Pipe Hangers Pipe hangers offered in this section are designed to support insulated or non-insulated pipe allowing for vertical adjustment and limited movement in the piping system. Materials Carbon Steel, Malleable Iron and AISI Type 304 & 316 Stainless Steel are used in the manufacturing of pipe hangers. Other materials are available. Finishes The standard finishes for mechanical supports are plain steel (oil coated) sometimes referred to as black, Electro-Galvanized Zinc (ASTM B633 SC3), Pre-Galvanized (ASTM A653 G90), Hot-Dip Galvanized After Fabrication (ASTM A123), Red Primer, Plastic Coating, DURA-GREEN ™ , DURA-COPPER ™ and other special coatings are available upon request. Note: Due to the design of some products, (threads, connecting hardware, swivels, etc.) items may or may not be uniformly coated with special finishes i.e. Hot-Dip Galvanized, DURA-GREEN, DURA-COPPER, PVC etc. In some cases, the hanger itself may be coated, however, the hardware may be supplied Electro-Plated, DURA-COPPER Painted or Stainless Steel. Consult B-Line Systems for availability. Approvals (as noted) Items in this section are Underwriters Laboratories Listed, Factory Mutual Approved, and comply with Federal Specification WW-H-171E & A-A-1192A or Manufacturers Standardization Society ANSI/MSS SP-69 & SP-58. Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development (OSHPD) All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified. Pipe Hangers Pipe Hangers & Supports 47
26
Embed
Pipe Hangers - The Macomb Group Hangers Pipe hangers offered in this section are designed to support insulated or non-insulated pipe allowing for vertical adjustment and …
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Pip
e H
an
gers
Pipe hangers offered in this section are designed to support insulated or non-insulated pipe allowing for verticaladjustment and limited movement in the piping system.
MaterialsCarbon Steel, Malleable Iron and AISI Type 304 & 316 Stainless Steel are used in the manufacturing of pipehangers. Other materials are available.
FinishesThe standard finishes for mechanical supports are plain steel (oil coated) sometimes referred to as black,Electro-Galvanized Zinc (ASTM B633 SC3), Pre-Galvanized (ASTM A653 G90), Hot-Dip Galvanized After Fabrication(ASTM A123), Red Primer, Plastic Coating, DURA-GREEN™, DURA-COPPER™ and other special coatings areavailable upon request.
Note: Due to the design of some products, (threads, connecting hardware, swivels, etc.) items may or may notbe uniformly coated with special finishes i.e. Hot-Dip Galvanized, DURA-GREEN, DURA-COPPER, PVC etc. In somecases, the hanger itself may be coated, however, the hardware may be supplied Electro-Plated, DURA-COPPERPainted or Stainless Steel. Consult B-Line Systems for availability.
Approvals (as noted)Items in this section are Underwriters Laboratories Listed, Factory Mutual Approved, and comply with FederalSpecification WW-H-171E & A-A-1192A or Manufacturers Standardization Society ANSI/MSS SP-69 & SP-58.Seismic Restraints Catalog approved by the State of California Office of Statewide Health Planning and Development(OSHPD)
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Function: Used as a spacer at a seismic brace location tokeep clevis hanger from collapsing during seismic event.
Approvals: Included in our Seismic Restraints Catalogapproved by the State of California Office of StatewideHealth Planning and Development (OSHPD). For additionalload, spacing and placement information relating to OSHPDprojects, please refer to the Seismic Restraint SystemsGuidelines.
Installation Note: Fig. 1CBS fits easily over the cross boltand attaches by pinching tabs down.
Finish: Pre-Galvanized. Contact B-Line for alternativefinishes and materials.
Function: Recommended for the suspension of non-insulated pipe or insulated pipe with a B3151 shield.
