24508_Ver3.20-EN.fm/2 Schneider Electric TeSys protection components 3 Thermal-magnetic motor circuit-breakers models GV2, GV3 and GV7 GV2-ME, GV2-P, GV3-ME and GV7-R motor circuit-breakers are 3-pole thermal-magnetic circuit-breakers specifically designed for the control and protection of motors, conforming to standards IEC 947-2 and IEC 947-4-1. These circuit-breakers are designed for connection by screw clamp terminals. Circuit-breaker GV2-ME can be supplied with spring terminal connections. These ensure secure, permanent and durable clamping that is resistant to harsh environments, vibration and impact and is even more effective when conductors without cable ends are used. Each connection can take two independent conductors. GV2-ME and GV3-ME: Pushbutton control. Energisation is controlled manually by operating the Start button “I” 1. De-energisation is controlled manually by operating the Stop button “O” 2, or automatically by the thermal-magnetic protection elements or by a voltage trip attachment. Control is manual and local when the motor circuit-breaker is used on its own. Control is automatic and remote when it is associated with a contactor. Motor protection is provided by the thermal-magnetic protection elements incorporated in the motor circuit-breaker. The magnetic elements (short-circuit protection) have a non-adjustable tripping threshold, which is equal to about 13 times the maximum setting current of the thermal trips. The thermal elements (overload protection) include automatic compensation for ambient temperature variations. The rated operational current of the motor is displayed by means of a graduated knob 4. Personnel protection is also provided. All live parts are protected against direct finger contact. The addition of an undervoltage trip allows the circuit-breaker to be de-energised in the event of an undervoltage condition. The user is therefore protected against sudden starting of the machine when normal voltage is restored, since the Start button “I” has to be pressed to restart the motor. With the addition of a shunt trip, de-energisation of the unit can be remotely controlled. The operators on both open-mounted and enclosed motor circuit-breakers can be locked in the Stop position “O” by up to 3 padlocks. Because they are suitable for isolation, these circuit-breakers, in the open position, provide an adequate isolation distance and indicate the actual position of the moving contacts by the position of the operators. These motor circuit-breakers are easily installed in any configuration thanks to their universal fixing arrangement: screw fixing or clip-on mounting on symmetrical, asymmetrical or combination rails. Connection Operation GV2-ME GV3-ME GV2-P GV7-R I O 1 2 4 810404 GV2-ME with screw clamp connections 810405 GV2-ME with spring terminal connections O I 1 2 4 810406 GV3-ME 1 2 4 3 810411 GV2-P O 2 3 1 810407 GV7-R Protection of motors and personnel Special features Presentation GV2-P: control by rotary knob. GV7-R: control by rocker lever. Energisation is controlled manually by moving the knob or rocker lever to position “I” 1. De-energisation is controlled manually by moving the knob or rocker lever to position “O” 2. De-energisation due to a fault automatically places the knob or rocker lever in the “Trip” position 3. Re-energisation is possible only after having returned the knob or rocker switch to position “O”. Characteristics: pages 24509/2 to 24513/7 Dimensions: pages 24538/2 to 24538/7 Schemes: pages 24538/8 and 24538/9
78
Embed
Presentation TeSys protection components - A Schneider … · TeSys protection components 3 ... Circuit-breaker GV2-ME can be supplied ... 0291Q_Ver3.10-EN.fm/2 Schneider Electric
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
24508_Ver3.20-EN.fm/2 Schneider Electric
TeSys protection components 3
Thermal-magnetic motor circuit-breakersmodels GV2, GV3 and GV7
GV2-ME, GV2-P, GV3-ME and GV7-R motor circuit-breakers are 3-pole thermal-magnetic circuit-breakers specificallydesigned for the control and protection of motors, conforming to standards IEC 947-2 and IEC 947-4-1.
These circuit-breakers are designed for connection by screw clamp terminals. Circuit-breaker GV2-ME can be suppliedwith spring terminal connections.These ensure secure, permanent and durable clamping that is resistant to harsh environments, vibration and impact andis even more effective when conductors without cable ends are used. Each connection can take two independentconductors.
GV2-ME and GV3-ME: Pushbutton control.Energisation is controlled manually by operating the Startbutton “I” 1.De-energisation is controlled manually by operating theStop button “O” 2, or automatically by the thermal-magneticprotection elements or by a voltage trip attachment.
Control is manual and local when the motor circuit-breaker is used on its own.Control is automatic and remote when it is associated with a contactor.
Motor protection is provided by the thermal-magnetic protection elements incorporated in the motor circuit-breaker.The magnetic elements (short-circuit protection) have a non-adjustable tripping threshold, which is equal to about 13times the maximum setting current of the thermal trips.The thermal elements (overload protection) include automatic compensation for ambient temperature variations.The rated operational current of the motor is displayed by means of a graduated knob 4.
Personnel protection is also provided. All live parts are protected against direct finger contact.
The addition of an undervoltage trip allows the circuit-breaker to be de-energised in the event of an undervoltagecondition. The user is therefore protected against sudden starting of the machine when normal voltage is restored, sincethe Start button “I” has to be pressed to restart the motor.
With the addition of a shunt trip, de-energisation of the unit can be remotely controlled.
The operators on both open-mounted and enclosed motor circuit-breakers can be locked in the Stop position “O” by upto 3 padlocks.
Because they are suitable for isolation, these circuit-breakers, in the open position, provide an adequate isolation distanceand indicate the actual position of the moving contacts by the position of the operators.
These motor circuit-breakers are easily installed in any configuration thanks to their universal fixing arrangement: screwfixing or clip-on mounting on symmetrical, asymmetrical or combination rails.
Connection
Operation
GV2-ME GV3-ME GV2-P GV7-R
IO 1
2
4
8104
04
GV2-ME with screw clamp connections
8104
05
GV2-ME with spring terminalconnections
O I12
4
8104
06
GV3-ME
1
2
4
3
8104
11
GV2-P
O 23
1
8104
07
GV7-R
Protection of motors and personnel
Special features
Presentation
GV2-P: control by rotary knob.GV7-R: control by rocker lever.Energisation is controlled manually by moving the knobor rocker lever to position “I” 1.De-energisation is controlled manually by moving theknob or rocker lever to position “O” 2.De-energisation due to a fault automatically places theknob or rocker lever in the “Trip” position 3. Re-energisationis possible only after having returned the knob or rockerswitch to position “O”.
Characteristics:pages 24509/2 to 24513/7
Dimensions:pages 24538/2 to 24538/7
Schemes:pages 24538/8 and
24538/9
0291Q_Ver3.10-EN.fm/2 Schneider Electric
Applications Motor protectionMagnetic circuit-breakers provide short-circuit protection. They must be combined with thermal overload relays toprovide motor overload protection
Tripping threshold on 13 In on average short-circuit
Standard motor Up to 15 kWratings in AC-3, 415 V
Operational current 0.4…32 Aat 415 V
Breaking capacity 10…100 kA 50…100 kAat 415 V (Icu)To IEC 947-2
Door interlock With Withmechanism
Device type GV2-LE GV2-L
Pages 24522/2 24522/2
Selection guide TeSys protection components 3
Magnetic circuit-breakers
0291Q_Ver3.10-EN.fm/3Schneider Electric
6...14 In 8...13 In 6.3...12.5 In
11…37 kW 0.37...250 kW
40…80 A 1.5...500 A
35 and 50 kA 25.70 and 150 kA 35.70 and 150 kA 45.70 and 150 kA
GK3-EF NS 80 NS100 to NS 400 and
NS 250 NS 630
24522/3 Please consult your Regional Sales Office
3
24508_Ver3.20-EN.fm/3Schneider Electric
TeSys protection components 3
Thermal-magnetic motor circuit-breakers models GV2-ME and GV2-P
GV2-ME: pushbutton control, GV2-P: control by rotary knob
With instantaneous auxiliary contact block (composition, see page 24512/3):- GV-AE1, add suffix AE1TQ to the motor circuit-breaker reference selected above. Example: GV2-ME01AE1TQ.- GV-AE11, add suffix AE11TQ to the motor circuit-breaker reference selected above. Example: GV2-ME01AE11TQ.- GV-AN11, add suffix AN11TQ to the motor circuit-breaker reference selected above. Example: GV2-ME01AN11TQ.These circuit-breakers with built-in contact block are sold in lots of 20 units in a single pack.(1) As % of Icu.(2) For use of GV2-ME in an enclosure, see page 80263/3.(3) Maximum rating which can be mounted in enclosures GV2-MC or MP, please consult your Regional Sales Office.
Thermal magnetic circuit-breakers GV2-ME & GV2-P with screw clamp terminals
Standard power ratings Setting Magnetic Reference Weightof 3-phase motors range tripping50/60 Hz in category AC-3 of current400/415 V 500 V 690 V thermal Id ± 20 %P Icu Ics P Icu Ics P Icu Ics trips
Thermal magnetic circuit-breakers GV2-ME with built-in auxiliary contact block
( > 100 kA.
References
Characteristics:pages 24509/2 to 24509/5
Dimensions:pages 24538/2 to 24538/4
Schemes:page 24538/8
24508_Ver3.20-EN.fm/4 Schneider Electric
TeSys protection components 3
Thermal-magnetic motor circuit-breakers model GV2-ME
Pushbutton control
(1) For connection of conductors from 1 to 1.5 mm2 the use of a cable end reducer LA9-D99 is recommended.
Thermal magnetic circuit-breakers GV2-ME with spring terminal connections (1)
Standard power ratings Setting Magnetic Reference Weightof 3-phase motors range of tripping50/60 Hz in category AC-3 thermal current400/415 V 500 V trips Id ± 20 %P Icu Ics (2) P Icu Ics (2)kW kA kW kA A A kg
Description Application Sold in Unit Weightlots of reference kg
Cable end reducer For connection of 20 LA9-D99 –conductors from 1 to 1.5 mm2
(2) As % of Icu. ( > 100 kA
8104
17
LA9-D99
References
Characteristics:pages 24509/2 to 24513/5
Dimensions:pages 24538/2 to 24538/4
Schemes:page 24538/8
24508_Ver3.20-EN.fm/5Schneider Electric
TeSys protection components 3
Thermal-magnetic motor circuit-breakersmodel GV3-ME
Pushbutton control
(1) As % of Icu.(2) Recommended for use in association with a contactor.
Thermal magnetic circuit-breakers GV3-ME with screw clamp terminals
Standard power ratings of 3-phase Setting range Reference Weightmotors 50/60 Hz in category AC-3 of thermal 400/415 V 500 V 660/690 V trips P Icu Ics (1) P Icu Ics (1) P Icu Ics (1) kW kA kW kA kW kA A kg
Thermal-magnetic motor circuit-breakersmodel GV7-R
Control by rocker lever
(1) As % of Icu.
Thermal magnetic circuit-breakers GV7-R with screw clamp terminals
Standard power ratings of 3-phase Setting range Reference Weightmotors 50/60 Hz in category AC-3 of thermal 400/415 V 500 V 660/690 V trips P Icu Ics (1) P Icu Ics (1) P Icu Ics (1) kW kA kW kA kW kA A kg
(1) Other accessories such as mounting, cabling and marking accessories are identical to those used for GV2-ME motorcircuit-breakers, see page 24512/9.
For motors with high current peak on starting
Standard power ratings Setting Magnetic Reference Weightof 3-phase motors range of tripping50/60 Hz in category AC-3 thermal current220 400 trips Id ± 20 %230 V 415 V 440 V 500 V 690 VkW kW kW kW kW A A kg
Standard power ratings Setting range Magnetic Reference Weight230 400 of thermal tripping current240 V 415 V 440 V 500 V 690 V trips Id ± 20 %kVA kVA kVA kVA kVA A A kg
Magnetic circuit breakers GV2-LE and GV2-L with screw clamp terminals
GV2-LE: rocker lever, GV2-L: rotary handleStandard power ratings Magnetic Trip- Use in Reference Weightof 3-phase motors protection ping association50/60 Hz in category AC-3 rating current with 400/415 V 500 V 690 V Id ± 20 % thermalP Icu Ics P Icu Ics P Icu Ics overload
(1) (1) (1) relaykW kA kW kA kW kA A A kg
0.06 g g – – – – – – 0.4 5 LR2-K0302 GV2-LE03 0.3300.09 g g – – – – – – 0.4 5 LR2-K0304 GV2-LE03 0.330
or LRD-03 GV2-L03 0.3300.12 g g – – – 0.37 g g 0.63 8 LR2-K0304 GV2-LE04 0.330
or LRD-04 GV2-L04 0.3300.18 g g – – – – – – 0.63 8 LR2-K0305 GV2-LE04 0.330
or LRD-04 GV2-L04 0.330– – – – – – 0.55 g g 1 13 LR2-K0305 GV2-LE05 0.330
or LRD-05 GV2-L05 0.3300.25 g g – – – – – – 1 13 LR2-K0306 GV2-LE05 0.330
or LRD-05 GV2-L05 0.330– – – – – – 0.75 g g 1 13 LR2-K0306 GV2-LE05 0.330
or LRD-06 GV2-L05 0.3300.37 g g 0.37 g g – – – 1 13 LR2-K0306 GV2-LE05 0.330
or LRD-05 GV2-L05 0.3300.55 g g 0.55 g g 1.1 g g 1.6 22.5 LR2-K0307 GV2-LE06 0.3300.55 g g 0.55 LRD-06 GV2-L06 0.330– – – 0.75 g g – – – 1.6 22.5 LR2-K0307 GV2-LE06 0.330
or LRD-06 GV2-L06 0.3300.75 g g 1.1 g g 1.5 3 75 2.5 33.5 LR2-K0308 GV2-LE07 0.3300.75 g g 1.1 g g 1.5 4 100 2.5 33.5 LRD-07 GV2-L07 0.3301.1 g g – – – – – – 2.5 33.5 LR2-K0308 GV2-LE08 0.330
or LRD-08 GV2-L08 0.3301.5 g g 1.5 g g 3 3 75 4 51 LR2-K0310 GV2-LE08 0.3301.5 g g 1.5 g g 3 4 100 51 LRD-08 GV2-L08 0.330– – – 2.2 g g – – – 4 51 LR2-K0312 GV2-LE08 0.330
or LRD-08 GV2-L08 0.330
2.2 g g 3 50 100 4 3 75 6.3 78 LR2-K0312 GV2-LE10 0.330
2.2 g g 3 g g 4 4 100 6.3 78 LRD-10 GV2-L10 0.3303 g g 4 10 100 5.5 3 75 10 138 LR2-K0314 GV2-LE14 0.3303 g g 4 10 100 5.5 4 100 10 138 LRD-12 GV2-L14 0.3304 g g 5.5 10 100 – – – 10 138 LR2-K0316 GV2-LE14 0.330
(1) Associated current limiter or fuses, where required. See characteristics page 24523/5.
