POCON – POWER CONNECTOR The compact test- disconnect terminal interface system for protection and secondary technology Let’s connect.
POCON – POWER CONNECTORThe compact test- disconnect terminal interface system for protection and secondary technologyLet’s connect.
For today’s more and more complex protection systems there are mainly three different types of tests.
1. Initial test, when a unit is put into operation for the first time 2. Main examination, testing the response values 3. Performance check from activation to release
POCON is a universally applicable test- disconnect terminal system that perfectly supports different types of measuring. The innovative interface system enables automatic shorting and disconnecting.
POCON – the compact test-disconnect terminal interface systemSafe control and testing of safety relays, measuring equipment and metering devices.
T1G
2
Example circuit
From the field for the fieldPOCON – the interface concept for flexibility and safety
Standard plug in operative function
Safety relay and measuring devices are “online”, the current and voltage instrument transformer is in operative function.
When developing the current and voltage converting terminal POCON, high attention was given to our customers’ practical know-how. Close co-operation ensured that routine details were transferred and taken over in order to guarantee a reliably operating product. This resulted in an innovative module, consisting of only few components, but suitable for a wide range of different applications with modular style.
Coding Voltage transformer*
Signal contact
Transformer
Safety relay
* When connecting voltage transformers coding elements are to be used on the rear side! (see page 6)
L-
L1 L2 L3L1 L2 L3
L+
L-
L 1 L2 L3L 1 L2 L3
L+
L-
L 1 L2 L3L 1 L2 L3
L+
4
Example circuit
Example circuit
Note: Please insert the cable before connecting the plug
Free configuration options for the test-disconnect terminalThe operator can connect safety relays and measuring devices at his choice. Additionally it is possible to loop reference measurement instruments and transmitters into the current and voltage circuits.
Short-circuit with lateral disconnection
Safety relay and measuring devices are “offline”, the current and voltage instrument transformer is protected. Current transformers are shorted at the input side, voltage transformers are disconnected.
Signal contact
Signal contact
Coding Voltage transformer*
Coding Voltage transformer*
Safety relay
Safety relay
N 1
4
2 3 4321
N321
1 2 3 4 5 6 7 8 9 POWER10
0
Measuring device
Transformer
Transformer
L-
L1 L2 L3L1 L2 L3
L+
L-
L 1 L2 L3L 1 L2 L3
L+
L-
L 1 L2 L3L 1 L2 L3
L+
L-
L1 L2 L3L1 L2 L3
L+
L-
L 1 L2 L3L 1 L2 L3
L+
L-
L 1 L2 L3L 1 L2 L3
L+
5
Sophisticated details in compact designPOCON – test-disconnect terminal interface for external operation
Voltage transformer
Current transformer
2 in 1Current and voltage transformer terminal combined in a single product. A coding element on the rear is used to switch between the functions.
Unplugged Plugged
Automatic shortingDuring a current transformer application a short circuit is enforced automatically when the connector is pulled out.
Quick installationDue to the compact design and smart assembly technique POCON is installed in an easy and fast way. It can be mounted in diverse types of switching cabinets or directly on the mounting rail.
6
Flexible and easy applicationUsing cross connections, the test plug offers free configuration options. Additionally it is possible to loop measurement instruments into the transformer current circuit via plug connectors or cable lugs. Thus, test devices can easily, securely and conveniently be connected.
Automatic lateral disconnection When the plug is removed, the PowerConnector automatically effects a lateral disconnection. Thus any connected protective or measurement instruments are safely disconnected from the transformer.
SealsMounting options for anti-tamper seals prevent unintentional or accidental removal of the front plug.
Please contact the responsible Weidmueller sales representative for further information.
