BPL B ilt P ow er H ouse
May 12, 2015
BPL
Bilt Power House
POWER HOUSE
46 Kg/ cm2 pressure and 35 TPH Babcock and wilcox spreader stoker Boiler X 1 NO
85 Kg/ cm2 pressure and 35 TPH x 03 nos (IJT)
TG Turbine 1 x 18 mw
46 Kg/ cm2 pressure and 25 TPH Heat recovery Boiler X 1 NO (JMW)
BTH TURBINE 6.25 MW X 1 NO (BRITISH THOMSON HOUSTEN)
46 Kg/ cm2 pressure and 25 TPH Heat recovery Boiler X 1 NO (ABL)
Ash handling plant
Coal handling plant
Boiler No. Units
7 1 2 3
Type of boiler
Water Tube
Water Tube
Make IJT IJT
Designed Capacity
t/hr 35 35
Designed efficiency
% 81 81
Operating Capacity
t/hr 30 to 40
30 to 40
Operating efficiency
% 77 to 80
77to 80
Fuel used coal coal
Boiler No. Units 7 1 2 3
Steam pressure
kg/cm2 46 85 85 85
Steam temperature
ºC 404 490 490 490
Blow down %
% 4-5 5-6 5-6 5-6
Pollution control device used
(ESP, cyclone)
ESP ESP ESP ESP
Water tube
IJT
35
81
30 to 40
77 to 80
Coal
Water Tube
B&W
35
78
10 to 35
75-77
coal
BOILER SPECIFICATIONS BOILER PARAMETERS
:
1.FEEDING SCREEN 2.VIBRATOR
3.COAL CRUSHER OR GRANULATOR (HAMMER TYPE)4.CONVEYER BELTS
5.ROLLERS 6.COAL BUNKER
Details of belt conveyor:Belt conveyer 1 [ 800 x 34, 263 long ]Belt conveyer 2 [ 600 x 14, 362 long ]Belt conveyer 3 [ 600 x 126,267 long]Belt conveyer 4 [ 600 x 21, 168 long ]Belt conveyer 5a & 5b [ 800 x 32, 500 long ]
Vibrating feeder [ 915 wide x 1500 long ]Coal size ¾ inches ( 15 – 20 mm )
Grade of coal BCalorific value of coal 4500- 5000 kcal/kg
COAL HANDLING LAY OUT
MakeTRF/GB
Capacity, tons /hr 80/40
1
2Coal charge
m
coalcrusher
1- gear ratio : 30:12- : 30:13- :20 :14- :20:15a : :30:15b : :30:1
COAL HANDLING LAY OUT
crusher
TRF
ELECON
OPP
me
crusher
3
45A
5B
OPP
800x
800x
450
trolley
Type: V1000
Type: 10.5 FSM
Type : V 800
Type: 7
sfm
FLUE GAS PATH HP BOILER
BOILER 1 ST CYCLON 2 ND CYCLON 3RD CYCLON
SECONDARY AIR
TO GRATE
ECONOMISERAIR PREHEATER
FD AIR
HOT AIR OUT
ESP
SCREW CONVEYERS
TO SUBMURGED ASH BELT
FLUE GAS PATH MP BOILER
econ
ID 90 KW
ID 200 KW
GRN
ESP
The flue gas laden with fly ash is sent through pipes having negatively charged plates which give the particles a negative charge. The particles are then routed past positively charged plates, or grounded plates, which attract the now negatively-charged ash particles. The particles stick to the positive plates until they are collected. The air that leaves the plates is then clean from harmful pollutants. Just as the spoon picked the salt and pepper up from the surface they were on, the electrostatic precipitator extracts the pollutants out of the air.
