Top Banner
1 2008 IEEE, IAS Electrical Safety Workshop Neil Coward, PE Texas Instruments - [email protected] Neil Van Geem, PE Consultant - [email protected] W P Blackley, PE ATC Consulting Services – [email protected] Precautions for Working with High Resistance Grounded Systems
28

Precautions for Working with High Resistance Grounded Systems

Dec 19, 2021

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Precautions for Working with High Resistance Grounded Systems

12008 IEEE, IAS Electrical Safety Workshop

Neil Coward, PETexas Instruments -

[email protected]

Neil Van Geem, PEConsultant -

[email protected]

W P Blackley, PE ATC Consulting Services –

[email protected]

Precautions for Working with

High Resistance Grounded Systems

Page 2: Precautions for Working with High Resistance Grounded Systems

22008 IEEE, IAS Electrical Safety Workshop

1981 –

HRG in Corporate Data Center

1996 -

Dallas, Texas Chip Manufacturer desired to improve -

480v System Reliability & Safety

IEEE IAS Dallas, Texas

Page 3: Precautions for Working with High Resistance Grounded Systems

32008 IEEE, IAS Electrical Safety Workshop

Facility Engineering evaluated three types Systems–Ungrounded–Solidly Grounded–High Resistance Grounded

IEEE IAS Dallas, Texas

Page 4: Precautions for Working with High Resistance Grounded Systems

42008 IEEE, IAS Electrical Safety Workshop

SYSTEM GROUNDING OPTIONS

Ungrounded

SolidlyGrounded

Resistance Grounded

Page 5: Precautions for Working with High Resistance Grounded Systems

52008 IEEE, IAS Electrical Safety Workshop

Transformer grounded through a resistor

Resistance Grounding What it is!

Page 6: Precautions for Working with High Resistance Grounded Systems

62008 IEEE, IAS Electrical Safety Workshop

Low Resistance– 100A ≤

I-g

1000A •

Circuit Interrupts -

1st

Ground Fault

High or Low Resistance Grounding

High Resistance –I-g

10A– No Interruption -

1st

Ground Fault

Page 7: Precautions for Working with High Resistance Grounded Systems

72008 IEEE, IAS Electrical Safety Workshop

System AttributesGrounding Methods

Solid Grounded HRG Ungrounded

IEEE IAS Dallas, Texas

Immediate Isolation of ground faults

No tripping of breakers on first ground fault

Minimize shock hazard from stray ground currents

Minimize ground fault arcingSuppress transient ground fault over voltage due to arcingMinimize arc flash hazards (1st fault ONLY)

High Probability of phase to ground fault escalating to phase to phase fault

High probability for sustained arc in phase to ground fault

Voltage dip on initial fault

Page 8: Precautions for Working with High Resistance Grounded Systems

82008 IEEE, IAS Electrical Safety Workshop

●HRG Design Issues

IEEE IAS Dallas, Texas

Sizing Ground Resistor−Suppress Transient Over voltages

Ground Fault Location System−Locate Fault Before Shutting Down for Repairs

No Single Phase (277V) Loads−

Economics

Page 9: Precautions for Working with High Resistance Grounded Systems

92008 IEEE, IAS Electrical Safety Workshop

HRG Design Issues Sizing Ground Resistor

Page 10: Precautions for Working with High Resistance Grounded Systems

102008 IEEE, IAS Electrical Safety Workshop

IEEE IAS Dallas, Texas

HRG Design IssuesNo Single Phase (277V) Loads

Install 480V Delta to 480V/277V Wye Transformer For Lighting

Page 11: Precautions for Working with High Resistance Grounded Systems

112008 IEEE, IAS Electrical Safety Workshop

Ground Fault LocatingHRG Design Issues

Tapped Grounding Resistor

Voltage Detecting

Relay

Pulse Contact Switch

Portable Ammeter

2A2A

2A2A

4A4A

4A4A

2A2A

2A2A

4A4A

4A4A

2A2A

2A2A

4A4A

4A4A

2A2A

2A2A

4A4A

4A4A

2A2A

2A2A

Page 12: Precautions for Working with High Resistance Grounded Systems

122008 IEEE, IAS Electrical Safety Workshop

HRG Design Issues•

Economics– New

No Additional Cost– Retrofit

$20K per Substation

IEEE IAS Dallas, TexasIEEE IAS Dallas, Texas

Page 13: Precautions for Working with High Resistance Grounded Systems

132008 IEEE, IAS Electrical Safety Workshop

– Improved Safety•

1st

Grd fault –

no arc flash or blast– Increased

Reliability

1st

Grd fault –

Non Event•

Production continues (Scheduled outages –

increased revenues)

– No Added Cost for New Substations

IEEE IAS Dallas, TexasHRG Was Chosen

Page 14: Precautions for Working with High Resistance Grounded Systems

142008 IEEE, IAS Electrical Safety Workshop

IEEE IAS Dallas, Texas

● Safety● Qualifications of Electrical Workers ● Training-Employee/Contractor ● Culture Changes

Page 15: Precautions for Working with High Resistance Grounded Systems

152008 IEEE, IAS Electrical Safety Workshop

IEEE IAS Dallas, Texas

●Safety– Assumptions of Workers

Think they have a free pass for faults•

All short circuits will be non events

Believe NO

flash hazard•

Do not need same level of PPE

ALL FALSE –

Why?

