Post-Tensioned
Prestressed Concrete
Post-Tensioned
Slab-on-Ground
Construction
Page 2
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 2/50
Reinforced vs Plain Concrete
It is important to recognize the difference between
reinforced and plain concrete when referring to post-
tensioned or conventionally reinforced concrete slabs-
on-ground. The American Concrete Institute (ACI)
defines reinforced concrete as concrete designed to
satisfy the minimum requirements of the code. The
category of plain concrete was developed by ACI to
refer to concrete used in ground supported construction
where loads are light, stresses are low, life safety
concerns are minimal or non-existent and the minimumrequirements for reinforced concrete are not necessary.
Page 3
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 3/50
Occupancy Loads
T e n s i o n T e n s i o n
f t = Mc /I or M/Sb
How Prestressing Works
The Basics
Edge Lift Edge Lift
Page 4
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 4/50
f t = M/Sb – (P/A)
CompressionForce Force
How Prestressing Works
For Slabs-on-Ground
Page 5
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 5/50
Advantages of Post-Tensioning
• Inherent compressive strength of concrete
• Less structural depth to achieve same design
strength
• Economical use of building materials
• Speed of construction
Page 6
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 6/50
• Single Family Residential
• Multi-Family Residential
• Commercial / Industrial
• Sports Courts
Applications of Post-TensioningSlab-on-Ground Foundations
Page 7
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 7/50
Post-Tension Steel
Tonnage Comparison
0
10000
20000
30000
4000050000
60000
70000
80000
1 9 9 4
1 9 9 5
1 9 9 6
1 9 9 7
1 9 9 8
1 9 9 9
2 0 0 0
2 0 0 1
2 0 0 2
2 0 0 3
Buildings SOG Bridges R&S Anchors
Page 8
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 8/50
Foundations TypesClassified by BRAB Report 33
In 1962, The Building Research Advisory
Board (BRAB) issued Report 33 which
classified residential foundations into four design categories based upon the degree
of severity of the supporting soil:
• Type I: Unreinforced
• Type II: Lightly Reinforced
• Type III: Reinforced and Stiffened
• Type IV: Structural
Page 9
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 9/50
The PTI design
procedure for expansive soil is
based on a ribbed
slab layout.
PTI Design Procedure
Slab-on-Ground Foundations
Page 10
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 10/50
The “key-word”
is Slab-on-GROUNDGROUND
• Slabs-on-Ground are designed to meet aspecific set of soil “parameters”.
• The performance of ANY foundation isdependent up on obtaining accurate soilinformation about the site.
• Expansive Soils
• Plasticity Index (PI) Greater than 15• Expansion Index (EI) Greater than 20
• Em, Ym, Bearing Capacity
Page 11
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 11/50
Site Inspection
Inspect site to look for unusual conditions
• Drainage ditches or low areas that hold water
• Trees that can influence soil moisture
• Anything that appears “out of the ordinary”
• Contact the geotechnical and structural engineer for recommendations
Page 12
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 12/50
Site Preparation
Strip Site of Organics & Trash
The site should be
initially stripped of all
surface vegetation and
other deleterious
material.
Page 13
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 13/50
Site Preparation
Recompact Scarified Surface Material
The exposed
subgrade shouldbe scarified and
recompacted.
Page 14
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 14/50
Site Preparation
Identify Voids & Recompact
Remove trees,
including theroot system
Proof roll the
site to identify
any loose soil
Page 15
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 15/50
Site Preparation
Drainage
Grade the lot for
positive drainageaway from the
foundation during
and after
construction.
Page 16
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 16/50
Site Preparation
Compaction tests should be performed on all fill material used
during the site development phase. The quality, as well as the
compaction, of all fill material should be documented.
Fill should exhibit low expansion properties, be free of organicsand other deleterious material, and be compatible with the
existing soil characteristics.
READ the General Notes sheet prepared by the structural
engineer. This sheet may contain special instructions about
specific site preparation requirements.
Contact the structural engineer should anything be unclear or in
question.
Page 17
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 17/50
Components of an
Unbonded PT System
• Unbonded Strand
• Anchorages
• Accessories
Page 18
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 18/50
Unbonded P-T Strand
Corrosion Protection "Grease"
High Density
PolyethyleneSheathing
P-T Coating
7 wire Steel
Strand
Unbonded strand consists of
three main components:
• Prestressing Steel
• PT Coating
• Sheathing
Page 19
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 19/50
Anchorage System
Anchor
2-pc Wedge
Page 20
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 20/50
Standard System
Fixed End Anchorage
Page 21
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 21/50
Standard System
Stress End Anchorage
Anchor Pocket Former
Page 22
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 22/50
Standard System Assembly
Page 23
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 23/50
Stressing Anchorage
Incorrect Correct
Page 24
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 24/50
Stressing Anchorage
• Replace Sheathing
• Tape
• 1 inch Rule
Tendon Sheathing Repair
Page 25
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 25/50
Installation
• Follow approved engineers drawings
• Anchors are placed 6 inches from edge
• Anchors are placed at T/2 or 3” below top of slab
• Anchors are securely attached to edge forms
Page 26
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 26/50
Installation
• Follow approved engineers drawings
• Anchors are placed 6 inches from edge
• Anchors are placed at T/2 or 3” below top of slab
• Anchors are securely attached to edge forms
Page 27
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 27/50
Installation
Horizontal transitions
are smooth, clear all
openings by 3 inches
and are straight past
the opening
Page 28
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 28/50
Chairs are placed
and tied at each
tendon intersection atless than 3’-6”
centers
Installation
Chair Placement
Page 29
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 29/50
Installation
Chair Placement
IncorrectCorrect
Page 30
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 30/50
Installation
Draped tendons are used in some designs to
provide compression in the bottom of beams
resisting tensile stresses caused from edge lift.
