Top Banner
UL Specifications Bronze Perma-Socket Bonding Lug REVISION 07/2013 Perma-Cast Co. Pueblo, CO www.permacastonline.com Call 719-544-9544 Bronze Perma-Socket Bonding Lug Meets UL Specifications Perma-Cast Bronze Sockets conforms to UL Specifications for grounding and Bonding Equipment UL 467 and UL 486A (Wire Connectors and Soldering lugs for Use with Copper Conductors). Lab Test were conducted by Underwriters Laboratories, Santa Clara, California. The test program included test for secureness, pull out, and Bonding Milli-Volt Drop Test Results Secureness Test: As specifies in UL 486B, Sec. 11. Test results:No Conductors seperated from the terminals. All samples passed. Pullout Test: As specified in UL 486A, Section 13. Test results: No Conductors seperated from the terminals. All samples passed. Milli-Volt Drop Test: As Specified in UL 676 Section 34. Test results: maximum allowable resistance, 0.1Ohm. Test range .0003 Ohms to .0013 Ohms. All samples Passed.
1

Perma-Cast Swimming Pool Products - UL Specifications Bronze … · 2019. 6. 10. · Perma-Cast Bronze Sockets conforms to UL Specifications for grounding and Bonding Equipment UL

Aug 31, 2020

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Perma-Cast Swimming Pool Products - UL Specifications Bronze … · 2019. 6. 10. · Perma-Cast Bronze Sockets conforms to UL Specifications for grounding and Bonding Equipment UL

UL SpecificationsBronze Perma-Socket

Bonding Lug

REVISION 07/2013

Perma-Cast Co. Pueblo, CO www.permacastonline.com

Call 719-544-9544

Bronze Perma-Socket Bonding LugMeets UL Specifications

Perma-Cast Bronze Sockets conforms to UL Specifications for grounding and Bonding Equipment UL 467 and UL 486A (Wire Connectors and Soldering lugs for Use with Copper Conductors).

Lab Test were conducted by Underwriters Laboratories, Santa Clara, California. The test program included test for secureness, pull out, and Bonding Milli-Volt Drop

Test ResultsSecureness Test: As specifies in UL 486B, Sec. 11. Test results:No Conductors seperated from the terminals. All samples passed.

Pullout Test: As specified in UL 486A, Section 13. Test results: No Conductors seperated from the terminals. All samples passed.

Milli-Volt Drop Test: As Specified in UL 676 Section 34. Test results: maximum allowable resistance, 0.1Ohm. Test range .0003 Ohms to .0013 Ohms. All samples Passed.