FOR VENTILATION WSI WS SERIES PRESSURE-OPPERATED DAMPER PITCH 50 FOR WALL OVERVIEW AND TECHNICAL DATA PRESSURE OPERATED DAMPER OVERVIEW: The WS series dampers are used to maintain overpressure or under pressure in premises or apartments; they can be used for in air conditioning, ventilation and heating systems. This type of damper can be supplied with an extraction grille with a 20 mm pitch or a net both already mounted. For the intake-model the net is replaced with a square mesh grille for external use, because of the higher strength and the better aspect. TECHNICAL DATA: Damper and grille frame (if present) Extruded anodized aluminium, width 25 mm, rounded edge. Blades In aluminium with pitch 50 mm, fixed with hinges on nylon wrist inserted on frame. Blades of grille (if present) In extruded anodized aluminium with 20mm pitch, fixed with wrist in a nylon self-locking lane inserted in the frame. Transversal reinforcement: all dampers having size B over 1000 mm. Counter frame Rigid in steal. Mounting on the wall ( H-30 ) X ( B-30 ) ( H+32 ) X ( BX32 ) ( H X B ) 25 50 PRESSURE OPERATED DAMPER FOR VENTILATION WSE ACCESSORY: ANTI-NOISE SEALING Mounting on the wall Without screws but clips and counter frame or in the traditional way with screws in wall or channel. Finishing In natural aluminium. ( H-30 ) X ( B-30 ) ( H+32 ) X ( B+32 ) ( H X B ) 70 6 25 50 76 6 Q Regulation-vers_16_00.xls Q-1
38
Embed
PRESSURE-OPPERATED DAMPER PITCH 50 FOR WALL WS … tecnico/Q_Regulation.pdf · PRESSURE OPERATED DAMPER OVERVIEW: The WS series dampers are used to maintain overpressure or under
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
FOR VENTILATION WSI
WSSERIES
PRESSURE-OPPERATED DAMPER PITCH 50 FOR WALL
OVERVIEW AND TECHNICAL DATA
PRESSURE OPERATED DAMPER
OVERVIEW:The WS series dampers are used to maintain overpressure or under pressure in premises or apartments; they can be used for in air conditioning, ventilation and heating systems. This type of damper can be supplied with an extraction grille with a 20 mm pitch or a net both already mounted. For the intake-model the net is replaced with a square mesh grille for external use, because of the higher strength and the better aspect.
TECHNICAL DATA: Damper and grille frame (if present)Extruded anodized aluminium, width 25 mm, rounded edge.BladesIn aluminium with pitch 50 mm, fixed with hinges on nylon wrist inserted on frame. Blades of grille (if present)In extruded anodized aluminium with 20mm pitch, fixed with wrist in a nylon self-locking lane inserted in the frame. Transversal reinforcement: all dampers having size B over 1000 mm. Counter frameRigid in steal. Mounting on the wall
( H
-30 )
X (
B-3
0 )
( H
+32
) X
( B
X32 )
( H
X B
)
2550
PRESSURE OPERATED DAMPER
FOR VENTILATION WSE
ACCESSORY:
ANTI-NOISE SEALING
Mounting on the wallWithout screws but clips and counter frame or in the traditional way with screws in wall or channel. FinishingIn natural aluminium.