Note: When an oversized clevis is used, a pipe spacer should be placed over the cross bolt to assure that thelower U-strap will not move in on the bolt. When attaching seismic bracing to the clevis hangers, a B3100PS(cross bolt spacer) must be installed. See Seismic Restraints Approval Guidelines.Order pipe sleeves Fig. 1CBS-(pipe size) separately.
Approvals: Included in our Seismic Restraints Catalog approved by the State of California Office of StatewideHealth Planning and Development (OSHPD). For additional load, spacing and placement information relating toOSHPD projects, please refer to the B-Line/TOLCO Seismic Restraint Systems Guidelines. Underwriter'sLaboratories Listed in the USA (UL) and Canada (cUL) for sizes 3/4” (20mm) thru 12" (300mm). Factory MutualEngineering Approved (FM) for 3/4” (20mm) thru 12” (300mm) pipe. Conforms to Federal Specification WW-H-171E &A-A-1192A, Type 1 and Manufacturers Standardization Society ANSI/MSS SP-69 & SP-58, Type 1. Also available toaccommodate rod schedule per per National Fire Protection Association (NFPA) Pamphlet 13.
Maximum Temperature: 650°F (343°C).
Standard Finish: Plain, Electro-Galvanized, DURA-GREEN™, or Hot-Dip Galvanizedalso available in Stainless Steel
Order By: Part number and finish.
For AWWA - Ductile Iron Clevis Hangers, see B3102, page 51.
** Note: Do not use the dimensions shown in the B3100 chart for NFPA hanger sizes.Contact B-Line for NFPA rod sizing on 1/2” (15mm) thru 12” (300mm) pipe.Part numbers will be 1NFPA-pipe size.
B3100 - Standard Clevis Hanger (TOLCO Fig.1)
*SLIDE-RITE™ Clevis Hanger design, as shown above, for sizes 2, 21/2, 3, 4, 5 & 6.
Component of State ofCalifornia OSHPD ApprovedSeismic Restraints System
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Pipe Hangers
50Pipe Hangers & Supports
Size Range: 4” (100mm) to 24” (600mm)
Material: Steel
Function: Recommended for the suspension offlanged or bell and spigot A.W.W.A. cast iron orductile iron pipe. The O.D. of the A.W.W.A. ironpipe is shown in the data table.
Approvals: Conforms to Federal SpecificationWW-H-171E & A-A-1192A, Type 1 andManufacturers Standardization Society ANSI/MSSSP-69 & SP-58, Type 1.
Standard Finish: Plain & Electro-Galvanized.Contact B-Line for alternative finishes andmaterials.
Order By: Part number and finish.
B3102 - A.W.W.A. Clevis Hanger (TOLCO Fig.1CI)
Pipe O.D. Rod Size B C D E F Design Load Approx. Wt./100Part No. in. (mm) A in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) Lbs. (kN) Lbs. (kg)
Function: Recommended for the suspension of insulatedpipe where the temperature does not require the use ofslides, guides, or rollers for movement.
Approvals: Conforms to Federal Specification WW-H-171E& A-A-1192A, Type 1 and Manufacturers StandardizationSociety ANSI/MSS SP-69 & SP-58, Type 1.
Maximum Temperature: 650°F (343°C).
Order By: Part number and finish. For service For Stainless Steel add SS to part number.
Standard Finish: Plain, Electro-Galvanized or Hot DipGalvanizedFor service temperatures of 750°F (399°C) thru1050°F (565°C) specify Type 304 Stainless Steel
B
D
C
E
A(Rod Size)
Hanger Rod NotIncluded
BBottom of pipe to top of hanger.
CCenter of pipe to top of hanger.
DRod Take-Out
Center of pipe to bottom ofhanger rod.
EMinimum thread length of
hanger rod.
FAdjustment
Top of cross bolt to bottom ofhanger rod nut inside the hanger.
HMaximum insulation thickness.
