055-070 HIGH HEAT
48P4,P5,P8,P9 055-070 HIGH HEAT
48P2,P3,P6,P7 075-100 LOW HEAT
HEATINGSTAGES
INPUTCAPACITY(1000 Btuh)
% FULL FIRE THERMAL EFFICIENCY %
OUTPUT CAPACITY
(1000 Btuh)
OUTPUT CAPACITY PER SECTION (1000 Btuh)
SECTION 1 SECTION 2 SECTION 3
1 244 38% 80.0% 195.0 195.0 0.0 N/A2 325 50% 80.0% 260.0 260.0
0.0 N/A3 488 75% 80.0% 390.0 195.0 195.0 N/A4 569 88% 80.0% 455.0
260.0 195.0 N/A5 650 100% 80.0% 520.0 260.0 260.0 N/A
HEATINGSTAGES
INPUTCAPACITY(1000 Btuh)
% FULL FIRE THERMAL EFFICIENCY %
OUTPUT CAPACITY
(1000 Btuh)
OUTPUT CAPACITY PER SECTION (1000 Btuh)
SECTION 1 SECTION 2 SECTION 3
1 244 38% 80.0% 195.0 195.0 0.0 N/A2 325 50% 80.0% 260.0 260.0
0.0 N/A3 488 75% 80.0% 390.0 195.0 195.0 N/A4 569 88% 80.0% 455.0
260.0 195.0 N/A5 650 100% 80.0% 520.0 260.0 260.0 N/A
HEATINGSTAGES
INPUTCAPACITY(1000 Btuh)
% FULL FIRE THERMAL EFFICIENCY %
OUTPUT CAPACITY (1000 Btuh)
OUTPUT CAPACITY PER SECTION (1000 Btuh)
SECTION 1 SECTION 2 SECTION 3
1 244 25% 80.0% 195.0 195.0 0.0 0.02 325 33% 80.0% 260.0 260.0
0.0 0.03 488 50% 80.0% 390.0 195.0 195.0 0.04 569 58% 80.0% 455.0
260.0 195.0 0.05 650 67% 80.0% 520.0 260.0 260.0 0.06 731 75% 80.0%
585.0 195.0 195.0 195.07 813 83% 80.0% 650.0 195.0 260.0 165.08 894
92% 80.0% 715.0 260.0 260.0 195.09 975 100% 80.0% 780.0 260.0 260.0
260.0
HEATINGSTAGES
INPUTCAPACITY(1000 Btuh)
% FULL FIRE THERMAL EFFICIENCY %
OUTPUT CAPACITY (1000 Btuh)
OUTPUT CAPACITY PER SECTION (1000 Btuh)
SECTION 1 SECTION 2 SECTION 3
1 244 25% 80.0% 195.0 195.0 0.0 0.02 325 33% 80.0% 260.0 260.0
0.0 0.03 488 50% 80.0% 390.0 195.0 195.0 0.04 569 58% 80.0% 455.0
260.0 195.0 0.05 650 67% 80.0% 520.0 260.0 260.0 0.06 731 75% 80.0%
585.0 195.0 195.0 195.07 813 83% 80.0% 650.0 195.0 260.0 195.08 894
92% 80.0% 715.0 260.0 260.0 195.09 975 100% 80.0% 780.0 260.0 260.0
260.0
HEATINGSTAGES
INPUTCAPACITY(1000 Btuh)
% FULL FIRE THERMAL EFFICIENCY %
OUTPUT CAPACITY (1000 Btuh)
OUTPUT CAPACITY PER SECTION (1000 Btuh)
SECTION 1 SECTION 2 SECTION 3
1 244 38% 80.0% 195.0 195.0 0.0 N/A2 325 50% 80.0% 260.0 260.0
0.0 N/A3 488 75% 80.0% 390.0 195.0 195.0 N/A4 569 88% 80.0% 455.0
260.0 195.0 N/A5 650 100% 80.0% 520.0 260.0 260.0 N/A
-
10
GAS HEATING CAPACITIES — UNITS WITH STAGED GAS CONTROL OPTION
(CONT)
48P4,P5,P8,P9 075-100 LOW HEAT
48P2,P3,P6,P7 075-100 HIGH HEAT
48P4,P5,P8,P9 075-100 HIGH HEAT
GAS HEATING CAPACITIES — UNITS WITH MODULATING GAS CONTROL
OPTION
48P2,P3,P6,P7 030-050 LOW HEAT
48P4,P5,P8,P9 030-050 LOW HEAT
48P2,P3,P6,P7 030-050 HIGH HEAT
LEGEND
HF — High FireLF — Low Fire
HEATINGSTAGES
INPUTCAPACITY(1000 Btuh)
% FULL FIRE THERMAL EFFICIENCY %
OUTPUT CAPACITY (1000 Btuh)
OUTPUT CAPACITY PER SECTION (1000 Btuh)
SECTION 1 SECTION 2 SECTION 3
1 244 38% 80.0% 195.0 195.0 0.0 N/A2 325 50% 80.0% 260.0 260.0
0.0 N/A3 488 75% 80.0% 390.0 195.0 195.0 N/A4 569 88% 80.0% 455.0
260.0 195.0 N/A5 650 100% 80.0% 520.0 260.0 260.0 N/A
HEATINGSTAGES
INPUTCAPACITY(1000 Btuh)
% FULL FIRE THERMAL EFFICIENCY %
OUTPUT CAPACITY (1000 Btuh)
OUTPUT CAPACITY PER SECTION (1000 Btuh)
SECTION 1 SECTION 2 SECTION 3
1 244 25% 80.0% 195.0 195.0 0.0 0.02 325 33% 80.0% 260.0 260.0
0.0 0.03 488 50% 80.0% 390.0 195.0 195.0 0.04 569 58% 80.0% 455.0
260.0 195.0 0.05 650 67% 80.0% 520.0 260.0 260.0 0.06 731 75% 80.0%
585.0 195.0 195.0 195.07 813 83% 80.0% 650.0 195.0 260.0 165.08 894
92% 80.0% 715.0 260.0 260.0 195.09 975 100% 80.0% 780.0 260.0 260.0
260.0
HEATINGSTAGES
INPUTCAPACITY(1000 Btuh)
% FULL FIRE THERMAL EFFICIENCY %
OUTPUT CAPACITY (1000 Btuh)
OUTPUT CAPACITY PER SECTION (1000 Btuh)
SECTION 1 SECTION 2 SECTION 3
1 244 25% 80.0% 195.0 195.0 0.0 0.02 325 33% 80.0% 260.0 260.0
0.0 0.03 488 50% 80.0% 390.0 195.0 195.0 0.04 569 58% 80.0% 455.0
260.0 195.0 0.05 650 67% 80.0% 520.0 260.0 260.0 0.06 731 75% 80.0%
585.0 195.0 195.0 195.07 813 83% 80.0% 650.0 195.0 260.0 195.08 894
92% 80.0% 715.0 260.0 260.0 195.09 975 100% 80.0% 780.0 260.0 260.0
260.0
GAS INPUT(1000 Btuh)
PERCENTFULL FIRE
OUTPUTCAPACITY(1000 Btuh)
FIRING STAGE
1 2 3
92 - 325 28 - 100% 68 - 263 Modulating — —
GAS INPUT(1000 Btuh)
PERCENTFULL FIRE
OUTPUTCAPACITY(1000 Btuh)
FIRING STAGE
1 2 3
92 - 325 28 - 100% 68 - 260 Modulating — —
GAS INPUT(1000 Btuh)
PERCENTFULL FIRE
OUTPUTCAPACITY(1000 Btuh)
FIRING STAGE
1 2 3
92 - 325 14 - 50% 68 - 256 Modulating 0 —335 - 569 52 - 88% 265
- 455 Modulating LF —416 - 650 64 - 100% 333 - 527 Modulating HF
—
Ratings and capacities (cont)
-
11
GAS HEATING CAPACITIES — UNITS WITH MODULATING GAS CONTROL
OPTION (CONT)
48P4,P5,P8,P9 030-050 HIGH HEAT
48P2,P3,P6,P7 055-070 LOW HEAT
48P4,P5,P8,P9 055-070 LOW HEAT
48P2,P3,P6,P7 055-070 HIGH HEAT
48P4,P5,P8,P9 055-070 HIGH HEAT
48P2,P3,P6,P7 075-100 LOW HEAT
48P4,P5,P8,P9 075-100 LOW HEAT
LEGEND
HF — High FireLF — Low Fire
GAS INPUT(1000 Btuh)
PERCENTFULL FIRE
OUTPUTCAPACITY(1000 Btuh)
FIRING STAGE
1 2 3
92 - 325 14 - 50% 68 - 256 Modulating 0 —335 - 569 52 - 88% 265
- 455 Modulating LF —416 - 650 64 - 100% 333 - 520 Modulating HF
—
GAS INPUT(1000 Btuh)
PERCENTFULL FIRE
OUTPUTCAPACITY(1000 Btuh)
FIRING STAGE
1 2 3
92 - 325 14 - 50% 68 - 256 Modulating 0 —335 - 569 52 - 88% 265
- 455 Modulating LF —416 - 650 64 - 100% 333 - 525 Modulating HF
—
GAS INPUT(1000 Btuh)
PERCENTFULL FIRE
OUTPUTCAPACITY(1000 Btuh)
FIRING STAGE
1 2 3
92 - 325 14 - 50% 68 - 256 Modulating 0 —335 - 569 52 - 88% 265
- 455 Modulating LF —416 - 650 64 - 100% 333 - 520 Modulating HF
—
GAS INPUT(1000 Btuh)
PERCENTFULL FIRE
OUTPUTCAPACITY(1000 Btuh)
FIRING STAGE
1 2 3
92 - 325 9 - 33% 68 - 256 Modulating 0 0335 - 569 34 - 58% 265 -
455 Modulating LF 0416 - 650 43 - 67% 333 - 520 Modulating HF 0579
- 813 59 - 83% 463 - 650 Modulating LF LF660 - 894 68 - 92% 528 -
721 Modulating HF LF741 - 975 76 - 100% 593 - 787 Modulating HF
HF
GAS INPUT(1000 Btuh)
PERCENTFULL FIRE
OUTPUTCAPACITY(1000 Btuh)
FIRING STAGE
1 2 3
92 - 325 9 - 33% 68 - 256 Modulating 0 0335 - 569 34 - 58% 265 -
455 Modulating LF 0416 - 650 43 - 67% 333 - 520 Modulating HF 0579
- 813 59 - 83% 463 - 650 Modulating LF LF660 - 894 68 - 92% 528 -
721 Modulating HF LF741 - 975 76 - 100% 593 - 780 Modulating HF
HF
GAS INPUT(1000 Btuh)
PERCENTFULL FIRE
OUTPUTCAPACITY(1000 Btuh)
FIRING STAGE
1 2 3
92 - 325 14 - 50% 68 - 256 Modulating 0 —335 - 569 52 - 88% 265
- 455 Modulating LF —416 - 650 64 - 100% 333 - 526 Modulating HF
—
GAS INPUT(1000 Btuh)
PERCENTFULL FIRE
OUTPUTCAPACITY(1000 Btuh)
FIRING STAGE
1 2 3
92 - 325 14 - 50% 68 - 256 Modulating 0 —335 - 569 52 - 88% 265
- 455 Modulating LF —416 - 650 64 - 100% 333 - 520 Modulating HF
—
-
12
GAS HEATING CAPACITIES — UNITS WITH MODULATING GAS CONTROL
OPTION (CONT)
48P2,P3,P6,P7 075-100 HIGH HEAT
48P4,P5,P8,P9 075-100 HIGH HEAT
LEGEND
HF — High FireLF — Low Fire
ELECTRIC HEATER CAPACITIES
NOTES:1. Electric heat options are NOT AVAILABLE on discharge
plenum
units or size 030-070 horizontal units.2. Electric heat is
available on horizontal size 075-100 units with air-
foil fan option only.
