Point of Contact : Doug Ingerson Department of Transportation Federal Aviation Administration WJ Hughes Technical Center Fire Safety Branch, ATO-P (formerly AAR-440) Bldg 205 Atlantic City Int'l Airport, NJ 08405 USA tel: 609-485-4945 fax: 609-485-7074 email: [email protected]web page: www.fire.tc.faa.gov Federal Aviation Administration ~ WJ Hughes Technical Cent Fire Safety Branch, AAR-440 ~ Atlantic City Int’l Airport, NJ 084 rnational Aircraft Systems Fire Protection Working Group 4June2005 London, England Engine Nacelle Halon Replacement
18
Embed
Point of Contact :Doug Ingerson Department of Transportation Federal Aviation Administration WJ Hughes Technical Center Fire Safety Branch, ATO-P (formerly.
Slide #3 Federal Aviation Administration ~ WJ Hughes Technical Center Fire Safety Branch, AAR-440 ~ Atlantic City Int’l Airport, NJ USA International Aircraft Systems Fire Protection Working Group 23-24June2005London, England OVER-PRESSURE ANALYSIS PENDING OVER-PRESSURE ANALYSIS
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Point of Contact : Doug Ingerson
Department of TransportationFederal Aviation Administration
Federal Aviation Administration ~ WJ Hughes Technical CenterFire Safety Branch, AAR-440 ~ Atlantic City Int’l Airport, NJ 08405 USA
International Aircraft Systems Fire Protection Working Group23-24June2005 London, England
Engine Nacelle Halon Replacement
Slid
e#2
Federal Aviation Administration ~ WJ Hughes Technical CenterFire Safety Branch, AAR-440 ~ Atlantic City Int’l Airport, NJ 08405 USA
International Aircraft Systems Fire Protection Working Group23-24June2005 London, England
PRESENTATION CONTENTS
OVERVIEW OF PENDING ANALYSIS FOR THE OVER-PRESSURE BEHAVIOR IN THE NACELLE FIRE SIMULATORBRIEF DESCRIPTION OF PROBLEMDESCRIPTIONS OF MODIFICATIONS TO TEST FIXTURE
NEW TELEMETRYDUCT INTERFACE BOX
TEST PLAN INITIAL OBSERVATIONS
GENERIC STATUSTESTING REMAININGTABLE OF CALCULATED EQUIVALENT CONCENTRATIONS
Slid
e#3
Federal Aviation Administration ~ WJ Hughes Technical CenterFire Safety Branch, AAR-440 ~ Atlantic City Int’l Airport, NJ 08405 USA
International Aircraft Systems Fire Protection Working Group23-24June2005 London, England
OVER-PRESSURE ANALYSIS
PENDING OVER-PRESSURE ANALYSIS
Slid
e#4
Federal Aviation Administration ~ WJ Hughes Technical CenterFire Safety Branch, AAR-440 ~ Atlantic City Int’l Airport, NJ 08405 USA
International Aircraft Systems Fire Protection Working Group23-24June2005 London, England
OVER-PRESSURE ANALYSIS - OVERVIEW
DURING TESTING WITH 2-BTP & HFC-125 ANOMOLOUS BEHAVIOR WAS NOTED IN THE TEST FIXTURE
BEHAVIOR CHARACTERIZED AS AN OVER-PRESSURE AT AN ATMOSPHERIC GAP IN THE FIXTURE
WORST-CASE EXAMPLE RESULTED IN FIREBALL & AUDIBLE SIGNATURE
NO TELEMETRY ORIGINALLY LOCATED IN REGION OF INTEREST
TEST FIXTURE HAS BEEN MODIFIED TO ALLOW COLLECTION OF PERTINENT DATA
DATA TO BE COLLECTED AND SCRUTINIZED TO ASSESS MAGNITUDE AND ATTEMPT AN UNDERSTANDING
Slid
e#5
Federal Aviation Administration ~ WJ Hughes Technical CenterFire Safety Branch, AAR-440 ~ Atlantic City Int’l Airport, NJ 08405 USA
International Aircraft Systems Fire Protection Working Group23-24June2005 London, England
~ 123 Inches
~ 240 Inches
DUCT INTERFACE.