( H
-30 )
X (
B-3
0 )
( H
+32 )
X (
B+
32
)
( H
X B
)
706
25
50
76
6
Q Regulation-vers_16_00.xls Q-1
PRESSURE-OPERATED DAMPER FOR
INTAKE WITH GRILLE WSI + UR
WSSERIES
PRESSURE-OPPERATED DAMPER PITCH 50 FOR WALL
CONSTRUCTIONS
PRESSURE-OPERATED DAMPER FOR
VENTILATION WITH GRILLE WSE + UR
25
( H
+32
) X
( B
+32
)
( H
-30
) X
( B
-30
)
( H
-75
) X
( B
-75
)
( H
-30
) X
( B
-30
)
( H
+32
) X
( B
+32
)
25693
PRESSURE-OPERATED DAMPER FOR
VENTILATION WITH NET WSE + RE
PRESSURE-OPERATED DAMPER FOR
INTAKE WITH GRILLE WSI + UQ
6
137
693
70
( H
-30
) X
( B
-30
)
( H
+32
) X
( B
+32
)
5025
6
( H
+32
) X
( B
+32
)
( H
-30
) X
( B
-30
)
25
693
50
Q Regulation-vers_16_00.xls Q-2
IE
--RE
--UR
PRESSURE-OPPERATED DAMPER PITCH 50 FOR WALL WS
SERIESHOW TO ORDER
WS
Exit
Pressure opperated damper
Intake
Haight
WS I RE UR 600 400
Without netWith net
Without UR grilleWith UR grille
Base
400500
Standard bases
mm
200300
600700800
Standard Haights
mm
200300400500600
Q Regulation-vers_16_00.xls Q-3
Q Regulation-vers_16_00.xls Q-4
PRESSURE-OPERATED DAMPERFOR DUCT WCS
SEIRESOVERVIEW
)) )
OVERVIEW:The WCS series dampers enable the flow of air in a natural single direction when a difference of pressure between the two sides exits. The blades are free to move on the wrist enabling the flow of air. Once this is achieved the blades shut simply by with the force of gravity.
CHARACTERISTICS:Frame : in extruded aluminium, 120 mm wide, made in 4 parts assembled together mechanically. Blades : in aluminium with pitch 100 mm (up to height 600 mm pitch 50 mm). Execution : with flanges for channel.Grille (on request) : in aluminium pitch 50 mm
( H
X B
- 2
5 )
( H
X B
- 8
5 )
50125
30
100
125
100
30
( H
X B
+ 1
1
SIZES : Nominal sizes B x H from 300 x 120 up to 1600 x 1010 mm.
WM-10 control dampers are a new series of products from the WM series. The WM-10 series of control dampers are suitable for the application on square and rectangular ducts. The control of these dampers can be manual, electric or pneumatic, according to the needs of the ventilation system. The installation of these components allows the control of the air flow rate variation (VAV) or the pressure variation control on several kinds of plants. Specifically:
a) HVAC plants regulationb) modulated calibrationc) modulated or total closing
WM-10 control damper is new in its type due to the innovative movement transmission system of gear-drives, the non existent friction of the mechanism, the assembly method of the materials used, the particular requirement of air flow control with the wing design of the movable blades and the integrated interchangeable controls, allow for a diverse integration and installation in ventilation systems.
Incastro a tenuta
2 Aletta
3
1 Telaio
Battuta5
4 Ingranaggio interno
MANUAL COMMAND DETAIL
WM-10 Figure n° 1
FRAME
BLADE
HOLDING JOINT
INTERNAL MECHANISM
STOPPER
ASSEMBLY DIAGRAMS : SPECIAL ASSEMBLY WITH HINGE :
H
B
Q Regulation-vers_16_00.xls Q-9
CONTROL DAMPERS
PITCH 100 mm WM-10SERIES
TECHNICAL DATANSTALLATION PROCEDURE
CHARACTERISTICS :
DamperMobile closing system mounted into an air duct, designed to control and close air flow.
Frame, materials and construction methodThe frame is manufactured in extruded aluminium and designed to withstand the lateral stress from to air pressure, and built with lateral frame to protect the drive gears.
FlangeManufactured with 30 mm height.
Blades, materials and construction systemThe blades are manufactured from extruded aluminium with a particular profile in order to be a better sealing surface and a good strength to air pressure.
Transversal reinforcementPresent on all dampers with B dimension wider than 1300 mm.
Finishing
MountingBy screws through damper flange and duct flange or by self-threading screws through damper flange and air-treatment unit panel.
MOUNTING SYSTEM :
Damper mounted inside (figure n°2) or at the beginning or at the end of the air duct (figure n°3 and 4) fixed by the frame flange to the duct flange. The control damper can be mounted on the floor or ceiling (figure n°5).
