NOTES FIRE SUPPRESION EQUIPMENT LEGEND VERTICAL RUNS (mm) MATERIAL PIPE SIZE HORIZONTAL RUNS SUPPORT DISTANCE (mm) 4600 3700 3700 3000 3000 4600 4600 2400 3000 3000 2400 2400 2400 3000 DN 100 DN 80 DN 65 DN 50 DN 40 DN 32 STEEL DN 25 PIPE SUPPORTS SPACING TABLE A 5. PIPE SUPPORTS SHALL BE AS PER TABLE A BELOW. PIPEWORK 1. PIPEWORK SHALL BE MEDIUM GRADE GALVANIZED STEEL 2mm/METER. 2. BURIED PIPEWORK SHALL BE PROTECTED AGAINST CORROSION. 3. PIPES SHALL BE INSTALLED WITH ONE COAT OF RED OXIDE PAINT. 4. PIPES SHALL BE PAINTED SIGNAL RED AFTER INSTALLATION. 5. ALL PIPEWORK SHALL BE INSTALLED TO SLOPE TO DRAIN AT GRADIENT OF INLET VALVES. FIRE HOSE REEL AND EXTINGUISHERS 1. FIRE HOSE REEL WATER SUPPLY PIPES SHALL BE MEDIUM GRADE GALVANISED MILD STEEL 2. ALL FIRE HOSE REEL SHALL BE PROVIDED WITH 25mm Ø 30M LONG HOSES AND 3. FIRE HOSE REEL BRACKETS ARE TO BE THE SWINGING TYPE WITH HINGES AS DETAILED 4. ALL FIRE EXTINGUISHERS TO BE WALL MOUNTED COMPLETE WITH TIMBER BACKING. FIRE ENGINE BOOSTER PUMP CONNECTION FEBC FIRE HYDRANT FH FIRE HOSE REEL FHR FIRE EXTINGUISHERS FE 4.5 KG DRY POWDER FIRE EXTINGUISHERS FE (45) 6. This drawing shall be read in conjuction with the Mechanical Standard Specifications. 9 KG DRY POWDER FIRE EXTINGUISHERS FE (90) SEPARATION LEGEND 6. PIPE RISER TO ABOVE. 7. PIPE DROPPER TO BELOW. 7. Site water reticulation as per civil engineering drawing. 8. All work to comply to SANS 10400: T-2011 - FIRE DOORS FD30 - 30 MINUTES FIRE RATED DOORS WITH GRAVITY ACTIVATED SELF CLOSING HINGES 6. FIRE EXTINGUISHERS TO BE INSTALLED TO SANS 10139 AND FIRE HOSE REELS TO SANS 543. TYPICAL WALL MOUNTED PHOTOLUMINISCENT FIRE SIGNAGE SCALE : N.T.S 150mm X 150mm PHOTOLUMINISCENT SIGNATE (SABS APPROVED) 15mm Lift Off x 300mm LIGHT DUTY ALUMINIUM Z CLIP TO MOUNT FRAMES TO WALL 150mm x 300mm COMBO ALUMINIUM SAFETY SIGN FRAME SIDE VIEW FRONT VIEW 150mm X 150mm PHOTOLUMINISCENT SIGNATE (SABS APPROVED) 150mm x 300mm COMBO ALUMINIUM SAFETY SIGN FRAME LOCKABLE STEEL CABINET WITH SIGNAL RED EPOXY POWDER COATING BREAK GLASS FOR ACCESS 30m FIRE HOSE REEL ISOLATING VALVES UNION DIA 25mm PIPE BREAK GLASS FOR ACCESS KEY LOCKABLE STEEL CABINET IN SIGNAL RED EPOXY POWDER COATING ISOLATING VALVES UNION DIA 25mm PIPE 30m FIRE HOSE REEL TYPICAL WALL BACKBOARD FOR FIRE EXTINGUISHER SCALE : N.T.S BRACKET FOR FIRE EXTINGUISHER ATTACHED TO WOODEN BACK BOARD BY MEANS OFF 4x20 BRASS WOODEN SCREWS SELECTED MERANTI WOODEN BACKBOARD ATTACHED TO BRICK WALL WITH TWO 6 x76 NAIL-IN TYPE SREWS SELECTED MERANTI WOODEN BLOCK SECURE WITH 5x35 COUNTER SUNK WOOD SCREWS FROM BACK OF BACKBARD MINIMUM 680mm OR 80mm LONGER THAN THE FIRE EXTINGUISHER FINISHED FLOOR LEVEL FIRE EXTINGUISHER FRONT VIEW SIDE VIEW DETAIL FOR WOODEN DISTANCE PIECE FOR EXTINGUISHER SCALE : N.T.S 1702m 1702 1702m 1702m 1701m 1701m 1703m EP EP BM1 T 1012 1013 1014 1/1014 102 1205 1/1010 1265 1233 1/1009 1/1011 1/1012 1/1013 9/1015 1/1008 NEW CLEAR-VU FENCING TO