TEST SECTION EXIT = 22” DIA
EXHAUST DUCT ENTRANCE = 33” DIA
GAP BETWEEN CIRCULAR PLANES = 8”
~ 65 Inches
FIRE ZONE
AGENT INJECTION
OVER-PRESSURE ANALYSIS, PERTINENT TEST FIXTURE GEOMETRY
AIRFLOW
Slid
e#6
Federal Aviation Administration ~ WJ Hughes Technical CenterFire Safety Branch, AAR-440 ~ Atlantic City Int’l Airport, NJ 08405 USA
International Aircraft Systems Fire Protection Working Group23-24June2005 London, England
OVER-PRESSURE ANALYSIS, PERTINENT TEST FIXTURE GEOMETRY
DUCT INTERFACE.
TEST SECTION ~ EXHAUST NOZZLE
RED DUCT
Slid
e#7
Federal Aviation Administration ~ WJ Hughes Technical CenterFire Safety Branch, AAR-440 ~ Atlantic City Int’l Airport, NJ 08405 USA
International Aircraft Systems Fire Protection Working Group23-24June2005 London, England
OVER-PRESSURE ANALYSIS – FIXTURE MODIFICATIONS
ADDED 4 THERMOCOUPLES IN RED DUCT ALL ALONG 12:00 STARTED 2 FEET IN FROM INLET, PLACED EVERY 2 FEET BEADS ARE 8 INCHES OFF WALL
ADDED 2 STATIC PRESSURE MEASUREMENT LOCATIONS 0-5” H2O PSID (REFERENCE TO TEST BAY) 1 POINT IN TEST SECTION, 03:00, STA 522 1 POINT IN RED DUCT SECTION, 04:30, 21 INCHES IN FROM INLET USING STATIC PORTS OFF 1/8”OD PITOT-STATIC TUBES INSERTED
INTO FLOW FIELD
Slid
e#8
Federal Aviation Administration ~ WJ Hughes Technical CenterFire Safety Branch, AAR-440 ~ Atlantic City Int’l Airport, NJ 08405 USA
International Aircraft Systems Fire Protection Working Group23-24June2005 London, England
OVER-PRESSURE ANALYSIS – FIXTURE MODIFICATIONS
ADDED 4 OPTO-ELECTRONIC DEVICES TO DETECT FLAME PROPRAGATION THROUGH TEST FIXTURE PHOTODIODE PHOTOCONDUCTIVE CIRCUITS SENSOR VALUES
0 VDC, DARK/NO FIRE 6.1 VDC, SATURATES WHEN VIEWING FLAMES OF TEST FIRE
1 VIEWS TUBE ARRAY IN FIRE ZONE REMAINING 3 LOOK AT 12:00
ENTRANCE TO EXHAUST NOZZLE EXIT OF EXHAUST NOZZLE RED DUCT
A BOX IS BEING FABRICATED WHICH WILL CLOSE OUT THE DUCT INTERFACE COMPLETELY
Slid
e#9
Federal Aviation Administration ~ WJ Hughes Technical CenterFire Safety Branch, AAR-440 ~ Atlantic City Int’l Airport, NJ 08405 USA
International Aircraft Systems Fire Protection Working Group23-24June2005 London, England
OVER-PRESSURE ANALYSIS, TELEMETRY LOCATIONS
TYPE “K” THERMOCOUPLESTATIC PRESSURE MEASUREMENTPHOTODIODE FLAME DETECTOR
BOX TO CLOSEOUT DUCT INTERFACE
STA 551
STA 527
STA 502
Slid
e#1
0
Federal Aviation Administration ~ WJ Hughes Technical CenterFire Safety Branch, AAR-440 ~ Atlantic City Int’l Airport, NJ 08405 USA
International Aircraft Systems Fire Protection Working Group23-24June2005 London, England
OVER-PRESSURE ANALYSIS – TEST PLAN
PURPOSE : TO CAPTURE THE ENVIRONMENT OF THE OVER-PRESSURE