Pip
e H
an
gers
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Pipe Hangers
52Pipe Hangers & Supports
E Adjustment F Design Load Approx. Wt./100Part No. in. (mm) in. (mm) Lbs. (kN) Lbs. (kg)
Service: The B3100F is designed for the suspension ofcopper tube so as to prevent electrolysis between tubingand hanger. The B3100C is designed for steel or otherpipe types of the same O.D. Both B3100F and B3100Cact to reduce noise and vibration in pipe or tubingsystems.
Approvals: Underwriter's Laboratories Listed in the USA(UL) and Canada (cUL).
Maximum Temperature: 650°F (343°C).
Standard Finish: Plain, Electro-Galvanized, or Hot-DipGalvanized. Contact B-Line for alternative finishes andmaterials.
Order By: Part number and finish.
B3100C - Standard Clevis Hanger - Plastic Coated (TOLCO Fig.1PVC)B3100F - Standard Clevis Hanger - Felt Lined for Copper Tubing (TOLCO Fig.1F)
Pipe Size Rod Size B C DPart No. in. (mm) A in. (mm) in. (mm) in. (mm)
Top of cross bolt to bottom of hangerrod nut inside the hanger.
B3100C
B3100F
Pip
e H
an
gers
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Pipe Hangers
Pipe Hangers & Supports53
Pip
e H
an
gers
Size Range: 1/2” (15mm) to 10” (250mm) pipe size
Material: Steel
Function: Recommended for the suspension of non-insulated pipe, or insulated pipe with B3151 shield.Side hole allows for wall mounting.B3690F and B3690C are designed to reduce noise andvibration and/or prevent electrolysis between pipe andhanger.
Approvals: Conforms Manufacturers StandardizationSociety ANSI/MSS SP-69 & SP-58, Type 5.
Standard Finish: Electro-Plated. Contact B-Linefor alternative finishes and materials.
Order By: Part number and finish.
B3690 - J-Hanger for Pipe or Conduit (TOLCO Fig. 3)B3690F - Felt Lined J-Hanger for Copper Tubing (TOLCO Fig. 3F)B3690C - PVC Coated J-Hanger for Pipe or Conduit (TOLCO Fig. 3PVC)
BF
DDia.
C
E
A(Rod Size)
Hanger Rod NotIncluded
BCenter of pipe to top of hanger.
FRod Take-Out
Center of pipe to bottom ofhanger rod.
B3690F B3690C
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Pipe Hangers
54Pipe Hangers & Supports
Pipe O.D. Rod Size B C D E F Design Load Approx. Wt./100Part No. in. (mm) A in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) Lbs. (kN) Lbs. (kg)
Pipe Size Rod Size B CPart No. in. (mm) A in. (mm) in. (mm)
B3106-2 1/2" to 2" (15 to 50) 3/8"-16 515/16" (150.8) 41/16" (103.2)
B3106-4 21/2" to 4" (65 to 100) 1/2"-13 93/8" (238.1) 6" (152.4)
Size Range: 1/2” (15mm) to 4” (100mm) pipe
Material: Steel
Function: Recommended for the suspension offlexible plastic pipe. Use with B3106V supporttrough for plastic pipe.
Approvals: Complies with ManufacturersStandardization Society ANSI/MSS SP-69 & SP-58Type 1.
Standard Finish: Plain & Electro-Galvanized.Contact B-Line for alternative finishes and materials.
Order By: Part number and finish.
B
DC
A(Rod Size)
Hanger Rod NotIncluded
BOverall Height
CCenter of pipe to top of hanger.
DRod Take-Out
Center of pipe to bottom of hanger rod.
EMinimum thread length of hanger rod.