Page 31
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 31/50
Installation
Drops in Slabs
Page 32
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 32/50
Plumbing Blockouts
• Deflect tendons toavoid blockoutsthrough the slab.
• Maintain minimum of 3” concrete cover between tendon andblockout
Page 33
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 33/50
Plumbing Blockouts
Corner blockouts
can cause
concreting
difficulties. Rebar
solutions can
alleviate the
congestion and
prevent corner failures
Page 34
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 34/50
Anchorage Zone Penetrations
Penetrations through the anchorage zone
should be sleeved with schedule 40 pipe.
Page 35
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 35/50
Reentrant Corners
Initial curing tensile
stresses build-up at
reentrant (inside)corners causing
cracking to occur.
Rebar is typically
installed at these
locations.
Page 36
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 36/50
Stressing
• Initial Concrete Strength (2,000 psi MIN)
• Initial Marking (Elongations)
• Calibration of Jack/Gauge
• Stressing Force vs. Gauge Pressure
• Final Elongation Measurement
Page 37
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 37/50
Cutting Stressing Tails
Page 38
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 38/50
Finishing Stressing Recess
• Clean the pocket former recess of any
dirt, grit, oil or other material that will
prevent the grout from bonding to the
concrete
• Grout pocket former recess with non-
shrink cement, sand and water mix that
will reach the minimum compressive
strength of the concrete slab.
Page 39
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 39/50
Inspections
Inspections should be conducted to insure
the quality of the construction.
• Pre-pour: Installation of P-T and rebar
• Pour: Placement of Concrete
• Stressing: Tensioning of P-T Tendons
Page 40
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 40/50
Pre-Pour Inspection
• Check the tendon and bar count
• Check the placement of the fixed-end anchors for
the required cover over the end of the steel
• Check to be sure that the stressing ends are
securely nailed to the forms (2 nails) and that the
tendon is perpendicular to the anchor
• Check to be sure that you have adequate
concrete cover over all of the steel
Page 41
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 41/50
Pour Inspection
• Do not add excessive water at the site
• Place the concrete in one continuous
operation - NO COLD JOINTS
• Consolidate (vibrate) the concrete around the
P-T anchors, especially in the corners where
multiple anchors are located.
Page 42
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 42/50
Pour Inspection
DO NOT displace or walk on any of the reinforcement
- P-T or rebar
Page 43
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 43/50
Post-Concrete Placement
• Notify the P-T stressing company the day after
the concrete is placed to schedule stressing
• Remove the forms - ALL OF THEM. Do thiswithin 3 days after the concrete is placed
• Do NOT damage stressing tails in rough grade
• Do NOT cover tendon tails with dirt or lumber
Page 44
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 44/50
Trouble-Shooting
• Honeycombs
• Low strength and poor quality concrete
• Plumbing mistakes
Page 45
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 45/50
Trouble-Shooting
Correct Incorrect
Page 46
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 46/50
Foundation Maintenance
• Do not alter the drainage pattern of the site
• Provide a minimum of 3%-5% of slope away fromthe foundation with the first 5 feet
• Roof drains should not dischargewater at the perimeter of thefoundation
• Do not plant trees within the tree’s drip line
• Do not cut off natural moisture around thefoundation by constructing decks or pools
Page 47
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 47/50
The long-term performance of any
slab-on-ground foundation is dependent upon good drainage and a moisture
maintenance program by the property
owner.
Performance
Page 48
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 48/50
PTI Certification Program
• Consistency of material quality
• Quality of extrusion and fabrication process
• Traceability of components
• Stressing equipment calibration
• Company commitment to the long termperformance of the system
Page 49
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 49/50
Construction & Maintenance
More information concerning theconstruction & maintenance of post-tensioned slabs-on-ground, can be found ina manual published by the Post-Tensioning Institute.
The 3rd Editions is currently being reviewed by committee and will be available in thenext few months.
602-870-7540
www.post-tensioning.org
Page 50
7/16/2019 Presentation- Ground Slabs-Post-Tensioned Prestressed Concrete
http://slidepdf.com/reader/full/presentation-ground-slabs-post-tensioned-prestressed-concrete-56338564a8149 50/50
Design Procedures & Code
602-870-7540
www.post-tensioning.org
New in 2005