References
GK3-EF
Characteristics :pages 24523/2 to 24513/7
Dimensions :page 24527/4
Schemes :page 24527/5
24512_Ver3.10-EN.fm/2 Schneider Electric
GV2-AK00GV1-L3
GV-AD
GV-AM11
GV-AM11
GV-AN
GV-AN
GV2-P
GV2-ME
GV-AX
GV-AU
GV-AS
GV-AE1
GV-AE1
GV-AE11, AE20
GV2-L
GV2-LE
24512_Ver3.10-EN.fm/3Schneider Electric
TeSys protection componentsThermal-magnetic and magnetic motor circuit-breakers type GV2 with screw clamp connectionsAccessories
Undervoltage trip, INRS (can only be mounted on GV2-ME)Safety device for dangerous machines, conforming to INRS and VDE 0113
(1) Mounting of a GV-AE contact block or a GV2-AK00 visible isolation block on GV2-P and GV2-L.(2) Choice of N/C or N/O contact operation, depending on which way round the reversible block is mounted.(3) The GV-AD is always mounted next to the circuit-breaker.(4) To order an undervoltage trip: replace the dot (/) in the reference with a U, example: GV-AU025. To order a shunttrip: replace the dot (/) in the reference with an S, example: GV-AS025.(5) Visible isolation of the 3 poles upstream of circuit-breaker GV2-P and GV2-L.
Contact blocks
Description Mounting Maximum Type of contacts Sold in Unit Weightnumber lots of reference kg
Side 24 V 50 Hz GV-A/025 0.105(1 block on RH side 60 Hz GV-A/026 0.105of circuit-breaker) 48 V 50 Hz GV-A/055 0.105
60 Hz GV-A/056 0.105100 V 50 Hz GV-A/107 0.105100…110 V 60 Hz GV-A/107 0.105110…115 V 50 Hz GV-A/115 0.105
60 Hz GV-A/116 0.105120…127 V 50 Hz GV-A/125 0.105127 V 60 Hz GV-A/115 0.105200 V 50 Hz GV-A/207 0.105200 V…220 V 60 Hz GV-A/207 0.105220 V…240 V 50 Hz GV-A/225 0.105
60 Hz GV-A/226 0.105380 V…400 V 50 Hz GV-A/385 0.105
60 Hz GV-A/386 0.105415 V…440 V 50 Hz GV-A/415 0.105415 V 60 Hz GV-A/416 0.105440 V 60 Hz GV-A/385 0.105480 V 60 Hz GV-A/415 0.105500 V 50 Hz GV-A/505 0.105600 V 60 Hz GV-A/505 0.105
Side 110…115 V 50 Hz GV-AX115 0.110(1 block on RH side 60 Hz GV-AX116 0.110of circuit-breaker 127 V 60 Hz GV-AX115 0.110GV2-ME) 220…240 V 50 Hz GV-AX225 0.110
60 Hz GV-AX226 0.110380…400 V 50 Hz GV-AX385 0.110
60 Hz GV-AX386 0.110415…440 V 50 Hz GV-AX415 0.110440 V 60 Hz GV-AX385 0.110
Add-on contact blocks
Description Mounting Maximum Reference Weightnumber kg
Visible isolation Front (1) 1 GV2-AK00 0.150block (5)Limiters At top 1 GV1-L3 0.130
(GV2-ME and GV2-P)Independent 1 LA9-LB920 0.320
References
Characteristics : pages 24513/2, 24513/6 and
24513/7 Dimensions and schemes pages 24538/2 to 24527/5
LA9-LB920
24512_Ver3.10-EN.fm/4 Schneider Electric
GV3-A08GV3-A09
GV3-A01...A07
24512_Ver3.10-EN.fm/5Schneider Electric
TeSys protection componentsMotor circuit-breakers: thermal-magnetic type GV3-ME and magnetic type GK3 with screw clamp connectionsAccessories
Contact blocks
(1) 1 voltage trip OR 1 fault signalling contact to be fitted inside the motor circuit-breaker.
For thermal-magnetic circuit breakers GV3-ME
Contact blocksDescription Type of standard Reference Weight
Electric tripsDescription Voltages Reference Weight
50 Hz 60 Hz kg
Undervoltage trips (1) 110, 120, 127 V 120, 127 V GV3-B11 0.070
220, 240 V 277 V GV3-B22 0.070
380, 415 V 440, 480 V GV3-B38 0.070
Shunt trips (1) 110, 120, 127 V 120, 127 V GV3-D11 0.070
220, 240 V 277 V GV3-D22 0.070
380, 415 V 440, 480 V GV3-D38 0.070
AccessoryDescription Sold in Unit Weight
lots of reference kg
Padlocking device, for locking 5 GV1-V02 0.010the start button (on open-mounted product)
For magnetic circuit-breakers GK3
Description Composition Reference Weightkg
Auxiliary contact blocks for On-Off signalling and N/O GK2-AX10 0.025“control circuit test” function (1 or 2 blocks per device) N/O + N/O GK2-AX20 0.031mounted on RH side of GK3-EF N/C + N/O GK2-AX50 0.031
Instantaneous fault signalling contact blocks N/O GK2-AX12 0.025(1 or 2 blocks per device) N/O + N/O GK2-AX22 0.031mounted on LH side of GK3-EF N/C + N/O GK2-AX52 0.031
AccessoriesDescription Reference Weight
kg
Padlocking device GK3-AV01 0.020for padlocking the operator, using up to 3 padlocks(padlocks to be ordered separately)
External operator GK3-AP03 0.300for mounting on the enclosure door.Red Ø 40 pushbutton on yellow plate. Can be locked in position Oby means of up to 3 padlocks, with door locked in position I and door locked in position O when padlocked.
Other versions 24 to 690 V 50 or 60 Hz voltage trips for circuit-breakers GV3-ME.Please consult your Regional Sales Office.
References
Characteristics :pages 24513/3 and 24513/6
Dimensions and schemes :pages 24538/2 to 24527/5
24512_Ver3.10-EN.fm/6 Schneider Electric
GV7-RE, RS
GV7-AE11, AB11
GV7-AU, AS
12
34
24512_Ver3.10-EN.fm/7Schneider Electric
TeSys protection componentsThermal-magnetic motor circuit-breakers type GV7-Rwith screw clamp connectionsAccessories
They allow remote indication of the circuit-breaker contact states. They can be used for signalling, electrical locking,relaying, etc. Two versions are available: standard and low level. They include a terminal block and the auxiliary circuitsleave the circuit-breaker through a hole provided for this purpose.They perform the following functions, depending on where they are located in the circuit-breaker:
They make it possible to:- either differentiate a thermal fault from a magnetic fault,- or open the contactor only in the event of a thermal fault.
These allow the circuit-breaker to be tripped via an electrical control signal.
/ Undervoltage trip GV7-AU- Trips the circuit-breaker when the control voltage drops below the tripping threshold, which is between 0.35 and 0.7times the rated voltage.- Circuit-breaker closing is only possible if the voltage exceeds 0.85 times the rated voltage.Circuit-breaker tripping by a GV7-AU trip meets the requirements of IEC 947-2.
/ Shunt trip GV7-ASTrips the circuit-breaker when the control voltage rises above 0.7 times the rated voltage.
/ Operation (GV7-AU or GV7-AS)- When the circuit-breaker has been tripped by a GV7-AU or AS, it must be reset either locally or by remote control.(For remote control, please consult your Regional Sales Office).- Tripping has priority over manual closing: if a tripping instruction is present, manual action does not result in closing,even temporarily, of the contacts.
(1) For mounting of a GV7-AD or a GV7-AU or AS.
Add-on auxiliary contact blocks
Location Function Application
1 and/or 4 C/O contact Indicates the position of the circuit-breaker poles
2 Tripindication
Indicates that the circuit-breaker has tripped due to an overload, a short-circuit,a differential faul or the operation of a voltage trip (undervoltage or shunt tripor of the “push to trip” test button.It resets when the circuit-break is reset.
3 Electrical fault Indicates that the circuit-breaker has tripped due to an overload, a short-circuit orindication a differential fault. It resets when the circuit-breaker is reset.
Type Reference Weightkg
Standard GV7-AE11 0.015
Low level GV7-AB11 0.015
Fault discrimination devices
Voltage Reference Weightkg
" 24...48 and $ 24…72 V GV7-AD111 (1) 0.100
7 110…240 V GV7-AD112 (1) 0.100
Electric trips
- Durability: 50 % of the mechanical life of the circuit-breaker.
TeSys protection componentsThermal-magnetic and magnetic motor circuit-breakers type GV2 with screw clamp connectionsAccessories
Accessories
Description Application Sold in Unit Weightlots of reference kg
Adapter plate For mounting a GV2-ME 10 GV2-AF02 0.021or GV2-LE by screw fixingFor montage a GV2-ME or 1 LAD-31 0.040GV2-P and contactor LC1-D09 toD38 with front faces aligned
Height compensation plate 7.5 mm 10 GV1-F03 0.003
Combination block Between GV2 and contactor 10 GV2-AF01 0.020LC1-K or LP1-K Between GV2 and contactor 10 GV2-AF3 0.016LC1-D09…D38Between GV2 mounted 10 GV2-AF4 0.016on LAD-31 andcontactor LC1-D09…D38
Motor starter With 3-pole connection 1 GK2-AF01 0.120adapter plate for mounting a GV2 and
an LC1-D09 to D25 contactor Description Application Pitch Reference Weight
mm kg
Sets of 3-pole 2 tap-offs 45 GV2-G245 0.03663 A busbars 54 GV2-G254 0.038
72 GV2-G272 0.0423 tap-offs 45 GV2-G345 0.058
54 GV2-G354 0.0604 tap-offs 45 GV2-G445 0.077
54 GV2-G454 0.08572 GV2-G472 0.094
5 tap-offs 54 GV2-G554 0.100Description Application Sold in Unit Weight
lots of reference kg
Protective end cover For unused busbar outlets 5 GV1-G10 0.005
Terminal blocks for Connection from the top 1 GV1-G09 0.040supply to one or more Can be fitted with current limiter 1 GV2-G05 0.115GV2-G busbar sets GV1-L3 (GV2-ME and GV2-P)
Cover for terminal block For mounting in 10 LA9-E07 0.005modular panels
Flexible 3-pole connection Centre distance between 10 GV1-G02 0.013for connecting a GV2 mounting rails: 100…120 mmto an LC1-D09…D25contactor
Set of connections For connecting GV2-ME 10 GV2-GA01 0.045upstream/downstream to a printed circuit board
Clip-in marker holders For GV2-P, GV2-L, GV2-LE 100 LA9-D92 (1) 0.001(supplied with each and GV2-RT (8 x 22 mm)circuit-breaker)
Padlockable external operator
Description Reference Weightkg
For GV2-P and GV2-L Padlocking in “On” and “Off” position GV2-AP01 0.200(150 to 290 mm) Black handle, blue legend plate, IP 54
Padlocking in “Off” position GV2-AP02 0.200Red handle, yellow legend plate, IP 54
For GV2-LE Padlocking in “On” and “Off” position GV2-AP03 0.280Black handle, blue legend plate, IP 54
Padlocking device
For all GV2 devices For use with up to 6 padlocks (not supplied), GV2-V03 0.130Ø 6 mm shank max.
References
Dimensions :pages 24538/2 to 24527/4
24512_Ver3.10-EN.fm/10 Schneider Electric
ON
OFFO
ON
OFFO
ON
OFFO
OFFO
ON
ON
OFFO
GV7RE, RS
GV7AP03
OFFO
ON
GV7AP04
GV7AP01, AP02
GV7V01
GV7AP05
GV7RE, RS
GV7AC01
GV7AC03 GV7AC01
GV7-AC04
GV7AC04
24512_Ver3.10-EN.fm/11Schneider Electric
TeSys protection componentsThermal-magnetic motor circuit-breakers type GV7-R with screw clamp connectionsAccessories
(2) contactor. The cover
Replaces the circuit-breaker front cover; secured by screws. It includes a device for locking the circuit-breaker in the O (Off) position by means of up to 3 padlocks with a shank diameter of 5 to 8 mm (padlocks not supplied). A conversion accessory allows the direct rotary handle to be mounted on the enclosure door. In this case, the door cannot be opened if the circuit-breaker is in the “tripped” position. Circuit-breaker closing is inhibited if the enclosure door is open
Allows a circuit-breaker installed in the back of an enclosure to be operated from the front of the enclosure. It comprises:- a unit which screws onto the front cover of the circuit-breaker,- an assembly (handle and front plate) to be fitted on the enclosure door,- an extension shaft which must be adjusted (distance between the mounting surface and the door: 185 mm minimum,600 mm maximum). It includes a device for locking the circuit-breaker in the O (Off) position by means of up to 3 padlockswith shank diameter of 5 to 8 mm (padlocks not supplied). This prevents the enclosure door from being opened.
Allows circuit-breakers not fitted with a rotary handle to be locked in the O (Off) position by means of up to 3 padlocks with a shank diameter of 5 to 8 mm (padlocks not supplied).
(1) Terminal shields cannot be used together with spreaders.(2) Le kit comprises links, a protective shield and a depth adjustable metal bracket for the breaker.(3) This conversion accessory makes it impossible to open the door if the device is closed and prevents the device frombeing closed if the door is open.
Cabling accessories
Description Application For Sold Unit Weightcontactor in reference kg
lots of
Clip-on Up to 150 A, 1.5…95 mm2 – 3 GV7-AC021 0.300connectorsfor GV7-R Up to 220 A, 1.5…185 mm2 – 3 GV7-AC022 0.350
3-pole To increase the – 1 GV7-AC03 0.180spreader (1) pitch to 45 mm
Terminal shields Supplied with the – 1 GV7-AC01 0.125IP 405 (1) sealing accessory
Phase Safety accessories used – 2 GV7-AC04 0.075barriers when fitting of shields
is impossible
Insulating screens Ensure insulation between – 2 GV7-AC05 0.075the connections and thebackplate
Kit for combination Allowing link between the LC1-F115 1 GV7-AC06 0.550with contactor circuit-breaker and the to F185
provides protection against LC1F225 1 GV7-AC07 0.550direct finger contact. and F265
LC1-D115 1 GV7-AC08 0.550and D150
Direct rotary handle
Description Type Degree of Reference Weightprotection kg
Direct Black handle, black legend plate IP 40 GV7-AP03 0.205rotary handle
Red handle, yellow legend plate IP 40 GV7-AP04 0.205
Conversion For mounting direct rotary IP 43 GV7-AP05 0.100accessory (3) handle on enclosure door
Extended rotary handle
Description Type Degree of Reference Weightprotection kg
Extended Black handle, black legend plate IP 55 GV7-AP01 0.775rotaryhandle Red handle, yellow legend plate IP 55 GV7-AP02 0.775
Locking device
Description Application Reference Weight kg
Locking device For circuit-breaker not fitted GV7-V01 0.100with a rotary handle
References
Characteristics :pages 24513/2 to 24513/7
Dimensions :pages 24538/5 to 24538/7
Schemes :page 24538/9
24509_Ver4.10-EN.fm/2 Schneider Electric
TeSys protection componentsThermal-magnetic motor circuit-breakers
(1) For operation up to 70 °C, please consult your Regional Sales Office.
Environment
Circuit-breaker type GV2-ME GV2-P GV3-ME GV7-R
Conforming to standards IEC 947-1, 947-2, 947-4-1, IEC-947-2, 947-4-1, IEC-947-1, 947-2, 947-4-1,EN 60204, UL 508, NF EN, BS EN, EN 60947-1, 60947-2,CSA C22-2 n° 14, DIN EN 60 947 EN 60947-4-1, NF C 63-650,NF C 63-650, 63-120, 79-130, NF C 63-120, 79-130,VDE 0113, 0660 VDE 0113, 0660
Electrical durability 440 V In/2 C.O. 100,000 100,000 50,000 30,000 50,000 40,000 20,000for AC-3 duty 440 V In C.O. – – – – 30,000 20,000 10,000
Duty class (maximum operating rate) C.O./h 25 25 25
Maximum conventional rated A 0.16…32 0.16…32 0.40…23 1.6…25 40…63 80 12…100 150 220thermal current (Ith) to IEC 947-4-1
Rated duty conforming to IEC 947-4-1 Continuous duty
Characteristics
References:pages 24508/2 to 24508/7
Dimensions:pages 24538/2 to 24538/7
Schemes:pages 24538/8 and 24538/9
24509_Ver4.10-EN.fm/3Schneider Electric
Connection to bars, cables with lugs or bare cables
Mounting characteristics
Operating position Without derating, in relation tonormal vertical mounting plane
Side view Front view
GV3-ME: preferably vertical
Cabling characteristics
Circuit-breaker type GV2-ME GV2-P GV3ME06…ME20 ME25…ME80
Connection to screw clamp terminalsNumber of conductors and c.s.a. Min. Max. Min. Max. Min. Max. Min. Max.