B3106V - Plastic Pipe Support Channel (TOLCO Fig. 1VT)
MaximumFor Nominal Steel Size Hanger Design Approx.Pipe Sizes T x L B Spacing Load Wt./100
Part No. in. (mm) in. (mm) in. (mm) Ft. (M) Lbs. (kN) Lbs. (kg)
B3106V-2 1/2" to 2" (15 to 50) 18 Ga. x 96" (1.2 x 2438.4) 19/16" (39.7) 8 (2.44) 150 (.67) 449 (203.6)
B3106V-4 21/2" to 4" (65 to 100) 18 Ga. x 120" (1.2 x 3048.0) 31/8" (79.4) 10 (3.05) 150 (.67) 1123 (509.4)
Size Range: 1/2” (15mm) to 4” (100mm) pipe
Material: Steel
Function: Designed for use with B3106 as asupport for plastic or other flexible pipe systems.
Standard Finish: Pre-Galvanized. ContactB-Line for alternative finishes andmaterials.
Order By: Part number and finish.
B
T x LSteel Size
Pip
e H
an
gers
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Pipe Hangers
56Pipe Hangers & Supports
Size Range: 1/2” (15mm) to 4” (100mm) pipe
Material: Steel
Function: Recommended for the suspension of lightstationary pipe allowing for vertical adjustment.
Approvals: Underwriter's Laboratories Listed in the USA (UL)and Canada (cUL) for sizes 3/4” (20mm) thru 4” (100mm).Conforms to Federal Specification WW-H-171E & A-A-1192A,Type 12 and Manufacturers Standardization SocietyANSI/MSS SP-69 & SP-58, Type 1.
Standard Finish: Plain, Electro-Galvanized,or DURA-GREEN™
*Slide-Rite™ Clevis Hangerdesign for sizes 2, 3 & 4.
Pat. No. 5,848,7705,924,655
Pip
e H
an
gers
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Pipe Hangers
Pipe Hangers & Supports57
Size Range: 1/2” (15mm) to 6” (150mm) copper tubing
Material: Steel
Function: Recommended for the suspension ofnon- insulated stationary copper tubing lines.Available with plastic coating to provide additionalseparation between tubing and hanger.
Approvals: Conforms to Federal SpecificationWW-H-171E & A-A-1192A, Type 12 andManufacturers Standardization SocietyANSI/MSS SP-69 & SP-58, Type 1.
Standard Finish: DURA-COPPER™
Order By: Part number and finish.
B3104CTB3104CTC
A(Rod Size)
Hanger Rod NotIncluded
B
D C
E
BBottom of pipe to top of hanger.
CCenter of pipe to top of hanger.
DRod Take-Out
Center of pipe to bottomof hanger rod.
EMinimum thread length
of hanger rod.
FAdjustment
Top of cross bolt to bottom ofhanger rod nut inside the hanger.
Tubing Size Rod Size B C Rod Take-Out DPart No. in. (mm) A in. (mm) in. (mm) in. (mm)
Function: Recommended for the suspension of non-insulated pipe or insulated pipe with B3151 shield.Fig. 2NFPA accomodates the reduced rod schedule ofthe National Fire Pretection Association Pamphlet 13.
Approvals: Factory Mutual Engineering Approved.Underwriters Laboratories Listed. Conforms to FederalSpecification WW-H-171E & A-A-1192A Type 10 andManufacturers Standardization Society ANSI/MSSSP-69 & SP-58, Type 10.
Standard Finish: Pre-Galvanized
Note: Available in Stainless Steel material.
Order By: Part number and finish.
Nominal Pipe Size Rod Size B C D Max. Rec. Load Approx Wt./100Part No. in. (mm) A in. (mm) in. (mm) in. (mm) lbs. (kN) lbs. (kg)
Function: Recommended for the suspension ofcopper tubing, allowing for vertical adjustment.(Available with plastic coating to provide additionalseparation between tubing and hanger.)
Approvals: Conforms to Federal SpecificationWW-H-171E & A-A-1192A, Type 10 and ManufacturersStandardization Society ANSI/MSS SP-69 & SP-58,Type 10.
Standard Finish: DURA-COPPER™
Order By: Part number and finish.