WORKING OF ESP
ASH HANDLING PLANT MAIN EQUIPMENTS:1.ASH BELT CONVEYER2.SUBMERGE BELTS3.SCREW CONVEYERS (SMALL AND LONG)4.ASH HOPPERS5.RIDDLING HOPPERS6. ROLLERS
ASH HANDLING LAY OUT
SB1 SB3 SB3
ABC 1
ABC 2
ABC 3
ABC 3 BYPASS
INC
LIN
ED
BE
LT
Impact rollersplain rollers
SkirtingScrapper
To main ash Hooper
ReturnPla
in r
etu
rn
Carrying idlerImpact
Carrying idlerTrough
ASH HANDLING LAY OUT
IB
HB
SB
SB1
SB2
SB3
BELT 1
BELT 2
BELT 3
ABC 3 BYPASS
BL 7 ESP
ESPAPHECO
APH
ESP
RH
FAH
FAH
RAH
ASH HANDLING PRE CAUTIONS
If inclined belt trips, Horizontal and submerged belt will automatically stopsOPP Submerged belt bypass : Trolley is used to transfer ash when it is bypassed.Inclined belt : Bypass ABC 3 with in 3-5 minutes
Horizontal belt : ESP Hooper bypass NPP Submerged belt has two bypass.
ABC 3 bypass
Pull cord switch
( Belt 1,Belt 2, Belt 3 (ABC 3by pass) ,horizontal belt, Inclined belt, submerged belts (3 in NPP and 1 in OPP). Only horizontal belt in OPP is having chain drive.
P C S
Z S S
B S S
AB
LD
AR
E.
OT
DEAERATOR
PDM
ABLFP
ABLSTEAMFP
85 KGSTEAMFP
EFP1EFP2
LAY OUT FEED WATER (HP) SYSTEM
TOHP BOILERS
TOABL BOILERS
ABLdeae. pump
Suction
Suction
FEED PUMP SPECIFICATIONS
ABL STEAM FP
85 KG SFP
ELECT FP 1
ELECT FP 2
ABL FP
MAKE KSB MATH & PLATT
MATH & PLATT
MATH & PLATT
KSB
TYPE HAD 50/15
4/6 BFO
9 CHR
4/6 BFO
9 CHR
4/6 BFO
9 CHR
HAD 50/15
FLOW 25.3 145 145 145 25.3
HEAD 747MLC 1068 M 1068 M 1068 M 747 MLC
RPM 2960 2980 2980 2980 2950
KW/HP ------- ------- 700/938 700/938 100/134
NE
W P
OW
ER
P
LA
NT
Over head tank
Condtank
Deaerat
or
STST M
46 KG
Ex
h Ex
h
suction
MAINDIRECT
Prv
outlet
Prv
outlet
Prv
outlet
Ve
nt Ve
nt
BL 7 FEED PUMP LINES
Cond. F
rom
plant
3 KG
BL 7 FEED PUMP AREA PRE CAUTIONS
Condensate pump running indication by bulbs.
ABL feed pumps running indication by bulbs.
Inside feed pump attendants room electric feed pump running indication bulb
OT Level 10.5 feet indication bulb
OCT and NCT Level gauges (OCT-0-50-100 %=0-0.25-0.50 LEVEL), (NCT-0-50-100 % = 0-0.20-0.4 LEVEL) Inform DM plant if OCT level falls below 20 %)
OT level graphical indication also
Alarm will ring when any of the above condition is not satisfied.
Electric feed pump Amps above 370 Amps (OL on 380), Immediately steam feed pump to be taken in service. Or if demand is more, inform NPP to start supply from their end for ABL boiler in case BL 7 is running.
If any pump stops or trips immediately standby pump to be started.
Deaerator bypass system always in lineBalancing pressure should be within operating range to maintain the thrust clearanceThere are 2 supplies for ABL/Condensate / Deaerator pump viz. BTH / TG
Incase 2nd extraction pressure is more in BTH , Steam pump extraction line valve required to be operate if instructed from BTH
Gland cooling line is to be continuously observed, There are two valves which are of 55 & 150 hp , and if this is not available third one which comes from emergency tank , valve to be opened
When JMW & BL 7 are in operation, ABL boiler feed water supply to be stopped and ABL condensate pump to be started. (Valve near ABL boiler stairs entry). If only JMW boiler is running feed water supply is from BL 7 feed pump.