7
Technical data
POCON 4
Technical data
Rated voltageMaximum voltageRated current AC: - ambient temperature = 20 °C
Temperature range ambient temperature duringClampable conductors solid1 conductor (2 conductors) stranded
flexibleflexible with ferrule
IP protectionApprovalsMounting typeNumber of feed-through contactsNumber of signal contacts
AccessoriesCross connectionNote
Ordering data
POCON 4 Terminal Unit
POCON 4 Standard connector
POCON 4 Test connector
Note
Accessories
Cross Connection 2-poleCross Connection 3-pole
Coding elementRing cable connector
Fork-type cable connectorText plug
Note
250 V / 2.5 kV / 32.21 kV / 50 Hz for 1 minconductors 1 mm2: 19 A300 A / 1 sec60 A / 6 secoperation: -40 °C ... +55 °C0.5 - 10 mm2 (2.5 mm²)1.5 - 10 mm2 (2.5 mm²)0.5 - 10 mm2 „f“ (2.5 mm²)0.5 - 6 mm2 „f“ (2.5 mm²)IP20GOST-Rcutout (See p. 11, No. 5)41
2-pole and 3-polesee dimension drawing 1, page 11
Type Qty. Order No.KIT KLTR 2TR POCON 4 5 1052150000
SDST 2TR POCON 4 5 1052160000
TCN 2TR POCON 4 5 1052180000
Type Qty. Order No.QV 2POL POCON 50 1091670000QV 3POL POCON 50 1091680000KOEL POCON 50 1091690000LIR 1.5M3 V 100 9200070000LIS 1.5M3 V 100 9200290000PS 4 F.STB 4 20 0299600000
250 V / 2.5 kV / 32.21 kV / 50 Hz for 1 minconductors 1 mm2: 19 A300 A / 1 sec60 A / 6 secoperation: -40 °C ... +55 °C0.5 - 10 mm2 (2.5 mm²)1.5 - 10 mm2 (2.5 mm²)0.5 - 10 mm2 „f“ (2.5 mm²)0.5 - 6 mm2 „f“ (2.5 mm²)IP20GOST-RMounting rail (See p. 11, No. 5)41
2-pole and 3-polesee dimension drawing 2, page 11
Type Qty. Order No.KIT KLTR 2TR TSBF POCON 5 1189230000
SDST 2TR POCON 4 5 1052160000
TCN 2TR POCON 4 5 1052180000
Type Qty. Order No.QV 2POL POCON 50 1091670000QV 3POL POCON 50 1091680000KOEL POCON 50 1091690000LIR 1.5M3 V 100 9200070000LIS 1.5M3 V 100 9200290000PS 4 F.STB 4 20 0299600000
8
Technical data
POCON 8
Technical data
Rated voltageMaximum voltageRated current AC: - ambient temperature = 20 °C
Temperature range ambient temperature duringClampable conductors solid1 conductor (2 conductors) stranded
flexibleflexible with ferrule
IP protectionApprovalsMounting typeNumber of feed-through contactsNumber of signal contacts
AccessoriesCross connectionNote
Ordering data
POCON 8 Terminal Unit
POCON 8 Standard connector
POCON 8 Test connector
Note
Accessories
Cross Connection 2-poleCross Connection 3-pole
Coding elementRing cable connector
Fork-type cable connectorText plug
Note
250 V / 2.5 kV / 32.21 kV / 50 Hz for 1 minconductors 1 mm2: 19 A300 A / 1 sec60 A / 6 secoperation: -40 °C ... +55 °C0.5 - 10 mm2 (2.5 mm²)1.5 - 10 mm2 (2.5 mm²)0.5 - 10 mm2 „f“ (2.5 mm²)0.5 - 6 mm2 „f“ (2.5 mm²)IP20GOST-Rcutout (See p. 11, No. 6)81
2-pole and 3-polesee dimension drawing 3, page 11
Type Qty. Order No.KIT KLTR 4TR POCON 8 5 1052140000
SDST 4TR POCON 8 5 1052170000
TCN 4TR POCON 8 5 1052080000
Type Qty. Order No.QV 2POL POCON 50 1091670000QV 3POL POCON 50 1091680000KOEL POCON 50 1091690000LIR 1.5M3 V 100 9200070000LIS 1.5M3 V 100 9200290000PS 4 F.STB 4 20 0299600000
250 V / 2.5 kV / 32.21 kV / 50 Hz for 1 minconductors 1 mm2: 19 A300 A / 1 sec60 A / 6 secoperation: -40 °C ... +55 °C0.5 - 10 mm2 (2.5 mm²)1.5 - 10 mm2 (2.5 mm²)0.5 - 10 mm2 „f“ (2.5 mm²)0.5 - 6 mm2 „f“ (2.5 mm²)IP20GOST-RMounting rail (See p. 11, No. 6)81
2-pole and 3-polesee dimension drawing 4, page 11
Type Qty. Order No.KIT KLTR 4TR TSBF POCON 5 1189240000
SDST 4TR POCON 8 5 1052170000
TCN 4TR POCON 8 5 1052080000
Type Qty. Order No.QV 2POL POCON 50 1091670000QV 3POL POCON 50 1091680000KOEL POCON 50 1091690000LIR 1.5M3 V 100 9200070000LIS 1.5M3 V 100 9200290000PS 4 F.STB 4 20 0299600000
9
Technical data
