1 | Page EXPERIMENT-1[Computation & Modeling of Transmission Line Parameters] PROBLEM-1: A three-phase transposed line composed of one ACSR, 1,43,000 cmil, 47/7 Bobolink conductor per phase with flat horizontal spacing of 11m between phases a and b and between phases b and c. The conductors have a diameter of 3.625 cm and a GMR of 1.439cm. The line is to be replaced by a three-conductor bundle of ACSR 477,000-cmil, 26/7Hawk conductors having the same cross sectional area of aluminum as the single-conductor line. The conductors have a diameter of 2.1793 cm and a GMR of 0.8839 cm. The new line will also have a flat horizontal configuration, but it is to be operated at a higher voltage and therefore the phase spacing is increased to 14m as measured from the center of the bundles. Spacing between the conductors in the bundle is 45 cm. (a) Determine the inductance and capacitance per phase per kilometer of the above two lines. (b) Verify the results using the MATLAB program. [Practice Problem-4.9] MATLAB CODE: GMD=input('Enter GMD Value: '); GMRL= input('Enter GMRL Value: '); GMRC= input('Enter GMRC Value: '); disp('Value of L in mF/KM:’); L = 0.2*log(GMD/GMRL) disp('Value of C in µF/KM:’); C = 0.0556/log(GMD/GMRC) MANUEL SOLUTION:
42

Power system simulation lab manuel

Jun 21, 2015

Download

Engineering

POWER SYSTEM SIMULATION
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Power system simulation lab manuel

1 | P a g e

EXPERIMENT-1[Computation & Modeling of Transmission Line Parameters]

PROBLEM-1: A three-phase transposed line composed of one ACSR, 1,43,000 cmil, 47/7 Bobolink conductor per phase with flat horizontal spacing of 11m between phases a and b and between phases b and c. The conductors have a diameter of 3.625 cm and a GMR of 1.439cm. The line is to be replaced by a three-conductor bundle of ACSR 477,000-cmil, 26/7Hawk conductors having the same cross sectional area of aluminum as the single-conductor line. The conductors have a diameter of 2.1793 cm and a GMR of 0.8839 cm. The new line will also have a flat horizontal configuration, but it is to be operated at a higher voltage and therefore the phase spacing is increased to 14m as measured from the center of the bundles. Spacing between the conductors in the bundle is 45 cm.

(a) Determine the inductance and capacitance per phase per kilometer of the above two lines.

(b) Verify the results using the MATLAB program. [Practice Problem-4.9]

MATLAB CODE:

GMD=input('Enter GMD Value: '); GMRL= input('Enter GMRL Value: '); GMRC= input('Enter GMRC Value: '); disp('Value of L in mF/KM:’); L = 0.2*log(GMD/GMRL)

disp('Value of C in µF/KM:’); C = 0.0556/log(GMD/GMRC)

MANUEL SOLUTION:

Page 2: Power system simulation lab manuel

2 | P a g e

Page 3: Power system simulation lab manuel

3 | P a g e

PROBLEM-2: A three phase overhead line 200km long R = 0.16 ohm/km and Conductor diameter of

2cm with spacing 4, 5, 6 m transposed. Find A, B, C, D constants, sending end voltage, current,

power factor and power when the line is delivering full load of 50MW at 132kV, 0.8 pf lagging,

transmission efficiency, receiving end voltage and regulation.

MATLAB CODE:

clc clear all z=[]; z=input('Enter the length of line(km),Receiving

voltage(v),Power(W),Powerfactor,L,R&C(per phase per km)'); l=z(1);vr=z(2);p=z(3);pf=z(4);L=z(5);R=z(6);c=z(7); vrph=(vr*1000)/1.732; ir=(p*1000000)/(3*vrph); z=(R+(2*50*3.14*L*i))*l; y=i*2*3.14*50*c*l; disp('Medium Transmission line by nominal T method:') A=1+(z*y)/2;C=y;B=z*(1+(z*y)/4);D=1+(z*y)/2; disp('Generalized ABCD Constants are:') disp(A); disp(B); disp(C); disp(D); vs=(A*vrph)+(ir*B); fprintf('Sending end voltage Vs is %f\n',vs); is=(vrph*C)+(D*ir); fprintf('Sending end current Is is %f\n',is); reg=(3*conj(vs)* conj(is))*100/A; fprintf('Voltage Regulation is %f\n',reg); pows=3* conj(vs)* conj(is)*0.808; eff=p*100/pows; fprintf('Efficiency is %f\n',eff);

Page 4: Power system simulation lab manuel

4 | P a g e

MANUEL SOLUTION:

Page 5: Power system simulation lab manuel

5 | P a g e

EXPERIMENT-2 [ YBUS,ZBUS matrix Formation ]

PROBLEM-1: 1) (i) Determine the Y bus matrix for the power system network shown in fig.