C
D
B
Nominal Rod Size B C DPart No. Pipe Size A in. (mm) in. (mm) in. (mm)
Material: Steel, Pre-Galvanized to G90 specifications
Function: For fire sprinkler and other general piping purposes. Knurledswivel nut design permits hanger adjustment after installation.
Features:• (1/2” (15mm) thru 2” (50mm)) Flared edges ease installation for all pipetypes and protect CPVC plastic pipe from abrasion. Captured design keeps adjusting nut from separating with hanger. Hanger is easilyinstalled around pipe.
• (21/2” (65mm) thru 8” (200mm)) Spring tension on nut holds it securely inhanger before installation. Adjusting nut is easily removed.
Approvals: Underwriters Laboratories listed (1/2” (15mm) thru 8” (200mm))in the USA (UL) and Canada (cUL) for steel and CPVC plastic pipe andFactory Mutual Engineering Approved (3/4” (20mm) thru 8” (200mm)).Conforms to Federal Specifications WW-H-171E & A-A-1192A, Type 10and Manufacturers Standardization Society ANSI/MSS SP-69 & SP-58,Type 10.
Maximum Temperature: 650°F (343°C)
Finish: Pre-Galvanized. Stainless Steelmaterials will be supplied with (2) hex nutsin place of a knurl nut.
Order By: Part number and pipe size
** Note: For metric hanger rod sizes add themetric rod size to the figure number.Example: 200M8-11/2 or 200M10-11/2
A
B
Fig. 200-1/2 to 200-2 Fig. 200-21/2 to 200-8
Pipe Size Rod Size A B Max. Rec. Load Approx. Wt./100Part No. in. (mm) in. mm** in. (mm) in. (mm) lbs. (kN) lbs. (kg)
Function: Designed primarily to support substantially heavier loadsthan is normally intended for the nominal hanger size. Usedextensively to support trapeze installations and the increased loadsfrom both above and below the trapeze assembly.
Features: Furnished with 3/8"-16 or 1/2"-13 adjusting threaded ring nut.
Approvals: Underwriters Laboratories listed in the USA (UL) andCanada** (cUL). Conforms to Federal Specification WW-H-171E &A-A-1192A, Type 10 and Manufacturers Standardization SocietyANSI/MSS SP-69 & SP-58, Type 10.
Maximum Temperature: 650°F (343°C)
Finish: Pre-Galvanized
Order By: Part number, pipe size and rod size.
Important Design Note. Because of the increased loads applied to thetrapeze assembly, both the upper trapeze supports as well as the lowerhanging unit must be able to hold the maximum loads intended.
A
B
Pipe Size Rod Size A B Max. Rec. Load Approx. Wt./100Part No. in. (mm) in. (mm) in. (mm) lbs. (kN) lbs. (kg)
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Pipe Hangers
66Pipe Hangers & Supports
Pip
e H
an
gers
Fig. 120RWA - (Model B) Retrofit Wrap Around “U” Hanger Clamp
Size Range: 1" (25mm) thru 6" (150mm) pipe
Material: Steel
Function: Designed to restrain movement of the pipe within standardU-hangers as required by NFPA 13. Where retrofit capability is crucial, theFig. 120RWA is a labor efficient alternative to the standard Cooper B-LineFig. 120W wrap around U-hanger.
Features Installs easily by tightening two hex nuts. Features a uniquebracing slot that locks onto a standard U-hanger to become a solid unit thatwill stabilize the pipe during seismic activity or sprinkler head activation.Designed to be used in retrofit or new construction applications. Will clampto existing U-Hangers without restriction to leg angle.
Approvals: Underwriters Laboratories listed in the USA (UL) and Canada(cUL) as a restrainer. Included in our Seismic Restraints Catalog approvedby the State of California Office of Statewide Health Planning andDevelopment (OSHPD). For additional load, spacing and placementinformation relating to OSHPD projects, please refer to the Cooper B-LineSeismic Restraint Systems Guidelines. NFPA 13 (2010) 9.3.6.3.