JMW boiler feed water heater out temperature 130 deg. Cel. Maximum and steam outlet temperature 405 deg. Cel. Maximum (Runs max 450 deg. Cel. )
No steam / water valve should be opened till the written memo is received and physical check for drain, or isolation is confirmed
BL 7 FEED PUMP AREA PRE CAUTIONS
Direct
MAIN
RTD
TO STEAM DRUM
ECO IN
ECO OUT
TI
BL 7 FEED PUMP LINES
JMW FEED WATER LINES
To Boiler Drum
Direct3 kg steam
Condensate to NCT
Eco in
Feed water heater Mai
n
Sr no Parameter O V Alarm Trip
1 Condensate pump load 30-32 A
2 Deaerator water temperature 105
3 Deaerator pump load 15-17 A
4 Deaerator discharge pressure 2-2.5
5 Electric feed pump load 350 370 380
6 Suction pressure 1.5-2
7 Discharge pressure 58-60
8 Balancing pressure 3 6
9 Oil level
10 Overhead tank level ABOVE 10.5 FT
10.5
11 OCT LEVEL Above 30 % 30 % Below 20%
12 NCT Level Above 50 % 50 % Below 40 %
FE
ED
PU
MP
OP
ER
AT
ING
PA
RA
ME
TE
RS
FEED PUMP
Make: M & P
Type: V.G PLUROVANE
Head : 1980 ft. (600 m)
Size : 6” x 4”Discharge : 349 GPM
92 M3/HR
Motor : 322 HP 430 KW
RPM :SP 1 : 3850SP 2 : 3740EFP : 2960
CONDENSATE TANKS AND PDM
TG condensate goes to PDM tank and from PDM tank to HP deaerator
BTH turbine,PM4, SPL machine condensate to NCT, then it is pumped to DM plant for polishing, back to PDM tank
Remaining condensate from clo2,PM1,PM2,Pulp mill, S/R plant, chemical house comes in OCT
From OCT it is pumped to Overhead feed tank of Boiler no 7 and other pump for ABL overhead tank
OCT & NCT are inter connected ,OCT being on height than NCT. Level is maintained by DM plant, still if OCT level drops to 25 – 20 % verbally to be inform to DM plant SE.Hydrazine + Ammonia –LP Dosing & Nalcol 2518 + Caustic – HP DosingPOLISHING: NCT Charcoal filter Iron filter DM tank
PDM Tank Secondary mixed bed
PDM PUMP
Total head:45 m
Flow : 416.7 lps BEFORE START UP OF BL 7, DM PLANT TO BE IMFORMED
Attempt. Line
pg
85 kg st pum
p
TO
T
G
Range v/v
BL1
Range v/v
BL2
Range v/v B
L 3
85/46
46 KG
H
EA
DE
R
46 kg to TG
E
jector
To A
BL st
pump
85/46 STEAM HEADER
Condensate tank pump ( 1 and 3) and 2Raw water pump 1 and 3Type: 4 U P3 (Double extraction)Size : 150 x 100Capacity : 40 lps (144 m3 / hr)Head : 40 mHP : 50RPM : 1450
46 KG/CM2 FROM 85/46 PRV
AB
L 46
Location: JMW
46/3 PRV
JMW
46 O
LD
46
46/17/7
Ste
am f
eed
pum
p B
TH
BTH TURBINE
46/3 STEAM HEADER
When condensate flow to TG condenser is less ,46/3 PRV is required to be charged. Control of opening of this valve is in TG Control room.
It is assumed that steam flow from this line is 5 Tons Per Hour.