(ii) Check the results obtained in using MATLAB.

MATLAB CODE:

clear all; clc; n=input('enter the number of buses:'); for i=1:n for j=i+1:n y(i,j)=input(['enter the line admittance

y',num2str(i),num2str(j),':']); y(j,i)=y(i,j); end end for i=1:n y1(i)=input( ['enter the admittance to ground y',num2str(i),':']); end for i=1:n for j=1:n if i==j ybus(i,j)=0; for k=1:n ybus(i,j)=ybus(i,j)+y(i,k); end else ybus(i,j)=-1*y(i,j); end end end for i=1:n ybus(i,i)=ybus(i,i)+y1(i);

Page 6: Power system simulation lab manuel

6 | P a g e

end disp('y bus matrix is:'); disp(ybus); disp('z bus matrix is:'); z=inv(ybus); disp(z);

MANUEL SOLUTION:

Y11=y11+y12+y13+y14 ; Y22=y22+y21+y23+y24 ; Y33=y33+y32+y31+y34

Y44=y41+y42+y43+y44

Page 7: Power system simulation lab manuel

7 | P a g e

PROBLEM-2:

2. (i) Determine Z bus matrix for the power system network shown in fig.

(ii) Check the results obtained using MATLAB.

MATLAB CODE:

clc clear all close all g=[1.2 0.2 0.15 1.5 0.3]; z1=[g(1)]; disp(z1); disp('TYPE I MODIFICATION') z2=[g(1) g(1) g(1) g(1)+g(2)]; disp(z2); disp('TYPE II MODIFICATION') z3=[g(1) g(1) g(1) g(1) g(1)+g(2) g(1)+g(2) g(1) g(1)+g(2) g(1)+g(2)+g(3)]; disp(z3); disp('TYPE III MODIFICATION') z4=[g(1) g(1) g(1) g(1) g(1) g(1)+g(2) g(1)+g(2) g(1)+g(2) g(1) g(1)+g(2) g(1)+g(2)+g(3) g(1)+g(2)+g(3) g(1) g(1)+g(2) g(1)+g(2)+g(3) g(1)+g(2)+g(3)+g(4)] z4=[z4];

Page 8: Power system simulation lab manuel

8 | P a g e

disp(z4); disp('Actual Zbus matrix is:') n=4; for i=1:1:n for j=1:1:n z4(i,j)=z4(i,j)-(z4(i,n)*z4(n,j)/z4(n,n)); end end z4(:,4)=[]; z4(4,:)=[]; disp(z4); disp('TYPE IV MODIFICATION MATRIX') l=4; p=2;q=4; for i=1:l-1 z4(l,i)=z4(p-1,i)-z4(q-1,i); z4(i,l)=z4(l,i); end z4(l,l)=g(5)+z4(1,1)+z4(3,3)-2*z4(1,3); disp(z4); n=4; for i=1:1:n for j=1:1:n z4(i,j)=z4(i,j)-(z4(i,n)*z4(n,j)/z4(n,n)); end end z4(:,4)=[]; z4(4,:)=[]; disp('THE REQUIRED ZBUS MATRIX IS:'); ZBUS=z4*1i; disp(ZBUS);

Page 9: Power system simulation lab manuel

9 | P a g e

MANUEL SOLUTION:

Page 10: Power system simulation lab manuel

10 | P a g e

EXPERIMENT-3[Gauss-Seidal]

Problem:

The magnitude at bus 1 is adjusted to 1.05pu. The scheduled loads at buses 2 and 3 are marked on the diagram. Line impedances are marked in p.u. The base value is 100kVA. The line charging susceptances are neglected. Determine the phasor values of the voltage at the Load bus 2 and 3. (i) Find the slack bus real and reactive power. (ii) Verify the result using MATLAB.