POCON 9
Technical data
Rated voltageMaximum voltageRated current AC: - ambient temperature = 20 °C
Temperature range ambient temperature duringClampable conductors solid1 conductor (2 conductors) stranded
flexibleflexible with ferrule
IP protectionApprovalsMounting typeNumber of feed-through contactsNumber of signal contacts
AccessoriesCross connectionNote
Ordering data
POCON 9 Terminal Unit
POCON 9 Standard connector
POCON 9 Test connector
Note
Accessories
Cross Connection 2-poleCross Connection 3-pole
Coding elementRing cable connector
Fork-type cable connectorText plug
Note
250 V / 2.5 kV / 32.21 kV / 50 Hz for 1 minconductors 1 mm2: 19 A300 A / 1 sec60 A / 6 secoperation: -40 °C ... +55 °C0.5 - 10 mm2 (2.5 mm²)1.5 - 10 mm2 (2.5 mm²)0.5 - 10 mm2 „f“ (2.5 mm²)0.5 - 6 mm2 „f“ (2.5 mm²)IP20GOST-Rcutout (See p. 11, No. 6)9-
2-pole and 3-polesee dimension drawing 3, page 11
Type Qty. Order No.KIT KLTR 4TR POCON V1 5 1191220000
SDST 4TR POCON 8 5 1052170000
TCN 4TR POCON 8 5 1052080000
Type Qty. Order No.QV 2POL POCON 50 1091670000QV 3POL POCON 50 1091680000KOEL POCON 50 1091690000LIR 1.5M3 V 100 9200070000LIS 1.5M3 V 100 9200290000PS 4 F.STB 4 20 0299600000
250 V / 2.5 kV / 32.21 kV / 50 Hz for 1 minconductors 1 mm2: 19 A300 A / 1 sec60 A / 6 secoperation: -40 °C ... +55 °C0.5 - 10 mm2 (2.5 mm²)1.5 - 10 mm2 (2.5 mm²)0.5 - 10 mm2 „f“ (2.5 mm²)0.5 - 6 mm2 „f“ (2.5 mm²)IP20GOST-RMounting rail (See p. 11, No. 6)9-
2-pole and 3-polesee dimension drawing 4, page 11
Type Qty. Order No.KIT KLTR 4TR POCON V2 5 1193780000
SDST 4TR POCON 8 5 1052170000
TCN 4TR POCON 8 5 1052080000
Type Qty. Order No.QV 2POL POCON 50 1091670000QV 3POL POCON 50 1091680000KOEL POCON 50 1091690000LIR 1.5M3 V 100 9200070000LIS 1.5M3 V 100 9200290000PS 4 F.STB 4 20 0299600000
10
Technical data
Interconnection example for multiple protection relays at one transformer set
Configuration for 2 transformers
+
or
+
standard connector1052160000
test connector (IP20)1052180000
3-pole cross connection1091680000
2-pole cross connection1091670000
coding element1091690000
+
current transformerapplication
voltage transformerapplication
terminal unit for 2 transformers1052150000
Configuration for 4 transformers
+
or
+
standard connector1052170000
test connector (IP20)1052080000
3-pole cross connection1091680000
2-pole cross connection1091670000
coding element1091690000
+
current transformerapplication
voltage transformerapplication
terminal unit for 4 transformers1052140000
1 32 4
L- L- L-
N 1
4
2 3 4321
N321
1 2 3 4 5 6 7 8 9 POWER10
0
L+ L+L+
L1
L2
L3
Protection in operation Protection out of operation Protection out of operationTest mode
Dimensional drawing
1
2
3
4
5
6
56.7
5
82.5 33.6 21.55
1-3Cutout
56.7
5
81.75
39.58 24.37
Mounting rail
56.7
5
130.5 33.6 21.55
1-3Cutout
56.7
5
129.7
Mounting rail
51 ±
0.25
mm
82.5 mm+0.5 0
1-3 mmPOCON 4
51 ±
0.25
mm
130.5 mm+0.5 0
1-3 mmPOCON 8
11
09/2018/SMR
Weidmüller – Your partner in Industrial Connectivity
As experienced experts we support our customers and partners around the world with products, solutions and services in the industrial environment of power, signal and data. We are at home in their industries and markets and know the technological challenges of tomorrow. We are therefore continuously developing innovative, sustainable and useful solutions for their individual needs. Together we set standards in Industrial Connectivity.
Personal support canbe found on our website:www.weidmueller.com/contact
Weidmüller Interface GmbH & Co. KGKlingenbergstraße 1632758 Detmold, GermanyT +49 5231 14-0F +49 5231 14-292083www.weidmueller.com