GAS INPUT(1000 Btuh)
PERCENTFULL FIRE
OUTPUTCAPACITY(1000 Btuh)
FIRING STAGE
1 2 3
92 - 325 9 - 33% 68 - 256 Modulating 0 0335 - 569 34 - 58% 265 -
455 Modulating LF 0416 - 650 43 - 67% 333 - 520 Modulating HF 0579
- 813 59 - 83% 463 - 650 Modulating LF LF660 - 894 68 - 92% 528 -
719 Modulating HF LF741 - 975 76 - 100% 593 - 784 Modulating HF
HF
GAS INPUT(1000 Btuh)
PERCENTFULL FIRE
OUTPUTCAPACITY(1000 Btuh)
FIRING STAGE
1 2 3
92 - 325 9 - 33% 68 - 256 Modulating 0 0335 - 569 34 - 58% 265 -
455 Modulating LF 0416 - 650 43 - 67% 333 - 520 Modulating HF 0579
- 813 59 - 83% 463 - 650 Modulating LF LF660 - 894 68 - 92% 528 -
715 Modulating HF LF741 - 975 76 - 100% 593 - 780 Modulating HF
HF
UNIT SIZE NO. STAGES LOW(kW)
CAPACITYPER
STAGE (%)
MED(kW)
CAPACITYPER
STAGE (%)
HIGH(kW)
CAPACITYPER
STAGE (%)
MINCFM
MAXCFM
50P2,P3,P6,P7030-050208 v 2 29 50,100 59 50,100 88 67,100 9,000
20,000230 v 2 36 50,100 72 50,100 108 67,100 9,000 20,000380 v 2 25
50,100 51 50,100 76 67,100 9,000 20,000460 v 2 36 50,100 72 50,100
108 67,100 9,000 20,000575 v 2 36 50,100 72 50,100 108 67,100 9,000
20,000
50P2,P3,P6,P7055-070208 v 2 29 50,100 59 50,100 88 67,100 15,000
30,000230 v 2 36 50,100 72 50,100 108 67,100 15,000 30,000380 v 2
25 50,100 51 50,100 76 67,100 15,000 30,000460 v 2 36 50,100 72
50,100 108 67,100 15,000 30,000575 v 2 36 50,100 72 50,100 108
67,100 15,000 30,000
50P5075-100460 v 2 — — 108 67,100 216 50,100 15,000 44,000
Ratings and capacities (cont)
-
13
CAPACITY CONTROL STAGING SEQUENCES
SIZES 030,035
*Hot Gas Bypass.SIZES 030,035 WITH DIGITAL COMPRESSOR
*On units with optional digital scroll compressor, compressor A1
modu-lates from minimum to maximum capacity to provide increased
stages.
SIZE 040 WITH HGBP
*Hot Gas Bypass.SIZE 040 WITH DIGITAL COMPRESSOR
*On units with optional digital scroll compressor, compressor A1
modu-lates from minimum to maximum capacity to provide increased
stages.
SIZE 040 WITHOUT HGBP
COMP
STAGE0 1* 1 2
Compressor StatusA1 OFF ON ON ONB1 OFF OFF OFF ON
UNIT Capacity 48/50P030 0% 36% 50% 100%035 0% 38% 50% 100%
COMP
STAGE0 1 2
Compressor StatusA1* OFF ON ONB1 OFF OFF ON
UNIT Capacity 48/50P030 0% 25% to 50% 75% to 100%035 0% 25% to
50% 75% to 100%
COMP
STAGE0 1* 1 2 3
Compressor StatusA1 OFF ON ON ON ONB1 OFF OFF OFF ON ONB2 OFF
OFF OFF OFF ON
UNIT Capacity 48/50P040 0% 36% 47% 73% 100%
COMP
STAGE0 1 2 3
Compressor StatusA1* OFF ON ON ONB1 OFF OFF ON ONB2 OFF OFF OFF
ON
UNIT Capacity 48/50P040 0% 23% to 47% 50% to 73% 77% to 100%
COMP
STAGE0 1 2 3 4
Compressor StatusA1 OFF OFF ON ON ONB1 OFF ON OFF ON ONB2 OFF
OFF OFF OFF ON
UNIT Capacity 48/50P040 0% 27% 47% 73% 100%
-
14
CAPACITY CONTROL STAGING SEQUENCES (CONT)
SIZES 050-075
*Hot Gas Bypass.SIZES 050-075 WITH DIGITAL COMPRESSOR
* On units with optional digital scroll compressor, compressor
A1 modu-lates from minimum to maximum capacity to provide increased
stages.
SIZES 090-100
*Hot Gas Bypass.SIZES 090-100 WITH DIGITAL COMPRESSOR
* On units with optional digital scroll compressor, compressor
A1 modu-lates from minimum to maximum capacity to provide increased
stages.
COMP
STAGE0 1* 1 2 3 4
Compressor StatusA1 OFF ON ON ON ON ONA2 OFF OFF OFF OFF ON ONB1
OFF OFF OFF ON ON ONB2 OFF OFF OFF OFF OFF ON
UNIT Capacity 48/50P050 0% 15% 23% 50% 73% 100%055 0% 17% 25%
50% 75% 100%060 0% 18% 25% 50% 75% 100%070 0% 16% 23% 46% 73%
100%075 0% 19% 25% 50% 75% 100%
COMP
STAGE0 1 2 3 4
Compressor StatusA1* OFF ON ON ON ONA2 OFF OFF OFF ON ONB1 OFF
OFF ON ON ONB2 OFF OFF OFF OFF ON
UNIT Capacity 48/50P050 0% 12% to 23% 38% to 50% 62% to 73% 88%
to 100%055 0% 13% to 25% 38% to 50% 63% to 75% 88% to 100%060 0%
13% to 25% 38% to 50% 63% to 75% 88% to 100%070 0% 11% to 23% 34%
to 46% 61% to 73% 89% to 100%075 0% 13% to 25% 38% to 50% 63% to
75% 88% to 100%
COMP
STAGE0 1* 1 2 3 4 5 6
Compressor StatusA1 OFF ON ON ON ON ON ON ONA2 OFF OFF OFF OFF
ON ON ON ONA3 OFF OFF OFF OFF OFF OFF ON ONB1 OFF OFF OFF ON ON ON
ON ONB2 OFF OFF OFF OFF OFF ON ON ONB3 OFF OFF OFF OFF OFF OFF OFF
ON
UNIT Capacity 48/50P090 0% 12% 17% 33% 50% 67% 83% 100%100 0%
11% 15% 33% 49% 67% 82% 100%
COMP
STAGE0 1 2 3 4 5 6
Compressor StatusA1* OFF ON ON ON ON ON ONA2 OFF OFF OFF ON ON
ON ONA3 OFF OFF OFF OFF OFF ON ONB1 OFF OFF ON ON ON ON ONB2 OFF
OFF OFF OFF ON ON ONB3 OFF OFF OFF OFF OFF OFF ON
UNIT Capacity 48/50P090 0% 8% to 17% 25% to 33% 42% to 50% 58%
to 67% 75% to 83% 92% to 100%100 0% 8% to 15% 26% to 33% 41% to 49%
59% to 67% 74% to 82% 92% to 100%
Ratings and capacities (cont)
-
15
48P 030,035
LEGEND
BASE UNIT 48P 030 48P 035NOMINAL CAPACITY (tons) 30 35OPERATING
WEIGHT (lb) Standard Chassis Extended Chassis Standard Chassis
Extended Chassis
Base UnitLow Heat 5310 5810 5410 5910High Heat 5440 5940 5540
6040
With EconomizerLow Heat 5610 6110 5710 6210High Heat 5740 6240
5840 6340
COMPRESSORS ScrollQuantity...Type 1...ZP154/1...ZP154
1...ZP182/1...ZP182Oil Charge (oz) per Compressor 110 110Number of
Refrigerant Circuits 2 2
REFRIGERANT R-410AOperating Charge (lb), Ckt 1/Ckt 2
Standard Evaporator Coil 15.4/14.8 17.1/17.5Standard Evaporator
with Humidi-MiZer® System 15.4/24.9 17.1/27.6Alternate
High-Capacity Evaporator Coil 18.8/17.8 N/AAlternate High-Capacity
Evaporator with Humidi-MiZer 18.8/27.9 N/A
CONDENSER COILS Aluminum Novation® Heat Exchanger with
Microchannel CoilsQuantity 1 1Total Face Area (sq ft) 33.3 33.3
EVAPORATOR COILSQuantity 1Total Face Area (sq ft)
32.1Refrigerant Feed Device...No. per Circuit TXV...1Standard
Evaporator Coils
Rows...Fins/in. 3...15.0 4...15.0Fin Type Double Wavy Double
WavyTube Type Cross Hatched Cross Hatched
Alternate, High-Capacity Evaporator CoilsRows...Fins/in.