Solid cable mm2 2 x 1 2 x 6 2 x 1 2 x 6 2 x 1 2 x 6 1 x 2.5 1 x 35Flexible cablewithout cable end mm2 2 x 1.5 2 x 6 2 x 1.5 2 x 6 2 x 1 2 x 6 1 x 2.5 2 x 16Flexible cablewith cable end mm2 2 x 1 2 x 4 2 x 1 2 x 4 2 x 1 2 x 4 1 x 2.5 2 x 16
Tightening torque N.m 1.7 1.7 1.7 1.7 1.7 1.7 5 5
Connection to spring terminalsNumber of conductors and c.s.a.
Solid cable mm2 2 x 1 (1) 2 x 6 – – – – – –Flexible cablewithout cable end mm2 2 x 1.5 (1) 2 x 4 – – – – – –
GV7 circuit-breaker type GV7-R/20...GV7-R/100 GV7-R/150 GV7-R/220
Pitch without spreaders mm 35 35 35
with spreaders mm 45 45 45
Bars or cables with lugs e mm ≤ 6 ≤ 6 ≤ 6
L mm ≤ 25 ≤ 25 ≤ 25
d mm ≤ 10 ≤ 10 ≤ 10
Screws M6 M8 M8
Tightening torque N.m 10 15 15
Bare cables (copper or aluminium)with connectors height mm 20 20 20
c.s.a. mm2 1.5...95 1.5...95 1.5...185
Tightening torque N.m 15 15 15
(1) For c.s.a. of 1 to 1.5 mm2, the use of a cable end reducer LA9-D99 is recommended.
90° 90° 90° 90°
e
d
L
d
L
h
TeSys protection componentsThermal-magnetic motor circuit-breakers
Characteristics
References:pages 24508/2 to 24508/7
Dimensions:pages 24538/2 to 24538/7
Schemes:pages 24538/8 and 24538/9
24509_Ver4.10-EN.fm/4 Schneider Electric
TeSys protection componentsThermal-magnetic motor circuit-breakersmodels GV2-ME and GV2-P
( > 100 kA.(1) As % of Icu.
Breaking capacity of GV2-ME and GV2-P
Circuit-breaker type GV2- GV2-ME01 ME07 ME08 ME10 ME14 ME16 ME20 ME21 ME32 P01 P07 P08 P10 P14 P16 P20 P21 P32to and to andME06 ME22 P06 P22
Rating A 0.1 2.5 4 6.3 10 14 18 23 32 0.1 2.5 4 6.3 10 14 18 23 32to and to and1.6 25 1.6 25
Rating A 0.4 2.5 4 6.3 10 14 18 25 32 0.4 2.5 4 6.3 10 14 18 25 32 to to
1.6 1
Breaking capacity 230/ Icu kA g g g g g g g 50 50 g g g g g g g 50 50to IEC 947-2 240 V
Ics g g g g g g g 100 100 g g g g g g g 100 100% (1)
400/ Icu kA g g g g g 15 15 15 10 g g g g g 50 50 50 50415 V
Ics g g g g g 50 50 40 50 g g g g g 50 50 50 50% (1)
440 V Icu kA g g g 50 15 8 8 6 6 g g g g 20 20 20 20 20
Ics g g g 100 100 50 50 50 50 g g g g 75 75 75 75 75% (1)
500 V Icu kA g g g 50 10 6 6 4 4 g g g g 10 10 10 10 10
Ics g g g 100 100 75 75 75 75 g g g g 100 75 75 75 75% (1)
690 V Icu kA g 3 3 3 3 3 3 3 3 g 4 4 4 4 4 4 4 4
Ics g 75 75 75 75 75 75 75 75 g 100 100 100 100 100 100 100 100% (1)
Associated fuses (if required)If Isc > breaking capacity Icuto IEC 947-2 230/ aM A g g g g g g g 80 80 g g g g g g g 100 100amendment 1 240 V
gG A g g g g g g g 100 100 g g g g g g g 125 125
400/ aM A g g g g g 63 63 80 80 g g g g g 80 100 100 100415 V
gG A g g g g g 80 80 100 100 g g g g g 100 125 125 125
440 V aM A g g g 50 50 50 50 63 63 g g g g 50 63 80 80 80
gG A g g g 63 63 63 63 80 80 g g g g 63 80 100 100 100
500 V aM A g g g 50 50 50 50 50 50 g g g g 50 50 50 50 50
gG A g g g 63 63 63 63 63 63 g g g g 63 63 63 63 63
690 V aM A g 16 25 32 32 40 40 40 40 g 20 25 40 40 50 50 50 50
gG A g 20 32 40 40 50 50 50 50 g 25 32 50 50 63 63 63 63
Cable protection against thermalstress in the event of short-circuit(PVC insulated copper cables)
Minimum c.s.a. 1 mm2 kA p p p ≤ 10 ≤ 6 (2) (2) (2) (2) p p p ≤ 10 ≤ 6 (2) (2) (2) (2)protected at 40 °Cand at Isc max 1.5 mm2 kA p p p ≤ 20 ≤ 10 (2) (2) (2) (2) p p p ≤ 20 ≤ 10 (2) (2) (2) (2)
2.5 mm2 p p p p p p p p (2) p p p p p p p p (2)
4…6 mm2 p p p p p p p p p p p p p p p p p pg > 100 kA
Characteristics (continued)
References : pages 24522/2 and 24522/3
Dimensions :pages 24527/2 to 24527/4
Schemes :page 24527/5
4523 Ver2.00-EN.fm/4 Schneider Electric
TeSys protection componentsMagnetic motor circuit-breakers GK3
Environment
Conforming to standards IEC 947-2, EN 60-204
Protective treatment “TC”
Degree of protection GK3-EF basic unit: IP 20conforming to IEC 529
Shock resistance 22 gn for 20 msconforming to IEC 68-2-27
Vibration resistance 2.5 gn (0…25 Hz)conforming to IEC 68-2-6
Flame resistance Conforms for 960 °Cconforming to IEC 695-2-1
Ambient air temperatureStorage °C - 40…+ 80
Operation °C - 20… + 70 open mounted
Maximum operating altitude m 3000
Operating position Any
CablingSolid cable mm2 1 x 2.5 to 35 conductor
Flexible cable without cable end mm2 1 x 2.5 to 25 conductor or 2 x 2.5 to 16 conductors
Flexible cable with cable end mm2 1 x 2.5 to 25 conductor or 2 x 2.5 to 16 conductors
Tightening torque N.m 5
Suitability for isolation Yes, conforming to IEC 947-1ß7-1-6
Technical characteristics
Rated insulation voltage (Ui) V 750 conforming to IEC 947-2
Rated impulse withstand voltage kV 10(U imp) conforming to IEC 947-2
Rated operational voltage (Ue) V 690 conforming to IEC 947-2
Rated operational frequency Hz 50…60
Electrical durability C.O. C.O.: Closing-Openingfor AC-23/400 V duty 1500
Mechanical durability C.O. 20 000
Maximum operating rate C.O./h 40
Operating threshold of About 13 times the rating of the GK3-EF selected (non adjustable threshold)magnetic trips
Utilisation category Aconforming to IEC 947-2
Characteristics
References :pages 24522/2 and 24522/3
Dimensions :pages 24527/2 to 24527/4
Schemes :page 24527/5
24523 Ver2.00-EN.fm/Schneider Electric
TeSys protection componentsMagnetic motor circuit-breakers GK3
(1) As % of ICU
Type GK3-EF40 GK3-EF65 GK3-EF80
Breaking capacity of the 230/240 V Icu kA 100 50 50circuit-breaker only or of thecircuit-breaker combinedwith a suitably rated Ics 20 40 40thermal overload relay % (1)
400/415 V Icu kA 50 35 35
Ics 30 25 25% (1)
440 V Icu kA 30 25 25
Ics 30 30 30% (1)
500 V Icu kA 20 15 15
Ics 30 30 30% (1)
690 V Icu kA 6 6 6
Ics 60 50 50% (1)
Associated fuses (if required) 230/240 V aM A 160 200 200for use with circuit-breaker onlyor circuit-breaker combined gG A 250 315 315with a thermal overload relayif Isc > breaking capacity 400/415 V aM A 160 200 200
gG A 200 250 250
440 V aM A 160 160 160
gG A 200 250 250
500 V aM A 125 160 160
gG A 160 200 200
690 V aM A 100 125 125
gG A 125 160 160
Use of circuit-breakers without fuses Minimum cable length (in metres) limiting the maximum short-circuit current to 35 kA maximum, so enabling breakers GK3-EF to be used without fuses
Cable c.s.a. mm2 ≤ 25 35 50 70 95 120
Isc (kA rms) 3-phase, 50 kA m 5 6 8 10 13 15incoming (Ue = 400 V)
45 kA m 5 5 7 8 10 12
40 kA m 5 5 5 5 8 9
37 kA m 5 5 5 5 5 5
Characteristics (continued)
References : pages 24522/2 and 24522/3
Dimensions :pages 24527/2 to 24527/4
Schemes :page 24527/5
24513_Ver3.00-EN.fm/2
Characteristics
page 24512/3 pages 24538/2 to 24527/5
TeSys protection componentsThermal-magnetic and magnetic motor circuit-breakers GV2Auxiliary contacts
instantaneous auxiliary contacts
(1) For application example of fault signalling contact and short-circuit signalling contact, see page 24538/8.(2) Add an RC circuit type LA4-D to the load terminals, see page 24511/5.
Type of contacts Instantaneous auxiliaryGV-AN, GV-AD GV-AD, GV-AM11 (1) GV-AE
Rated insulation voltage (Ui)(associated insulation coordination) V 690 690 250 (690 in relation toto IEC 947-1 main circuit)to CSA C22-2 n° 14 and UL 508 V 600 300 300
Conventional rated thermal current(Ith) to IEC 947-5-1 A 6 2.5 2.5to CSA C22-2 n° 14 and UL 508 A 5 1 1
Mechanical durability C.O. 100 000 1000 100 000
Operational power and currentto IEC 947-5-1, a.c. operation AC-15/100 000 C.O. AC-14/1000 C.O. AC-15/100 000 C.O.
Operational power, normal conditions W 140 240 180 140 120 – – 24 15 9 – 24 15 9 –
Occasional breaking and making W 240 360 240 210 180 – – 100 50 50 – 100 50 50 –capacities, abnormal conditions
Rated operational current (Ie) A 6 5 3 1.3 0.5 – – 1 0.3 0.15 – 1 0.3 0.15 –
Low level switching contact reliability GV-AE: Number of failures for for “n” million operating cycles (17 V-5 mA) : = 10-6
Minimum operational conditions V 17d.c. operation mA 5
Short-circuit protection By GB2-CB// circuit breaker (rating according to operational current GB2-CB06 or for Ue ≤ 415 V) or by gG fuse 10 A max gG fuse 10 A max
Cabling, screw clamp terminalsNumber of conductors 1 2Solid cable mm2 1…2.5 1…2.5Flexible cable without cable end mm2 0.75…2.5 0.75…2.5Flexible cable with cable end mm2 0.75…1.5 0.75…1.5Tightening torque N.m 1.4 max 1.4 max
Cabling, spring terminal connections GV-AN onlyFlexible cable without cable end mm2 0.75…2.5 0.75…2.5 – 0.75…1.5
Contact operation,
Operation of faultsignalling contacts
GV-AM11Change of state following tripping on short-circuit.
GV-AD10// and GV-AD01//Change of state following trippingon short-circuit, overload or undervoltage.
References : Dimensions and schemes :
GV-AN20
GV-AN11
GV-AE1
Power pole
GV-AE20
Contact open
Contact closed
GV-AD//01
GV-AD//10
GV-AE11
0 1
N/ON/O
N/ON/C
N/ON/C
N/ON/O
N/ON/C
N/O
N/C
Instantaneous auxiliaryFault signalling
Schneider Electric
Schneider Electric
Characteristics
page 24512/5 pages 24538/2 to 24527/5
TeSys protection componentsThermal-magnetic motor circuit-breakers GV3-MEAuxiliary contacts
0 1P
OF
FF
FF
O
FF
F
FF
Type of contacts Instantaneous auxiliary Fault signallingGV3-A01 to A07 GV3-A08 and A09
Rated insulation voltage (Ui)to IEC 158-1 V 690 690
to CSA C22-2 n° 14. UL 508 V 600 (B600) 600 (B600)
Conventional rated thermal current (Ith)to IEC 337-1 A 6 6
to CSA C22-2 n° 14. UL 508 A 5 (B600) 5 (B600)
Mechanical durability C.O. 100 000 1000
Operational power and currentconforming to IEC 337-1a.c. operation 110 220 380 110 220 380
Rated operational current (Ie)AC-12 A 6 6 6 6 6 6 6 5 5 5 5 5 5 5
AC-15 A 6 6 5 4 3 3 0.1 5 5 4 3 2.5 2.5 0.1
Operational currentconforming to IEC 947-5-1
d.c. operation DC-12 or DC-14. 50 000 C.O. DC-12 or DC-14. 50 000 C.O.
Rated operational voltage (Ue) V 24 48 110 250 24 48 110 250
Rated operational current (Ie)DC-12 A 2.5 2.5 0.8 0.3 2 2 0.5 –
DC-14 A 1 0.2 0.5 0.03 0.5 0.1 0.25 –
Minimum operational conditionsd.c. operation V 17 12
mA 5 5
Short-circuit protection By GB2-CB// circuit breaker (rating according to operational current for Ue ≤ 415 V) or gG fuse, 10 A max.
CablingSolid cable mm2 1 x 1.5 conductor 1 x 1.5 conductor
Flexible cable without cable end mm2 1 x 1.5 conductor 1 x 1.5 conductor
Flexible cable with cable end mm2 1 x 1.5 conductor 1 x 1.5 conductor
References : Dimensions and schemes :
Schneider Electric
Schneider Electric
Characteristics
page 24512/5 pages 24538/2 to 24527/5
TeSys protection componentsMagnetic motor circuit breakers GK3
Characteristics of Start-Stop and fault signalling contacts
Rated insulation voltage (Ui) Conforming to IEC 947-5-1 V 500
Rated operational voltage (Ue) Conforming to IEC 947-5-1 V 500
Conventional rated thermal Conforming to IEC 947-5-1 A 6current (Ith)
Operational power and current 110 220 380 conforming to IEC 947-5-1. C.O.: Closing-Opening V 48 127 240 415 440 500 a.c. operation
Operational power VA 360 500 800 850 700 700AC-15/20 000 C.O.