FinishingExtruded aluminium.
Gear drive, materials and construction systemOpposed rotation gears made from PBT with 30% of glass fibre. The gear drive is closed and protected on the frame. The materials used allow a use between a a temperature range between - 40 °C and + 130 °C.
WM-10 Figure no. 2 WM Figure no. 3
WM-10 Figure no.4 WM-10 Figure no. 5
Q Regulation-vers_16_00.xls Q-10
CONTROL DAMPERS
PITCH 100 mm WM-10SERIES
AIR FLOW RATE - PRESSURE DROPBLADES REGULATION - DAMPER SECTION
CONTROL DAMPER ON FIGURE No. 1
WM-10 Figure No. 6
CORRECTION FACTOR "C" FOR DIFFERENT INSTALLATION THAN FIGURE 1
Type of installationControl damper opening as function of blades inclination
The diagram shows the values of acoustic level in dB(A) as a result of the frontal velocity and pressure drop. The acoustic levels found on the diagram are relative to an air section 1 m². For other sections see correction factor K in below table.
CALCULATION EXAMPLE:a) values as shown in figure No.1b) Calculate the result between velocity V(m/s) x pressure drop rp (Pa) with result 5 x 53 = 265
9 8 6 5 4 3 2 1 0 1 2 3 4 5K (dB)
Mechanism, manual control: The basic kit (figure n° 7) includes a handle for the movement and locking, a transmission lever for the strength of the transmission shaft axle and a numbered modular plate inserted in the internal mechanism, inside the frame.
Mechanism, servo control: The complete kit (figure no. 8) guarantees the functionality of the mechanism via means of an electrical signal. It includes the transmission axle and adjustable plate fixed to the frame. This plate is drilled in order to fix standard actuators available on the market.
Figure no. 8
Figure no. 7
Q Regulation-vers_16_00.xls Q-12
CP
C10
CONTROL DAMPERSPITCH 100 mm WM-10
SERIESHOW TO ORDER
Control damper
with manual commandwith hinge
Base
Haight
WM 800 611
standard bases
B mm
200
standard haight
H mm
211
10 pitch 100 mm
WM
1700
1200
600700800
13001400
300400500
180019002000
311411511611
91110111211
811711
90010001100
16002011
141116111811
1500
H
B
Q Regulation-vers_16_00.xls Q-13
Fixing leaver with fixing bolt, complete with knob for graduated plate for motor support.
WM 21
Image Description Code
CONTROL DAMPERSPITCH 100 mm WM-10
SERIESOPTIONALS
Aluminium graduated plate for attuator support. WM 20
Complete manual command kit, compelte with graduated plate, actioning lever, fixing bolt and knob.
WM 22
Q Regulation-vers_16_00.xls Q-14
CONTROL DAMPERS
50mm PITCH WM-05SERIES
OVERVIEW
OVERVIEW : The WM-05 series forms a new range do calibration dampers. These dampers are used in ventilation systems and for the regulation of the air distribution in the network.The regulation of the air flow is managed from a manual command able to regulate the blade inclination (WM-05C). In alternative the damper can be equipped with an electric servomotor that can be controlled by the individual themselves (WM-05P).With this scope, a version has also been designed with a control hinge, as shown in the diagrams here below shown.
CHARACTERISTICS:Frame: extruded aluminium, 30 mm flange, 65 mm thick, built in four parts joined by mechanical assembly.Winglets: drummed to a wing profile in extruded aluminium extruded 50mm internal axis.Mechanism : transmission system composed by the movement of the interlocking gears.
Available dimensions :Minimum : 100 x 61Maximum : 800 x 811F i l di i l il bili d ff
Incastro a tenuta
2 Aletta
3
1 Telaio
Battuta5
4 Ingranaggio interno
MANUAL COMMAND DETAIL :
FRAME
BLADE
AIR SHUT OFF JOINT
INTERNAL MECHANISM
STOPPER
For special dimensions please request availability and offer.