4...15.0 N/AFin Type Double Wavy N/ATube Type Cross Hatched N/A
OPTIONAL HUMIDI-MIZER ADAPTIVE DEHUMIDIFICATION SYSTEM Coil
Construction E-Coated Aluminum Novation® Heat Exchanger with
Microchannel Coil Technology Quantity 1 1 Face Area (sq ft) 26.7
26.7OPTIONAL HYDRONIC HEAT COIL ½-in. OD copper tubes, aluminum
plate fins, galvanized steel frame
Face Area (sq ft) 22.6 22.6 Rows...Fins Per Inch 2...8 2...8
Circuit Arrangement Half Half Connections — (Qty) Dim Supply (in.)
Return (in.)
(1) 2 1/2 NPT(1) 2 1/2 NPT
(1) 2 1/2 NPT(1) 2 1/2 NPT
Header Material Steel Steel Internal Volumes (cu ft) 0.5272
0.5272HEATING SECTION Low Heat High Heat Low Heat High Heat
Number of Heat Exchangers 7 14 7 14Input (MBtuh) 325 650 325
650Output (MBtuh) (Vertical/Horizontal) 263/260 527/520 263/260
527/520Temperature Rise Range (F) 10-40 25-55 10-40 25-55Efficiency
(%) (Vertical/Horizontal) 81/80 81/80 81/80 81/80Burner Orifice
Diameter
Quantity (in. ...drill no.) 7 (.1285...30) 14 (.1285...30) 7
(.1258...30) 14 (.1258...30)Manifold Pressure (in. wg) 3.5 3.5 3.5
3.5Line Pressure (in. wg) (min...max) 5.0...13.0 5.0...13.0
5.0...13.0 5.0...13.0Firing Stages 2 2 2 2Number of Gas Valves 1 2
1 2
CONDENSER FANS Propeller TypeQuantity...Diameter (in.) 2...30
2...30Nominal Cfm 18,000 19,500Motor Hp...Rpm 1.0...1140
1.0...1140
SUPPLY FAN Centrifugal 25 x 25 in.Nominal Cfm 12,000
14,000Maximum Allowable Cfm 15,000 15,000Maximum Allowable Rpm 900
900Shaft Diameter at Pulley (in.) 111/16 111/16
SUPPLY-FAN MOTOR AND DRIVE (Any motor available on any
unit)Motor Hp 7.5 10 15 20 25Motor Frame Size 213T 215T 254T 256T
284TEfficiency at Full Load (%) 91.7 91.7 93.0 93.6 93.6Fan Pulley
Pitch Diameter (in.) 13.7 13.7 13.7 13.7 13.7Motor Pulley Pitch
Diameter (in.) 3.4 4.3 4.9 5.5 6.5Resulting Fan Speed (rpm) 438 549
626 703 830 Belts Quantity...Type 2...BX60 2...5VX630 2...5VX630
2...5VX630 2...5VX650Center Distance Range (in.) 17.74-14.30
17.74-14.30 17.63...14.01 17.63...14.01 16.63...12.87
MBtuh — Btuh in ThousandsTXV — Thermostatic Expansion Valve
Physical data — 48 series units
-
16
48P 030,035 (CONT)
LEGEND
BASE UNIT 48P 030 48P 035NOMINAL CAPACITY (tons) 30 35OPTIONAL
POWER EXHAUST Centrifugal, 18 x 15 in. (Any motor available on any
unit)
Quantity...Motor Hp 2...3.0 2...5.0 2...7.5 2...10Motor Frame
Size 182T 184T 213T 215TEfficiency at Full Load (%) 88.5 89.5 91.7
91.7Fan Pulley Pitch Diameter (in.) 11.0 10.4 12 12Motor Pulley
Pitch Diameter Range (in.) 4.1-3.1 4.7-3.7 6.0-4.8 7.0-5.8Motor
Pulley Pitch Diameter Factory Setup (in.) 4.1 4.2 5.4 6.4Blower
Shaft Diameter at Pulley (in.) 17/16 17/16 17/16 17/16Fan Rpm Range
500-656 621-785 717-882 854-1000Factory Setup Fan Rpm 656 703 800
927Maximum Allowable Rpm 1000 1000 1000 1000
OPTIONAL RETURN FAN Plenum Fan, 30 in. (Any motor available on
any unit)Quantity …Motor HP 1…10 1…15 1…20 1…25Motor Frame Size
215T 254T 256T 284TEfficiency at Full Load (%) 91.7 93 93.6 93.6Fan
Pulley Pitch Diameter (in.) 6.6 7.4 6.8 8Motor Pulley Pitch
Diameter (in.) 4.9 6.6 6.6 8Shaft Diameter at Pulley (in.) 1-7/16
1-7/16 1-7/16 1-7/16Resulting Fan Rpm 1300 1540 1700 1730Maximum
Allowable Rpm 1750 1750 1750 1750
FILTERSStandard Efficiency Throwaway (Standard)
Quantity...Size (in.) 8...20 x 25 x 2, 8...20 x 20 x 2 8...20 x
25 x 2, 8...20 x 20 x 2Medium Efficiency (30%) Pleated
(Optional)
Quantity...Size (in.) 8...20 x 25 x 2, 8...20 x 20 x 2 8...20 x
25 x 2, 8...20 x 20 x 2High Efficiency (90%) Bag Filters
with High Velocity Prefilters (Opt)Quantity...Size (in.)
Bag Filter 6...20 x 24 x 22, 6...20 x 20 x 22 6...20 x 24 x 22,
6...20 x 20 x 22Prefilter 12...16 x 20 x 2, 3...20 x 24 x 2 12...16
x 20 x 2, 3...20 x 24 x 2
Cartridge Filters with High Velocity Prefilters
(Opt)Quantity...Size (in.)
Cartridge Filter 6...20 x 24 x 12, 6...20 x 20 x 12 6...20 x 24
x 12, 6...20 x 20 x 12Prefilter 12...16 x 20 x 2, 3...20 x 24 x 2
12...16 x 20 x 2, 3...20 x 24 x 2
OUTSIDE AIR SCREENSStandard Hood (25%) Quantity...Size (in.)
None None
OPTIONAL ECONOMIZER FILTER Aluminum Frame, Permanent
Quantity...Size (in.) 5...20 x 20 x 22...20 x 25 x 15...20 x 20
x 12...20 x 25 x 1
MBtuh — Btuh in ThousandsTXV — Thermostatic Expansion Valve
Physical data — 48 series units (cont)
-
17
48P 040,050
LEGEND
* 460-3-60 only.
BASE UNIT 48P 040 48P 050NOMINAL CAPACITY (tons) 40 50OPERATING
WEIGHT (lb) Standard Chassis Extended Chassis Standard Chassis
Extended Chassis
Base UnitLow Heat 5810 6310 6025 6525High Heat 5940 6440 6155
6655
With EconomizerLow Heat 6110 6610 6325 6825High Heat 6240 6740
6455 6955
COMPRESSORS ScrollQuantity...Type 2...ZP103/1...ZP182
2...ZP120/2...ZP137Oil Charge (oz) per Compressor 110 110Number of
Refrigerant Circuits 2 2
REFRIGERANT R-410AOperating Charge (lb), Ckt 1/Ckt 2
Standard Evaporator Coil 22.6/27.9 29.4/29.0Standard Evaporator
with Humidi-MiZer® System 22.6/40.6 29.4/41.4Alternate
High-Capacity Evaporator Coil 31.1/37.2 35.2/36.5Alternate
High-Capacity Evaporator with Humidi-MiZer 31.1/49.6 35.2/48.9
CONDENSER COILS Aluminum Novation® Heat Exchanger with
Microchannel CoilsQuantity 2 2Total Face Area (sq ft) 66.7 66.7
EVAPORATOR COILSQuantity 2Total Face Area (sq ft)
45.5Refrigerant Feed Device...No. per Circuit TXV...2Standard
Evaporator Coils
Rows...Fins/in. 3...15.0 4...15.0Fin Type Double Wavy Double
WavyTube Type Cross Hatched Cross Hatched
Alternate, High-Capacity Evaporator CoilsRows...Fins/in.