Occasional breaking and VA 4000 12 000 20 000 20 000 15 000 15 000making capacities
Rated operational current (Ie) A 6 4.5 3.5 2.2 1.5 1.5
Operational power and current C.O.: Closing-Opening V 24 48 60 110 220 conforming to IEC 947-5-1.d.c. operation
Operational power W 180 240 180 140 120DC-13/1000 C.O.
Occasional breaking and W 240 380 240 210 180making capacities
Rated operational current (Ie) A 6 5 3 1.3 0.5
Short-circuit protection Conforming to IEC 947-5-1 By GB2-CB08 circuit breaker or gG fuse, 6 A max
Cabling Solid cable mm2 1 x 1…4 conductor
Flexible cable without mm2 1 x 2.5 conductorcable end
Flexible cable with cable end mm2 1 x 1…2.5 conductor or 2 x 1…2.5 conductors
Tightening torque N.m 0.8
References : Dimensions and schemes :
24513_Ver3.00-EN.fm/5
24513_Ver3.00-EN.fm/6
Characteristics
pages 24512/2 to 24512/7 pages 24538/2 to 24538/7
TeSys protection componentsThermal-magnetic motor circuit-breakers Electric trips
Type of circuit breaker GV2-ME, GV2-P GV3-ME GV7-R
Type of trip GV-AU GV-AX (1) GV-AS GV3-B GV3-D GV7-AU GV7-AS
Characteristics of electric trips
Rated insulation voltage (Ui)conforming to IEC 947-1 V 690 500 690 690 690 690 690
to CSA C22-2 n° 14. UL 508 V 600 – 600 600 (B600) 600 (B600) 600 600
Operational currentconforming to IEC 947-1 V 0.85…1.1 Un 0.7…1.1 Un 0.8…1.1 Un 0.85…1.1 Un 0.7…1.1 Un
Drop-out voltage V 0.7…0.35 Un 0.75…0.2 Un 0.7…0.35 Un 0.35…0.7 Ue 0.2…0.75 Ue
Inrush consumption" VA 12 14 12 < 10
$ W 8 10.5 7 < 5
Sealed consumption" VA 3.5 5 7 < 5
$ W 1.1 1.6 2.5 < 5
Operating time From the moment the voltage reaches its operational value until opening of the circuit breaker.conforming to IEC 947-1 ms 10…15 10 15 < 50
On-load factor 100 % 100 % 100 %
CablingNumber of conductors 1 or 2 1 or 2 1
Solid cable mm2 1…2.5 1…2.5 1…2.5 1.5
Flexible cable without cable end mm2 0.75…2.5 0.75…2.5 0.75…2.5 1.5
Flexible cable with cable end mm2 0.75…1.5 0.75…2.5 0.75…2.5 1
Tightening torque N.m 1.4 max 1.2 1.2 1.2
Mechanical durability C.O. 100 000 50 % of the mechanical durability of the circuit breaker.(C.O.: Closing-Opening)
(1) Wiring scheme of undervoltage trip for dangerous machines (conforming to INRS) on GV2-ME only, see page 24538/8.
References : Dimensions : Schemes :
Schneider Electric
pages 24538/8 and 24538/9
Schneider Electric
Characteristics
page 24512/9 pages 24538/2 to 24527/5
TeSys protection componentsThermal-magnetic and magnetic motor circuit-breakers GV2Accessories
Characteristics of 3-pole busbars GV2-G///
Rated insulation voltage (Ui) Conforming to IEC 947-1 V 690
Conventional rated thermal current Conforming to IEC 439-1 A 63(Ith)
Permissible peak current kA 11(I peak)
Permissible thermal limit kA2s 104(I2t)
Degree of protection Conforming to IEC 529 IP 20
Characteristics of terminal blocks GV2-G05 and GV1-G09
Rated insulation voltage (Ui) Conforming to IEC 947-1 V 690
Conventional rated thermal current Conforming to IEC 439-1 A 63(Ith)
Degree of protection Conforming to IEC 529 IP 20
Cabling Solid cable mm2 1 x 1.5 to 25 conductor or 2 x 1.5 to 10 conductors
Flexible cable without mm2 1 x 1.5 to 25 conductor or 2 x 2.5 to 10 conductorscable end
Flexible cable with mm2 1 x 1.5 to 16 conductor or 2 x 1.5 to 4 conductorscable end
Tightening torque Connector N.m 2.2
Screw clamp N.m 1.7
Characteristics of current limiters (GV2-ME and GV2-P)
Type GV1-L3 LA9-LB920
Rated insulation voltage (Ui) Conforming to IEC 947-1 V 690 690
Conventional rated thermal current Conforming to IEC 947-1 A 63 63(Ith)
Operating threshold rms current A 1500 (non adjustable threshold) 1000 (non adjustable threshold)
Auxiliary contacts 1 N/C and 1 N/O instantaneous incorporated in the contactors, with add-on blocks common to the whole
Compatible manual-auto thermaloverload relays Class 10 A 0.10…10 A 0.10…13 A 0.10…18 A 0.10…32 A 0.10…38 A 0.10…38 A
Class 20 2.5…10 A 2.5…13 A 2.5…18 A 2.5…32 A –
Suppressor modules(d.c. and low Varistor p p p p p p p pconsumption Diode – – p – – p – –contactors have RC circuit p p p p p p p pbuilt-in suppress- Bidirectional peak p p p p p p p pion as standard) limiting diode
Interfaces Relay p p p p p p p pRelay + override function p p p p p p p pSolid state p p p p p p p p
LC1-D09 LC1-D12 LC1-D18 LC1-D25 LC1-D32 LC1-D38Contactor a or c 3-poletype references
– LC1-D12 – LC1-D25 – –a 4-pole
– LP1-D12 – LP1-D25 – –c 4-pole
LC2-D09 LC2-D12 LC2-D18 LC2-D25 LC2-D32 LC2-D38Reversing a 3-poleContactor
LC2-D09 LC2-D12 LC2-D18 LC2-D25 LC2-D32 LC2-D38type references c 3-pole
– LC2-D12 – LC2-D25 – –a 4-pole
– LP2-D12 – LP2-D25 – –c 4-pole
Pages Contactors 24501/2 to 24502/3Reversing contactors 24503/2 to 24510/3
0246Q Ver3.00-EN.fmSchneider Electric
40 A 50 A 65 A 80 A 95 A 115 A 150 A60 A 80 A 125 A 200 A
range comprising up to 4 N/C or N/O instantantaneous, up to 1 N/O + 1 N/C time delay and up to 2 N/O or N/C protected contacts and 2 screen continuity terminals
17…50 A 17…70 A 17…80 A 17…104 A 17…104 A 60…150 A 60…150 A17…40 A 17…65 A 17…70 A 17…80 A 60…150 A 60…150 A
p p p p p p p p p p –p p p p p p p p – – –p p p p p p p p p p pp p p p p p p p – – –
p p p p p p p p p p pp p p p p p p p p p pp p p p p p p p p p –
Rated operational currentIe max AC-3 (Ue ≤ 440 V) 9 A 12 A 18 A
Ie AC-1 (θ ≤ 60 °C) 25 A 25 A 32 A
Rated operational voltage 690 V
Rated 220/240 V 2.2 kW 3 kW 4 kWoperationalpower 380/400 V 4 kW 5.5 kW 7.5 kWin AC-3
415/440 V 4 kW 5.5 kW 9 kW
500 V 5.5 kW 7.5 kW 10 kW
660/690 V 5.5 kW 7.5 kW 10 kW
Coil consumption 2.4 W (100 mA – 24 V)
Operating ranges 0.7…1.25 Uc
Operating time at20 °C and at Uc Closing 70 ms
Opening 25 ms
Auxiliary contact blocks 1 N/C and 1 N/O instantaneous contacts incorporated in the contactors, with add-on blocks, common to the
whole range, comprising up to 2 N/C or 2 N/O instantaneous standard or dust and damp protected contactsand 2 screen continuity terminals.
Interference suppression Built-in suppression as standard, by bi-directional peak limiting diode
Contactor type LC1-D09 LC1-D12 LC1-D18
Reversing contactor type LC2-D09 LC2-D12 LC2-D18
Pages Contactors 24501/2 to 24502/3
Reversing contactors 24503/2 to 24510/3
TeSys contactorsLow consumption, D range
Selection guide
0247Q Ver2.00-EN.fmSchneider Electric
25 A 32 A 38 A
40 A 50 A 50 A
5.5 kW 7.5 kW 9 kW
11 kW 15 kW 18.5 kW
11 kW 15 kW 18.5 kW
15 kW 18.5 kW 18.5 kW
15 kW 18.5 kW 18.5 kW
LC1-D25 LC1-D32 LC1-D38
LC2-D25 LC2-D32 LC2-D38
4501_Ver5.00-EN.fm/2 Schneider Electric
TeSys contactors For motor control up to 75 kW at 400 V, in category AC-3Control circuit: a.c., d.c. or low consumption
Insert the digit 6 before the voltage code in the references selected above.Example: LC1-D09// becomes LC1-D096//.
Auxiliary contact blocks and modules: see pages 24511/2 to 24511/9.
(2) Standard control circuit voltages.
LC1-D115 and D150: clip-on mounting on 2 x 35 mm rails AM1-DP or screw fixing.(4) LC: low consumption.(5) The weights indicated are for contactors with a.c. control circuit. For d.c. or low consumption control circuit, add0.160 kg for contactors LC1-D09 to D38, 0.785 kg for contactors LC1-D40 to D65 and 1 kg for contactors LC1-D80 andD95.(6) For purchase in bulk packs, see page A0005/3.
3-pole contactors for connection by screw clamp terminals or connectors (1)
Standard power ratings Rated Instantan- Basic reference. Weightof 3-phase motors opera- eous Complete with code indicating (5)50/60 Hz in category AC-3 tional auxiliary control circuit voltage (2)(θ ≤ 60 °C) current contacts Fixing (3)
in AC-3220V 380V 660V 440 V Standard voltages230V 400V 415V 440V 500V 690V 1000V up to " $ LC(4)kW kW kW kW kW kW kW A kg
3-pole contactors for connection by lugs or bars (1)
LC1-D09//
8103
56
LC1-D25//
8103
5381
0352
LC1-D95//
Accessories
(1) See note (1) on next page.
a.c. supplyVolts 24 42 48 110 115 220 230 240 380 400 415 440 500LC1-D09...D150 (D115 and D150 coils with integral suppression device fitted as standard)50/60 Hz B7 D7 E7 F7 FE7 M7 P7 U7 Q7 V7 N7 R7 –LC1-D40...D11550 Hz B5 D5 E5 F5 FE5 M5 P5 U5 Q5 V5 N5 R5 S560 Hz B6 – E6 F6 – M6 – U6 Q6 – – R6 – d.c. supplyVolts 12 24 36 48 60 72 110 125 220 250 440LC1-D09...D38 (coils with integral suppression device fitted as standard)U 0.7…1.25 Uc JD BD CD ED ND SD FD GD MD UD RDLC1-D40...D95U 0.85…1.1 Uc JD BD CD ED ND SD FD GD MD UD RDU 0.75…1.2 Uc JW BW CW EW – SW FW – MW – –LC1-D115 and D150 (coils with integral suppression device fitted as standard)U 0.75…1.2 Uc – BD – ED ND SD FD GD MD UD RDLow consumptionVolts $ 5 24 48 72LC1-D09...D38 (coils with integral suppression device fitted as standard) U 0.7…1.25 Uc AL BL EL SLFor other voltages between 5 and 690 V, see pages 24507/2 to 24507/9.
LC1-D115//
1055
17
(3) LC1-D09 to D38: clip-on mounting on 35 mm rail AM1-DP or screw fixing.LC1-D40 to D95 ": clip-on mounting on 35 mm or 75 mm rail AM1-DL or screw fixing.LC1-D40 to D95 $: clip-on mounting on 75 mm rail AM1-DL or screw fixing.
References
Selection:pages 24565/2 to 24572/5
Characteristics:pages 24505/2 to 24505/7
Dimensions:pages 24531/2 to 24531/5
Schemes:pages 24532/2 and 24532/3
24501_Ver5.00-EN.fm/3Schneider Electric
Selection:pages 24565/2 to 24572/5
Characteristics:pages 24505/2 to 24505/7
Dimensions:pages 24531/2 to 24531/5
Schemes:pages 24532/2 and 24532/3
TeSys contactors For motor control up to 15 kW at 400 V, in category AC-3Control circuit: a.c., d.c. or low consumption
These contactors are fitted with Faston connectors: 2 x 6.35 mm on the power poles and 1 x 6.35 mm or 2 x 2.8 mmon the coil and auxiliary terminals.For contactors LC1-D09 and LC1-D12 only, replace the digit 3 with a 9 in the references selected above.Example: LC1-D093// becomes LC1-D099//.
Auxiliary contact blocks and modules: see pages 24511/2 to 24511/9.
(1) 3-pole contactors LC1-D09 to D150 can be supplied without safety cover. To order, insert the digit 5 before thevoltage code in the references selected from either above or the previous page.
(2) Standard control circuit voltages.
(3) LC1-D09 to D32: clip-on mounting on 35 mm rail AM1-DP or screw fixing.(4) LC: low consumption.(5) The weights indicated are for contactors with a.c. control circuit. For d.c. or low consumption control circuit, add0.160 kg for contactors LC1-D09 to D32.(6) For purchase in bulk packs, see page A0005/3.(7) For use with power connection module LAD-34 or Quickfit technology outgoing terminal block LAD-33, see page15021/5.
3-pole contactors for connection by spring terminals (1)
Standard power ratings Rated Instantan- Basic reference. Weightof 3-phase motors opera- eous Complete with code indicating (5)50/60 Hz in category AC-3 tional auxiliary control circuit voltage (2)(θ ≤ 60 °C) current contacts Fixing (3)
in AC-3220V 380V 660V 440 V Standard voltages230V 400V 415V 440V 500V 690V up to " $ LC(4)kW kW kW kW kW kW A kg
d.c. supplyVolts 12 24 36 48 60 72 110 125 220 250 440LC1-D09...D32 (coils with integral suppression device fitted as standard)U 0.7…1.25 Uc JD BD CD ED ND SD FD GD MD UD RD
Low consumption Volts $ 5 24 48 72LC1-D09...D32 (coils with integral suppression device fitted as standard)U 0.7…1.25 Uc AL BL EL SLFor other voltages between 5 and 690 V, see pages 24507/2 to 24507/9.
References
Insert the digit 6 before the voltage code in the references selected above.Example: LC1-D09// becomes LC1-D096//.
These contactors are fitted with Faston connectors: 2 x 6.35 mm on the power poles and 1 x 6.35 mm on the coilterminals.For contactors LC1-D09 and LC1-D12 only, insert the digit 9 before the voltage code in the references selected above.Example: LC1-D09// becomes LC1-D099//.
Auxiliary contact blocks and modules: see pages 24511/2 to 24511/9.
(1) 3-pole contactors LC1-D09 to D95 can be supplied without safety cover. To order, insert the digit 5 before the voltagecode in the references selected above.