TECHNICAL DIAGRAMS :
B
H
SPECIAL ASSEMBLY WITH HINGE :
Q Regulation-vers_16_00.xls Q-15
LEGEND :
v Section speed BxHS Section area BxHpt Total pressure lossLwA Sound level pondered in A for 1 m2
The graphs and diagrams shown, refer to the pressure losswith reference to the speed of the air and of the inclinationof the blades and in the same way the relative noise levels ofthe single unit.For different areas to the ones shown, the correcting factorK must be added.
OVERVIEW: The regulation dampers (DIN 1946/4) are used in ventilation systems for the exclusion of particular areas.
CHARACTERISTICS :Frame in galvanised steel sheet Z275, 1,5mm thick;Tubular blades with special profile for the insertion of the internal frame also in galvanised steel sheet but 0,8+0,8mm thick.Blade weight 200 mm;External hinges for the damper regulation;bronze ringlets;command hinge ø18 mm;Lateral fixing with stainless steel blades on each large blade.
PERFORMANCE DATA:Sealing of the blades class 4 according to EN 1751Tightness of the case class C according to EN 1751Test of pressure drops performed according to ISO 7244Test of self-generated noise made according to EN 25135
MAIN DIMENSIONS :
ACCESSORIES :manual command R12;Electric servo motor:-up to 0.2 m² Belimo NM model;-from 0.21 to 1.0 m² Belimo SM model;-from 1.1 to 1.5 m2 Belimo AM model;-from 1.51 to 2.2 m² Belimo GM model;-above 2.21 m² two motors in relation to the surface of each damper.
AVAILABLE SIZES :Base B from 200mm to 2000mmHeight H from 210mm to 2010mm
Q Regulation-vers_16_00.xls Q-19
REGULATION DAMPER
WITH HOLD PITCH 200 mm. CL-SRRSERIES
PERFORMANCE
speed 0° 30° 60°ANGLE APERTURE (0°=OPEN DAMPER)
130 49m/s ∆Pt LwA ∆Pt LwA ∆Pt
23 23 49 520
LwA1 <5 <20 6 32
693 <5 34 52 58 1185 762 <5
4 <5 42 94 66 1350
53 215 75
835 <5 48 145 71
7 7 57 290 796 <5
8 9 61 380 83
68 580 889 11 64 480 86
11 16 71 700 9110 13
12 19 73 830 93
77 1130 9713 22 75 975 95
15 27 79 1300 9914 25
PRESSURE LOSS AND GENERATED NOISE:
haight
1100 2010
800 1800 1410
500
900 1900 16101000 2000 1810
700 1700 1210
1500 810600 1600 1010
300 1300 410400 1400 610
410
standard standard standard bases mm bases mm haights mm
CL-SR Regulation damper
R Rectangular
T Din 1646 guarantee
base
CL-SR R T 400
200 1200 210
Q Regulation-vers_16_00.xls Q-20
CIRCULAR REGULATION DAMPERWITH HOLD CL-SRC
SERIESOVERVIEW
Overview :The CL-SRC series of circular regulation dampers areunits commonly used for the regulation of air circulationsystems.Technical characteristics :The CL-SRC dampers are made by:- circular covering in galvanized steel sheeting withdiameters from 125 to 710 mm, corresponding to thestandard diameters for circular air flow ducts;- regulation damper of air flow in galvanised steel withrubber ring to guarantee the maximum linearity in theregulation and level of noise;- command hinge with a diameter suitable to thediameter of the equipment;- bronze ringlets for the hinge support;
Performance data:Sealing of the blades class 4 according to EN 1751Tightness of the case class C according to EN 1751Test of pressure drops performed according to ISO 7244Test of self-generated noise made according to EN 25135
Special assembly requests:
Main dimentions
630 400 1,5 12 2,0
C S ØX P
100 0,8 8 0,8mmØE
160 200 0,8 8 0,8
mm mm mm mm
200
250 200 0,8 8 0,8
125 200 0,8 8 0,8
315 300 1,0 12 1,2
200 200 0,8 8 0,8
400 400 1,2 12 1,5
300 300 1,0 12 1,2
1,5
355
400 1,2 12 1,5
300 1,0 12 1,2
560 400 1,5 12 2,0
450500 400 1,2 12
Assembly in stainless steel AISI 304Assembly in stainless steel AISI 316
Applications:The CL-SRC series dampers are used to balance the airflow in ventilation and conditioning systems.Noise emitting tests have been done following ENISO3741 regulations.