6...16.0 6...16.0Fin Type Double Wavy Double WavyTube Type Cross
Hatched Cross Hatched
OPTIONAL HUMIDI-MIZER ADAPTIVE DEHUMIDIFICATION SYSTEM Coil
Construction E-Coated Aluminum Novation® Heat Exchanger with
Microchannel Coil Technology Quantity 1 1 Face Area (sq ft) 26.7
26.7OPTIONAL HYDRONIC HEAT COIL ½-in. OD copper tubes, aluminum
plate fins, galvanized steel frame
Face Area (sq ft) 22.6 22.6 Rows...Fins Per Inch 2...8 2...8
Circuit Arrangement Half Half Connections — (Qty) Dim Supply (in.)
Return (in.)
(1) 2 1/2 NPT(1) 2 1/2 NPT
(1) 2 1/2 NPT(1) 2 1/2 NPT
Header Material Steel Steel Internal Volumes (cu ft) 0.5272
0.5272HEATING SECTION Low Heat High Heat Low Heat High Heat
Number of Heat Exchangers 7 14 7 14Input (MBtuh) 325 650 325
650Output (MBtuh) (Vertical/Horizontal) 263/260 527/520 263/260
527/520Temperature Rise Range (F) 10-40 25-55 10-40 25-55Efficiency
(%) (Vertical/Horizontal) 81/80 81/80 81/80 81/80Burner Orifice
Diameter
Quantity (in. ...drill no.) 7 (.1285...30) 14 (.1285...30) 7
(.1285...30) 14 (.1285...30)Manifold Pressure (in. wg) 3.5 3.5 3.5
3.5Line Pressure (in. wg) (min...max) 5.0...13.0 5.0...13.0
5.0...13.0 5.0...13.0Firing Stages 2 2 2 2Number of Gas Valves 1 2
1 2
CONDENSER FANS Propeller TypeQuantity...Diameter (in.) 3...30
4...30Nominal Cfm 30,000 38,000Motor Hp...Rpm 1.0...1140
1.0...1140
SUPPLY FAN Centrifugal 25 x 25 in.Nominal Cfm 16,000
20,000Maximum Allowable Cfm 20,000 20,000Maximum Allowable Rpm 900
900Shaft Diameter at Pulley (in.) 111/16 111/16
SUPPLY-FAN MOTOR AND DRIVE (Any motor available on any
unit)Motor Hp 7.5 10 15 20 25 30*Motor Frame Size 213T 215T 254T
256T 284T 286TEfficiency at Full Load (%) 91.7 91.7 93.0 93.6 93.6
93.6Fan Pulley Pitch Diameter (in.) 13.7 13.7 13.7 13.7 13.7
12.5Motor Pulley Pitch Diameter (in.) 3.4 4.3 4.9 5.5 6.5
6.5Resulting Fan Speed (rpm) 438 549 626 703 830 910Belts
Quantity...Type 2...BX60 2...5VX630 2...5VX630 2...5VX630
2...5VX650 3...5VX630Center Distance Range (in.) 17.74-14.30
17.74-14.30 17.63...14.01 17.63...14.01 16.63...12.87
16.63...12.87
MBtuh — Btuh in ThousandsTXV — Thermostatic Expansion Valve
-
18
48P 040,050 (CONT)
LEGEND
BASE UNIT 48P 040 48P 050NOMINAL CAPACITY (tons) 40 50OPTIONAL
POWER EXHAUST Centrifugal, 18 x 15 in. (Any motor available on any
unit)
Quantity...Motor Hp 2...3.0 2...5.0 2...7.5 2...10Motor Frame
Size 182T 184T 213T 215TEfficiency at Full Load (%) 88.5 89.5 91.7
91.7Fan Pulley Pitch Diameter (in.) 11.0 10.4 12 12Motor Pulley
Pitch Diameter Range (in.) 4.1-3.1 4.7-3.7 6.0-4.8 7.0-5.8Motor
Pulley Pitch Diameter Factory Setup (in.) 4.1 4.2 5.4 6.4Blower
Shaft Diameter at Pulley (in.) 17/16 17/16 17/16 17/16Fan Rpm Range
500-656 621-785 717-882 854-1000Factory Setup Fan Rpm 656 703 800
927Maximum Allowable Rpm 1000 1000 1000 1000
OPTIONAL RETURN FAN Plenum Fan, 30 in. (Any motor available on
any unit)Quantity …Motor HP 1…10 1…15 1…20 1…25Motor Frame Size
215T 254T 256T 284TEfficiency at Full Load (%) 91.7 93 93.6 93.6Fan
Pulley Pitch Diameter (in.) 6.6 7.4 6.8 8Motor Pulley Pitch
Diameter (in.) 4.9 6.6 6.6 8Shaft Diameter at Pulley (in.) 1-7/16
1-7/16 1-7/16 1-7/16Resulting Fan Rpm 1300 1540 1700 1730Maximum
Allowable Rpm 1750 1750 1750 1750
FILTERSStandard Efficiency Throwaway (Standard)
Quantity...Size (in.) 8...20 x 25 x 2, 8...20 x 20 x 2 8...20 x
25 x 2, 8...20 x 20 x 2Medium Efficiency (30%) Pleated
(Optional)
Quantity...Size (in.) 8...20 x 25 x 2, 8...20 x 20 x 2 8...20 x
25 x 2, 8...20 x 20 x 2High Efficiency (90%) Bag Filters
with High Velocity Prefilters (Opt)Quantity...Size (in.)
Bag Filter 6...20 x 24 x 22, 6...20 x 20 x 22 6...20 x 24 x 22,
6...20 x 20 x 22Prefilter 12...16 x 20 x 2, 3...20 x 24 x 2 12...16
x 20 x 2, 3...20 x 24 x 2
Cartridge Filters with High Velocity Prefilters
(Opt)Quantity...Size (in.)
Cartridge Filter 6...20 x 24 x 12, 6...20 x 20 x 12 6...20 x 24
x 12, 6...20 x 20 x 12Prefilter 12...16 x 20 x 2, 3...20 x 24 x 2
12...16 x 20 x 2, 3...20 x 24 x 2
OUTSIDE AIR SCREENSStandard Hood (25%) Quantity...Size (in.)
None None
OPTIONAL ECONOMIZER FILTER Aluminum Frame, Permanent
Quantity...Size (in.) 5...20 x 20 x 22...20 x 25 x 15...20 x 20
x 12...20 x 25 x 1
MBtuh — Btuh in ThousandsTXV — Thermostatic Expansion Valve
Physical data — 48 series units (cont)
-
19
48P 055-070
LEGEND
BASE UNIT 48P 055 48P 060 48P 070NOMINAL CAPACITY (tons) 55 60
70OPERATING WEIGHT (lb) Standard Chassis Extended Chassis Standard
Chassis Extended Chassis Standard Chassis Extended Chassis
Base UnitLow Heat 7810 8360 7865 8415 8205 8755High Heat 7940
8490 7995 8545 8335 8885
With EconomizerLow Heat 8340 8890 8395 8945 8735 9285High Heat
8470 9020 8525 9075 8865 9415
COMPRESSORS ScrollQuantity...Type 2...ZP137/2...ZP137
2...ZP154/2...ZP154 1...ZP154,1...ZP182Oil Charge (oz) per
Compressor 110 110 110Number of Refrigerant Circuits 2 2 2
REFRIGERANT R-410AOperating Charge (lb), Ckt 1/Ckt 2
Standard Evaporator Coil 37.6/37.9 37.6/37.9 41.2/44.8Standard
Evaporator with Humidi-MiZer®
System 37.6/50.3 37.6/50.3 41.2/57.2
Alternate High-Capacity Evaporator Coil 43.5/42.8 44.6/43.5
52.5/52.0Alternate High-Capacity Evaporator with
Humidi-MiZer43.5/55.2 44.6/55.9 52.5/64.4
CONDENSER COILS Aluminum Novation® Heat Exchanger with
Microchannel CoilsQuantity 2 2 4Total Face Area (sq ft) 66.7 66.7
106.7
EVAPORATOR COILSQuantity 2Total Face Area (sq ft)
61.5Refrigerant Feed Device...No. per Circuit TXV...2Standard
Evaporator Coils
Rows...Fins/in. 4...15 4...15 4...15Fin Type Double Wavy Double
Wavy Double WavyTube Type Cross Hatched Cross Hatched Cross
Hatched
Alternate, High-Capacity Evaporator CoilsRows...Fins/in. 6...16
6...16 6...16Fin Type Double Wavy Double Wavy Double WavyTube Type
Cross Hatched Cross Hatched Cross Hatched
OPTIONAL HUMIDI-MIZER ADAPTIVE DEHUMIDIFICATION SYSTEM Coil
Construction E-Coated Aluminum Novation® Heat Exchanger with
Microchannel Coil Technology Quantity 1 1 1 1 1 1 Face Area (sq ft)
26.7 26.7 26.7 26.7 26.7 26.7OPTIONAL HYDRONIC HEAT COIL ½-in. OD
copper tubes, aluminum plate fins, galvanized steel frame
Face Area (sq ft) (2) sections: total 27.1 (2) sections: total
27.1 (2) sections: total 27.1 Rows...Fins Per Inch 2...11 2...11
2...11 Circuit Arrangement Half Half Half Connections — (Qty) Dim
Supply (in.) Return (in.)