(2) See note (2) page 24502/3.(3) LC1-D09 to D38 and LC1-DT20 to DT80: clip-on mounting on 35 mm rail AM1-DP or screw fixing.LC1-D40 to D95 ": clip-on mounting on 35 mm or 75 mm rail AM1-DL or screw fixing.LC1 or LP1-D40 to D95 $: clip-on mounting on 75 mm rail AM1-DL or screw fixing.LC1-D115 and D150: clip-on mounting on 2 x 35 mm rails AM1-DP or screw fixing.(4) LC: low consumption.(5) The weights indicated are for contactors with a.c. control circuit. For d.c. or low consumption control circuit, add0.160 kg for contactors LC1-D09 to D38, 0.785 kg for contactors LC1-D40 to D65 and 1 kg for contactors LC1-D80 andD95.(6) For purchase in bulk packs, see page A0005/3.(7) Selection according to the number of operating cycles, see AC-1 curve, page 24561/2.(8) 32 A if the contactor is used with the power connection module LAD-34 or Quickfit technology outgoing terminalblock LAD-33, see page 15021/5. 25 A without these accessories.
3-pole contactors for connection by screw clamp terminals or connectors (1)
Non inductive loads maximum current (θ ≤ 60 °C) utilisation category AC-1
Numberof poles
Instantaneous Basic reference. Weightauxiliary Complete with code indicating (5)contacts control circuit voltage (2)
TeSys contactors For control in utilisation category AC-1, 25 to 200 AControl circuit: a.c., d.c. or low consumption
Insert the digit 6 before the voltage code in the references selected above.Example: LC1-DT20// becomes LC1-DT206//.
Auxiliary contact blocks and modules: see pages 24511/2 to 24511/9.(1) See note (1) page 24502/2.(2) Standard control circuit voltages.
For other voltages between 5 and 690 V, see pages 24507/2 to 24507/9.(3) LC: low consumption.(4) The weights indicated are for contactors with a.c. control circuit. For d.c. or low consumption control circuit, add0.165 kg and for contactors LC1-D80, 1 kg.
4-pole contactors for connection by screw clamp terminals or connectors
Non inductive loads maximum current (θ ≤ 60 °C) utilisation category AC-1
Numberof poles
Instantaneous Basic reference. Weightauxiliary Complete with code indicating (4)contacts control circuit voltage (2)
a.c. supplyVolts 24 42 48 110 115 220 230 240 380 400 415 440 500LC1-D09...D150 and LC1-DT20...DT60 (coils with integral suppression device fitted as standard)50/60 Hz B7 D7 E7 F7 FE7 M7 P7 U7 Q7 V7 N7 R7 –LC1-D40...D11550 Hz B5 D5 E5 F5 FE5 M5 P5 U5 Q5 V5 N5 R5 S560 Hz B6 – E6 F6 – M6 – U6 Q6 – – R6 – d.c. supplyVolts 12 24 36 48 60 72 110 125 220 250 440LC1-D09...D38 and LC1-DT20...DT60 (coils with integral suppression device fitted as standard)U 0.7…1.25 Uc JD BD CD ED ND SD FD GD MD UD RDLC1 or LP1-D40...D80U 0.85…1.1 Uc JD BD CD ED ND SD FD GD MD UD RDU 0.75…1.2 Uc JW BW CW EW – SW FW – MW – –LC1-D115 (coil with integral suppression device fitted as standard)U 0.75…1.2 Uc – BD – ED ND SD FD GD MD UD RD Low consumption Volts $ 5 24 48 72LC1-D09...D38 and LC1-DT20...DT60 (coils with integral suppression device fitted as standard)U 0.7…1.25 Uc AL BL EL SL
TeSys contactors For control in utilisation category AC-1, 20 to 200 AControl circuit: a.c., d.c. or low consumption
References
Selection:pages 24565/2 to 24572/5
Characteristics:pages 24505/2 to 24505/7
Dimensions:pages 24531/2 to 24531/5
Schemes:pages 24532/2 and 24532/3
TeSys contactorsReversing contactors for motor control up to75 kW on 400 V in category AC-3,horizontally mounted, pre-assembledControl circuit: a.c., d.c. or low consumption
Pre-wired power connectionsMechanical interlock without electrical interlocking.
For reversing contactors LC2-D09 to LC2-D38, LC2-D115 and LC2-D150, insert the digit 6 before the voltage code in the references selected above. Example: LC2-D09// becomes LC2-D096//.
Auxiliary contact blocks and modules: see pages 24511/2 to 24511/9.
(3) LC: low consumption.(4) The weights indicated are for reversing contactors with a.c. control circuit. For d.c. or low consumption control circuit,add 0.330 kg.(5) For reversing contactors with electrical interlocking pre-wired at the factory, add suffix V to the references selectedabove. Example: LC2-D09P7 becomes LC2-D09P7V.
3-pole reversing contactors for connection by screw clamp terminals or connectors
Standard power ratings Rated Instantaneous Contactors supplied with coil Weightof 3-phase motors opera- auxiliary Basic reference. Complete with code (4)50/60 Hz in category AC-3 tional contacts per indicating control circuit voltage (2)
current contactor Fixing (1)in AC-3(θ ≤ 60°C)
220 V 380 V 660 V 440 V Standard voltages230 V 400 V 415 V 440 V 500 V 690 V 1000 V up to " $ LC (3)kW kW kW kW kW kW kW A kg
3-pole reversing contactors for connection by lugs or bars
Accessories
(1) LC2-D09 to D38: clip-on mounting on 35 mm rail AM1-DP or screw fixing.LC2-D40 to D95: clip-on mounting on 35 mm or 75 mm rail AM1-DL or screw fixing.LC2-D115 and D150: clip-on mounting on 2 x 35 mm rails AM1-DP or screw fixing.(2) Standard control circuit voltages. a.c. supplyVolts 24 42 48 110 115 220 230 240 380 400 415 440 500LC2-D09...D150 (D115 and D150 coils with integral suppression device fitted as standard)50/60 Hz B7 D7 E7 F7 FE7 M7 P7 U7 Q7 V7 N7 R7 –LC2-D40...D11550 Hz B5 D5 E5 F5 FE5 M5 P5 U5 Q5 V5 N5 R5 S560 Hz B6 – E6 F6 – M6 – U6 Q6 – – R6 – d.c. supplyVolts 12 24 36 48 60 72 110 125 220 250 440LC2-D09...D38 (coils with integral suppression device fitted as standard)U 0.7…1.25 Uc JD BD CD ED ND SD FD GD MD UD RD Low consumption Volts $ 5 24 48 72LC2-D09…D38 (coils with integral suppression device fitted as standard)U 0.7…1.25 Uc AL BL EL SLFor other voltages between 5 and 690 V, see pages 24507/2 to 24507/9.
References
Selection:pages 24565/2 to 24572/5
Characteristics:pages 24505/2 to 24505/7
Dimensions, schemes:pages 24533/2 and 24533/3
TeSys contactorsReversing contactors for motor control up to15 kW on 400 V in category AC-3,horizontally mounted, pre-assembledControl circuit: a.c., d.c. or low consumption
Pre-wired power connectionsMechanical interlock without electrical interlocking.
These contactors are fitted with Faston connectors: 2 x 6.35 mm on the power poles and 1 x 6.35 mm or 2 x 2.8 mmon the coil and auxiliary terminals.For reversing contactors LC2-D09 and LC2-D12 only, replace the digit 3 with a 9 in the references selected above.Example: LC2-D093// becomes LC2-D099//.
Auxiliary contact blocks and modules: see pages 24511/2 to 24511/9.
(3) LC: low consumption.(4) The weights indicated are for reversing contactors with a.c. control circuit. For d.c. or low consumption control circuit,add 0.330 kg.(5) For use with power connection module LAD-34 or Quickfit technology outgoing terminal block LAD-33, see page15021/5.
3-pole reversing contactors for connection by spring terminals
Standard power ratings Rated Instantaneous Contactors supplied with coil Weightof 3-phase motors opera- auxiliary Basic reference. Complete with code (4)50/60 Hz in category AC-3 tional contacts indicating control circuit voltage (2)
current per Fixing (1)in AC-3 contactor (θ ≤ 60°C)
220 V 380 V 660 V 440 V Standard voltages230 V 400 V 415 V 440 V 500 V 690 V up to " $ LC (3)kW kW kW kW kW kW A kg
d.c. supplyVolts 12 24 36 48 60 72 110 125 220 250 440LC2-D09...D32 (coils with integral suppression device fitted as standard)U 0.7…1.25 Uc JD BD CD ED ND SD FD GD MD UD RD
Low consumption Volts $ 5 24 48 72LC2-D09...D32 (coils with integral suppression device fitted as standard)U 0.7…1.25 Uc AL BL EL SLFor other voltages between 5 and 690 V, see pages 24507/2 to 24507/5.
References
Selection:pages 24565/2 to 24572/5
Characteristics:pages 24505/2 to 24505/7
Dimensions, schemes:pages 24533/2 and 24533/3
24510_Ver5.00-EN.fm/2 Schneider Electric
Pre-wired power connections
LC2-DT20 to LC2-DT60 mechanical interlock without electrical interlocking. LC2-D65 and LC2-D80 : order separately2 auxiliary contact blocks LAD-N/1 to obtain electrical interlocking between the 2 contactors (see page 24511/3). Forelectrical interlocking incorporated in the mechanical interlock, please consult your Regional Sales Office.LC2-D115 mechanical interlock with integral, pre-wired electrical interlocking.
Auxiliary contact blocks and add-on modules: see pages 24511/2 to 24511
(1) LC2-DT20 to DT60: clip-on mounting on 35 mm rail AM1-DP or screw fixing.LC2-D65 and D80: clip-on mounting on 35 mm or 75 mm rail AM1-DL or screw fixing.LC2-D115: clip-on mounting on 2 x 35 mm rails AM1-DP or screw fixing.(2) See note (2) next page.(3) LC: low consumption.(4) For replacement in existing equipment.
4-pole changeover contactor pairs for connection by screw clamp terminals or connectors
Utilisation category AC-1 Instantaneous Contactors supplied with coils WeightNon-inductive loads auxiliary Basic reference. Complete with codeMaximum rated contacts indicating control circuit voltage (2)operational current per Fixing (1)(θ < 60 °C) contactor
TeSys contactorsChangeover contactor pairs for control in utilisation category AC-1, 20 to 200 A, horizontally mounted, pre-assembledControl circuit: a.c., d.c. or low consumption
Selection :pages 24565/2 to 24572/
5 Characteristics :
pages 24505/2 to 24505/7
Dimensions, schemes :pages 24533/2 and 24533/
3
References
24510_Ver5.00-EN.fm/3Schneider Electric
Pre-wired power connections
With mechanical interlock without electrical interlocking
Auxiliary contact blocks and add-on modules: see pages 24511/2 to 24511/9.
(1) Clip-on mounting on 35 mm rail AM1-DP or screw fixing.(2) Standard control circuit voltages.
For other voltages between 5 and 690 V, see pages 24507/2 to 24507/9.(3) LC : low consumption.
4-pole changeover contactor pairs for connection by spring terminals
Utilisation category AC-1 Instantaneous Contactors supplied with coils WeightNon-inductive loads auxiliary Basic reference. Complete with codeMaximum rated contacts indicating control circuit voltage (2)operational current per Fixing (1)(θ < 60 °C) contactor
Standard voltages" $ LC (3)
A kg
20 1 1 LC2-DT203// B7 P7 BD BL 0.760
25 1 1 LC2-DT253// B7 P7 BD BL 0.760
4-pole changeover contactor pairs for connection by lugs or bars
d.c. supplyVolts 12 24 36 48 60 72 110 125 220 250 440LC2-DT20…DT60 (coils with integral suppression device fitted as standard)U 0.7…1.25 Uc JD BD CD ED ND SD FD GD MD UD RD
Low consumption Volts $ 5 24 48 72LC2-DT20...DT60 (coils with integral suppression device fitted as standard)U 0.7…1.25 Uc AL BL EL SL
TeSys contactorsChangeover contactor pairs for control in utilisation category AC-1, 20 and 25 A, horizontally mounted, pre-assembledControl circuit: a.c., d.c. or low consumption
References
Selection :pages 24565/2 to 24572/
5 Characteristics :
pages 24505/2 to 24505/7
Dimensions, schemes :pages 24533/2 and 24533/
3
(1) To order the 2 contactors: see pages 24501/2 and 24501/3.(2) Including mechanical interlock.
For 3-pole motor reversing contactors
Contactors with screw clamp terminals or connectorsHorizontally mounted, assembled by customerUsing Set of Mechanical2 identical power connections interlockcontactors (1) Reference Weight Reference Weight
kg of kit kg
Including mechanical interlock and an electrical interlocking kit for the contactors
LC1-D09…D38 LAD-9R1V (2) 0.045 – –
Including mechanical interlock with integral electrical interlocking
LC1-D40…D65 LA9-D6569 0.290 LA9-D4002 0.170
LC1-D80 and D95 (") LA9-D8069 0.290 LA9-D4002 0.170
LC1-D80 and D95 ($) LA9-D8069 0.490 LA9-D8002 0.170
LC1-D115 and D150 LA9-D11569 1.450 LA9-D11502 0.290
Including mechanical interlock without electrical interlocking
LC1-D09…D38 LAD-9R1 (2) 0.045 – –
LC1-D40…D65 LA9-D6569 0.290 LA9-D50978 0.170
LC1-D80 and D95 (") LA9-D8069 0.490 LA9-D50978 0.170
LC1-D80 and D95 ($) LA9-D8069 0.490 LA9-D80978 0.170
For low speed - high speed starter
Description For contactorswith connections
Reference Weightkg
Connection kit enabling reversing of slow and high speed directions, using a reversing contactor and a2N/O + 2N/C main pole contactor
Screw clamps or connectors LAD-9PVGV 0.016
Spring terminals LAD-3PVPG 0.068
LA9-D4002
810
376
LA9-D6569
8103
74
LA9-D8069
8103
7581
0373
LAD-9R1
810
377
References TeSys contactorsComponent parts for assembling reversing contactors for motor control or low speed - high speed starters
Selection:pages 24565/2 to 24565/5
Characteristics:pages 24505/2 to 24505/7
Dimensions, schemes:pages 24533/2 and 24533/3
References TeSys contactorsComponent parts for assembling changeover contactor pairs for distribution
Including mechanical interlock with integral electrical interlocking
(1) To order the 2 contactors: see pages 24502/3 and 24503/2.(2) Including mechanical interlock.(3) Order 2 contact blocks LAD-N/1 to obtain electrical interlocking between the contactors, see page 24511/3.
For 4-pole changeover contactor pairs (3-phase distribution + neutral)
Contactors with screw clamp terminals or connectorsHorizontally mounted, assembled by customerUsing Set of Mechanical 2 identical power connections interlockcontactors (1) Reference Weight Reference Weight
kg of kit kg
Including mechanical interlock and an electrical interlocking kit for the contactors
LC1-DT20…DT32 LAD-T9R1V (2) 0.040 – –
LC1-DT40 and DT60 LAD-T9R2V (2) 0.045 – –
Including mechanical interlock with integral electrical interlocking
LC1-D65004 LA9-D6570 0.150 LA9-D4002 0.170
LC1-D80004 LA9-D8070 0.280 LA9-D4002 0.170
LP1-D80004 LA9-D8070 0.280 LA9-D8002 0.170
LC1-D115004 LA9-D11570 1.100 LA9-D11502 0.280
Including mechanical interlock without electrical interlocking (3)
LC1-DT20…DT32 LAD-T9R1 (2) 0.035 – –
LC1-DT40 and DT60 LAD-T9R2 (2) 0.040 – –
LC1 or LP1-D65004 LA9-D6570 0.150 LA9-D50978 0.155
LC1-D80004 LA9-D8070 0.280 LA9-D50978 0.155
LP1-D80004 LA9-D8070 0.280 LA9-D80978 0.180
For 3-pole changeover contactor pairs
LA9-D4002
8103
84
LA9-D6570
810
379
LA9-D50978
810
383
LA9-D8070
8103
80
LC1-D115 and D150 LA9-D11571 0.960 LA9-D11502 0.280
Selection:pages 24565/2 to 24565/5
Characteristics:pages 24505/2 to 24505/7
Dimensions, schemes:pages 24533/2 and 24533/3
24511_Ver5.00-EN.fm/2 Schneider Electric
LA1-DX, DY, DZ
LAD-NLAD-C
LAD-N
LAD-8N
LAD-8N
LC1
LAD-R
LAD-TLAD-S2
LA6-DKorLAD-6K
LAD-N10, N01
8104
36
See page opposite for mounting possibilities according to the contactor type and rating
24511_Ver5.00-EN.fm/3Schneider Electric
Characteristics:pages 24506/2 to 24506/4
Dimensions:pages 24531/2 to 24531/5
Schemes:pages 24532/2 and 24532/3
TeSys contactors Contactors and reversing contactors, model dInstantaneous auxiliary contact blocks
For use in normal operating environmentsIn order to mount on an LAD-8N on an LC1-D40 to D95, a set of shims must be ordered separately, see page 24511/9.