Description summary :Circular regulation dampers, CL-SRC series, made fromgalvanized steel (or other material).
Accessories :- flange drilled and stamped;- manual command R9 (Ø8 hinge);- manual command R11 (Ø12 hinge);- command via electrical motor;- Pressure operated command with double effect piston.
opening angle (0°=completly opened)V= velocity refering to section ØE (m/s)∆Pt Total pressure loss (Pa)
Q Regulation-vers_16_00.xls Q-22
Standard
Size
M for manual control
CL-SR C T G 160 M
C Circular
T Din 1646 guarantee
G with gaskets
CIRCULAR REGULATION DAMPERWITH HOLD CL-SRC
SERIESHOW TO ORDER
CL-SR Regulation damper
Manual comand lever for Ø8 hinge (diameters from 125 to 250 included):CL-SRCR9Manual comand lever for Ø12 hinge (diameters from 315 to 630 included):CL-SRCR11
500560630
355400
diameters mm100125160
450
200250300315
Q Regulation-vers_16_00.xls Q-23
Q Regulation-vers_16_00.xls Q-24
CIRCULAR CONTROL DAMPERSWR5
SERIESOVERVIEW AND
TECHNICAL DATA
OVERVIEW :
WR control dampers are a new series of products used for control on circular ducts. This series is available with models WR5 WR6 WR7 WR8 for application on all HVAC plants with manual, pneumatic or electric control. The installation of these components permits the control of the air flow rate variation (VAV) or the pressure variation control on several kinds of plants. Specifically:
a) HVAC plants regulationb) modulated calibrationc) modulated or total closing
Circular control dampers have a different construction according to different installation. Indeed they can be mounted by coupling (figure n° 1) and by flanges (figure n° 2).
Figure no. 1 WR5 WR6 Circular control dampers for coupling installation
A Sez A- A
WR5 P=200mm
WR6 P=300mm
WR7 P=300mm
WR8 P=400mm
Figure no. 2 WR7 WR8 Circular control dampers for installation with flanges
A
50
P
Ø =
DN
- 3
Ø +
30
Sez A- A
AA
50
P
Ø =
DN
- 3
Q Regulation-vers_16_00.xls Q-25
CIRCULAR CONTROL DAMPERSWR5
SERIESTECNICAL DATA
INSTALLATION PROCEDURE
CHARACTERISTICS :
Damper: Mobile closing system mounted into an air duct, designed to control and close air flow.
Circular frame, material and construction: Manufactured from galvanized sheet steel with stiffening ribs, complete of two couplings at the ends of the control damper.Circular frame with rims, material and construction:Manufactured from galvanized sheet steel with stiffening ribs, complete of two rims at the ends of the control damper for installation by collars.Circular frame with flanges, material and construction: Manufactured from galvanized sheet steel with stiffening ribs, complete of two flanges at the ends of the control damper for installation by flanges.
Blade, material and construction: Manufactured from galvanized sheet steel and designed.
Control mechanism material and construction: Control by
Figure no.3 Coupling damper
Control mechanism, material and construction: Control by central axle directly fixed on the blade by manual or pneumatic or electric control system.
Fixing, duct without flanges: Installation by rivets or self-threading screws between duct and damper ends.Fixing, duct with flange: Installation by clamping of flanges with bolts and nuts between flanges on duct and damper.
Operative Temperature: From minimum - 0° to maximum + 150° C.