(2) 1 1/2 NPT(2) 1 1/2 NPT
(2) 1 1/2 NPT(2) 1 1/2 NPT
(2) 1 1/2 NPT(2) 1 1/2 NPT
Header Material Steel Steel Steel Internal Volumes (cu ft)
0.6327 0.6327 0.6327HEATING SECTION Low Heat High Heat Low Heat
High Heat Low Heat High Heat
Number of Heat Exchangers 14 21 14 21 14 21Input (MBtuh) 650 975
650 975 650 975Output (MBtuh) (Vertical/Horizontal) 525/520 787/780
525/520 787/780 525/520 787/780Temperature Rise Range (F) 10-40
20-50 10-40 20-50 10-40 20-50Efficiency (%) (Vertical/Horizontal)
81/80 81/80 81/80 81/80 81/80 81/80Burner Orifice Diameter
Quantity (in. ...drill no.) 14 (.1285...30) 21 (.1285...30) 14
(.1285...30) 21 (.1285...30) 14 (.1285...30) 21
(.1285...30)Manifold Pressure (in. wg) 3.5 3.5 3.5 3.5 3.5 3.5Line
Pressure (in. wg) (min...max) 5.0...13.0 5.0...13.0 5.0...13.0
5.0...13.0 5.0...13.0 5.0...13.0Firing Stages 2 2 2 2 2 2Number of
Gas Valves 2 3 2 3 2 3
CONDENSER FANS Propeller TypeQuantity...Diameter (in.) 4...30
4...30 4...30Nominal Cfm 36,000 36,600 39,000Motor Hp...Rpm
1.0...1140 1.0...1140 1.0...1140
SUPPLY FAN Centrifugal 30 x 27.5 in.Nominal Cfm 22,000 24,000
28,000Maximum Allowable Cfm 25,000 30,000 30,000Maximum Allowable
Rpm 800 800 800Shaft Diameter at Pulley (in.) 111/16 111/16
111/16
SUPPLY-FAN MOTOR AND DRIVE (Any motor available on any
unit)Motor Hp 15 20 25 30 40Motor Frame Size 254T 256T 284T 286T
S324TEfficiency at Full Load (%) 93.0 93.6 93.6 93.6 94.5Fan Pulley
Pitch Diameter (in.) 13.7 13.7 13.7 15.5 16.1Motor Pulley Pitch
Diameter (in.) 4.5 5.1 5.5 5.9 6.7Resulting Fan Speed (rpm) 575 651
703 711 740
Belts Quantity...Type 2...5VX1230 2...5VX1230 2...5VX1230
2...5VX1230 3...5VX1250
Center Distance Range (in.) 48.25-44.00 48.25-44.00 48.50-44.25
48.50-44.25 48.25-44.00
MBtuh — Btuh in ThousandsTXV — Thermostatic Expansion Valve
-
20
48P 055-070 (CONT)
LEGEND
BASE UNIT 48P 055 48P 060 48P 070NOMINAL CAPACITY (tons) 55 60
70OPTIONAL POWER EXHAUST Centrifugal, 18 x 15 in. (Any motor
available on any unit)
Quantity...Motor Hp 2...5 2...7.5 2...10Motor Frame Size 184T
213T 215TEfficiency at Full Load (%) 89.5 91.7 91.7Resulting Fan
Rpm 740 820 920Maximum Allowable Rpm 1000 1000 1000
OPTIONAL RETURN FAN Plenum Fan, 36 in. (Any motor available on
any unit)Quantity …Motor HP 1…15 1…20 1…25 1…30Motor Frame Size
254T 256T 284T 286TEfficiency at Full Load (%) 93 93.6 93.6 93.6Fan
Pulley Pitch Diameter (in.) 9.1 9.1 9.1 9.1Motor Pulley Pitch
Diameter (in.) 5.9 6.1 6.7 6.9Shaft Diameter at Pulley (in.)
1-11/16 1-11/16 1-11/16 1-11/16Resulting Fan Rpm 1150 1200 1300
1327Maximum Allowable Rpm 1750 1750 1750 1750
FILTERSStandard Efficiency Throwaway (Standard)
Quantity...Size (in.) 12...20 x 25 x 2, 12...20 x 20 x 2 12...20
x 25 x 2, 12...20 x 20 x 2 12...20 x 25 x 2, 12...20 x 20 x 2Medium
Efficiency (30%) Pleated (Optional)
Quantity...Size (in.) 12...20 x 25 x 2, 12...20 x 20 x 2 12...20
x 25 x 2, 12...20 x 20 x 2 12...20 x 25 x 2, 12...20 x 20 x 2High
Efficiency (90%) Bag Filters
with High Velocity Prefilters (Optional)Quantity...Size
(in.)
Bag Filter 6...24 x 24 x 22, 6...24 x 20 x 22 6...24 x 24 x 22,
6...24 x 20 x 22 6...24 x 24 x 22, 6...24 x 20 x 22 Prefilter
6...24 x 24 x 2, 6...20 x 24 x 2 6...24 x 24 x 2, 6...20 x 24 x 2
6...24 x 24 x 2, 6...20 x 24 x 2
Cartridge Filters with High Velocity Prefilters (Optional)
Quantity...Size (in.) Cartridge Filter 6...24 x 24 x 12, 6...24
x 20 x 12 6...24 x 24 x 12, 6...24 x 20 x 12 6...24 x 24 x 12,
6...24 x 20 x 12 Prefilter 6...24 x 24 x 2, 6...20 x 24 x 2 6...24
x 24 x 2, 6...20 x 24 x 2 6...24 x 24 x 2, 6...20 x 24 x 2
OUTSIDE AIR SCREENSStandard Hood (25%) Quantity...Size (in.)
4...25 x 16 x 1, 2...20 x 16 x 1 4...25 x 16 x 1, 2...20 x 16 x 1
4...25 x 16 x 1, 2...20 x 16 x 1
OPTIONAL ECONOMIZER FILTER Aluminum Frame, Permanent
Quantity...Size (in.) 12...16 x 25 x 1, 2...16 x 20 x 1 12...16 x
25 x 1, 2...16 x 20 x 1 12...16 x 25 x 1, 2...16 x 20 x 1
MBtuh — Btuh in ThousandsTXV — Thermostatic Expansion Valve
Physical data — 48 series units (cont)
-
21
48P 075-100
LEGEND
BASE UNIT 48P 075 48P 090 48P 100NOMINAL CAPACITY (tons) 75 90
100OPERATING WEIGHT (lb) Standard
ChassisExtendedChassis
StandardChassis
ExtendedChassis
StandardChassis
ExtendedChassis
Base UnitLow Heat 9065 9615 9665 10,215 9685 10,235High Heat
9195 9745 9795 10,345 9815 10,365
With EconomizerLow Heat 9595 10,145 10,195 10,745 10,215
10,765High Heat 9725 10,275 10,325 10,875 10,345 10,895
COMPRESSORS ScrollQuantity...Type 2...ZP182/2...ZP182
3...ZP154,3...ZP154 3...ZP154,3...ZP182Oil Charge (oz) per
Compressor 110 110 110Number of Refrigerant Circuits 2 2 2
REFRIGERANT R-410AOperating Charge (lb), Ckt 1/Ckt 2
Standard Evaporator Coil 41.2/44.8 50.4/51.3 50.8/52.8Standard
Evaporator with Humidi-MiZer® System 41.2/57.2 50.4/69.1
50.8/70.6Alternate High-Capacity Evaporator Coil 52.5/52.0
61.5/62.9 59.3/62.8Alternate High-Capacity Evaporator
withHumidi-MiZer
52.5/64.4 61.5/80.7 59.3/80.6
CONDENSER COILS Aluminum Novation® Heat Exchanger with
Microchannel CoilsQuantity 4 6 6Total Face Area (sq ft) 106.7 160.0
160.0
EVAPORATOR COILSQuantity 2Total Face Area (sq ft)
61.5Refrigerant Feed Device...No. per Circuit TXV...2Standard
Evaporator Coils
Rows...Fins/in. 4...15 4...15 4...15Fin Type Double Wavy Double
Wavy Double WavyTube Type Cross Hatched Cross Hatched Cross
Hatched
Alternate, High-Capacity Evaporator CoilsRows...Fins/in. 6...16
6...16 6...16Fin Type Double Wavy Double Wavy Double WavyTube Type
Cross Hatched Cross Hatched Cross Hatched
OPTIONAL HUMIDI-MIZER® ADAPTIVE DEHUMIDIFICATION SYSTEM Coil
Construction E-Coated Aluminum Novation® Heat Exchanger with
Microchannel Coil Technology Quantity 1 1 1 Face Area (sq ft) 26.7
33.3 33.3OPTIONAL HYDRONIC HEAT COIL ½-in. OD copper tubes,
aluminum plate fins, galvanized steel frame
Face Area (sq ft) (2) sections: total 27.1 (2) sections: total
27.1 (2) sections: total 27.1 Rows...Fins Per Inch 2...11 2...11
2...11 Circuit Arrangement Half Half Half Connections — (Qty) Dim
Supply (in.) Return (in.)