46/17/7
46 HEADER SOOTING JMW
BTH 7
Not in use
Chem house
650/250/100
Pulp millBladecoating
From 10/7 TG
17
7
7/3 PRV
Supplim. For PM1
7 / 3 PRV
PM 2 Supplim
3 kg
PM1 , PM2 LINES
From BTH
PM 1 Supplim
PM1
PM2
10 KGTG
PULP MILL
7 KG BTH
rail clo2
SM
OPP office10KG STEAM HEADER
PRV 10/7
Dorr plant JMW APH
From
46/17/7 prv
ABL
LIME KLIN
PM
4
PM
1.2
3 KG NETWORK
BT
H 7
K
G
SR EVAP
CH
PU
LP
M
ILL
DE
AE
RA
TO
R
SPL M/CF
P E
XH
L
INE
DE
AE
RA
TO
R
CLO2
DORR
JMW FW HEATER
85 KG SFP
10 KG
ABL
SMCLO2
PMC4
MP STEAM VALVE LOCATIONS
Sr. No.
Customer Pr.
Kg/cm2
Location
1 PM 5 10 Back side of CT
2 STARCH MILL 10 Railway gate
3 ABL 10 Railway gate
4 PULP MILL 10 Behind TG room platform
5 CLO2 10 Behind OPP Office
6 PULP MILL 7 Wooden bridge Boiler & BTH
7 CHEMICAL HOUSE 7 BTH header chain valve
8 BLADE COATING 17 Wooden bridge Boiler & BTH
9 FEED PUMP 46 ASH plant
LP STEAM VALVE LOCATIONS
Sr. No.
Customer Pr.
Kg/cm2
Location
1 CHEMICAL HOUSE 3 Above MW section TR 18 (Toilet)
2 PM 1 3 Platform in front of PM 1
3 PM2 3 Platform in front of PM 2
4 PM1 SUPPLM.VALVE 3 BTH house
5 PM2 SUPPLM.VALVE 3 In front of BTH between 2 tanks
6 S/R EVAPORATOR 3 Near 46/3 PRV STAIRS
7 PM 5 / 6 / 7 3 Above BL 7 Control room
8 PM4 3 Near BL 1 FD fan area
9 DORR PLANT 3 Near JMW ESP Stairs
10 HP DEAERATOR 3 Hp deaerator
11 ABL DEAERATOR 3 ABL deaerator
12 BL 7 DEAERATOR 3 BL 7 feed pump area
13 PULP MILL 3 Rail gate + 46/10 PRV
14 MC NO 4 3 From BTH also
15 CLO2 3 Above BL 7 Control room
BOILER NO 7
FR
ON
TRE
AR
RIGHT
LEFT
CO
AL F
EE
DE
R S
IDE
FRONT AND REAR TUBES GOES TO STEAM DRUM
RIGHT & LEFT END TUBES FORM HEADER ,THEN GOES TO STEAM DRUM
REAR END
LEFT ENDRIGHT END
FRONT END
MUD DRUM
BL NO 7 WATER WALLS
BOILER NO 7,8 MOUNTINGS AND FITTINGSDrum safety valvesSH stop valveSH safety valveDrum gauge glassRange valveBlow down valve (04 + 02)Economizer safety valveSteam flow meterWater flow meterHi and LO Whistle
RGG
DOSING
COOLING TOWERS
MAKE : PAHARPUR COOLING TOWERS (Induced draft )
. TUBE WELL SUPPLY:
CHEMICALS USED:
H2SO4 - PH CONTROL 70022718: 75007000: CHLORINE
Total fans :9 nosCurrent : 36 ampsCirculation rate: 2900 m3/hrEvaporation lass : 16 m3/hr
BTH
Fans : 02 nosCurrent : Fan 1 VFD 45 amps
Fan 2 65 ampsCirculation rate : 3200 m3/hrEvaporation loss: 32 m3/hr
3,4,8,16,20,22. 10,12,14,15,17 18,19 1,21
TG
150 HP PUMP HOUSE
12345
PM 4 & OLDPH
TO HYDRANT
OLD PH PULP MILLNOT IN USE
TANK LEVEL 12 FEET SCALEREADING -------FEET EMPTY
Pump 1 current: 25 AVFD 40 HZ
3,4,8,16,20,22. 10,12,14,15,17 18,19 1,21TUBE WELL LINES:
150 HP PUMP HOUSE ELECTRICAL SUPPLY
PUMP NO 1 IS HAVING VFD.