This type of connection is not possible for blocks with dust and damp protected contacts. For all other instantaneous auxiliarycontact blocks, add the digit 6 to the end of the references selected above. Example: LAD-N10 becomes LAD-N106.
This type of connection is not possible for LAD-8, LAD-N with 1 contact or blocks with dust and damp protected contacts. For all other contact blocks, add the digit 3 to the end of the references selected above. Example: LAD-N11 becomes LAD-N113.
This type of connection is not possible for LAD-8, LAD-N with 1 contact or blocks with dust and damp protected contacts. For all other contact blocks, add the digit 9 to the end of the references selected above. Example: LAD-N11 becomes LAD-N119.(1) Maximum number of auxiliary contacts that can be fitted
Instantaneous auxiliary contact blocks for connection by lugs
Instantaneous auxiliary contact blocks for connection by spring terminals
Instantaneous auxiliary contact blocks for connection by Faston connectors
Contactors Instantaneous auxiliary contact blocks Time delaySide Front mounted Front
Type Number of poles and size mounted 1 contact 2 contacts 4 contacts mounted" 3P LC1-D09…D38 1 on left-hand side & – 1 or 1 or 1
LC1-D40…D95 (50/60 Hz) 1 on each side or 2 and 1 or 1 or 1LC1-D40…D95 (50 or 60 Hz) 1 on each side & 2 and 1 or 1 or 1LC1-D115 and D150 1 on left-hand side & – 1 or 1 or 1
4P LC1-DT20…DT60 1 on left-hand side & – 1 or 1 or 1LC1-D65 and D80 1 on each side or 1 or 1 or 1 or 1LC1-D115 1 on each side & 1 or 1 or 1 or 1
$ 3P LC1-D09…D38 – – 1 or 1 or 1LC1-D40…D95 – 1 or 1 or 1 or 1LC1-D115 and D150 1 on left-hand side & – 1 or 1 or 1
4P LC1-DT20…DT80 1 on left-hand side or – 1 or 1 or 1LP1-D65 and D80 – 2 and 1 or 1 or 1LC1-D115 1 on each side – and 1 or 1 or 1
LC (3) 3P LC1-D09…D38 – – 1 (4) – –4P LC1-DT20…DT60 1 on left-hand side & – 1 or 1 or 1
References
24511_Ver5.00-EN.fm/4 Schneider Electric
Maximum number of auxiliary contact blocks that can be fitted per contactor, see page 24511/3Sealing cover to be ordered separately, see page 24511/9LAD-T0 and LAD-R0: with extended scale from 0.1 to 0.6 s.LAD-S2: with switching time of 40 ms ± 15 ms between opening of the N/C contact and closing of the N/O contact.
Add the digit 6 to the end of the references selected above. Example: LAD-T0 becomes LAD-T06.
Add the digit 3 to the end of the references selected above. Example: LAD-T0 becomes LAD-T03.
Add the digit 9 to the end of the references selected above. Example: LAD-T0 becomes LAD-T09.
(1) For purchase in bulk packs, see page A0005/3.
(3) The mechanical latching block must not be powered up at the same time as the contactor. The duration of the controlsignal for the mechanical latching block and the contactor should be ≥ 100 ms.
Time delay auxiliary contact blocks for connection by screw clamp terminals
Clip-on Number Time delay Reference Weightmounting of Type Setting
contacts range kg
Front 1 N/O On- 0.1…3 s LAD-T0 (1) 0.060+ delay1 N/C
0.1…30 s LAD-T2 (1) 0.060
10…180 s LAD-T4 (1) 0.060
1…30 s LAD-S2 0.060
Off- 0.1…3 s LAD-R0 (1) 0.060delay
0.1…30 s LAD-R2 (1) 0.060
10…180 s LAD-R4 (1) 0.060
LAD-T
8104
38
Time delay auxiliary contact blocks for connection by lugs
Time delay auxiliary contact blocks for connection by spring terminals8104
41
LAD-T/3
Time delay auxiliary contact blocks for connection by Faston connectors
Mechanical latch blocks (3)
Clip-on Unlatching For use on Basic reference. Standard Weightmounting control contactor Complete with
code indicatingvoltages
control voltage (2) kg
Front Manual or LC1-D40…D65 3P " or $ LA6-DK10/ B E F M Q 0.070electric LC1-D65 4P "
LP1-D65 4P $
LC1-D80…D150 3P " LA6-DK20/ B E F M Q 0.090LC1-D80 and D115 3P $LP1-D80 and LC1-D115 4P $
LC1-D09…D38 " or $ LAD-6K10/ B E F M Q 0.070LC1-DT20…DT60 " or $
(2) Standard control circuit voltages (for other voltages please consult your Regional Sales Office).Volts 50/60 Hz, $ 24 32/36 42/48 60/72 100 110/127 220/240 256/277 380/415Code B C E EN K F M U Q
LA6-DK
8104
39
LA6-DK
8104
40TeSys contactorsContactors and reversing contactors, model dTime-delay auxiliary contact blocksMechanical latch blocks
References
Characteristics:pages 24506/2 to 24506/4
Dimensions:pages 24531/2 to 24531/5
Schemes:pages 24532/2 and 24532/3
24511_Ver5.00-EN.fm/5Schneider Electric
TeSys contactorsContactors and reversing contactors, model dCoil suppressor modules
/ Protection provided by limiting the transient voltage to 2 Uc max./ Maximum reduction of transient voltage peaks.
(1) For satisfactory protection, a suppressor module must be fitted across the coil of each contactor.(2) From LC1-D09 to D38 and LC1-DT20 to DT60, d.c. and low consumption 3-pole contactors are fitted with built-insuppression as standard.(3) Clipping-on makes the electrical connection. The overall size of the contactor remains unchanged.(4) Mounting at the top of the contactor on coil terminals A1 and A2.
RC circuits (resistor-capacitor)
/ Effective protection for circuits highly sensitive to “high frequency” interference. For use only in cases where thevoltage is virtually sinusoidal, i.e. less than 5 % total harmonic distortion.
/ Voltage limited to 3 Uc maximum and oscillating frequency limited to 400 Hz maximum./ Slight increase in drop-out time (1.2 to 2 times the normal time).
Mounting For use with contactor (1) Reference WeightRating Type
/ Protection provided by limiting the transient voltage to 2 Uc max./ Maximum reduction of transient voltage peaks./ Slight increase in drop-out time (1.1 to 1.5 times the normal time).
Spreaders D115, D115, 3 GV7-AC03 0.180for increasing the D150 D150pole pitch to 45 mm
LA9-D3260
8104
45
LA9-D11560/
8104
47
LA9-D11550/
8104
46
LA9-D11570/
8104
50
LA9-D80962
8104
48
LA9-D6567
8104
49References
Dimensions:pages 24531/2 to 24531/5
Schemes:pages 24532/2 and 24532/3
24511_Ver5.00-EN.fm/9Schneider Electric
TeSys contactorsContactors and reversing contactors, model dAccessories
(1) These legends are for sticking onto the safety cover of the contactors or add-on block, if fitted.(2) For purchase in bulk packs, see page A0005/3.
Sets of contacts and arc chambers
Description For use on Reference Weightcontactors kg
Set of contacts 3-pole LC1-D115 LA5-D1158031 0.260LC1-D150 LA5-D150803 0.260
For adapting existing wiring LC1-D09…D38 Without coil suppression LAD-4BB 0.019to a new product LC1- With coil " 24…48 V LAD-4BBVE 0.014
DT20…DT60 suppress- " 50…127 V LAD-4BBVG 0.014ion " 110…250 V LAD-4BBVU 0.014
Set of 63 A busbars for 2 contactors LC1-D09…D18 or D25…D38 GV2-G245 0.036parallelling of contactors 4 contactors LC1-D09…D18 or D25…D38 GV2-G445 0.077
Terminal block for supply to: One or more GV2-G busbar sets GV1-G09 0.040
Protection accessories
Description Application Sold in Unit Weightlots of reference kg
Miniature circuit-breaker 5 x 20 with 4 A-250 V fuse 1 LA9-D941 0.025
Sealing cover For LAD-T, LAD-R 1 LA9-D901 0.005
Safety cover LC1-D09…D38 and DT20…DT60 1 LAD-9ET1 0.026preventing access to the LC1-D40…D65 1 LAD-9ET2 0.012moving contact carrier LC1-D80 and D95 1 LAD-9ET3 0.004
LC1-D115 and D150 1 LAD-9ET4 0.004
Lens cap for safety cover LC1-D09...D38 and DT20…DT60 100 LAD-9ECT1 0.001
Marking accessories
Description Application Sold in Unit Weightlots of reference kg
Sheet of 64 blank legends Contactors (excluding 10 LAD-21 0.020self-adhesive, 8 x 33 (1) 4-pole LC1-D65…D115)
LAD-N (4 contacts), LA6-DK
Sheet of 112 blank legends LAD-N (2 contacts), 10 LAD-22 0.020self-adhesive, 8 x 12 (1) LAD-T, LAD-R, LRD
Sheet of 64 blank legends Contactors (excluding 10 LAD-23 0.050for marking using plotter or 4-pole LC1-D65…D115)8 x 33 engraver LAD (4 contacts), LA6-DK
Sheet of 112 blank legends All products 35 LAD-24 0.200for marking using plotter or8 x 12 mm engraver
Legend holder 4-pole contactors LC1-D65 100 LA9-D92 (2) 0.001snap-in, 8 x 22 mm and D80, LA6-DK
Bag of 300 blank legends On holder LA9-D92 1 LA9-D93 0.001self-adhesive, 7 x 21 mm“SIS Label” label Multi-language version
(EN, FR, DE, SP, 1T)creation software 1 XBY-1U 0.060
Mounting accessories
Mounting plate For replacement of LC1-F115 1 LA9-D730 0.360or F150 by LC1-D115 or D150
Set of shims For fitting side mounting blocks 1 LA9-D511 0.020LAD-8N on LC1-D40 to D95
GV2-G245
8104
52
GV1-G09
8104
53
LA9-D941
8104
51
LAD-9ET/
8104
54
XBY-1U
8104
55
References (continued)
24505_Ver5.00-EN.fm/2 Schneider Electric
TeSys contactorsModel d
(1) Protection ensured for the connection cross-sections shown on the next page and for connection via cable.(2) In the least favourable direction, without change of contact state (coil supplied at Ue).
Type of contactor LC1- LC1- LC1- LC1- LC1-D115 &D09…D18 D25…D38 D40 D50…D95 LC1-D150DT20 & DT25 DT32…DT60
Environment
Rated insulation voltage (Ui) Conforming to IEC 947-4-1, overvoltage category III,degree of pollution: 3 V 690 1000
Conforming to UL, CSA V 600
Rated impulse withstand voltage Conforming to IEC 947 kV 6 8(Uimp)
Tightening torque N.m – – – – – 1.2 1.2 1.2 1.2(1) Spade connector or cable lug, see connection via cable above.
Characteristics
Selection:pages 24565/2 to 24572/5
References:pages 24501/2 to 24502/3
Dimensions:pages 24531/2 to 24531/5
Schemes:pages 24532/2 and 24532/3
24505_Ver5.00-EN.fm/4 Schneider Electric
TeSys contactorsModel d
(1) Protection ensured for the connection cross-sections shown on page 24505/3 and for connection via cable.(2) In the least favourable direction, without change of contact state (coil supplied at Ue).(3) The closing time “C” is measured from the moment the coil supply is switched on to initial contact of the main poles. The opening time “O” is measured fromthe moment the coil supply is switched off to the moment the main poles separate.
Type of contactor LC1- D09 DT20 D12 DT25 D18 DT32 D25 DT40
Pole characteristics
Rated operational current (Ie) In AC-3, θ ≤ 60 °C A 9 12 18 25(Ue ≤ 440 V) In AC-1, θ ≤ 60 °C A 25 20 25 32 40
Rated operational voltage (Ue) Up to V 690 690 690 690
Frequency limits Of the operating current Hz 25…400 25…400 25…400 25…400
Conventional thermal current (Ith) θ ≤ 60 °C A 25 20 25 25 32 32 40 40
Rated making capacity (440 V) Conforming to IEC 947 250 250 300 450
Permissible short-time rating For 1 s A 210 210 240 380No current flowing for preceding For 10 s A 105 105 145 24015 minutes at θ ≤ 40 °C For 1 min A 61 61 84 120
For 10 min A 30 30 40 50
Protection by fuse Without thermal overload relay, type 1 A 25 40 50 63 against short-circuits (U ≤ 690 V) fuse gG
type 2 A 20 25 35 40
With thermal overload relay A See pages 24514/2 and 24514/3, for aM or gG fuse ratingscorresponding to the associated thermal overload relay
Average impedance per pole At Ith and 50 Hz mΩ 2.5 2.5 2.5 2
Power dissipation per pole AC-3 W 0.20 0.36 0.8 1.25for the above operating currents AC-1 W 1.56 1.56 2.5 3.2
a.c. control circuit characteristics
Rated control circuit voltage (Uc) 50/60 Hz V 12…690
Control voltage limits50 or 60 Hz coils Operational –
Drop-out –50/60 Hz coils Operational 0.8…1.1 Uc on 50 Hz and
0.85…1.1 Uc on 60 Hz at 60 °CDrop-out 0.3…0.6 Uc at 60 °C
Average consumption " 50 Hz Inrush 50 Hz coil VA –at 20 °C and at Uc Cos ϕ 0.75
50/60 Hz coil VA 70
Sealed 50 Hz coil VA –Cos ϕ 0.350/60 Hz coil VA 7
" 60 Hz Inrush 60 Hz coil VA –Cos ϕ 0.7550/60 Hz coil VA 70
Sealed 60 Hz coil VA –Cos ϕ 0.350/60 Hz coil VA 7.5
Heat dissipation 50/60 Hz W 2…3
Operating time (3) Closing “C” ms 12…22Opening “O” ms 4…19
Mechanical life 50 or 60 Hz coil –in millions of operating cycles 50/60 Hz coil on 50 Hz 15
Maximum operating rate In operating cycles per hour 3600at ambient temperature ≤ 60 °C
– 0.85…1.1 Uc at 55 °C 0.85…1.1 Uc at 55 °C– 0.3…0.6 Uc at 55 °C 0.3…0.5 Uc at 55 °C0.8…1.1 Uc on 50 Hz and 0.8…1.1 Uc on 50 Hz and0.85…1.1 Uc on 60 Hz at 60 °C 0.85…1.1 Uc on 60 Hz at 55 °C 0.8…1.15 Uc on 50/60 Hz at 55 °C0.3…0.6 Uc at 60 °C 0.3…0.6 Uc at 55 °C 0.3…0.5 Uc at 55 °C
(1) Operating times depend on the type of contactor electromagnet and its control mode. The closing time “C” is measured from the moment the coil supply is switched on to initial contact of the main poles. The opening time “O” is measured from themoment the coil supply is switched off to the moment the main poles separate.(2) In the least favourable direction, without change of contact state.
d.c. control circuit characteristics
Type of contactor LC1- LC1- or LP1- LC1 or LC1-D115 &D09…D38 D40…D65 LP1-D80 LC1-D150DT20…DT60
Rated control circuit voltage (Uc) $ V 12…440 12…440 24…440
Rated insulation voltage Conforming to IEC 947-1 V 690
Conforming to UL, CSA V 600
Control voltage limits Operational Standard coil 0.7…1.25 Uc 0.85…1.1 Uc at 55 °C 0.75…1.2 Ucat 60 °C at 55 °C
Wide range coil – 0.75…1.2 Uc at 55 °C –
Drop-out 0.1…0.25 Uc 0.1…0.3 Uc at 55 °C 0.15…0.4 Ucat 60 °C at 55 °C
Average consumption $ Inrush W 5.4 22 22 270 to 365at 20 °C and at Uc
Sealed W 5.4 22 22 2.4…5.1
Average operating time (1) Closing “C” ms 55 85…110 95…130 20…35at Uc
Opening “O” ms 20 20…35 20…35 40…75Note: The arcing time depends on the circuit switched by the poles. For normal 3-phase applications, the arcing timeis usually less than 10 ms. The load is isolated from the supply after a time equal to the sum of the opening time andthe arcing time.