(2) 1 1/2 NPT(2) 1 1/2 NPT
(2) 1 1/2 NPT(2) 1 1/2 NPT
(2) 1 1/2 NPT(2) 1 1/2 NPT
Header Material Steel Steel Steel Internal Volumes (cu ft)
0.6327 0.6327 0.6327
HEATING SECTION Low Heat High Heat Low Heat High Heat Low Heat
High HeatNumber of Heat Exchangers 2 3 2 3 2 3Input (MBtuh) 650 975
650 975 650 975Output (MBtuh) (Vertical/Horizontal) 526/520 784/780
526/520 784/780 526/520 784/780Temperature Rise Range (F) 10-40
20-50 10-40 20-50 10-40 20-50Efficiency (%) (Vertical/Horizontal)
81/80 81/80 81/80 81/80 81/80 81/80Burner Orifice Diameter
Quantity (in. ...drill no.) 7 (.1285...30) 7 (.1285...30) 7
(.1285...30) 7 (.1285...30) 7 (.1285...30) 7 (.1285...30)Manifold
Pressure (in. wg) 3.5 3.5 3.5 3.5 3.5 3.5Line Pressure (in. wg)
(Min...Max) 5.0...13.0 5.0...13.0 5.0...13.0 5.0...13.0 5.0...13.0
5.0...13.0Number of Gas Valves 2 3 2 3 2 3
CONDENSER FAN Propeller TypeQuantity...Diameter (in.) 4...30
6...30 6...30Nominal Cfm 39,000 58,000 58,000Motor Hp (ea)...rpm
1.0...1140 1.0...1140 1.0...1140
STANDARD SUPPLY FAN Forward Curved Centrifugal 36 x 30
in.Nominal Cfm 30,000 36,000 40,000Maximum Allowable Cfm 30,000
36,000 40,000Maximum Allowable Rpm 680 680 680Shaft Diameter at
Pulley (in.) 111/16 111/16 111/16
STANDARD SUPPLY-FAN MOTOR AND DRIVE (Any motor available on any
unit)Motor Hp 30 40 50 60Motor Frame Size S268T S324T S326T
S364TEfficiency at Full Load (%) 93.6 94.5 94.5 95.4Fan Pulley
Pitch Diameter (in.) 18.5 18.5 18.5 18.5Motor Pulley Pitch Diameter
(in.) 5.3 5.7 6.5 7.1Resulting Fan Rpm 501 539 615 672Belts
Quantity...Type 3...5VX1320 4...5VX1320 4...5VX1320
4...5VX1320Center Distance Range (in.) 47.88-45.01 47.64-44.76
47.42-44.52 47.42-44.52
DWDI — Double Width, Double InletMBtuh — Btuh in ThousandsSWSI —
Single Width, Single InletTXV — Thermostatic Expansion Valve
-
22
48P 075-100 (CONT)
LEGEND
BASE UNIT 48P 075 48P 090 48P 100ALTERNATE, AIRFOIL FAN DWDI
Airfoil, 33 in.
Nominal Airflow (cfm) 30,000 36,000 40,000Maximum Allowable
Airflow (cfm) 30,000 36,000 40,000Maximum Allowable Wheel Speed
(rpm) 1846 1846 1846Shaft Diameter at Pulley (in.) 211/16 211/16
211/16
ALTERNATE SUPPLY-FAN MOTOR AND DRIVE (Any motor available on any
unit)
Motor Hp 30 40 50 60 75Motor Frame Size S268T S324T S326T S364T
365TEfficiency at Full Load (%) 93.6 94.5 94.5 95.4 95.4Fan Pulley
Pitch Diameter (in.) 9.7 10.2 8.9 8.9 10.8Motor Pulley Pitch
Diameter (in.) 7.5 8.7 8.1 8.7 11.1Resulting Fan Rpm 1353 1493 1593
1711 1799Belts Quantity...Type 2...5VX1150 2...5VX1180 3...5VX1150
3...5VX1150 3...5VX1230Center Distance Range (in.) 42.96...45.82
42.96...45.57 42.96...45.57 42.45...45.35 42.45...45.35
OPTIONAL POWER EXHAUST Centrifugal, 18 x 15 in. (Any motor
available on any unit.)Quantity...Motor Hp 2...5 2...7.5
2...10Motor Frame Size 184T 213T 215TEfficiency at Full Load (%)
89.5 91.7 91.7Fan Pulley Pitch Diameter (in.) 10.6 10.6 10.6Motor
Pulley Pitch Diameter (in.) 4.5 5.0 5.6Shaft Diameter at Pulley
(in.) 17/16 17/16 17/16Resulting Fan Rpm 740 820 920Maximum
Allowable Rpm 1000 1000 1000
OPTIONAL HIGH-CAPACITY POWER EXHAUST
Centrifugal, 22 x 20 in., 111/16 in. shaft diameter (Any motor
available on any unit)
Total HpQuantity...Motor HpMotor Frame SizeEfficiency at Full
Load (%)Fan Sheave Pitch Diameter (in.)
Motor Sheave Pitch Diameter (in.)Resulting Fan Rpm
Maximum Allowable RpmBelts Quantity...Type
OPTIONAL RETURN FAN SWSI Plenum Fan, 47.13 in. (Any motor
available on any unit.)Quantity...Motor HpMotor Frame
SizeEfficiency at Full Load (%)Fan Pulley Pitch Diameter (in.)Motor
Pulley Pitch Diameter (in.)Shaft Diameter at Pulley (in.)Resulting
Fan RpmMaximum Allowable Rpm
FILTERSStandard Efficiency Throwaway (Standard)
Quantity...Size (in.) 12...20 x 25 x 2, 12...20 x 20 x 2 12...20
x 25 x 2, 12...20 x 20 x 2 12...20 x 25 x 2, 12...20 x 20 x 230%
and 65% Pleated (Optional)
Quantity...Size (in.) 12...20 x 25 x 2, 12...20 x 20 x 2 12...20
x 25 x 2, 12...20 x 20 x 2 12...20 x 25 x 2, 12...20 x 20 x
2OUTSIDE AIR SCREENS
Standard Hood (25%) Quantity...Size (in.) 4...25 x 16 x 1,
2...20 x 16 x 1 4...25 x 16 x 1, 2...20 x 16 x 1 4...25 x 16 x 1,
2...20 x 16 x 1OPTIONAL ECONOMIZER FILTER Aluminum Frame,
Permanent
Quantity...Size (in.) 12...16 x 25 x 1, 2...16 x 20 x 1 12...16
x 25 x 1, 2...16 x 20 x 1 12...16 x 25 x 1, 2...16 x 20 x 1
20 30 40 50 602...10 2...15 2...20 2...25 2...30S215T D254T
S256T S284T S286T
91.7 93.0 93.6 93.6 93.612.4 12.4 11.1 11.1 11.14.8 5.8 5.9 6.5
6.9714 841 928 1020 10941175 1175 1175 1175 1175
1...20 1...25 1...30 1...40256T 284T 286T 324T93.6 93.6 93.6
93.88.5 9.8 8.5 8.55.3 6.7 6.1 6.7
215/16 215/16 215/16 215/161104 1209 1271 13961447 1447 1447
1447
DWDI — Double Width, Double InletMBtuh — Btuh in ThousandsSWSI —
Single Width, Single InletTXV — Thermostatic Expansion Valve
Physical data — 48 series units (cont)
-
23
48P 030,035 WITH RETURN/EXHAUST FAN OPTION
LEGEND
BASE UNIT 48P 030 48P 035NOMINAL CAPACITY (tons) 30 35OPERATING
WEIGHT (lb) (without IFM or R/E FM/VFD) Standard Chassis Extended
Chassis Standard Chassis Extended Chassis
Base Unit (with Econ)Low Heat 6123 6623 6223 6723High Heat 6253
6753 6353 6853
COMPRESSORS ScrollQuantity …type, Ckt 1 / Ckt 2 1...ZP154 /
1...ZP154 1...ZP182 / 1...ZP182
Oil Charge (oz) per Compressor 110 110Capacity Steps (%) CV 50,
100 50, 100 VAV (with digital scroll) 25 to 100 25 to 100Number of
Refrigerant Circuits 2 2REFRIGERANT R-410A
Operating Charge (lb), Ckt 1 / Ckt 2Standard Evaporator Coil
15.4 / 14.8 17.1 / 17.5Standard Evaporator with Humidi-MiZer®
System 15.4 / 24.9 17.1 / 27.6Alternate High-Capacity Evaporator
Coil 18.8/17.8 N/AAlternate High-Capacity Evaporator with
Humidi-MiZer 18.8/27.9 N/A
CONDENSER COILS Material, Type Aluminum Novation® Heat Exchanger
with Microchannel Coils
Quantity 1 1Total Face Area (sq ft) 33.3 33.3
EVAPORATOR COILSQuantity 1Total Face Area (sq ft)
32.1Refrigerant Feed Device...No. per Circuit TXV...1Standard
Evaporator Coils
Rows...Fins/in. 3...15.0 4...15.0Fin Type Double Wavy Double
WavyTube Type Cross Hatched Cross Hatched
Alternate, High-Capacity Evaporator CoilsRows...Fins/in.