PUMP NO 2 IS HAVING COS FROM DB2 (BTH AND TG).
PUMP NO 3 IS HAVING BTH SUPPLY
PUMP NO 4 AND 5 HAS COS FROM DB2.
FROM 150 HP PUMP HOUSE COS DB2 AND COS DB1 SUPPLY IS GIVEN.
PUMP NO 1 RUNS NORMALLY IN 150 HP PUMP HOUSE
PUMP NO 4 – HYDRANT
55 HP PUMP HOUSE
5421
TANK LEVEL 5 FEET SCALEREADING -------FEET FULL
MC 1,4 NOT IN USE COATING PLANT
NOT IN USE
NOT IN USE
MC 1,4 / DM/ DORR/ SR/ PH/ CH/ NPP
Pump 5 current: 82-84 A
3,4,8,16,20,22. 10,12,14,15,17 18,19 1,21TUBE WELL LINES:
55 HP PUMP HOUSE
BFW PUMPSGLAND
EMERGENCY GLANDFILLING TANK
DM PLANTTUBE WELL NO 6 / 9 CONNECTION
BTH DRINKING/WASHING
BTH OIL / AIR COOLER
PM
C 1
, 2
DORR / SR/NPP BFW PUMPSGLAND
SR/NPP
CH
FROM SPL PUMP
BTH SUMP
FR
OM
SP
LIT
Y P
UM
P
HO
US
E
55
55 HP PUMP HOUSE ELECTRICAL SUPPLY
PUMP NO 5 IS HAVING VFD.
SUPPLY FROM PANEL NO 2
DB1 SUPPLY TO TUBE WELL NO 1 AND 2 ,AND TO SERVICE PUMP NO 4.
COS IS FOR ABOVE. (Main supply from 150 HP pump house)
SUPPLY FOR PUMP NO 1 FROM PANEL NO 1.
COS FOR DB2 IS FOR SERVICE PUMP NO 1 , 2 , AND 5.
PUMP NO 5 RUNS NORMALLY.
FIRE PUMP DETAILS
At four location Fire pump stations are available
Main fire pump house at S/R area (4 Pumps)
At ETP (2 Pumps, One electric driven and other Diesel 12 cyl driven )
At Yard sump Electric pump
At 150 HP pump house , pump no 4.
From main fire pump house, pump no 4 runs normally
Yard fire pump some times used when sump level to be make up
All three supply available
Fire hydrant circuit 1 (cooling pond)Pump 1 (Pump no 3)Make : Mather and PlattType : 7.2 ST MEDICapacity: 1000 gpmHead : 290 ftHP : 190 RPM : 1450
Pump 2Make Mather and greevesType: 8/8 MHLCapacity: 1500 gpmHead : 290 ftHP : 200 RPM: 1450
Pump 2B (ETP)Make : KirloskarType: SVA 8Size: 8 x 8Capacity : 1400 gpmHead : 225 ftHP : 200 RPM : 1450
Diesel engine driven pump :8/8 MHL Mather and plattCapacity : 1500 gpmHead : 290 ftRPM : 1450Diesel engine make: MWMType: TD – 237 – VIZBHP : 200RPM : 1500
Fire hydrant circuit 3 ( Chipper yard)
Pump no 3:Make : Mather and PlattCapacity : 1500 gpmHead : 290 ftHP : 200 RPM : 1440Reservoir capacity : 2 lacs gallon
FIRE PUMP DETAILS
FIRE PUMP HOUSE
3421
Sometimes pump no 2 is started for CH increased consumption
66 A / 2.5 K/c2
SPECIALITY PUMP HOUSE DETAILS
1 RUNNING 1 RUNNINGSHUT
250 M3/HR4 K/C285 A
M3/HR2-2.5 K/C265-70 A