INSTALLATION PROCEDURE:
Inner installation of coupling damper (figure no.3)
Q Regulation-vers_16_00.xls Q-26
CIRCULAR CONTROL DAMPERSWR5
SERIESAIR FLOW RATE - PRESSURE DROP
BLADE REGULATION - DAMPER SECTION
SELECTION EXAMPLE : a) Air flow = 2000 m3/h b) Pressure drop p = 100 Pa c) Blade deflection angle α = 27° d) Damper diameter = 250 mm
WR5 Figure no. 4
Mechanism, manual control: Standard kit (figure no. 5) is constituted by a knob to handle for moving and fixing, lever of swinging shaft, adjustable plate fixed on the frame.
Mechanism, servo control: This kit (figure no. 6) permits to obtain the damper remote control by electric signal. It's constituted by transmission axle and adjustable plate fixed on the frame. This plate is drilled in order to fix standard actuators
Figure no. 6
Figure no. 5
65
100
Q Regulation-vers_16_00.xls Q-27
5 By coupling, depth 200 mm, squared axis 8 mm, 8/10 steel sheet6 By coupling, depth 300 mm, circular axis 12 mm, 8/10 steel sheet7 With flanges, depth 300 mm, circular axis 12 mm, 10/10 steel sheet8 With flanges, depth 400 mm, circular axis 18 mm, 15/10 steel sheet
WR5SERIES
WR 8
100 100
CIRCULAR CONTROL DAMPERS
Size
250
standard diameters
WR
HOW TO ORDER
WR 5 WR 6 WR 7
125 125
150 150
Circular regulation damper
WR 5
160 160
175 175
200 200
225 225
250250
275 275
300
450
315 315
350 350
550 550
600
400 400
450
650
700
500 500
700
710 710
300
650
600
Q Regulation-vers_16_00.xls Q-28
IRIS REGULATION DAMPERWMIRSERIES
OVERVIEW
CONSTRUCTION : The WMIR iris dampers are equipped with a supporting structure with a series of regulation blades, activated by turning a nut or lever (80 diameter). The dampers also have a regulation scale together with sockets for differential pressure gauges. The structure and the blades are made of hot galvanised steel, while the other components are made of plastic. The connections have a gasket on the outside used to ensure the joint is sealed.
USE :The WMIR iris dampers are the ideal solution for precise, quick measuring and regulation of flow rates. For ducts that carryacid fumes or agents that are particularly corrosive, these iris dampers can be used.
Made of AISI 316 stainless steel, upon specific request.
DIMENSIONS :
Nom. Dia. Ø d [mm] Ø D [mm] L [mm] A [mm]
80 79 125 110 30 22165 110 30 32
B [mm]Weight
[kg]
0,50,5
125 124 188 110 30 32 0,7100 99
35 0,9150 149 230 210 27 40
285 110 30 42
0,9160 159 230 110 30
1,4250 249 335 135 40 42 2,1200 199
62 6,4315 314 410 135 40 47
655 170 50 77
3,5400 398 525 190 60
9,6630 628 815 170 50 92 15,6500 498
25,0800 798 1015 270 100 107
NOMINAL DIAMETER 80 NOMINAL DIAMETER 100 TO 800
Q Regulation-vers_16_00.xls Q-29
IRIS REGULATION DAMPERWMIRSERIES
PERFORMANCE
Q Regulation-vers_16_00.xls Q-30
IRIS REGULATION DAMPERWMIRSERIES
PERFORMANCE
Q Regulation-vers_16_00.xls Q-31
IRIS REGULATION DAMPERWMIRSERIES
INSTALLATIONMEASURING FLOW RATES
Type of flow disturbance
Safe distance L, for a measuring tolerance of
± 7 %
Safe distance L, for a measuring tolerance of
± 10 %
≥ 2 D ≥ 1 D
≥ 4 D ≥ 2 D
INSTALLATION :The WMIR iris dampers can be riveted in position. For vertical installations, the weight of the ducting positioned on top of thedamper must be fully supported. In addition, the iris damper must be positioned sufficiently far away from branches, unions and any element that can cause disturbances to the measuring of air flow rates. In this case, we recommend installing the units at the safe distance, as indicated below.
