Top Banner
Please furnish your quotation for the works mentioned in the enclosed quotation form "Schedule of work", -Your quotation should fulfill the following conditions:- A. Quotations should be sent in a SEALED ENVELOPE addressed to the BECIL official (As per details given below) so as to reach him on or before 24/08/2015 up to 12.30 P.M., quotations received late will be rejected.
4

Please furnish your quotation for the works mentioned in ...

Dec 20, 2021

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Please furnish your quotation for the works mentioned in ...

Please furnish your quotation for the works mentioned in the enclosed quotation form "Schedule of work", -Yourquotation should fulfill the following conditions:-

A. Quotations should be sent in a SEALED ENVELOPE addressed to the BECIL official (As per detailsgiven below) so as to reach him on or before 24/08/2015 up to 12.30 P.M., quotations received late willbe rejected.

Page 2: Please furnish your quotation for the works mentioned in ...

E. VAU[;)ITY:· Tender should remain open for acceptance for a period of three months from the date ofopening.

G. This office reserves the right to accept any quotation not necessarily the lowest. Further this officereserves right of increasing / decreasing the quantity. of the material tender depending 0 actualrequirements. The unit rate quoted in the tender shall be applicable to the quantity for which the orderis placed.

H. EMD/Security deposit: - An EMD of Rs 1100/·(One Thousand One Hundred Only) shall be depositat the time of tender submission in the form of DO in favor of Broadcast Engineering Consultant IndiaLimited payable at Delhi. The EMD of the successful tenderer shall be returned aftercompletion of work, whereas the EMD of the unsuccessful tenderer shall be returnedwithin 15 days of the finalization of the contractor. The EMD shall not carry any interest.

Page 3: Please furnish your quotation for the works mentioned in ...

Enquiry form

Quotation No. - BECIL IDD/DTT(DVB·T2) Antenna IEP/2015·2016 Dated: 03/08/2015

S. No. Description Unit Qty. Rate Amount1. Preparation and commissioning of earth pits with Nos. 03

600 x 600 x 3.15 mm thick copper electrode withwatering arrangement of chamber funnel, charcoalsalt etc. The electrode shall be connected with25mmx3mm thick copper strip and terminated intothe chamber with nut bolt arrangement. The rateshall include cost of earthing strip upto thechamber. The earth resistance shall not exceed1.0 ohms. The rate shall include testing the same& documentation. (IS 3043 : 1987) for details referBECIL Drawing No. BECIL/GENERAL/EP-001.

Total

Service Tax @

VAT ISales Tax@

WCT@

Grand Total

Excise Duty I VAT I WCT.

Site Address.

Completion period

Forwarding and Transportation Charges.

Shall be shown separately.High Power Transmitter, Doordarshan, Tulsipur, Cuttack,753008 (Orrisa)Two·weeks after award of work.

Inclusive.

Not applicable.1 Months from date of opening of tender.

95% Payment will be made after completion of workcertified by authorized representative of BECIUDDKCuttack. •5%after defect liability period of One year.

Declaration to be given by tenderer "we declare that all the conditions as given in the enquiry form have beenread by us."

Other Charges (If any).Validity of the tender.

Page 4: Please furnish your quotation for the works mentioned in ...

THIS DRAWING IS COPYRIGHT AND THEPROPERTY OF 'B E C I L ' AND IS NOT TO

BE REPRODUCED, COPIED HANDED OVERTO A THIRD PARTY OR USEDFOR ANY

PURPOSE OTHER THAN THAT FOR WHICHIT HAS BEEN ISSUED.

DETAIL OF EARTHING ARRANGEMENT

C. I. COVER HINGED TO C. I. FRAME 150mmI ABOVE G.LI

rCHROME PLATEDWIRE MESH

25mmX3mmCOPPER STRIP

38mm G. I.PIPE

ALTERNATE LAYER200(APPROX.)OF CHARCOAL ORCOKE ANDSALT IN 70:30 RATIO

CHARCOALLAYER

SALT LAYERu-------- ...•.•.•.,,'~.' .~.<C:.~.,:

DRG. No.:· BECIL I EPI GENERAL /001

CAD DRG. No.:-

1. BOTH 25X3mm COPPER STRIPS SHOULD BE FIXED TO THEPLATE & THEN BRAZED UPTO 4" CONTINUOUSLY.

3. ALL THE COPPER STRIPS USED INSIDE THE EARTH SHOULD BEPROVIDED WITH PROTECTIVE COVERING WITH. HEATSHRINKABLE PVC SLEEVES.

• BROADCAST ENGINEERINGCONSULTANTS INDIA LIMITED

HEAD OFFICE:- 1~-8, RING ROAD,I. P. ESTATE. NEW DELHI-110 002 (INDIA),

Tele:- 23378823. Fax No. 2337 9885