Page 1: Polarisation and depolarisation current measurement (PDC) · สีเขียว =Model curveat moisture 3% Tx.25 MVA 115-22 kV. 22 5.Application of PDC. 23 EGAT Power for Thai

Electricity Generating Authority of Thailand Electricity Generating Authority of Thailand Power for Thai happinessPower for Thai happiness

Polarization and depolarization current measurement (PDC)

นาย สุทัศน' สุขสกุลป,ญญา

[email protected]

Page 2: Polarisation and depolarisation current measurement (PDC) · สีเขียว =Model curveat moisture 3% Tx.25 MVA 115-22 kV. 22 5.Application of PDC. 23 EGAT Power for Thai

2

ขอบเขตการนําเสนอ

• Dielectric response

• Moisture in transformer insulation

• Moisture assessment by electrical method

• Polarization and depolarization current measurement

• Application of PDC

Page 3: Polarisation and depolarisation current measurement (PDC) · สีเขียว =Model curveat moisture 3% Tx.25 MVA 115-22 kV. 22 5.Application of PDC. 23 EGAT Power for Thai

3

1.Dielectric response

Dielectric response คืออะไร

Page 4: Polarisation and depolarisation current measurement (PDC) · สีเขียว =Model curveat moisture 3% Tx.25 MVA 115-22 kV. 22 5.Application of PDC. 23 EGAT Power for Thai

4

1.Dielectric response

Page 5: Polarisation and depolarisation current measurement (PDC) · สีเขียว =Model curveat moisture 3% Tx.25 MVA 115-22 kV. 22 5.Application of PDC. 23 EGAT Power for Thai

5

1.Dielectric response

Page 6: Polarisation and depolarisation current measurement (PDC) · สีเขียว =Model curveat moisture 3% Tx.25 MVA 115-22 kV. 22 5.Application of PDC. 23 EGAT Power for Thai

6

1.Dielectric response

Page 7: Polarisation and depolarisation current measurement (PDC) · สีเขียว =Model curveat moisture 3% Tx.25 MVA 115-22 kV. 22 5.Application of PDC. 23 EGAT Power for Thai

7

1.Dielectric response

Measurement technique

Time domain Frequency domain

Polarization and depolarization current measurement (PDC)

Frequency domain spectroscopy (PDC)

Page 8: Polarisation and depolarisation current measurement (PDC) · สีเขียว =Model curveat moisture 3% Tx.25 MVA 115-22 kV. 22 5.Application of PDC. 23 EGAT Power for Thai

8

2.Moisture in transformer insulation

Cigre WG 12.8 Life management of transformers, 1999

Page 9: Polarisation and depolarisation current measurement (PDC) · สีเขียว =Model curveat moisture 3% Tx.25 MVA 115-22 kV. 22 5.Application of PDC. 23 EGAT Power for Thai

9

2.Moisture in transformer insulation

L.E. Lundgaard, “Aging of oil-impregnated paper in power transformer”, IEEE Transaction on Power Delivery, Jan. 2004

Page 10: Polarisation and depolarisation current measurement (PDC) · สีเขียว =Model curveat moisture 3% Tx.25 MVA 115-22 kV. 22 5.Application of PDC. 23 EGAT Power for Thai

10

2.Moisture in transformer insulation

Page 11: Polarisation and depolarisation current measurement (PDC) · สีเขียว =Model curveat moisture 3% Tx.25 MVA 115-22 kV. 22 5.Application of PDC. 23 EGAT Power for Thai

11

2.Moisture in transformer insulation

(Ryzhenko, V.Sokolov, V.: Effect of moisture on dielectric withstand strength of winding insulations in power transformer. Electrical stations (Electric power plants) No.9, 1981

Page 12: Polarisation and depolarisation current measurement (PDC) · สีเขียว =Model curveat moisture 3% Tx.25 MVA 115-22 kV. 22 5.Application of PDC. 23 EGAT Power for Thai

12

3. Moisture assessment by electrical method

• 1960+

• Dielectric loss at power frequency (%PF, %tan δ)

• Polarization index (PI)

• 1991 Recovery voltage measurement (RVM) (Tettex)

• 1999+ Polarization and depolarization current measurement (PDC)

(Alff Engineering)

• 1999+ Frequency domain spectroscopy (FDS) (ABB)

Page 13: Polarisation and depolarisation current measurement (PDC) · สีเขียว =Model curveat moisture 3% Tx.25 MVA 115-22 kV. 22 5.Application of PDC. 23 EGAT Power for Thai

13

4. Polarization and depolarization current measurement

Page 14: Polarisation and depolarisation current measurement (PDC) · สีเขียว =Model curveat moisture 3% Tx.25 MVA 115-22 kV. 22 5.Application of PDC. 23 EGAT Power for Thai

14

4. Polarization and depolarization current measurement

Page 15: Polarisation and depolarisation current measurement (PDC) · สีเขียว =Model curveat moisture 3% Tx.25 MVA 115-22 kV. 22 5.Application of PDC. 23 EGAT Power for Thai

15

4. Polarization and depolarization current measurement

Insulation

Homogeneous systems

Multi layer systems

Bushing Cable Instrument transformer

Generator Motor

Transformer

Page 16: Polarisation and depolarisation current measurement (PDC) · สีเขียว =Model curveat moisture 3% Tx.25 MVA 115-22 kV. 22 5.Application of PDC. 23 EGAT Power for Thai

16

4. Polarization and depolarization current measurementHomogeneous systems

Page 17: Polarisation and depolarisation current measurement (PDC) · สีเขียว =Model curveat moisture 3% Tx.25 MVA 115-22 kV. 22 5.Application of PDC. 23 EGAT Power for Thai

17

4. Polarization and depolarization current measurementMulti layer systems

Page 18: Polarisation and depolarisation current measurement (PDC) · สีเขียว =Model curveat moisture 3% Tx.25 MVA 115-22 kV. 22 5.Application of PDC. 23 EGAT Power for Thai

18

4. Polarization and depolarization current measurementMulti layer systems

Page 19: Polarisation and depolarisation current measurement (PDC) · สีเขียว =Model curveat moisture 3% Tx.25 MVA 115-22 kV. 22 5.Application of PDC. 23 EGAT Power for Thai

19

4. Polarization and depolarization current measurementMulti layer systems

Page 20: Polarisation and depolarisation current measurement (PDC) · สีเขียว =Model curveat moisture 3% Tx.25 MVA 115-22 kV. 22 5.Application of PDC. 23 EGAT Power for Thai

20

4. Polarization and depolarization current measurementMulti layer systems

Page 21: Polarisation and depolarisation current measurement (PDC) · สีเขียว =Model curveat moisture 3% Tx.25 MVA 115-22 kV. 22 5.Application of PDC. 23 EGAT Power for Thai

21

4. Polarization and depolarization current measurement

การวิเคราะห'ผลทดสอบ

Master curve หรือ Math model

Tx .25 MVA 115-22 kVสีเขียว = Model curve at moisture 3%

Page 22: Polarisation and depolarisation current measurement (PDC) · สีเขียว =Model curveat moisture 3% Tx.25 MVA 115-22 kV. 22 5.Application of PDC. 23 EGAT Power for Thai

22

5. Application of PDC

Page 23: Polarisation and depolarisation current measurement (PDC) · สีเขียว =Model curveat moisture 3% Tx.25 MVA 115-22 kV. 22 5.Application of PDC. 23 EGAT Power for Thai

23

EGATPower for Thai happiness