Time constant (L/R) ms 28 65 75 25
Mechanical life at Uc In millions of operating cycles 30 20 20 8
Maximum operating rate In operating cycles per hour 3600 3600 3600 1200at ambient temperature ≤ 60 °C
Low consumption control circuit characteristics
Rated insulation voltage Conforming to IEC 947-1 V 690
Conforming to UL, CSA V 600
Maximum voltage Of the control circuit on $ 250
Average consumptiond.c. Wide range coil Inrush W 2.4at 20 °C and at Uc (0.7…1.25 Uc)
Sealed W 2.4
Operating time (1) Closing “C” ms 70at Uc and at 20 °C
Opening “O” ms 25
Voltage limits (θ ≤ 60 °C) Operational 0.7 to 1.25 Ucof the control circuit
Drop-out 0.1…0.3 Uc
Time constant (L/R) ms 40
Mechanical life In millions of operating cycles 30
Maximum operating rate At ambient temperature ≤ 60 °C ops/h 3600
Characteristics (continued)
Selection:pages 24565/2 to 24572/5
References:pages 24501/2 to 24502/3
Dimensions:pages 24531/2 to 24531/5
Schemes:pages 24532/2 and 24532/3
24505_Ver5.00-EN.fm/7Schneider Electric
Contactor integral auxiliary contact characteristics
Linked contacts conforming to Each contactor has 2 N/O and N/C contacts mechanically linked on the same movable contact holderdraft standard IEC 947-4-5
Mirror contact The N/C contact on each contactor represents the state of the power contacts and can be connected to aPREVENTA safety module
Rated operational voltage (Ue) Up to V 690
Rated insulation voltage (Ui) Conforming to IEC 947-1 V 690
Conforming to UL, CSA V 600
Conventional thermal current (Ith) For ambient temperature ≤ 60 °C A 10
Operating current frequency Hz 25…400
Minimum switching capacity U min. V 17λ = 10–8
I min. mA 5
Short-circuit protection Conforming to IEC 947-5-1 gG fuse: 10 A
Rated making capacity Conforming to IEC 947-5-1, I rms A ": 140, $: 250
Short-time rating Permissible for 1 s A 100500 ms A 120100 ms A 140
Insulation resistance MΩ > 10
Non-overlap time Guaranteed between N/C and N/O contacts ms 1.5 on energisation and on de-energisation
a.c. supply categories AC-14 and AC-15 d.c. supply category DC-13Contact operating power Electrical life (valid for up to 3600 operating cycles/hour) Electrical life (valid for up to 1200 operating cycles/hour)conforming to IEC 947-5-1 on an inductive load such as the coil of an electromagnet: on an inductive load such as the coil of an electromagnet,
making power (cos ϕ 0.7) = 10 times the power broken without economy resistor, the time constant increasing(cos ϕ 0.4). with the load.
V 24 48 115 230 400 440 600 V 24 48 125 250 4401 million operating cycles VA 60 120 280 560 960 1050 1440 W 96 76 76 76 443 million operating cycles VA 16 32 80 160 280 300 420 W 48 38 38 32 –10 million operating cycles VA 4 8 20 40 70 80 100 W 14 12 12 – –
AC-15 DC-13
0,1 0,2 0,3 0,40,5
0,60,7
0,80,9
1 2 3 45
67
8910
0,1
0,2
0,3
0,4
0,60,5
0,80,7
7
1
2
3
54
6
81
Current broken in A
Mill
ions
of o
pera
ting
cycl
es
0,1 0,2 0,3 0,40,5
0,60,7
0,80,9
1 2 3 45
67
8910
0,1
0,2
0,3
0,4
0,60,5
0,80,7
7
1
2
3
54
6
81
440 V
48 V
250 V
125 V
24 V
Current broken in A
Mill
ions
of o
pera
ting
cycl
es
TeSys contactorsModel d
Characteristics (continued)
Selection:pages 24565/2 to 24572/5
References:pages 24501/2 to 24502/3
Dimensions:pages 24531/2 to 24531/5
Schemes:pages 24532/2 and 24532/3
TeSys contactorsAuxiliary contact blocks withoutdust and damp protected contactsfor model d contactors
Contact block type LAD-N or C LAD-T & S LAD-R LAD-8
Environment
Conforming to standards IEC 947-5-1, NF C 63-140, VDE 0660, BS 4794, EN 60947-5-1
Product certifications UL, CSA
Protective treatment Conforming to IEC 68 “TH”
Degree of protection Conforming to VDE 0106 Protection against direct finger contact IP 2X
Ambient air temperature Storage °C - 60…+ 80around the device
Operation °C - 5…+ 60
Permissible for operation at Uc °C - 40…+ 70
Maximum operating altitude Without derating m 3000
Cabling Phillips N° 2 and Ø 6 mm mm2 Min.: 1 x 1; max.: 2 x 2.5Flexible or solid cable with or without cable end
Connection by spring terminals Flexible or solid cable without cable end mm2 Max.: 2 x 2.5
Instantaneous and time delay contact characteristics
Number of contacts 1, 2 or 4 2 2 2
Rated operational voltage (Ue) Up to V 690
Rated insulation voltage (Ui) Conforming to IEC 947-5-1 V 690
Conforming to UL, CSA V 600
Conventional thermal current (Ith) For ambient temperature ≤ 60 °C A 10
Frequency of operational current Hz 25…400
Minimum switching capacity U min. V 17
I min. mA 5
Short-circuit protection Conforming to IEC 947-5-1 and VDE 0660. gG fuse A 10
Rated making capacity Conforming to IEC 947-5-1, I rms A ": 140; $: 250
Short-time rating Permissible for: 1 s A 100
500 ms A 120
100 ms A 140
Insulation resistance MΩ > 10
Non-overlap time Guaranteed between N/C and N/O contacts ms 1.5 (on energisation and on de-energisation)
Overlap time Guaranteed between N/C and N/O on LAD-C22 ms 1.5 – – –
Time delay Ambient air temperature for operation °C – - 40…+ 70 - 40…+ 70 –(LAD-T, R and S contact blocks)Accuracy only valid for setting range Repeat accuracy – ± 2 % ± 2 % –indicated on the front face
Drift up to 0.5 million operating cycles – + 15 % + 15 % –
Drift depending on ambient air temperature – 0.25 % per °C 0.25 % per °C –
Mechanical durability In millions of operating cycles 30 5 5 30
Operational power of contacts See page 24506/4
Characteristics
References:pages 24511/3 and 24511/4
Dimensions:pages 24531/2 and 24531/3
Schemes:pages 24532/2 and 24532/3
TeSys contactorsAuxiliary contact blocks withdust and damp protected contactsfor model d contactors
Contact block type LA1-DX LA1-DX LA1-DYprotected non protected
Environment
Conforming to standards IEC 947-5-1, VDE 0660
Product certifications UL, CSA
Protective treatment Conforming to IEC 68 “TH”
Degree of protection Conforming to VDE 0106 Protection against direct finger contact IP 2X
Ambient air temperature Storage and operation °C - 25…+ 70
Cabling Phillips N° 2 and Ø 6 mmFlexible or solid cable mm2 Min.: 1 x 1with or without cable end Max.: 2 x 2.5
Number of contacts 2 2 2 2
Contact characteristics
Rated operational voltage (Ue) Up to V 50 50 690 24
Rated insulation voltage (Ui) Conforming to IEC 947-5-1 V 250 250 690 250
Conforming to UL, CSA V – – 600 –
Conventional thermal current (Ith) For ambient temperature ≤ 40 °C A – – 10 –
Maximum operational current (Ie) mA 50 50 10 50
Frequency of operational current Hz – – 25…400 –
Minimum switching capacity U min. V 3 3 17 3
I min. mA 0.3 0.3 5 0.3
Short-circuit protection Conforming to IEC 947-5-1. gG fuse A – – 10 –
Rated making capacity Conforming to IEC 947-5-1, I rms A – – ": 140; $: 250 –
Short-time rating Permissible for: 1 s A – – 100 –
500 ms A – – 120 –
100 ms A – – 140 –
Insulation resistance MΩ > 10 > 10 > 10 > 10
Mechanical durability In millions of operating cycles 5 5 30 5
Materials and technology Gold - Single Gold - Single – Gold - Singleused for dust and damp break with break with break withprotected contacts crossed bars crossed bars crossed bars
Characteristics
References:page 24511/3
Dimensions:pages 24531/2 and 24531/3
Schemes:pages 24532/2 and 24532/3
0,1 0,2 0,3 0,40,5
0,60,7
0,80,9
1 2 3 45
67
8910
0,1
0,2
0,3
0,4
0,60,5
0,80,7
7
1
2
3
54
6
81
0,1 0,2 0,3 0,40,5
0,60,7
0,80,9
1 2 3 45
67
8910
0,1
0,2
0,3
0,4
0,60,5
0,80,7
7
1
2
3
54
6
81
440 V
48 V
250 V
125 V
24 V
Mill
ions
of o
pera
ting
cycl
esM
illio
ns o
f ope
ratin
g cy
cles
Current broken in A
Current broken in A
a.c. supply, categories AC-14 and AC-15
Electrical durability (valid up to 3600 operating cycles/hour) on an inductive load such as the coil of an electromagnet:making power (cos ϕ 0.7) = 10 times the power broken (cos ϕ 0.4).
d.c. supply, category DC-13
Electrical durability (valid up to 1200 operating cycles/hour) on an inductive load such as the coil of an electromagnet,without economy resistor, the time constant increasing with the power.
Operational power of contacts (conforming to IEC 947-5-1)
V 24 48 115 230 400 440 6001 million operating cycles VA 60 120 280 560 960 1050 14403 million operating cycles VA 16 32 80 160 280 300 42010 million operating cycles VA 4 8 20 40 70 80 100
V 24 48 125 250 4401 million operating cycles W 120 90 75 68 613 million operating cycles W 70 50 38 33 2810 million operating cycles W 25 18 14 12 10
TeSys contactorsAuxiliary contact blocks withdust and damp protected contactsfor model d contactors
Characteristics
References:pages 24511/3 and 24511/4
Dimensions:pages 24531/2 and 24531/3
Schemes:pages 24532/2 and 24532/3
TeSys contactorsControl modules, coil suppressor modulesand mechanical latch blocksfor model d contactors
Unlatching can be manually operated or electrically controlled (pulsed or maintained).The LA6-DK or LAD-6K latch coil and the LC1-D operating coil must not be energised simultaneously. The duration ofthe LA6-DK or LAD-6K and LC1-D control signals must be ≥ 100 ms.