MANUEL CALCULATION:

Page 11: Power system simulation lab manuel

11 | P a g e

Page 12: Power system simulation lab manuel

12 | P a g e

MATLAB CODING:

y12=10-j*20;

y13=10-j*30;

y23=16-j*32;

V1=1.05+j*0;

V2=1+j*0;

V3=1+j*0;

S2=-2.566-j*1.102;

S3=-1.386-j*.452;

iter =0;

for I=1:10;

iter=iter+1;

V2 = (conj(S2)/conj(V2)+y12*V1+y23*V3)/(y12+y23);

V3 = (conj(S3)/conj(V3)+y13*V1+y23*V2)/(y13+y23);

disp([iter, V2, V3])

end

Page 13: Power system simulation lab manuel

13 | P a g e

V2= .98-j*.06;

V3= 1-j*.05;

I12=y12*(V1-V2); I21=-I12;

I13=y13*(V1-V3); I31=-I13;

I23=y23*(V2-V3); I32=-I23;

S12=V1*conj(I12); S21=V2*conj(I21);

S13=V1*conj(I13); S31=V3*conj(I31);

S23=V2*conj(I23); S32=V3*conj(I32);

I1221=[I12,I21]

I1331=[I13,I31]

I2332=[I23,I32]

S1221=[S12, S21 (S12+S13) S12+S21]

S1331=[S13, S31 (S31+S32) S13+S31]

S2332=[S23, S32 (S23+S21) S23+S32]

Page 14: Power system simulation lab manuel

14 | P a g e

EXPERIMENT-4[Newton-Raphson Method]

Problem:

Consider the 3 bus system each of the 3 line bus a series impedance of 0.02 + j0.08 p.u and a

total shunt admittance of j0.02 p.u. The specified quantities at the bus are given below.

Verify the result using MATLAB

MANUEL CALCULATIONS:

Page 15: Power system simulation lab manuel

15 | P a g e

Page 16: Power system simulation lab manuel

16 | P a g e

MATLAB CODING: V = [1.04; 1; 1.04]; d = [0; 0; 0]; Ps=[0.5; -1.5]; Qs= 1.0; YB = [ 5.882-j*23.528 -2.941-j*11.76 -2.941-j*11.76 -2.941-j*11.76 5.882-j*23.528 -2.941-j*11.76 -2.941-j*11.76 -2.941-j*11.76 5.882-j*23.528]; Y= abs(YB); t = angle(YB); iter=0; pwracur = 0.00025; % Power accuracy DC = 10; % Set the maximum power residual to a high value while max(abs(DC)) > pwracur iter = iter +1 P=[V(2)*V(1)*Y(2,1)*cos(t(2,1)-d(2)+d(1))+V(2)^2*Y(2,2)*cos(t(2,2))+ ...

V(2)*V(3)*Y(2,3)*cos(t(2,3)-d(2)+d(3));

V(3)*V(1)*Y(3,1)*cos(t(3,1)-d(3)+d(1))+V(3)^2*Y(3,3)*cos(t(3,3))+ ...

V(3)*V(2)*Y(3,2)*cos(t(3,2)-d(3)+d(2))];

Q= -V(2)*V(1)*Y(2,1)*sin(t(2,1)-d(2)+d(1))-V(2)^2*Y(2,2)*sin(t(2,2))- ...

V(2)*V(3)*Y(2,3)*sin(t(2,3)-d(2)+d(3));

J(1,1)=V(2)*V(1)*Y(2,1)*sin(t(2,1)-d(2)+d(1))+...

V(2)*V(3)*Y(2,3)*sin(t(2,3)-d(2)+d(3));

J(1,2)=-V(2)*V(3)*Y(2,3)*sin(t(2,3)-d(2)+d(3));

J(1,3)=V(1)*Y(2,1)*cos(t(2,1)-d(2)+d(1))+2*V(2)*Y(2,2)*cos(t(2,2))+...

V(3)*Y(2,3)*cos(t(2,3)-d(2)+d(3));

J(2,1)=-V(3)*V(2)*Y(3,2)*sin(t(3,2)-d(3)+d(2));

J(2,2)=V(3)*V(1)*Y(3,1)*sin(t(3,1)-d(3)+d(1))+...

V(3)*V(2)*Y(3,2)*sin(t(3,2)-d(3)+d(2));

J(2,3)=V(3)*Y(2,3)*cos(t(3,2)-d(3)+d(2));

J(3,1)=V(2)*V(1)*Y(2,1)*cos(t(2,1)-d(2)+d(1))+...