3,4,8,16,20,22. 10,12,14,15,17 18,19 1,21TUBE WELL LINES:
CO
AT
ING
PL
AN
T
AIR
CO
MP
RE
SS
OR
TW NO 9 / 6
55/ 150 LINE
NEW POWER HOUSE
PU
LP
MIL
L
AIR COMPRESSORS
Air compressors in power house are situated as follows
1) 2 nos at old power plant
2) 2 nos at new power plant
3) 4 nos at specialty machine area
cooler
PROCESS
2.5 kg/cm2
Coating plant5 kg/cm2
AD AD
cooler
RECIEVERTANK
cooler
cooler
Pulp mill , spl machines , Clo2 plant, power house
5 kg/cm2
Air comp no 2,6,4,5
Motor load: 230-250 A
AIR COMPRESSORS
NPP : KG KHOSLA MAKEDouble stage3H Y2TCERRPM : 650Pr. : 7 kg/cm2Cap : 5.89 m3/minPr 1 st stage : 2 kg/cm2pr 2 nd stage : 5.5 kg/cm2oil pr. : 2.5 kg/cm2
SPL : KG KHOSLA MAKEDouble stageAir comp no 4,5,6RPM : 800Pr. : 7 kg/cm2Cap : 51.41 m3/minPr 1 st stage : 2 kg/cm2pr 2 nd stage : 5.5 kg/cm2oil pr. : 2.5 kg/cm2
SPL : KG KHOSLA MAKESingle stageAir comp no 2RPM : 560Pr. : 7 kg/cm2Cap : 11.01 m3/minoil pr. : 2.5 kg/cm2
Air is distributed from new power plant air compressors to POWER HOUSE Air compressors in Old Power House are standby.
In case of air pressure drop or compressor trip, SPL pump house air compressor valve can be opened which is at NPP electrical panel room.
Also one line from S/R plant air compressors is available for the same purpose but it is rarely used.
Air compressors in Old Power Plant can be started in emergencies, can be put in Auto mode .One will be Auto and other will be stand by.
AIR COMPRESSORS PRE CAUTIONS
TUBE WELL NETWORKTUBE WELL NO
LOCATION SUPPLY CHANGE OVER
1 CHAIR REPAIR WORK SHOP 55 HP PUMP HOUSE
2 COATING PLANT (BEHIND 55 HP PUMP HOUSE) 55 HP PUMP HOUSE
3 TI CLUB NEAR TUBE WELL 8
4 RAMLEELA STAGE NEAR TUBE WELL 8
5 DOES NOT EXSISTS -------
6 BEHIND DM PLANT SAME LOCATION
7 DISPENSARY NO 5 NEAR TUBE WELL 8
8 TR BUILDING NEAR TEMPLE NEAR TUBE WELL 8
9 GHEE PLANT FROM BOILER HOUSE DB
10 GATE NO 9 NEAR TUBE WELL 10
11 DOES NOT EXSISTS -------
12 ETP MACHINE NO 5 / 7
13 DOES NOT EXSISTS -------
14 200 QTR NEW GATE SAME LOCATION
15 GATE NO 8 NEAR TUBE WELL 10
16 CHUNA BHATTI NEAR DR BUILDING
17 NANGAL POWER HOUSE
18 PUNJAB MILL NANGAL NO CCHANGE OVER
19 PUNJAB MILL NANGAL NO CHANGE OVER
20 TR BUILDING GROUND NEAR TUBE WELL 8
21 NEAR TRAFFIC DEPT. Location
22 DR BUILDING OLD NEAR DR BUILDING
INS
IDE
1,2,6,7,9,10,12,14,15,17,21
OU
T S
IDE
3,4,8,16,20,22
PU
NJA
B
18,19