Page 16: Precautions for Working with High Resistance Grounded Systems

162008 IEEE, IAS Electrical Safety WorkshopPhase “A”

to Ground Bolted Fault

HRG Operation

IEEE IAS Dallas, TexasIEEE IAS Dallas, Texas

Page 17: Precautions for Working with High Resistance Grounded Systems

172008 IEEE, IAS Electrical Safety Workshop

Bolted faults on different phases

HRG Operation

Page 18: Precautions for Working with High Resistance Grounded Systems

182008 IEEE, IAS Electrical Safety Workshop

SO SORRY LIGHTS OUTSO SORRY LIGHTS OUT

Second Fault On Different Phase Before First Fault Was Cleared

Page 19: Precautions for Working with High Resistance Grounded Systems

192008 IEEE, IAS Electrical Safety Workshop

IEEE IAS Dallas, Texas

●Electrical Worker Qualification●Average Electrical Worker Unqualified

● Required by 2005 NEC 250-36●OSHA requires workers understand systems

●The Following Incident is What Happens When a Worker Is Not Qualified

Page 20: Precautions for Working with High Resistance Grounded Systems

202008 IEEE, IAS Electrical Safety Workshop

IEEE IAS Dallas, TexasOne of the worlds largest chip manufacturers corporate data center was undergoing renovation to

become a 24/365 operation capable of standing alone if all surrounding infrastructure went away.

During the work numerous temporary electrical feeds to keep the center operational were utilized.

At one point a technician from an air handler supplier was in to commission some new raised floor units.

He reported we had a "weird"

electrical system.

When questioned, he replied that C-phase to ground was zero volts and A and B phases to ground was 480V.

He had not a clue what was going on.

He was told

there was a ground fault on the system and he needed to stay out of the equipment

until the problem was resolved.

When checked the ground fault

voltmeter relay showed a ground fault but no alarm.

A failure in the relay portion of the voltmeter relay was determined to be the cause.

The ground fault was traced to a defective inline cable splice in a cable tray.

After this event company began using a second ground fault detection relay so one failure would not leave a system without an alarm.

Page 21: Precautions for Working with High Resistance Grounded Systems

212008 IEEE, IAS Electrical Safety Workshop

IEEE IAS Dallas, Texas

Training•

Classroom

–HRG Circuit Analysis –Simulator “Hands On”

Fault

location•

Pass Online Test Bi-Annually or Go Back To Class

Page 22: Precautions for Working with High Resistance Grounded Systems

222008 IEEE, IAS Electrical Safety Workshop

Real World Fault Simulation

Ckt #1

BreakersBreakers

Ø – ØVoltmeters

Grd. Resistor Voltmeter

Alarm Reset

Ø – Grd Voltmeters

Volt Meters describe system information

Ckt #2

Ckt #3

3 Load Indicating

Lights

Page 23: Precautions for Working with High Resistance Grounded Systems

232008 IEEE, IAS Electrical Safety Workshop

Real World Fault Simulation

Using Volt Meters & Ammeters ParticipantsIdentify Faulted Phase & Locate Faults

Bolted FaultHigh Resistance FaultsBolted & High Resistance Faults Same Phase

Page 24: Precautions for Working with High Resistance Grounded Systems

242008 IEEE, IAS Electrical Safety Workshop

Simulator Patch Panel

Unique Patch Panel Allows Instructor to Simulate•

High R to Ground Faults

Low R to Ground•

Bolted Faults•

Variable Resistance Faults

Phase to phase Faults•

High R on “A”

Phase, Low on “B”

With three circuits participant gets “real world”

experiences–

Real Alarms–

Real Pulse Operation–

Real Current Readings

Page 25: Precautions for Working with High Resistance Grounded Systems

252008 IEEE, IAS Electrical Safety Workshop

IEEE IAS Dallas, Texas

●Culture Changes●Verify No Ground Fault Prior To Energized

Work●Required On Energized Work Permit●No Energized Work On System W/Grd Fault

●Responding To Ground Faults●IEEE Standard 141-1993●Company Requires Shutdown and Clear

Within 24 Hours

Page 26: Precautions for Working with High Resistance Grounded Systems

262008 IEEE, IAS Electrical Safety Workshop

IEEE IAS Dallas, Texas

●Culture Changes●Management Understanding Risks Of

Extended Operation With a Grd Fault●Safety●Equipment Damage●Unplanned/Extended Interruption

Page 27: Precautions for Working with High Resistance Grounded Systems

272008 IEEE, IAS Electrical Safety Workshop

IEEE IAS Dallas, Texas

Eliminates Arc/Flash/Blast Hazard for 1st

Ground Fault

Improves Service Reliability•

No Additional Cost –

New Installation

Requires Culture & Training Change

TI’s HRG System Conclusions

Page 28: Precautions for Working with High Resistance Grounded Systems

282008 IEEE, IAS Electrical Safety Workshop

In Conclusion Thanks for Listening

to our Presentation

For additional information please contact

Neil Coward, PETexas Instruments -

[email protected]

Neil Van Geem, PEConsultant -

[email protected]

W P Blackley, PE ATC Consulting Services –

[email protected]