V(2)*V(3)*Y(2,3)*cos(t(2,3)-d(2)+d(3));

Page 17: Power system simulation lab manuel

17 | P a g e

J(3,2)=-V(2)*V(3)*Y(2,3)*cos(t(2,3)-d(2)+d(3));

J(3,3)=-V(1)*Y(2,1)*sin(t(2,1)-d(2)+d(1))-2*V(2)*Y(2,2)*sin(t(2,2))-...

V(3)*Y(2,3)*sin(t(2,3)-d(2)+d(3));

DP = Ps - P;

DQ = Qs - Q;

DC = [DP; DQ]

J

DX = J\DC

d(2) =d(2)+DX(1);

d(3)=d(3) +DX(2);

V(2)= V(2)+DX(3);

V, d, delta =180/pi*d;

end

P1= V(1)^2*Y(1,1)*cos(t(1,1))+V(1)*V(2)*Y(1,2)*cos(t(1,2)-d(1)+d(2))+...

V(1)*V(3)*Y(1,3)*cos(t(1,3)-d(1)+d(3))

Q1=-V(1)^2*Y(1,1)*sin(t(1,1))-V(1)*V(2)*Y(1,2)*sin(t(1,2)-d(1)+d(2))-...

V(1)*V(3)*Y(1,3)*sin(t(1,3)-d(1)+d(3))

Q3=-V(3)*V(1)*Y(3,1)*sin(t(3,1)-d(3)+d(1))-V(3)*V(2)*Y(3,2)*...

sin(t(3,2)-d(3)+d(2))-V(3)^2*Y(3,3)*sin(t(3,3))

Page 18: Power system simulation lab manuel

18 | P a g e

EXPERIMENT-5[TRANSIENT AND SMALL SIGNAL STABILITY OF SINGLE MACHINE INFINITE BUS SYSTEM]

PROBLEM:

1. A 60Hz synchronous generator having inertia constant H = 5 MJ/MVA and a direct axis

transient reactance Xd1 = 0.3 per unit is connected to an infinite bus through a purely reactive

circuit as shown in figure. Reactances are marked on the diagram on a common system base.

The generator is delivering real power Pe= 0.8 per unit and Q = 0.074 per unit to the infinite bus

at a voltage of V = 1 per unit.

a) A temporary three-phase fault occurs at the sending end of the line at point F.When

the fault is cleared, both lines are intact. Determine the critical clearing angle and the

critical fault clearing time.

b) Verify the result using MATLAB program.

MANUEL CALCULATION:

Page 19: Power system simulation lab manuel

19 | P a g e

PROGRAM

%(a) Fault at the sending end. Both lines intact when fault is cleared

Pm = 0.8; E= 1.17; V = 1.0; X1 = 0.65; X2 = inf; X3 = 0.65;

eacfault(Pm, E, V, X1, X2, X3)

%(b) Fault at the mid-point of one line. Faulted line is isolated

X2 = 1.8; X3 = 0.8;

eacfault(Pm, E, V, X1, X2, X3)

Page 20: Power system simulation lab manuel

20 | P a g e

EXPERIMENT-6[TRANSIENT AND SMALL SIGNAL STABILITY OF MULTI MACHINE INFINITE BUS SYSTEM]

PROBLEM:

MATLAB CODE:

basemva = 100; accuracy = 0.0001; maxiter = 10;

busdata=[1 1 1.06 0.0 00.00 00.00 0.00 00.00 0 0 0

2 2 1.04 0.0 00.00 00.00 150.00 00.00 0 140 0

3 2 1.03 0.0 00.00 00.00 100.00 00.00 0 90 0

4 0 1.0 0.0 100.00 70.00 00.00 00.00 0 0 0

5 0 1.0 0.0 90.00 30.00 00.00 00.00 0 0 0

6 0 1.0 0.0 160.00 110.00 00.00 00.00 0 0 0];

Page 21: Power system simulation lab manuel

21 | P a g e

linedata=[1 4 0.035 0.225 0.0065 1.0

1 5 0.025 0.105 0.0045 1.0

1 6 0.040 0.215 0.0055 1.0

2 4 0.000 0.035 0.0000 1.0

3 5 0.000 0.042 0.0000 1.0

4 6 0.028 0.125 0.0035 1.0

5 6 0.026 0.175 0.0300 1.0];

lfybus % form the bus admittance matrix

lfnewton % Power flow solution by Newton-Raphson method

busout % Prints the power flow solution on the screen

% Gen. Ra Xd' H

gendata=[ 1 0 0.20 20

2 0 0.15 4

3 0 0.25 5];

trstab %clearing time of the fault

OUTPUT:

NOTE: Fault Bus No: 6 Bus to Bus Line to be removed:[5,6]

Page 22: Power system simulation lab manuel

22 | P a g e

EXPERIMENT-7 [ECONOMIC DISPATCH IN POWER SYSTEMS]

PROGRAM-1:

MANUEL CALCULATION:

Page 23: Power system simulation lab manuel

23 | P a g e

MATLAB CODE:

alpha =[500; 400; 200]; beta = [5.3; 5.5; 5.8]; gama=[.004; .006; .009];

PD=800;

DelP = 10; % Error in DelP is set to a high value

lambda = input('Enter estimated value of Lambda = ');

fprintf('\n ')

disp([' Lambda P1 P2 P3 DP'... ' grad Delambda'])

iter = 0; % Iteration counter

while abs(DelP) >= 0.001 % Test for convergence

iter = iter + 1; % No. of iterations

P = (lambda - beta)./(2*gama);

Page 24: Power system simulation lab manuel

24 | P a g e

DelP =PD - sum(P); % Residual

J = sum( ones(length(gama), 1)./(2*gama)); % Gradient sum

Delambda = DelP/J; % Change in variable

disp([lambda, P(1), P(2), P(3), DelP, J, Delambda])

lambda = lambda + Delambda; % Successive solution

end

totalcost = sum(alpha + beta.*P + gama.*P.^2)

OUTPUT:

PROGRAM-2:

Page 25: Power system simulation lab manuel

25 | P a g e

MANUEL CALCULATION:

Page 26: Power system simulation lab manuel

26 | P a g e

Page 27: Power system simulation lab manuel

27 | P a g e

MATLAB CODE:

cost = [200 7.0 0.008

180 6.3 0.009

140 6.8 0.007];

mwlimits =[10 85

10 80

10 70];

Page 28: Power system simulation lab manuel

28 | P a g e

Pdt = 150;

B = [0.0218 0 0

0 0.0228 0

0 0 0.0179];

basemva = 100;

dispatch

gencost

OUTPUT:

Page 29: Power system simulation lab manuel

29 | P a g e

Experiment 8: compute the average load and the daily load factor. Using

MATLAB

MANUEL CALCULATION:

Page 30: Power system simulation lab manuel

30 | P a g e

MATLAB CODE:

data=[0 2 6; 2 6 5; 6 9 10; 9 12 15; 12 14 12; 14 16 14; 16 18 16;

18 20 18; 20 22 16; 22 23 12; 23 24 6];

p=data(:,3);

Dt=data(:,2)-data(:,1);

w=p'*Dt;

pavg=w/sum(Dt)

peak=max(p)

LF=pavg/peak*100

OUTPUT:

pavg = 11.5417 peak = 18 LF = 64.1204

Page 31: Power system simulation lab manuel

31 | P a g e

EXPERIMENT-9 [FAULT ANALYSIS] PROBLEM:

The one line diagram of a simple power system is shown in figure. The neutral of each generator is grounded through a current limiting reactor of 0.25/3 per unit on a 100MVA base. The system data expressed in per unit on a common 100 MVA base is tabulated below. The generators are running on no load at their rated voltage and rated frequency with their emf in phase. Determine the fault current for the following faults. (a) A balanced three phase fault at bus 3 through a fault impedance, Zf = j0.1 per unit. (b) A single line to ground fault at bus3 through a fault impedance, Zf = j0.1 per unit. (c) A line to line fault at bus3 through a fault impedance, Zf = j0.1 per unit. (d) A double line to ground fault at bus3 through a fault impedance, Zf = j0.1 per unit.

