Top Banner

of 15

Perhitungan Npsh Available

Oct 30, 2015

Download

Documents

npsh
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript

PowerPoint Presentation

PERHITUNGAN NPSH AVAILABLESUCTION LINE PIPING ISOMETRICPEMILIHAN MAIN PUMPEBARA 80-250/55DEBIT VOLUMETRIKQ=120 m3/h Head total = 87 m

ARTI KODE POMPA EBARA 80-250/55 80 Discharge Size250 Impeller Code55 Motor Output kW

ANALISA PERHITUNGAN NPSH availablePARAMETER YANG DIKETAHUIHead atm ( Ha ) : 30 mVolume tanki atmosferik ( V ) : 30 m3Diameter tanki atmosferik ( d ): 2,5 mDebit volumetrik ( Q ) : 120 m3/hHead total ( H ) : 87 mKoefisien kehalusan ( C ) : 120Head inlet ( Hi ) : 2 feet ( safety factor ) Diameter pipa ( D ) : 4 inchiSuhu air : 20o CHEAD STATIC

400 mmmm600 mmhFRICTION HEADFRICTION HEAD (Cont..)Panjang Pipa ( L ) yaitu diambil panjang dari pompa ke tanki. Dari gambar instalasi pemipaan fire fighting ( terlampir ), didapat :L1 : Pompa T111 = 7,210 mL2 : Pompa T112 = 12,805 m Dipakai yang terjauhDebit ( Q ) diketahui = 120 m3/h = 0,03333 m3/sNilai Coefisien Kehalusan Pipa untuk baja telah diketahui = 120. Jika tidak di ketahui di pakai Tabel Koefisien Hazen Williams.Diameter Pipa ( D ) diketahui = 4 inchi = 0,1 m

FRICTION HEAD (Cont..)Tabel Koefisien Hazen Williams

FRICTION HEAD (Cont..)INLET HEADInlet Head ( Hi ) diketahui sesuai safety factor yaitu : 2 feet = 0,6069 m

VAPOR HEAD

NPSH available