4...15.0 N/AFin Type Double Wavy N/ATube Type Cross Hatched N/A
OPTIONAL HUMIDI-MIZER ADAPTIVE DEHUMIDIFICATION SYSTEM Material,
Type E-Coated Aluminum Novation® Heat Exchanger with Microchannel
Coil Technology Quantity 1 1 Total Face Area (sq ft) 26.7
26.7CONDENSER FANS Propeller Type
Quantity...Diameter (in.) 2...30 2...30Nominal Cfm 18,000
19,500Motor Hp...Rpm 1.0...1140 1.0...1140
HEATING SECTION Low Heat High Heat Low Heat High HeatManifold
Pressure (in. wg) 3.5 3.5 3.5 3.5
FM — Fan MotorIFM — Indoor Fan MotorR/E — Return ExhaustVFD —
Variable Frequency Drive
-
24
48P 040,050 WITH RETURN/EXHAUST FAN OPTION
LEGEND
BASE UNIT 48P 040 48P 050NOMINAL CAPACITY (tons) 40 50OPERATING
WEIGHT (lb) (without IFM or R/E FM/VFD) Standard Chassis Extended
Chassis Standard Chassis Extended Chassis
Base Unit (with Econ)Low Heat 6623 7123 6838 7338High Heat 6753
7253 6968 7468
COMPRESSORS ScrollQuantity …type, Ckt 1 / Ckt 2 2...ZP103 /
1...ZP182 2...ZP120 / 2...ZP137
Oil Charge (oz) per Compressor 110 110Capacity Steps (%) CV
47,73,100 23,50,73, 100 VAV (with digital scroll) 23 to 100 12 to
100Number of Refrigerant Circuits 2 2REFRIGERANT R-410A
Operating Charge (lb), Ckt 1 / Ckt 2Standard Evaporator Coil
22.6 / 27.9 29.4 / 29.0Standard Evaporator with Humidi-MiZer®
System 22.6 / 40.6 29.4 / 41.4Alternate High-Capacity Evaporator
Coil 31.1 / 37.2 35.2 / 36.5Alternate High-Capacity Evaporator with
Humidi-MiZer 31.1 / 49.6 35.2 / 48.9
CONDENSER COILS Material, Type Aluminum Novation® Heat Exchanger
with Microchannel Coils
Quantity 2 2Total Face Area (sq ft) 66.7 66.7
EVAPORATOR COILSQuantity 2Total Face Area (sq ft)
45.5Refrigerant Feed Device...No. per Circuit TXV...2Standard
Evaporator Coils
Rows...Fins/in. 3...15.0 4...15.0Fin Type Double Wavy Double
WavyTube Type Cross Hatched Cross Hatched
Alternate, High-Capacity Evaporator CoilsRows...Fins/in.
6...16.0 6...16.0Fin Type Double Wavy Double WavyTube Type Cross
Hatched Cross Hatched
OPTIONAL HUMIDI-MIZER ADAPTIVE DEHUMIDIFICATION SYSTEM Material,
Type E-Coated Aluminum Novation® Heat Exchanger with Microchannel
Coil Technology Quantity 1 1 Total Face Area (sq ft) 26.7
26.7CONDENSER FANS Propeller Type
Quantity...Diameter (in.) 3...30 4...30Nominal Cfm 30,000
38,000Motor Hp...Rpm 1.0...1140 1.0...1140
HEATING SECTION Low Heat High Heat Low Heat High HeatManifold
Pressure (in. wg) 3.5 3.5 3.5 3.5
FM — Fan MotorIFM — Indoor Fan MotorR/E — Return ExhaustVFD —
Variable Frequency Drive
Physical data — 48 series units (cont)
-
25
48P 055-070 WITH RETURN/EXHAUST FAN OPTION
LEGEND
BASE UNIT 48P 055 48P 060 48P 070NOMINAL CAPACITY (tons) 55 60
70OPERATING WEIGHT (lb) (without IFM or R/E FM/VFD) Standard
Chassis Extended Chassis Standard Chassis Extended Chassis Standard
Chassis Extended Chassis
Base Unit (with Econ)Low Heat 9215 9765 9270 9820 9610
10,160High Heat 9345 9895 9400 9950 9740 10,290
COMPRESSORS ScrollQuantity …type, Ckt 1 / Ckt 2 2...ZP137 /
2...ZP137 2...ZP154 / 2...ZP154 1...ZP154 / 1...ZP182
Oil Charge (oz) per Compressor 110 110 110Capacity Steps (%) CV
25,50,75,100 25,50,75,100 23,46,73,100 VAV (with digital scroll) 13
to 100 13 to 100 11 to 100Number of Refrigerant Circuits 2 2
2REFRIGERANT R-410A
Operating Charge (lb), Ckt 1 / Ckt 2Standard Evaporator Coil
37.6 / 37.9 37.6 / 37.9 41.2 / 44.8Standard Evaporator with
Humidi-MiZer®
System 37.6 / 50.3 37.6 / 50.3 41.2 / 57.2
Alternate High-Capacity Evaporator Coil 43.5 / 42.8 44.6 / 43.5
52.5 / 52.0Alternate High-Capacity Evaporator with
Humidi-MiZer43.5 / 55.2 44.6 / 55.9 52.5 / 64.4
CONDENSER COILS Material, Type Aluminum Novation® Heat Exchanger
with Microchannel Coils
Quantity 2 2 4Total Face Area (sq ft) 66.7 66.7 106.7
EVAPORATOR COILSQuantity 2Total Face Area (sq ft)
61.5Refrigerant Feed Device...No. per Circuit TXV...2Standard
Evaporator Coils
Rows...Fins/in. 4...15 4...15 4...15Fin Type Double Wavy Double
Wavy Double WavyTube Type Cross Hatched Cross Hatched Cross
Hatched
Alternate, High-Capacity Evaporator CoilsRows...Fins/in. 6...16
6...16 6...16Fin Type Double Wavy Double Wavy Double WavyTube Type
Cross Hatched Cross Hatched Cross Hatched
OPTIONAL HUMIDI-MIZER ADAPTIVE DEHUMIDIFICATION SYSTEM Material,
Type E-Coated Aluminum Novation® Heat Exchanger with Microchannel
Coil Technology Quantity 1 1 1 Total Face Area (sq ft) 26.7 26.7
26.7CONDENSER FANS Propeller Type
Quantity...Diameter (in.) 4...30 4...30 4...30Nominal Cfm 36,000
36,600 39,000Motor Hp...Rpm 1.0...1140 1.0...1140 1.0...1140
HEATING SECTION Low Heat High Heat Low Heat High Heat Low Heat
High HeatManifold Pressure (in. wg) 3.5 3.5 3.5 3.5 3.5 3.5
FM — Fan MotorIFM — Indoor Fan MotorR/E — Return ExhaustVFD —
Variable Frequency Drive
-
26
48P 075-100 WITH RETURN/EXHAUST FAN OPTION
LEGEND
BASE UNIT 48P 075 48P 090 48P 100NOMINAL CAPACITY (tons) 75 90
100OPERATING WEIGHT (lb) (without IFM or R/E FM/VFD) Standard
Chassis Extended Chassis Standard Chassis Extended Chassis Standard
Chassis Extended Chassis
Base Unit (with Econ)Low Heat 10618 11168 11218 11768 11238
11788High Heat 10748 11298 11348 11898 11368 11918
COMPRESSORS ScrollQuantity …type, Ckt 1 / Ckt 2 2...ZP182 /
2...ZP182 3...ZP154,3...ZP154 3...ZP154,3...ZP182
Oil Charge (oz) per Compressor 110 110 110Capacity Steps (%) CV
25, 50, 75, 100 17, 33, 50, 67, 83, 100 15, 33, 49, 67, 82, 100 VAV
(with digital scroll) 13 to 100 8 to 100 8 to 100Number of
Refrigerant Circuits 2 2 2REFRIGERANT R-410A
Operating Charge (lb), Ckt 1 / Ckt 2Standard Evaporator Coil
41.2 / 44.8 50.4 / 51.3 50.8 / 52.8Standard Evaporator with
Humidi-MiZer®
System 41.2 / 57.2 50.4 / 69.1 50.8 / 70.6
Alternate High-Capacity Evaporator Coil 52.5 / 52.0 61.5 / 62.9
59.3 / 62.8Alternate High-Capacity Evaporator with
Humidi-MiZer52.5 / 64.4 61.5 / 80.7 59.3 / 80.6
CONDENSER COILS Material, Type Aluminum Novation® Heat Exchanger
with Microchannel Coils
Quantity 4 6 6Total Face Area (sq ft) 106.7 160.0 160.0
EVAPORATOR COILSQuantity 2Total Face Area (sq ft)
61.5Refrigerant Feed Device...No. per Circuit TXV...2Standard
Evaporator Coils
Rows...Fins/in. 4...15 4...15 4...15Fin Type Double Wavy Double
Wavy Double WavyTube Type Cross Hatched Cross Hatched Cross
Hatched
Alternate, High-Capacity Evaporator CoilsRows...Fins/in. 6...16
6...16 6...16Fin Type Double Wavy Double Wavy Double WavyTube Type
Cross Hatched Cross Hatched Cross Hatched
OPTIONAL HUMIDI-MIZER ADAPTIVE DEHUMIDIFICATION SYSTEM Material,
Type E-Coated Aluminum Novation® Heat Exchanger with Microchannel
Coil Technology Quantity 1 1 1 Total Face Area (sq ft) 26.7 33.3
33.3CONDENSER FANS Propeller Type
Quantity...Diameter (in.) 4...30 6...30 6...30Nominal Cfm 39,000
58,000 58,000Motor Hp...Rpm 1.0...1140 1.0...1140 1.0...1140
HEATING SECTION Low Heat High Heat Low Heat High Heat Low Heat
High HeatManifold Pressure (in. wg) 3.5 3.5 3.5 3.5 3.5 3.5
FM — Fan MotorIFM — Indoor Fan MotorR/E — Return ExhaustVFD —
Variable Frequency Drive
Physical data — 48 series units (cont)
-
27
50P 030,035
LEGEND
BASE UNIT 50P 030 50P 035NOMINAL CAPACITY (tons) 30 35OPERATING
WEIGHT (lb) Standard Chassis Extended Chassis Standard Chassis
Extended Chassis
Base UnitVertical Discharge 4810 5310 4910 5410Horizontal
Discharge and Vertical Discharge
with Discharge Plenum 5110 5610 5210 5710
With EconomizerVertical Discharge 5110 5610 5210 5710Horizontal
Discharge and Vertical Discharge
with Discharge Plenum 5410 5910 5510 6010
COMPRESSORS ScrollQuantity...Type 1...ZP154/1...ZP154
1...ZP182/1...ZP182Oil Charge (oz) per Compressor 110 110Number of
Refrigerant Circuits 2 2
REFRIGERANT R-410AOperating Charge (lb), Ckt 1/Ckt 2
Standard Evaporator Coil 15.4/14.8 17.1/17.5Standard Evaporator
with Humidi-MiZer® System 15.4/24.9 17.1/27.6Alternate
High-Capacity Evaporator Coil 18.8/17.8 N/AAlternate High-Capacity
Evaporator with Humidi-MiZer 18.8/27.9 N/A
CONDENSER COILS Aluminum Novation® Heat Exchanger with
Microchannel CoilsQuantity 1 1Total Face Area (sq ft) 33.3 33.3
EVAPORATOR COILSQuantity 1Total Face Area (sq ft)
32.1Refrigerant Feed Device...No. per Circuit TXV...1Standard
Evaporator Coils
Rows...Fins/in. 3...15.0 4...15.0Fin Type Double Wavy Double
WavyTube Type Cross Hatched Cross Hatched
Alternate, High-Capacity Evaporator CoilsRows...Fins/in.