≥ 4 D ≥ 2 D
≥ 2 D ≥ 2 D
In general, the measuring accuracy for an undisturbed flow is around ± 5 %. In the latter case however, the safe distance between the diffuser and the damper is intended to allow the diffuser to work normally, despite the damper being added to the system.
MEASURING THE FLOW RATE :The regulation blades make up an ideal measuring diaphragm, allowing the air flow rate to be measured easily and reliably. The flow rate value is determined by measuring the differential pressure Dpm via connection to a differential pressure gauge.Once the Dpm value is known, the regulation diagram is used to determine the corresponding flow rate. The regulation diagram is clearly shown on the damper close to the regulation nut and includes a set of curves that relate to the various regulation positions. It is important to note that the diagrams on the damper are used only for regulating and not for selection -the selection data is given on the previous pages.
Q Regulation-vers_16_00.xls Q-32
IRIS REGULATION DAMPERWMIRSERIES
ACOUSTIC CHARACTERISTICSMAINTENANCE
Nom. Dia.
Correction factor Koct [dB]
Mean frequency for the octave band [Hz]63 125 250 500 1000 2000 4000 8000
The acoustic power levels for the duct, for each octave band, are obtained by adding the correction factor, Koct for the octaveband (see table above) to the total acoustic pressure level Lp10A [dB(A)] using the following equation:
LWoct = Lp10A + Koct
The correction factor Koct for octave band is equal to the mean value for the field in which the WMIR series iris regulation isused.
MAINTENANCE :
Q Regulation-vers_16_00.xls Q-33
WMIR iris regulation damper
size
WMIR 250
IRIS REGULATION DAMPERWMIRSERIES
HOW TO ORDER
Q Regulation-vers_16_00.xls Q-34
0,500,600,801,051,102,001,551,553,303,30
0,500,600,500,750,800,901 05
Image Voltage State Micro Force Kg Code
( AC 230V ) On Off 5 Nm 1 m2 LM 230A
( AC 230V ) On Off 10 Nm 2 m2( AC 230V ) On Off 1 5 Nm 1 m2 LM 230A-S
NM 230A( AC 230V ) On Off 20 Nm 4 m2 SM 230A( AC 230V ) On Off 1 20 Nm 4 m2 SM 230A-S( AC 230V ) On Off 40 Nm 8 m2 GM 230A( AC 230V ) On Off ret. spring 4 Nm 0,8 m2 LF 230( AC 230V ) On Off ret. spring 1 4 Nm 0,8 m2 LF 230-S( AC 230V ) On Off ret. spring 15 Nm 3 m2 AF 230( AC 230V ) On Off ret. spring 2 15 Nm 3 m2 AF 230S
( AC 24V ) On Off 5 Nm 1 m2 LM 24A
( AC 24V ) Variable 5 Nm 1 m2( AC 24V ) On Off 1 5 Nm 1 m2 LM 24A-S
LM 24A-SR( AC 24V ) On Off 8 Nm 2 m2 NM 24A( AC 24V ) Variable 8 Nm 2 m2 NM 24A-SR( AC 24V ) Variable 8 Nm 2 m2 NM 24A-MF( AC 24V ) On Off 20 Nm 4 m2 SM 24A
SERVO MOTORSFOR REGULATION DAMPERS
TECHNICAL CHARACTERISTICS
1,051,051,052,002,001,401,401,401,403,003,002,70
Contatto ausiliario est. 1xSPDT 0,23Contatto ausiliario est. 2xSPDT 0,27
0,150,150,150,150,500,700,150,24