MATLAB PROGRAM:

Z133 = j*0.22; Z033 = j*0.35; Zf = j*0.1; disp('(a) Balanced three-phase fault at bus 3') Ia3F = 1.0/(Z133+Zf) disp('(b) Single line-to-ground fault at bus 3') I03 = 1.0/(Z033 + 3*Zf + Z133 + Z133); I012=[I03; I03; I03] %sctm; global sctm a =cos(2*pi/3)+j*sin(2*pi/3); sctm = [1 1 1; 1 a^2 a; 1 a a^2]; Iabc3 = sctm*I012 disp('(c) Line-to-line fault at bus 3') I13 = 1.0/(Z133 + Z133 + Zf); I012 = [0; I13; -I13] Iabc3 = sctm*I012 disp('(d) Double line-to-ground fault at bus 3') I13 = 1/(Z133 + Z133*(Z033+3*Zf)/(Z133+Z033+3*Zf)); I23 = -(1.0 - Z133*I13)/Z133; I03 = -(1.0 - Z133*I13)/(Z033+3*Zf); I012 = [I03; I13; I23] Iabc3 = sctm*I012

Page 32: Power system simulation lab manuel

32 | P a g e

MANUEL CALCULATION

Page 33: Power system simulation lab manuel

33 | P a g e

ZERO SEQUENCE NETWORK:

Page 34: Power system simulation lab manuel

34 | P a g e

Page 35: Power system simulation lab manuel

35 | P a g e

Page 36: Power system simulation lab manuel

36 | P a g e

EXPERIMENT-10 [LOAD – FREQUENCY DYNAMICS OF SINGLE AREA POWER SYSTEMS]

Problem: An isolated power station has the following parameters

Turbine time constant, τ T= 0.5sec

Governor time constant, τ g= 0.2sec

Generator inertia constant, H = 5sec Governor speed regulation = R per unit The load varies by 0.8 percent for a 1 percent change in frequency, i.e, D = 0.8 (a) Use the Routh – Hurwitz array to find the range of R for control system

stability. (b) Use MATLAB to obtain the root locus plot. (c) The governor speed regulation is set to R = 0.05 per unit.The turbine rated output is 250MW at nominal frequency of 60Hz. A sudden load change of 50 MW (∆PL= 0.2 per unit) occurs.

(i) Find the steady state frequency deviation in Hz. (ii) Use MATLAB to obtain the time domain performance specifications and the frequency deviation step response.

SOLUTION MANUEL

K=1/R; CHARACTERISTIC EQUATION IS

Page 37: Power system simulation lab manuel

37 | P a g e

MATLAB CODE: disp('Root-locus') num = 1; den = [1 7.08 10.56 .8]; figure (1), rlocus(num, den) disp('Frequency deviation step response') PL = 0.2; numc = [0.1 0.7 1]; denc = [1 7.08 10.56 20.8]; t = 0:.02:10; c = -PL*step(numc, denc, t); figure(2), plot(t, c), grid xlabel('t, sec'), ylabel('pu') title('Frequency deviation step response') timespec(numc, denc)

Page 38: Power system simulation lab manuel

38 | P a g e

SIMULINK DIAGRAM:

Page 39: Power system simulation lab manuel

39 | P a g e

EXPERIMENT-11 [LOAD – FREQUENCY DYNAMICS OF TWO AREA POWER SYSTEMS]

Problem: A two area system connected by a tie line has the following parameters on a 1000MVA common base

The units are operating in parallel at the nominal frequency of 60Hz.The synchronizing co-efficient is computed from the initial operating condition and is gain to be PS=20p.u. A load change of 187.5 MW in area 1.

a) Determine the new steady state frequency and change in tie line flow. b) Construct the SIMULINK block diagram and obtain the frequency deviation response for the condition specified.

SOLUTION:

Page 40: Power system simulation lab manuel

40 | P a g e

MATLAB CODE:

R1 = 0.05; R2 = 0.0625; D1 = 0.6; D2 = 0.9; DPL1 = 187.5/1000; Dw = -DPL1/(1/R1 + D1+ 1/R2+D2) Df = Dw*60, f = 60+Df DPm1 = -Dw/R1 DPm2 = -Dw/R2 DP12 = Dw*(1/R2 + D2)

SIMULINK DIAGRAM:

Page 41: Power system simulation lab manuel

41 | P a g e

EXPERIMENT-12 [AVR SYSTEM OF GENERATOR]

MATLAB CODE:

num=500; den=[1 33.5 307.5 775 500]; figure(1), rlocus(num, den); kA= 10; numc=kA*[25 500]; denc=[1 33.5 307.5 775 500+ 500*kA]; t=0:.05:20; c=step(numc, denc, t); figure(2), plot(t, c), xlabel('t, sec'), grid timespec(numc, denc)

SIMULINK MODEL

Page 42: Power system simulation lab manuel

42 | P a g e

MANUEL SOLUTION: