PREDIMENSIONAMIENTO DE COLUMNAS POR GRAVEDAD(VIVIENDA)
PREDIMENSIONAMIENTO DE COLUMNAS POR SISMO(VIVIENDA)
Datos por Sismo:
DATOS CALCULOS CORTANTE POR SISMOCATEGORIA DE EDIFICACION A U = 1.50
Vs = ZUCS x PeZONA SISMICA 2 Z = 0.30TIPO DE SUELO S2 Tp (s) = 0.60PERIODO FUNDAMENTAL (*) 1 S = 1.20ALTURA DE LA EDIFICACION (m) 7.20 CT = 35
(*)
1 Elementos resistentes en la dirección de los pórticos T = 0.21
2 Elementos resistentes pórticos, cajas de ascensores y esc C = 2.50
3 Elementos sismorresistentes por muros de corte ZUCS = 1.35
Calculo del Peso de la Estructura:
Numero de Pisos: 02 Pisos
Carga muerta (WD):
ALIGERADO Luz (m) = 3.85 15.40 H (cm) = 17.00 280.00 Kg/m2TABIQUERIA Tipo (*): solido Ancho (cm) = 15.00 Altura (m) = 2.60 741 330.00 Kg/m2ACABADOS 100.00 Kg/m2VIGAS 100.00 Kg/m2COLUMNAS 60.00 Kg/m2(*) Tipo de Ladrillo: SOLIDO / HUECO, Altura mayor de tabiqueria
WD = 870.00 Kg/m2Carga viva (WL):
VIVIENDA 300.00 kg/m2AZOTEA 100.00 kg/m2
WL = 400.00 Kg/m2Carga total (PU):
Peso total de cargas de gravedad que soporta la columna cada piso 1,845.00 Kg/m2Peso total de cargas de gravedad que soporta la columna 1 er Piso 1 er Piso 7,380.00 Kg/m2Peso total de cargas de gravedad que soporta la columna 2 er Piso 1,485.00 Kg/m2
Peso total de cargas de gravedad por 02 Pisos PU = ### Kg/m2
Calculo de Seccion de la Columna:
DATOS CORTANTE POR SISMOALTURA DEL PRIMER NIVEL (m) 3.40 m Vs = ZUCS x PeNro de Columnas 20.00 columnas Vs = ### kg/m2Resistencia del Concreto 210.00 kg/cm2 Pe = PU x Area TribDistorsion Permisible 0.007 mModulo de Elasticidad del Concreto 2.17E+05
GENERAL (ESTRUCTURACION SIMETRICA)TIPOS
Area tributaria Vs (Kg) b x D b x D Verifica
COLUMNAS 146.93 1,758,421.51 1292.25 35.95 25 55 1375.00 OK !!! 25x55 GENERAL
PREDIMENSIONAMIENTO DE COLUMNAS POR SISMO(VIVIENDA)
Datos por Sismo:
DATOS CALCULOS CORTANTE POR SISMOCATEGORIA DE EDIFICACION A U = 1.50
Vs = ZUCS x PeZONA SISMICA 2 Z = 0.30TIPO DE SUELO S2 Tp (s) = 0.60PERIODO FUNDAMENTAL (*) 1 S = 1.20ALTURA DE LA EDIFICACION (m) 7.20 CT = 35
(*)
1 Elementos resistentes en la dirección de los pórticos T = 0.21
2 Elementos resistentes pórticos, cajas de ascensores y esc C = 2.50
3 Elementos sismorresistentes por muros de corte ZUCS = 1.35
Calculo del Peso de la Estructura:
Numero de Pisos: 02 Pisos
Carga muerta (WD):
ALIGERADO Luz (m) = 3.85 15.40 H (cm) = 17.00 280.00 Kg/m2TABIQUERIA Tipo (*): solido Ancho (cm) = 15.00 Altura (m) = 2.60 741 330.00 Kg/m2ACABADOS 100.00 Kg/m2VIGAS 100.00 Kg/m2COLUMNAS 60.00 Kg/m2(*) Tipo de Ladrillo: SOLIDO / HUECO, Altura mayor de tabiqueria
WD = 870.00 Kg/m2Carga viva (WL):
VIVIENDA 300.00 kg/m2AZOTEA 100.00 kg/m2
WL = 400.00 Kg/m2Carga total (PU):
Peso total de cargas de gravedad que soporta la columna cada piso 1,845.00 Kg/m2Peso total de cargas de gravedad que soporta la columna 1 er Piso 1 er Piso 7,380.00 Kg/m2Peso total de cargas de gravedad que soporta la columna 2 er Piso 1,485.00 Kg/m2
Peso total de cargas de gravedad por 02 Pisos PU = ### Kg/m2
ALIGERADO Luz (m) = 5.00 20.00 20.00 300.00 Kg/m2TABIQUERIA Tipo (*): solido Ancho (cm) = 15.00 Altura (m) = 2.60 741 330.00 Kg/m2ACABADOS 100.00 Kg/m2VIGAS 100.00 Kg/m2COLUMNAS 60.00 Kg/m2(*) Tipo de Ladrillo: SOLIDO / HUECO, Altura mayor de tabiqueria
WD = 890.00 Kg/m2Carga viva (WL):
VIVIENDA 200.00 kg/m2AZOTEA 100.00 kg/m2
WL = 300.00 Kg/m2Carga total (PU):
Peso total de cargas de gravedad que soporta la columna cada piso 1,695.00 Kg/m2Peso total de cargas de gravedad que soporta la columna 4 er Piso 6,780.00 Kg/m2Peso total de cargas de gravedad que soporta la columna 5 er Piso 1,515.00 Kg/m2
Peso total de cargas de gravedad por 05 Pisos PU = ### Kg/m2
Calculo de Seccion de la Columna:
GENERAL (ESTRUCTURACION IRREGULAR)TIPOS
EJE TIPO H(cm)=Ln/11 b(cm)=L/20 b x H Verifica
A - A S 1.46 2.75 13.27 15.03 13.75 25 20 500.00 OK !!! 25x20 V1
A - A P 1.66 2.68 15.09 17.09 13.40 25 20 500.00 OK !!! 25x20 V2
A - A P 4.22 2.49 38.36 43.43 12.45 25 45 1125.00 OK !!! 25x45 V2
B - B S 1.45 2.46 13.18 14.92 12.28 25 20 500.00 OK !!! 25x20 V1
B - B P 5.65 4.76 51.36 58.15 23.78 25 60 1500.00 OK !!! 25x60 V2
C - C S 1.32 4.71 12.00 13.59 23.55 25 20 500.00 OK !!! 25x20 V1
C - C P 1.65 4.71 15.00 16.98 23.55 25 20 500.00 OK !!! 25x20 V1
C - C P 3.81 4.71 34.64 39.21 23.55 25 40 1000.00 OK !!! 25x40 V3
D - D P 3.10 2.26 28.18 31.91 11.28 25 35 875.00 OK !!! 25x35 V3
D - D P 3.64 3.48 33.09 37.47 17.40 25 40 1000.00 OK !!! 25x40 V3
E - E P 3.10 1.84 28.18 31.91 9.18 25 35 875.00 OK !!! 25x35 V3
E - E P 3.54 3.06 32.18 36.44 15.30 25 40 1000.00 OK !!! 25x40 V3
F - F P 3.10 1.84 28.18 31.91 9.18 25 35 875.00 OK !!! 25x35 V3
F - F P 3.40 1.84 30.91 34.99 9.18 25 35 875.00 OK !!! 25x35 V3
1 - 1 P 5.56 0.73 50.55 57.23 3.63 25 60 1500.00 OK !!! 25x60 V2
1 - 1 P 4.91 0.73 44.64 50.54 3.63 25 55 1375.00 OK !!! 25x55 V2
1 - 1 P 4.51 1.55 41.00 46.42 7.75 25 50 1250.00 OK !!! 25x50 V2
1 - 1 S 2.45 0.00 22.27 25.22 0.00 25 30 750.00 OK !!! 25x30 V3
1 - 1 P 3.67 1.55 33.36 37.77 7.75 25 40 1000.00 OK !!! 25x40 V3
2 - 2 P 5.36 3.55 48.73 55.17 17.75 25 60 1500.00 OK !!! 25x60 V2
2 - 2 P 4.91 3.55 44.64 50.54 17.75 25 55 1375.00 OK !!! 25x55 V2
3 - 3 P 4.51 3.46 41.00 46.42 17.28 25 50 1250.00 OK !!! 25x50 V2
3 - 3 S 2.45 3.37 22.27 25.22 16.85 25 30 750.00 OK !!! 25x30 V3
3 - 3 P 3.67 3.32 33.36 37.77 16.60 25 40 1000.00 OK !!! 25x40 V3
4 - 4 P 4.60 2.83 41.82 47.35 14.13 25 50 1250.00 OK !!! 25x50 V2
4 - 4 P 4.92 2.83 44.73 50.64 14.13 25 55 1375.00 OK !!! 25x55 V2
4 - 4 P 4.52 1.91 41.09 46.52 9.53 25 50 1250.00 OK !!! 25x50 V2
4 - 4 P 2.45 1.82 22.27 25.22 9.10 25 30 750.00 OK !!! 25x30 V3
4 - 4 S 3.68 1.77 33.45 37.88 8.85 25 40 1000.00 OK !!! 25x40 V3
LUZ LIBRE Ln(m)
ANCHO TRIBUT L(m)
H(cm) Ln/(4/RAIZ(WU
))
b (cm) (minimo)
H (cm) (calculado
)
PREDIMENSIONAMIENTO DE COLUMNAS POR SISMO(MODULO SSHH ANDABAMBA)
Datos por Sismo:
DATOS CALCULOSCATEGORIA DE EDIFICACION A U = 1.50ZONA SISMICA 2 Z = 0.30TIPO DE SUELO S2 Tp (s) = 0.60
S = 1.20COEFICIENTE DE REDUCCION DIRECCION X RX (*) Albañileria Armada o Confinada RX = 3.00COEFICIENTE DE REDUCCION DIRECCION Y RY (*) Concreto Armado, Dual RY = 7.00
TIPO DE ESTRUCTURA: REGULAR (1) / IRREGULAR 1 FACTOR PARA ESCALAR R 1.00 RX = 3.00RY = 7.00
t (cm) w (Kg/m2) Peso del tabique (Kg/m) Carga Equivalente (Kg/m2)17 280 74 o menos 3020 300 75 a 149 6025 350 150 a 249 9030 420 250 a 399 15035 475 400 a 549 210
550 a 699 270700 a 849 330
850 a 1000 390
USOS
SOBRECARGASALTURA TOTAL
USO AMBIENTE S/C (Kg/m2)Bibliotecas Sala de lectura 300
Sala de almacenaje 750Escuelas Aulas y laboratorio 300
Talleres 350Hospitales Cuartos 200
Sala de Operación y laboratorio 300Oficinas Ambientes Comunes 250
Sala de Archivos 500Tiendas Corredores y Escaleras 500Viviendas Corredores y Escaleras 200Azoteas * Planas no utilizable 100
DEPOSITOS
250 500 1000L/11 L/10 L/8
DEPARTAMENTO Y
OFICINASGARAGES Y
TIENDAS
MATERIALES PESO (Kg/m3)1.- AISLAMIENTOFibra de vidrio 300Corcho 200Poliuretano poliestireno 200Fibrocemento 6002.- ALBAÑILERIA DEAdobe 1600Unidades de albañileria solidas 1800Unidades de albañileria huecas 13503.- CONCRETO SIMPLE DEGrava 2300Cascote de ladrillo 1800Pomez 1600
4.- CONCRETO ARMADO
5.- ENLUCIDO O REVOQUE DEMortero de cemento 2000
Mortero de cal y cemento 1850Mortero de cal 1700Yeso 10006.- LIQUIDOSAgua 1000
(*) En estas edificaciones, a criterio del proyectista, se podrá omitir el análisis por fuerzas sísmicas,pero deberá proveerse de la resistencia y rigidez adecuadas para acciones laterales
ZONA SISMICA Z
1 0.152 0.303 0.40
TIPO DE SUELO S
S1 0.4 1S2 0.6 1.2S3 0.9 1.4S4 1.3 0.9
Características para hallar el periodo fundamental CT1 35 Elementos resistentes en la dirección de los pórticos2 45 Elementos resistentes pórticos, cajas de ascensores y escaleras3 60 Elementos sismorresistentes por muros de corte
Zona contribuyente Relación carga viva a carga muerta(metros cuadrados) 0.625 o menor
14.9 o menor 100%15 - 29.9999 80%30 - 44.9999 60%45 - 59.9999 50%
60 ó más 40%
R Coef Regular
R3 Acero, Arriostres en 6.000R2 Acero, Arriostres Exc 6.500R1 Acero, Porticos Duct 9.500R8 Albañileria Armada o 3.000R6 Concreto Armado, de 6.000R5 Concreto Armado, Du 7.000R4 Concreto Armado, Po 8.000R9 Madera (Por Esfuerzo 7.000
(*) En estas edificaciones, a criterio del proyectista, se podrá omitir el análisis por fuerzas sísmicas,pero deberá proveerse de la resistencia y rigidez adecuadas para acciones laterales
Roca o suelos muy rígidosSuelos intermedios
Suelos flexibles o con estratos de gran espesorCondiciones excepcionales
Elementos resistentes en la dirección de los pórticosElementos resistentes pórticos, cajas de ascensores y escalerasElementos sismorresistentes por muros de corte