PRODUCT APPLICATION ECHO SWITCH (TRANSMITTER) Echo ™ is an innovative range of entirely wireless, batteryless and self-powered switches and controls. Being wireless offers fantastic benefits, including instant installation and location flexibility. This reduces disruption and cost as there is no need to channel walls and run switching cables. 655 PERIMETER AND DISTRIBUTION PRODUCT APPLICATION
7
Embed
PRODUCT APPLICATION MK...PRODUCT APPLICATION ECHO SWITCH (TRANSMITTER) Echo™ is an innovative range of entirely wireless, batteryless and self-powered switches and controls. …
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
PRODUCT APPLICATIONECHO SWITCH (TRANSMITTER)
Echo™ is an innovative range of entirely wireless, batteryless and self-powered switches and controls. Being wireless offers fantastic benefits, including instant installation and location flexibility. This reduces disruption and cost as there is no need to channel walls and run switching cables.
655
PERIMETER AND
DISTRIBUTION
PR
OD
UC
T
AP
PL
ICA
TIO
N
Industrial Trunking
DescriptionEga Industrial trunking is a PVCu heavy duty system available in white or grey, used extensively for industrial wiring purposes. It is available in a large variety of sizes and has found wide acceptance throughout the world. Its durability, safety and strength are well proven.
Nine basic sizes are available ranging from 50 x 50 mm to 150 x 150 mm complete with a comprehensive variety of fittings. The trunkings have a simple clip on cover which positively locates when hand pressure is applied and enables fast, efficient installation.
TECHNICAL SPECIFICATION
MATERIALSPVCu materials used in the manufacture of MK products are self extinguishing non-flame propagating in accordance with BS 4678 Part 4.
Extrusion material has been tested by a UKAS accredited laboratory in accordance with the requirements of BS 476 Part 7 and has achieved a Class 1Y.
Moulding material has been tested by a UKAS accredited laboratory and conforms with IEC 695-2-1 at a severity of 650°C
IET WIRING REGULATIONSDesigned and manufactured to comply in all respects with BS 7671:2008 (IET Wiring Regulations 17th Edition: 2008)
QUALITY ASSURANCEThe system is manufactured to BS EN ISO 9001
Classifications to BS 4678-4:1982 available on request
Features
l Wide range of trunking sizes and capacity
l Wide range of integrated components maximises versatility of application
l Available in white or grey
l Extremely durable and impact resistant to Heavy Classification BS 4678, Part 4
l Easy to assemble and install
l All trunking fittings are supplied plain without couplings to avoid wastage
l External couplings strengthen the trunking and internal coupling pieces
l All extrusions manufactured from 100% recycled material*
ComponentsThe following components are fabricated sections and space must be allowed for inclusion in runs of trunking. All other components fit over standard trunking profiles.
Prior to installation strike a line of trunking using a plumb and chalk line for vertical, and spirit levels for horizontal runs.
Fixing
1 Fix trunking with screws. It is essential that the hole in the trunking is considerably oversized to allow for expansion.
2 Washers should be used under the head of the screw. The screw should not be tightened to its full extent to allow for movement.
3 For suspended trunking it is advisable to provide fixings every 1.25 m to 1.5 m and a maximum of 100mm either side of coupling.
4 Trunking and lid joints should be staggered to increase the strength of couplings.
Installation Guide
1
2
3
4
Fixing lids
5 Fix lid by sliding it onto the trunking at one end, aligning it to the run of trunking and then curving the cover at the same time as pressing the continuous clip into the trunking gap.
6 To remove lid grasp the trunking firmly at one end and pull in peeling motion so that the cover is gradually freed along its whole length.
mkelectric.co.uk
660
CA
BLE
MA
NA
GE
ME
NT
PERI
MET
ER A
ND
DIST
RIBU
TION Ega Industrial
Technical
100mm
1.25 to 1.50m
100mm
56
8
7
9
Industrial Trunking
Joining fittings
7 Drill trunking with a 7.2mm drill. Bridge pieces are available for retaining the cable in the trunking and the special corrugated shape allows them to be used as a support for dividing fillets required within the trunking.
8 External couplings are fitted by means of the special plastic rivet (ref: TPR/1). To connect couplings to trunking the trunking must be drilled centrally, size 7.2mm, and the rivet inserted.
9 Economical joints can be made using a vinyl adhesive tape especially where added strength is obtained by the lid and trunking being joined in different positions. The joint created is weather resistant and is ideal for surface installation and in conditions of wide temperature variations.