PRODUCED BY HFC-125 TO CAPTURE THE ENVIRONMENT AS PRODUCED BY HALON 1301 CHARACTERIZE THE MAGNITUDE OF THE ENVIRONMENT ATTEMPT TO TO UNDERSTAND THE PHENOMENA
PLAN : FIRE TEST WITH HFC-125 IN CONFIGURATIONS WHERE OVER-
PRESSURES WERE PREVIOUSLY OBSERVED FIRE TEST WITH HALON 1301 IN THE SAME CONDITION RUN EACH AGENT WITH & WITHOUT THE DUCT INTERFACE
BLOCKED OUT MULTIPLE OVER-PRESSURES WILL BE CAPTURED MULTIPLE HALON 1301 FIRE TESTS PLANNED TO CAPTURE
BEHAVIOR EXACT TEST COUNT TBD
Slid
e#1
1
Federal Aviation Administration ~ WJ Hughes Technical CenterFire Safety Branch, AAR-440 ~ Atlantic City Int’l Airport, NJ 08405 USA
International Aircraft Systems Fire Protection Working Group23-24June2005 London, England
OVER-PRESSURE ANALYSIS – INITIAL OBSERVATIONS
THE FOLLOWING GRAPHS ILLUSTRATE SOME OBSERVATIONS BASED ON 1.0 lbm/s 260*F VENTILATION, 0.25 GPM OIL SPRAY FIRE,
HFC-125 AT “equivalence” THE FOLLOWING BEHAVIORS WERE OBSERVED :
THIS TEST VISUALLY PRODUCED A “MINOR” OVER-PRESSURE GRAPH OF FIRE IGNITION, INITIAL VS. REIGNITION AT COMPLETION OF
REIGNITION TIME DELAY (RTD) FLAME FRONT PROPAGATION IS QUICKER DURING INITIAL IGNITION FIRE GROWTH IS QUICKER DURING REIGNITION STATIC PRESSURE PULSE IS LARGER FOR REIGNITION STATIC PRESSURE PULSE IS FRACTIONAL INCH MAGNITUDE
GRAPH OF THE COMPLETE REIGNITION TIME DELAY FLAME EXTINCTION AT RTD ONSET DOES NOT PROGRESS
LOGICALLY FLAME REIGNITION AFTER RTD PROGRESSES LOGICALLY STATIC PRESSURE HAS GREATER PULSE DURING FIRE REIGNITION
THAN DURING AGENT DISCHARGE GRAPH OF OVERALL TEMPERATURE BEHAVIOR INDICATES NOTHING
UNUSUAL
Slid
e#1
2
Federal Aviation Administration ~ WJ Hughes Technical CenterFire Safety Branch, AAR-440 ~ Atlantic City Int’l Airport, NJ 08405 USA
International Aircraft Systems Fire Protection Working Group23-24June2005 London, England
OVER-PRESSURE ANALYSIS – INITIAL OBSERVATIONS, FIRE IGNITION
-1.0
-0.5
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
-32 -31 -30 -29 -28 -27
TIME (SEC)
PHOTODIODE, TUBE ARRAY (VDC)
PHOTODIODE, EXH NZL ENTRANCE (VDC)
PHOTODIODE, EXH NZL EXIT (VDC)
PHOTODIODE, RED DUCT (VDC)
STATIC PRES., TEST SECTION ("H2O)
STATIC PRES., RED DUCT SECTION ("H2O)
lfhs 05 509 10 c4
-1.0
-0.5
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
6 7 8 9 10 11
TIME (SEC)
lfhs 05 509 10 c6
FIRE IGNITIONAT START OF TEST
NO FIRE
FIREREIGNITIONAT THE ENDOF THE RTD
Slid
e#1
3
Federal Aviation Administration ~ WJ Hughes Technical CenterFire Safety Branch, AAR-440 ~ Atlantic City Int’l Airport, NJ 08405 USA
International Aircraft Systems Fire Protection Working Group23-24June2005 London, England