Finish: Plain and Galvanized. Contact B-Line for alternative finishes andmaterials.
Order By: Part number, type numbers and pipe size
Ordering Note: Order by the following type and pipe size:Type 1 — (1" (25mm) and 11/4" (32mm) pipe size)Type 2 — (11/2" (40mm) and 2" (50mm) pipe size)Type 3 — (21/2" (65mm) and 3" (80mm) pipe size)Type 4 — (4" (100mm) pipe size)Type 6 — (5" (125mm) and 6" (150mm) pipe size)
Important Note: The bracing slot feature is sized to fit the U-Hanger rodschedule as required by NFPA 13 as follows:5/16" (7.9mm) rod for up to 2" (50mm) pipe3/8" (9.5mm) rod for 21/2" (65mm) - 6" (160mm) pipeFor other rod size requirements consult factory.
Component of State ofCalifornia OSHPD ApprovedSeismic Restraints System
Type Pipe SizePart No. in. (mm)
120RWA-TYPE1-1 1 1" (20)
120RWA-TYPE1-11/4 1 11/4" (25)
120RWA-TYPE2-11/2 2 11/2" (40)
120RWA-TYPE2-2 2 2" (50)
120RWA-TYPE3-21/2 3 21/2" (65)
120RWA-TYPE3-3 3 3" (80)
120RWA-TYPE4-31/2 4 31/2" (90)
120RWA-TYPE4-4 4 4" (100)
120RWA-TYPE6-5 6 5" (125)
120RWA-TYPE6-6 6 6" (150)
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Pipe Hangers
Pipe Hangers & Supports67
Pip
e H
an
gers
Fig. 120 - “U” Hanger
Size Range: Size 3/4" (20mm) thru 8" (200mm) pipe
Material: Steel
Function: Used to support piping from wood beamswhere no contraction is expected. Used extensively inautomatic fire sprinkler systems.
Approvals: Meets or exceeds the requirements ofNationalFire Protection Association (NFPA), Pamphlet 13. Includedin our Seismic Restraints Catalog approved by the State ofCalifornia Office of Statewide Health Planning andDevelopment (OSHPD). For additional load, spacing andplacement information relating to OSHPD projects, pleaserefer to the Seismic Restraint Systems Guidelines.
Maximum Temperature: 750°F (399°C)
Finish: Plain. Contact B-Line for alternative finishes andmaterials.
Order By: Part number, pipe size, length and finish
Length(Specify)
A
Pipe Size A Fastener Size Max. Rec. Load***Part No. in. (mm) in. (mm) lbs. (kN)
120-3/4 3/4" (20) 5/16" (7.9) 16 x 2* 250 (1.11)
120-1 1" (25) 5/16" (7.9) 16 x 2* 250 (1.11)
120-11/4 11/4" (32) 5/16" (7.9) 16 x 2* 250 (1.11)
120-11/2 11/2" (40) 5/16" (7.9) 16 x 2* 250 (1.11)
120-2 2" (50) 5/16" (7.9) 16 x 2* 250 (1.11)
120-21/2 21/2" (65) 3/8" (9.5) 3/8 x 21/2** 320 (1.42)
120-3 3" (80) 3/8" (9.5) 3/8 x 21/2** 320 (1.42)
120-31/2 31/2" (90) 3/8" (9.5) 3/8 x 21/2** 560 (2.49)
120-4 4" (100) 3/8" (9.5) 1/2 x 3** 560 (2.49)
120-5 5" (125) 1/2" (12.7) 1/2 x 3** 560 (2.49)
120-6 6" (150) 1/2" (12.7) 1/2 x 3** 760 (3.38)
120-8 8" (200) 1/2" (12.7) 5/8 x 3** -- (--)
* Drive Screw** Lag Bolt*** With minimum safety factor of 5
Fastener schedule per NFPA
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Pipe Hangers
68Pipe Hangers & Supports
Pip
e H
an
gers
Fig. 120MJ - Mutt & Jeff “U” Hanger
Size Range: Size 3/4" (20mm) thru 8" (200mm) pipe
Material: Steel
Function: Used to support piping from wood beams wherenocontraction is expected. Used extensively in automatic firesprinkler systems. Fig. 120MJ is used when the wood beam ison a diagonal.