( AC 24V ) On Off 20 Nm 4 m SM 24A( AC 24V ) On Off 1 20 Nm 4 m2 SM 24A-S( AC 24V ) Variable 20 Nm 4 m2 SM 24A-SR( AC 24V ) On Off 40 Nm 8 m2 GM 24A( AC 24V ) Variable 40 Nm 8 m2 GM 24A-SR( AC 24V ) On Off 4 Nm 0,8 m2 LF 24( AC 24V ) Variab., ret.spring 1 4 Nm 0,8 m2 LF 24-S( AC 24V ) On Off ret. spring 3 4 Nm 0,8 m2 LF 24-3( AC 24V ) Variab., ret.spring 4 Nm 0,8 m2 LF 24-SR( AC 24V ) On Off ret. spring 15 Nm 3 m2 AF 24( AC 24V ) On Off ret. spring 1 15 Nm 3 m2 AF 24-S( AC 24V ) Variab., ret.spring 15 Nm 3 m2 AF 24-SR
Image Description Max Force Kg Code
1 250 V S1A2 250 V S2A
Slave potentiometers 140 Ohm PA 140ASlave potentiometers 500 Ohm PA 500A
Slave potentiometers 2800 Ohm PA 2800A
Position transducer on guide 10 motori (24V) 50/60Hz SGE 24
Slave potentiometers 1000 Ohm PA 1000A
10 motori (24V) 50/60Hz SGA 24
Position transducer on panel 10 motori (24V) 50/60Hz SGF 24
Digital position indicator 0. 99% (24V) ZAD 24Position transducer on wall
Q Regulation-vers_16_00.xls Q-35
0,500,600,801,051,102,001,551,553,303,30
0,500,600,500,750,801 05
SERVO MOTORSFOR REGULATION DAMPERS
TECHNICAL CHARACTERISTICS
Image Voltage State Micro Strength Kg BELIMO
EQUIVALENTSIEMENS
( AC 230V ) On Off 5 Nm 1 m2 LM 230A GDB331.1E
GLB331.1E
( AC 230V ) On Off 2 5 Nm 1 m2 LM 230A-S GDB336.1E
15 Nm 3 m2 SM 230A GEB331.1E
( AC 230V ) On Off 10 Nm 2 m2 NM 230A
( AC 230V ) On Off 2 15 Nm 3 m2 SM 230A-S GEB336.1E
( AC 230V ) On Off
( AC 230V ) On Off 35 Nm 7 m2 GM 230A GIB331.1E
( AC 230V ) On Off ret. spring 7 Nm 1,4 m2 LF 230 GMA321.1E
On Off ret. spring 2 7 Nm 1,4 m2 LF 230-S GMA326.1E
GCA326.1E
( AC 230V ) On Off ret. spring 15 Nm 3,2 m2 AF 230 GCA321.1E
( AC 230V )
( AC 24V )
( AC 230V ) On Off ret. spring 2 15 Nm 3,2 m2 AF 230S
( AC 24V ) Variab., ret.spring 16 Nm 3,2 m2 AF 24-SR GCA161.1E
( AC 24V ) On Off ret. spring
Image Description Max Voltage Kg BELIMO
EQUIVALENTSIEMENS
Extern. auxiliary contact 1xSPDT 1 250 V S1A ASC77.1E
Extern. auxiliary contact. 2xSPDT 2 250 V S2A ASC77.2E
Position transducer on panel 10 motors (24V) 50/60Hz SGF 24 BSG61
Position transducer on guide 10 motors (24V) 50/60Hz SGE 24 BSG61
Position transducer on DIN * 0 - 100% (24V) 50/60Hz SGA 24 SEZ220*
Q Regulation-vers_16_00.xls Q-36
L E Lt L E Lt L E Lt L E Lt L E Lt L E Lt90 40 170 110 30 170 220 40 300 90 40 170 110 30 170 220 40 30090 40 170 110 30 170 220 40 300 90 40 170 110 30 170 220 40 300
Spiro control Lever control For servomotorWITHOUT GASKET
D
80
WITH GASKETSpiro control Lever control For servomotor
100
CIRCULAR CONTROL DAMPERSCK-WR5SERIES
Overview :The CK-WR5 series of circular regulation dampers areunits commonly used for the regulation of air circulationsystems.Technical characteristics :The CK-WR5 dampers are made by:- circular duct in galvanized steel;- regulation damper of air flow in galvanised steel;- command hinge.
Applications:The CK-WR5 series dampers are used to balance the airflow in ventilation and conditioning systems.