Environment
Conforming to standards IEC 947-5-1
Product certifications UL, CSA
Protective treatment Conforming to IEC 68 “TH”
Degree of protection Conforming to VDE 0106 Protection against direct finger contact IP 2X
Ambient air temperature Storage °C - 40…+ 80around the device Operation °C - 25…+ 55
Permissible for operation at Uc °C - 25…+ 70
“Auto - Man - Stop” control modules
Recommendation The Auto - Man selector switch must only be operated with the Start - Stop (“O” “I”) switch in position “O”
Rated insulation voltage Conforming to IEC 947-5-1 V 250
Rated operational voltage Conforming to IEC 947-5-1 V 250
Protection Against electric shocks kV 2
Built-in protection Contactor coil suppression By varistor
Indication By integral LED Illuminates when the contactor coil is energised
Electrical durability In operating cycles 20,000
Coil suppressor modules
Module type LA4-DA LA4-DB LA4-DC LA4-DELAD-4RC LAD-4T LAD-4V
Type of protection RC circuit Bidirectional Diode Varistorpeak limitingdiode
Rated control circuit voltage (Uc) V " " or $ $ " or $24…415 24…72 12…250 24…250
Maximum peak voltage 3 Uc 2 Uc Uc 2 Uc
Natural RC frequency 24/48 V Hz 400 – – –50/127 V Hz 200110/240 V Hz 100 – – –380/415 V Hz 150 – – –
Mechanical latch blocks
Mechanical latch block type LA6-DK10 LAD-6K10 LA6-DK20For mounting on contactor LC1D40…D65,
LP1-D65LC1-D09…D38,DT20…DT60
LC1-D80…D150LP1-D80 and LC1-D115
Certification UL, CSA UL, CSA
Rated insulation voltage Conforming to IEC 947-5-1 V 690 690
Rated control circuit voltage " 50/60 Hz and $ V 24…415 24…415
Power required For unlatching " VA 25 25$ W 30 30
Maximum operating rate In operating cycles/hour 1200 1200On-load factor 10 % 10 %Mechanical durability at Uc In millions of operating cycles 0.5 0.5
Characteristics
References:pages 24511/4 to 24511/7
Dimensions:pages 24531/2 and 24531/3
Schemes:pages 24532/2 and 24532/3
01
01
t 01
01
t
01
40 ms
TeSys contactorsElectronic serial timer modulesfor model d contactors
Time delay output
Module type LA4-DT (On-delay) LA4-DR (Off-delay) for LC1-D
Environment
Conforming to standards IEC 255-5Product certifications UL, CSAProtective treatment Conforming to IEC 68 “TH”Degree of protection Conforming to VDE 0106 Protection against direct finger contact IP 2X
Ambient air temperature Storage °C - 40…+ 80around the device Operation °C - 25…+ 55
For operation at Uc °C - 25…+ 70
Rated insulation voltage (Ui) Conforming to IEC 947-5-1 V 250
Cabling Phillips N° 2 and Ø 6 mm mm2 Min.: 1 x 1Flexible or solid cablewith or without cable end Max.: 2 x 2.5
Control circuit characteristics
Built-in protection On input By varistor By varistorSuppression of contactor By varistor By bidirectional peak limiting diode
Rated control circuit voltage (Uc) V " or $ 24…250 " 24…250
Permissible variation 0.8…1.1 Uc 0.8…1.1 Uc
Type of control By mechanical contact only By mechanical contact only,connecting cable < 10 m
Time delay characteristics
Timing ranges s 0.1…2; 1.5…30; 25…500 0.1…2; 1.5…30; 25…500
Repeat accuracy 0…40 °C ± 3 % (10 ms minimum) ± 3 % (10 ms minimum)
Reset time During the time delay period ms 150 225After the time delay period ms 50 –
Immunity to micro-breaks During the time delay period ms 10 20After the time delay period ms 2 –
Minimum control pulse duration ms – 40
Indication of time delay By LED Illuminates during time delay period Illuminates during time delay period
TeSys contactorsInterface modulesfor model d contactors
Environment
Conforming to standards IEC 255-5
Product certifications UL, CSA
Protective treatment Conforming to IEC 68 “TH”
Degree of protection Conforming to VDE 0106 Protection against direct finger contact IP 2X
Ambient air temperature Storage °C - 40…+ 80around the device Operation °C - 25…+ 55
Permissible for operation at Uc °C - 25…+ 70
Other characteristics
Module type LA4- LA4- LA4- LA4- LA4- LA4-DFBQ DFB DFE DLB DLE DWBWith With With With relay
+ overrideSolid
relay relay relay state
Rated insulation voltage Conforming to IEC 947-5-1 V 5 250
Rated operational voltage Conforming to IEC 947-5-1 V 415 250
Indication of input state By integral LED which illuminates when the contactor coil is energised
Input signals Control voltage (E1-E2) V $ 24 $ 24 $ 48 $ 24 $ 48 $ 24
Permissible variation V 17…30 17…30 33…60 17…30 33…60 5…30
Current consumption at 20 °C mA 25 25 15 25 15 8.5 for 5 V15 for 24 V
State “0” guaranteed for U V < 2.4 < 2.4 < 4.8 < 2.4 < 4.8 < 2.4
I mA < 2 < 2 < 1.3 < 2 < 1.3 < 2
State “1” guaranteed for U V 17 17 33 17 33 5
Built-in protection Against reverse polarity By diodeOf the input By diode
Electrical durability at 220/240 V In millions of operating cycles 3 10 10 3 3 20
Maximum immunity time ms 4 4 4 4 4 1to micro-breaks
Power dissipated At 20 °C W 0.6 0.6 0.6 0.6 0.6 0.4
Direct mounting without contactor With coil: " 24…250 V – LC1-D40…D150 –
" 100…250 V – – LC1-D40…D115
" 380…415 V LC1-D40…D150 – –
Mounting with cabling adaptor LAD-4BB
With coil: " 24…250 V – LC1-D09…D38, DT20…DT60
LC1-D09…D38,DT20…DT60
" 380…415 V LC1-D09…D38,DT20…DT60
– –
Total operating timeat Uc (of the contactor)
Operating times depend on the type of contactor electromagnet and its control mode.The closing time “C” is measured from the moment the coil supply is switched on to initial contact of the main poles.The opening time “O” is measured from the moment the coil supply is switched off to the moment the main polesseparate.
LC1-D09…D38, DT20…DT60
LC1-D40…D65 LC1-D80 and D95
With LA4-DF, DL N/O ms 20…30 28…34 28…43N/C ms 16…24 20…24 18…32
Cabling Phillips N° 2 and Ø 6 mmFlexible or solid cable
mm2 Min.: 1 x 1
with or without cable end mm2 Min.: 2 x 2.5
Characteristics
References:page 24511/7
Dimensions:pages 24531/2 and 24531/3
Schemes:pages 24532/2 and 24532/3
Specifications
Average consumption at 20 °C:- inrush (cos ϕ = 0.75) 70 VA,- sealed (cos ϕ = 0.3) 50 Hz: 7 VA, 60 Hz: 7.5 VA.Operating range (θ ≤ 60 °C): 50 Hz: 0.8…1.1 Uc, 60 Hz: 0.85…1.1 Uc.
(1) The last 2 digits of the reference represent the voltage code.(2) Voltage for special coils fitted in contactors with serial timer modules, with 24 V supply.
Control circuit voltage Average resistance Inductance of Reference (1) WeightUc at 20 °C ± 10 % closed circuitV Ω H kg
For 3-pole contactors LC1-D09...D38 and LC1-DT20…DT60
50/60 Hz
12 6.3 0.26 LXD-1J7 0.070
21 (2) 5.6 0.24 LXD-1Z7 0.070
24 6.19 0.26 LXD-1B7 0.070
32 12.3 0.48 LXD-1C7 0.070
36 – – LXD-1CC7 0.070
42 19.15 0.77 LXD-1D7 0.070
48 25 1 LXD-1E7 0.070
60 – – LXD-1EE7 0.070
100 – – LXD-1K7 0.070
110 130 5.5 LXD-1F7 0.070
115 – – LXD-1FE7 0.070
120 159 6.7 LXD-1G7 0.070
127 192.5 7.5 LXD-1FC7 0.070
200 – – LXD-1L7 0.070
208 417 16 LXD-1LL7 0.070
220 539 22 LXD-1M7 0.070
230 595 21 LXD-1P7 0.070
240 645 25 LXD-1U7 0.070
277 781 30 LXD-1W7 0.070
380 1580 60 LXD-1Q7 0.070
400 1810 64 LXD-1V7 0.070
415 1938 74 LXD-1N7 0.070
440 2242 79 LXD-1R7 0.070
480 2300 85 LXD-1T7 0.070
575 3432 119 LXD-1SC7 0.070
600 3600 135 LXD-1X7 0.070
690 5600 190 LXD-1Y7 0.070
8103
91
LXD-1//
Specifications
Average consumption at 20 °C:- inrush (cos ϕ = 0.75) 50 Hz: 200 VA, 60 Hz: 220 VA,- sealed (cos ϕ = 0.3) 50 Hz: 20 VA, 60 Hz: 22 VA.Operating range (θ ≤ 55 °C): 0.85…1.1 Uc.
Average consumption at 20 °C:- inrush (cos ϕ = 0.75) 50/60 Hz: 245 VA at 50 Hz,- sealed (cos ϕ = 0.3) 50/60 Hz: 26 VA at 50 Hz.Operating range (θ ≤ 55 °C): 0.85…1.1 Uc.
(1) The last 2 digits of the reference represent the voltage code.(2) For use on 230 V 50 Hz, apply a coefficient of 0.6 to the mechanical durability of the contactor (see pages 24505/4and 24505/5). This coil can be used on 240 V at 60 Hz.(3) This coil can be used on 220/240 V at 50 Hz and on 240 V only at 60 Hz.(4) For use on 400 V 50 Hz, apply a coefficient of 0.6 to the mechanical durability of the contactor (see pages 24505/4and 24505/5).
Control Average Induc- Reference (1) Average Induc- Reference (1) Weightcircuit resis- tance of resis- tance ofvoltage tance closed tance closedUc at 20 °C circuit at 20 °C circuit
± 10 % ± 10 % V Ω H Ω H kg
For 3 or 4-pole contactors LC1-D40, D50, D65, D80, D95
TeSys contactors a.c. coilsfor 3 or 4-pole contactors LC1-D
References (continued)
LX1-D6//
Specifications
Average consumption at 20 °C:- inrush (cos ϕ = 0.8) - 50 or 60 Hz: 300 VA,- sealed (cos ϕ = 0.3) - 50 or 60 Hz: 22 VA.Operating range (θ ≤ 55 °C): 0.85…1.1 Uc.
Specifications
Average consumption at 20 °C:- inrush: cos ϕ = 0.9 - 280 to 350 VA,- sealed: cos ϕ = 0.9 - 2 to 18 VA.Operating range (θ ≤ 55 °C): 0.8…1.15 Uc.Coils with integral suppression device fitted as standard, class B.
(1) The last 2 digits of the reference represent the voltage code.
Control Average Induc- Reference (1) Average Induc- Reference (1) Weightcircuit resis- tance resis- tancevoltage tance of closed tance of closedUc at 20 °C circuit at 20 °C circuit
TeSys contactors a.c. coilsfor 3 or 4-pole contactors LC1-D
References (continued)
LX1-D8//
Specifications
Average consumption: 22 W.Operating range: 0.85…1.1 Uc.
Specifications
Average consumption: 22 W. Operating range: 0.85…1.1 Uc.
(1) The last 2 digits of the reference represent the voltage code.
Control circuit Average resistance Inductance Reference (1) Weightvoltage at 20 °C of closedUc ± 10 % circuitV Ω H kg
For 3-pole contactors LC1-D40…D65 or 4-pole contactors LP1-D65
12 7.1 0.44 LX4-D6JD 0.415
24 26.8 1.69 LX4-D6BD 0.415
36 58 3.55 LX4-D6CD 0.415
48 109 6.86 LX4-D6ED 0.415
60 173 10.9 LX4-D6ND 0.415
72 234 14.7 LX4-D6SD 0.415
110 560 35.28 LX4-D6FD 0.415
125 717 45.2 LX4-D6GD 0.415
220 2255 142 LX4-D6MD 0.415
250 2940 185 LX4-D6UD 0.415
440 9080 572 LX4-D6RD 0.415
810
398
For 3-pole contactors LC1-D80 or 4-pole contactors LP1-D80
12 6.6 0.46 LX4-D7JD 0.680
24 27 1.89 LX4-D7BD 0.680
36 57 4 LX4-D7CD 0.680
48 107 7.5 LX4-D7ED 0.680
60 170 11.9 LX4-D7ND 0.680
72 230 16.1 LX4-D7SD 0.680
110 564 39.5 LX4-D7FD 0.680
125 718 50.3 LX4-D7GD 0.680
220 2215 155 LX4-D7MD 0.680
250 2850 200 LX4-D7UD 0.680
440 9195 640 LX4-D7RD 0.680
8103
98
TeSys contactors d.c. coilsfor 3 or 4-pole contactors
References
LX4-D6//
LX4-D7//
Specifications
Consumption: inrush 270 to 365 W, sealed 2.4 to 5.1 W.Operating range: 0.7…1.2 Uc.Coils with integral suppression device fitted as standard, class B.
(1) The last 2 digits of the reference represent the voltage code.
Control Average Inductance Reference (1) Weightcircuit resistance of closedvoltage at 20 °C circuitUc ± 10 %V Ω H kg
For 3 or 4-pole contactors LC1-D115, D150
24 147 3.03 LX4-D8BD 0.300
48 1061 24.19 LX4-D8ED 0.300
60 1673 38.44 LX4-D8ND 0.300
72 2500 56.27 LX4-D8SD 0.300
110 4377 109.69 LX4-D8FD 0.300
125 6586 152.65 LX4-D8GD 0.300
220 9895 210.72 LX4-D8MD 0.300
250 18 022 345.40 LX4-D8UD 0.300
440 21 501 684.66 LX4-D8RD 0.300
8103
99TeSys contactors d.c. coilsfor 3 or 4-pole contactors LC1-D
References (continued)
LX4-D8/D
Specifications
Average consumption: 22 W.Operating range: 0.75…1.2 Uc.Coils with "TH" treatment as standard.
Specifications
Average consumption: 23 W.Operating range: 0.75 to 1.2 Uc.Coils with "TH" treatment as standard.
(1) The last 2 digits of the reference represent the voltage code.
Control Average Inductance Reference (1) Weightcircuit resistance of closedvoltage at 20 °C circuitUc ± 10 %V Ω H kg
For 3-pole contactors LC1-D40…D65 or 4-pole contactors LP1-D65
12 6.8 0.45 LX4-D6JW 0.415
24 30 1.9 LX4-D6BW 0.415
36 53 3.5 LX4-D6CW 0.415
48 110 7.2 LX4-D6EW 0.415
72 215 14.2 LX4-D6SW 0.415
110 580 38.3 LX4-D6FW 0.415
220 2120 140 LX4-D6MW 0.415
810
400
For 3-pole contactors LC1-D80 or 4-pole contactors LP1-D80
12 6.2 0.49 LX4-D7JW 0.680
24 23.5 1.75 LX4-D7BW 0.680
36 51.9 4.18 LX4-D7CW 0.680
48 94.2 7 LX4-D7EW 0.680
72 204 15.7 LX4-D7SW 0.680
110 483 36 LX4-D7FW 0.680
220 1922 144 LX4-D7MW 0.680
TeSys contactorsWide range d.c. coils(for specific applications) for 3 or 4-pole contactors
References
LX4-D6//
4569 Ver2.00-EN.fm/2 Schneider Electric
TeSys contactorsFor switching 3-phase capacitor banks,used for power factor correctionDirect connection without choke inductors
Special contactors LC1-DpK are designed for switching 3-phase, single or multiple-step capacitor banks; they conform to standards IEC 70 and 831, NFC 54-100, VDE 0560, UL and CSA.
Specification
Contactors fitted with a block of early make poles and damping resistors, limiting the value of the current on closing to60 In max.This current limitation increases the life of all the components of the installation, in particular that of the fuses andcapacitors.The patented design of the add-on block (n° 90 119-20) ensures safety and long life of the installation.
Operating conditions
There is no need to use choke inductors for either single or multiple-step capacitor banks.Short-circuit protection must be provided by gI type fuses rated at 1.7…2 In.
Maximum operational power
The power values given in the selection table below are for the following operating conditions.
The correct contactor for each step is selected from the above table, according to the power rating of the step to beswitched.Example: 50 kVAR 3-step capacitor bank. Temperature 50 °C and U = 400 V or 440 V.One 25 kVAR step: contactor LC1-DMK, one 15 kVAR step: contactor LC1-DGK and one 10 kVAR step: contactorLC1-DFK.(1) Operational power of the contactor according to the scheme on the page opposite.(2) Standard control circuit voltages.
For other voltages between 24 and 440 V, please consult your Regional Sales Office(3) The average temperature over a 24-hour period, in accordance with standards IEC 70 and 831 is 45 °C.
Special contactors
Contactor applications
Prospective peak current at switch-on LC1-DpK 200 In
TeSys contactorsFor switching 3-phase capacitor banks,used for power factor correction
Dimensions
LC1-DppK
Cabling (maximum permissible c.s.a.)
LC1-DFK, DGK LC1-DPK, DTK
LC1- c Type of fixing LC1- Type of fixingDFK 117 LC1-D12 See pages 24531/4 and 24531/5 DPK LC1-D40 See pages 24531/4 and 24531/5DGK 122 LC1-D18 See pages 24531/4 and 24531/5 DTK LC1-D50 See pages 24531/4 and 24531/5
LC1-DLK, DMK LC1-DWK
LC1- c Type of fixing LC1- Type of fixingDLK 117 LC1-D25 See pages 24531/4 and 24014/5 DWK LC1-D80 See pages 24531/4 and 24531/5DMK 122 LC1-D32 See pages 24531/4 and 24014/5
Schemes
R = Pre-wired resistor connections.
Contactor type LC1- DFK DGK DLK DMK DPK, DTK DWKNumber of conductors 1 2 1 2 1 2 1 2 1 2 1 2Flexible cable with cable end (mm2) 2.5 1.5 4 2.5 4 4 6 4 16 6 50 25Solid cable without cable end (mm2) 4 4 6 6 10 6 16 10 25 16 50 35