DETAIL EXISTING STORMWATER CHANNEL NEW CLEAR-VU FENCING TO DETAIL NEW CLEAR-VU FENCING TO DETAIL BREAK AND CONNECT INTO EXISTING SEWER MH3 MH2 MH1 ENTRANCE EXIT NEW SIGNAGE WALL =1701.845 IL=1698.66 CL=1701.302 IL=1700.15 CL=1701.710 IL=1699.35 EWER EXISTING SEWER EX. MH EXISTING STORMWATER CHANNEL 4m WIDE X 3m DEEP STORMWATER CL=1701.542 IL=1700.46 KI SW KI CL=1701.375 KI CL=1702.300 CL=1701.853 CL=1701.826 CL=1701.488 STING MEDIAN C MOVEMENT LDING AREA PARKING AREA SERVITUDE (SEWERLINE PURPOSE) CITY AND SUBURBAN STREET MARITZBURG STREET EXISTING STORMWATER CHANNEL NEW CLEAR-VU FENCING TO DETAIL IL=1697.86 SW CL=1702.178 CL=1702.333 SW CL=1702.042 X 2900300 X 2900300 X 2900400 X 2900400 Y 93900 Y 94000 Y 93900 Y 94000 V.STALL A1 V.STALL A3 TOILETS TOILETS SEATING AREAS OFFICES SW_CP3 SW_CP4 SW_CP1 SW_CP2 SW_CP5 GREASE OUTLET 1 DISCHARGE INTO EXISTING STORMWATER CHANNEL TRAP SEATING AREAS V.STALL B RE RE CONNECTION INTO EXISTING WATER LINE POSITION TO BE CONFIRMED Ø80mm Ø80mm Ø80mm Ø100mm Ø100mm Ø80mm Ø80mm Ø80mm E2 F13 F14 2 x 4.5KG DCP FHR FH FH F13 E2 F13 E2 F13 E2 F13 E2 V.STALL A2 F14 FHR 2 x 4.5KG DCP 2 x 4.5KG DCP 2 x 4.5KG DCP 2 x 4.5KG DCP FEBC F.D DCP FE 4.5kg P * * F4 E1 F1 F3 F2 EE1 EE3 EE2 E3 E2 F6 F5 E4 F10 F12 F11 F7 F9 F8 F13 F16 F18 F17 F15 F14 F19 F21 F20 100mm Ø PE100 HDPE STREET MAINS 1. ALL PIPEWORK ABOVE GROUND LEVEL TO BE GALVANIZED AND BELOW GROUND TO BE PE100 HDPE. NOTE:- N.G.L. THRUSTBLOCK THRUSTBLOCK NON RETURN VALVE WATER METER 65mm DIA MALE BOOSTER CONNECTION c/w BLANK CAP 100mm DIA T-PIECE 2500 kPa PRESSURE GAUGE 100mmØ PE100 HDPE WATER SUPPLY TO SITE WATER RETICULATION: TO BUILDING DOMESTIC WATER SUPPLY (WITHIN 1 METER OF WET SERVICES SHAFT) NON RETURN VALVE ISOLATING VALVE TO BUILDING FIRE WATER SUPPLY (WITHIN 1M WET SERVICES SHAFT) NON RETURN VALVE ISOLATING VALVE GALVANIZED PIPING COPPER PIPING PRV VALVE Ø65mm INSTANTANEOUS, SIMULTANEOUS SINGLE HEADED FIRE HYDRANT WITH A NON-RETURN VALVE (QUICK COUPLER CONNECTOR) DIA 80mm PIPE DIA 65mm PROPOSED STORMWATER PIPE PROPOSED FIRE WATER PIPE EXISTING SEWER LINE PROPOSED PORTABLE WATER PIPE Project KASERNE TAXI HOLDING FACILITY FOR ERF 1230, DOORNFONTEIN No: 92-IR CITY AND SUBURBAN x 10 Drawing Description Drawn by : T.H. Pooe Scale : As shown Revision : Job No. Project Drawing Number Client REVISIONS Revision No. Date Issued by Description Consultant FIRE PROTECTION INSTALLATION MEC-BES-WIN-FR-00-00 Checked by BOTONG LENCOE ECSA Reg No201130060 SIGNATURE: EDWARD SINDANO ECSA Reg No:20090166 Co-ordinated by SIGNATURE: 00 15/10/ 2019 T.H. Pooe For Information Revision : 01 Date : 15/10/2019 N.T.S Fire Hose Reel Detail 5 2 N.T.S Safety signage detail N.T.S Wall Backboard for Fire Extiguisher 3 N.T.S Typical Fire Engine Booster Pump Connection (FEBC) Detail 6 Single Headed Instantaneous Fire Hydrant N.T.S 4 With Anti-temper key (Quick Coupler Connector) Services Layout Scale: 1:400 1 01 04/111 2019 T.H. Pooe For Tender