4...15.0 N/AFin Type Double Wavy N/ATube Type Cross Hatched N/A
OPTIONAL HUMIDI-MIZER® ADAPTIVE DEHUMIDIFICATION SYSTEM Coil
Construction E-Coated Aluminum Novation® Heat Exchanger with
Microchannel Coil Technology Quantity 1 1 1 1 Face Area (sq ft)
26.7 26.7 26.7 26.7OPTIONAL HYDRONIC HEAT COIL ½-in. OD copper
tubes, aluminum plate fins, galvanized steel frame
Face Area (sq ft) 22.6 22.6 Rows...Fins Per Inch 2...8 2...8
Circuit Arrangement Half Half Connections — (Qty) Dim Supply (in.)
Return (in.)
(1) 2 1/2 NPT(1) 2 1/2 NPT
(1) 2 1/2 NPT(1) 2 1/2 NPT
Header Material Steel Steel Internal Volumes (cu ft) 0.5272
0.5272CONDENSER FANS Propeller Type
Quantity...Diameter (in.) 2...30 2...30Nominal Cfm 18,000
19,500Motor Hp...Rpm 1.0...1140 1.0...1140
SUPPLY FAN Centrifugal 25 x 25 in.Nominal Cfm 12,000
14,000Maximum Allowable Cfm 15,000 15,000Maximum Allowable Rpm 900
900Shaft Diameter at Pulley (in.) 111/16 111/16
SUPPLY-FAN MOTOR AND DRIVE (Any motor available on any
unit)Motor Hp 7.5 10 15 20 25Motor Frame Size 213T 215T 254T 256T
284TEfficiency at Full Load (%) 91.7 91.7 93.0 93.6 93.6Fan Pulley
Pitch Diameter (in.) 13.7 13.7 13.7 13.7 13.7Motor Pulley Pitch
Diameter (in.) 3.4 4.3 4.9 5.5 6.5Resulting Fan Speed (rpm) 438 549
626 703 830 Belts Quantity...Type 2...BX60 2...5VX630 2...5VX630
2...5VX630 2...5VX650Center Distance Range (in.) 17.74-14.30
17.74-14.30 17.63...14.01 17.63...14.01 16.63...12.87
OPTIONAL POWER EXHAUST Centrifugal, 18 x 15 in. (Any motor
available on any unit)Quantity...Motor Hp 2...3.0 2...5.0 2...7.5
2...10Motor Frame Size 182T 184T 213T 215TEfficiency at Full Load
(%) 88.5 89.5 91.7 91.7Fan Pulley Pitch Diameter (in.) 11.0 10.4 12
12Motor Pulley Pitch Diameter Range (in.) 4.1-3.1 4.7-3.7 6.0-4.8
7.0-5.8Motor Pulley Pitch Diameter Factory Setup (in.) 4.1 4.2 5.4
6.4Blower Shaft Diameter at Pulley (in.) 17/16 17/16 17/16 17/16Fan
Rpm Range 500-656 621-785 717-882 854-1000Factory Setup Fan Rpm 656
703 800 927Maximum Allowable Rpm 1000 1000 1000 1000
TXV — Thermostatic Expansion Valve
Physical data — 50 series units
-
28
50P 030,035 (CONT) BASE UNIT 50P 030 50P 035NOMINAL CAPACITY
(tons) 30 35OPTIONAL RETURN/EXHAUST FAN Plenum Fan, 30 in. (Any
motor available on any unit)
Quantity …Motor HP 1…10 1…15 1…20 1…25Motor Frame Size 215T 254T
256T 284TEfficiency at Full Load (%) 91.7 93 93.6 93.6Fan Pulley
Pitch Diameter (in.) 6.6 7.4 6.8 8Motor Pulley Pitch Diameter (in.)
4.9 6.6 6.6 8Shaft Diameter at Pulley (in.) 1-7/16 1-7/16 1-7/16
1-7/16Resulting Fan Rpm 1300 1540 1700 1730Maximum Allowable Rpm
1750 1750 1750 1750
FILTERSStandard Efficiency Throwaway (Standard)
Quantity...Size (in.) 8...20 x 25 x 2, 8...20 x 20 x 2 8...20 x
25 x 2, 8...20 x 20 x 2Medium Efficiency (30%) Pleated
(Optional)
Quantity...Size (in.) 8...20 x 25 x 2, 8...20 x 20 x 2 8...20 x
25 x 2, 8...20 x 20 x 2High Efficiency (90%) Bag Filters
with High Velocity Prefilters (Opt)Quantity...Size (in.)
Bag Filter 6...20 x 24 x 22, 6...20 x 20 x 22 6...20 x 24 x 22,
6...20 x 20 x 22Prefilter 12...16 x 20 x 2, 3...20 x 24 x 2 12...16
x 20 x 2, 3...20 x 24 x 2
Cartridge Filters with High Velocity Prefilters
(Opt)Quantity...Size (in.)
Cartridge Filter 6...20 x 24 x 12, 6...20 x 20 x 12 6...20 x 24
x 12, 6...20 x 20 x 12Prefilter 12...16 x 20 x 2, 3...20 x 24 x 2
12...16 x 20 x 2, 3...20 x 24 x 2
OUTSIDE AIR SCREENSStandard Hood (25%) Quantity...Size (in.)
None None
OPTIONAL ECONOMIZER FILTER Aluminum Frame,
PermanentQuantity...Size (in.) 5...20 x 20 x 2, 2...20 x 25 x 1
5...20 x 20 x 1, 2...20 x 25 x 1
Physical data — 50 series units (cont)
-
29
50P 040,050
LEGEND * 460-3-60 only.
BASE UNIT 50P 040 50P 050NOMINAL CAPACITY (tons) 40 50OPERATING
WEIGHT (lb) Standard Chassis Extended Chassis Standard Chassis
Extended Chassis
Base UnitVertical Discharge 5310 5810 5525 6025Horizontal
Discharge and Vertical Discharge
with Discharge Plenum 5610 6110 5825 6325
With EconomizerVertical Discharge 5610 6110 5825 6325Horizontal
Discharge and Vertical Discharge
with Discharge Plenum 5910 6410 6125 6625
COMPRESSORS ScrollQuantity...Type 2...ZP103/1...ZP182
2...ZP120/2...ZP137Oil Charge (oz) per Compressor 110 110Number of
Refrigerant Circuits 2 2
REFRIGERANT R-410AOperating Charge (lb), Ckt 1/Ckt 2
Standard Evaporator Coil 21.6/27.9 29.4/29.0Standard Evaporator
with Humidi-MiZer® System 22.6/40.6 29.4/41.4Alternate
High-Capacity Evaporator Coil 31.1/37.2 35.2/36.5Alternate
High-Capacity Evaporator with Humidi-MiZer 31.1/49.6 35.2/48.9
CONDENSER COILS Aluminum Novation® Heat Exchanger with
Microchannel CoilsQuantity 2 2Total Face Area (sq ft) 66.7 66.7
EVAPORATOR COILSQuantity 2Total Face Area (sq ft)
45.5Refrigerant Feed Device...No. per Circuit TXV...2Standard
Evaporator Coils
Rows...Fins/in. 3...15.0 4...15.0Fin Type Double Wavy Double
WavyTube Type Cross Hatched Cross Hatched
Alternate, High-Capacity Evaporator CoilsRows...Fins/in.
6...16.0 6...16.0Fin Type Double Wavy Double WavyTube Type Cross
Hatched Cross Hatched
OPTIONAL HUMIDI-MIZER® ADAPTIVE DEH