Finish: Plain. Contact B-Line for alternative finishes andmaterials.
Order By: Part number, side length and finish
A
Pipe Size A Fastener Size Max. Rec. Load***Part No. in. (mm) in. (mm) lbs. (kN)
120MJ-3/4 3/4" (20) 5/16" (7.9) 16 x 2* 250 (1.11)
120MJ-1 1" (25) 5/16" (7.9) 16 x 2* 250 (1.11)
120MJ-11/4 11/4" (32) 5/16" (7.9) 16 x 2* 250 (1.11)
120MJ-11/2 11/2" (40) 5/16" (7.9) 16 x 2* 250 (1.11)
120MJ-2 2" (50) 5/16" (7.9) 16 x 2* 250 (1.11)
120MJ-21/2 21/2" (65) 3/8" (9.5) 3/8 x 21/2** 320 (1.42)
120MJ-3 3" (80) 3/8" (9.5) 3/8 x 21/2** 320 (1.42)
120MJ-31/2 31/2" (90) 3/8" (9.5) 3/8 x 21/2** 560 (2.49)
120MJ-4 4" (100) 3/8" (9.5) 1/2 x 3** 560 (2.49)
120MJ-5 5" (125) 1/2" (12.7) 1/2 x 3** 560 (2.49)
120MJ-6 6" (150) 1/2" (12.7) 1/2 x 3** 760 (3.38)
120MJ-8 8" (200) 1/2" (12.7) 5/8 x 3** -- (--)
Pipe Size A Fastener Size Max. Rec. Load***Part No. in. (mm) in. (mm) lbs. (kN)
120W-3/4 3/4" (20) 5/16" (7.9) 16 x 2* 250 (1.11)
120W-1 1" (25) 5/16" (7.9) 16 x 2* 250 (1.11)
120W-11/4 11/4" (32) 5/16" (7.9) 16 x 2* 250 (1.11)
120W-11/2 11/2" (40) 5/16" (7.9) 16 x 2* 250 (1.11)
120W-2 2" (50) 5/16" (7.9) 16 x 2* 250 (1.11)
* Drive Screw** Lag Bolt*** With minimum safety factor of 5
Fastener schedule per NFPA
* Drive Screw*** With minimum safety factor of 5
Fastener schedule per NFPA
Fig. 120W - Wrap Around “U” Hanger
Size Range: Size 3/4" (20mm) thru 2" (50mm) pipe
Material: Steel
Function: Required for automatic fire protection agencies tobe used on the end of branch lines to prevent pipe fromwhipping vertical and striking ceiling or beam.
Finish: Plain. Contact B-Line for alternative finishes andmaterials.
Order By: Part number, side length and finish
Length(Specify)
Length(Specify)
A
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Pipe Hangers
Pipe Hangers & Supports69
Pip
e H
an
gers
Rod Size Range: 3/8”-16 to 3/4”-10
Material: Steel
Service: Designed for use with a light piping system wherevertical movement does not exceed 11/4" (31.7).
Approvals: Conforms to Federal Specification WW-H-171E& A-A-1192A, Type 49 and Manufacturers StandardizationSociety ANSI/MSS SP-69 & SP-58, Type 48.
Order By: Part number.
B3262 Light Duty Spring Hanger
B
C
D
A(Rod Size)
A(Rod Size)
Spring Deflection Rated Load Approx. Wt./100Part No. In (mm) Lbs. (kN) Lbs. (kg)