NO BEBAN PERHITUNGAN TOTAL1 Plat 120 mm = 340 m2 x 0,12m x 2400 kg/m3 = 97920 Kg
2Balok Anak 250 x 350 =
( 2,5 m x 0,25m x 0,35m x 2400 kg/m3) + ( 6 m x 0,25m x 0,35m x 2400 kg/m3) = 1575 Kg
3Balok Induk 250 x 450 = 38 x ( 5 m x 0,25m x 0,45m x 2400 kg/m3) = 51300 Kg
4 Kolom 600 x 600 = 24 x (0,6m x 0,6m x 4 m x 2400 kg/m3) = 82944 Kg5 Spesi + Keramik = (21 kg/m2/cm x3cm +24 kg/m2/cm x0,7cm) x 340 m² = 27132 Kg6 Plafon Penggantung = (11 kg/m2 + 7 kg/m2) x 340 m2 = 6120 Kg
7 Ducting = 25kg/m2 x 340 m2 = 8500 Kg8 Bata tebal 15 cm = 80 m x 4 m x 250 kg/m² = 80000 Kg
9 Tangga (623,277 kg/m2 x 3,6 m x 1 m) + (375 kg/m x 1,95 m x 1 m) = 2975,047 Kg
Beban Mati WD 358466.047 Kg
2 Beban Hidup plat = 250 kg/m2 x 340 m2 = 85000 Kg 3 Tangga = (300 kg/m x 3 m x 1 m) + (300 kg/m x 1,95 x 1) = 1485 Kg
Beban Hidup WL 86485 Kg WD + 0,5WL 401708.547 Kg
FAKULTAS TEKNIK SIPIL DANPERENCANAAN
UNIVERSITAS KRISTEN PETRA
TUGAS STRUKTUR BETON Halaman: 43
BAGIAN STRUKTUR: NO. GAMBAR:
GEMPANRP: 21410170
21411161
PERHITUNGAN
NO BEBAN PERHITUNGAN TOTAL1 Plat 100 mm = 340 m2 x 0,1m x 2400 kg/m3 = 97920 Kg
2 Balok Anak 250 x 350 =( 2,5 m x 0,25m x 0,35m x 2400 kg/m3) + ( 5 m x 0,25m x 0,35m x 2400 kg/m3) = 1575 Kg
3Balok Induk 250 x 450 = 38 x ( 5 m x 0,25m x 0,45m x 2400 kg/m3) = 51300 Kg
4 Kolom 600x600 = 24 x (0,6m x 0,6m x 4 m x 2400 kg/m3)/2 = 41472 Kg5 Spesi = (21 kg/m2/cm x3cm) x 340 m² = 21420 Kg6 Plafon Penggantung = (11 kg/m2 + 7 kg/m2) x 340 m2 = 6120 Kg
7 Ducting = 25kg/m2 x 340 m2 = 8500 Kg8 Finishing waterproof = 50 kg/m2 x 340 m2 = 17000 Kg
Beban Mati WD 245307 Kg
1 Beban Hidup plat = 100 kg/m2 x 340 m2 = 34000 KgBeban Hidup WL 34000 Kg
WD + 0,5WL 262307 Kg
Jadi Berat Total Bangunan:
401708.547x 4 + 263207 = 1468332.641 kg 14683.32 KN
9. Menentukan Aspect Ratio Dari Bangunan
Dalam arah-x : H/Bx = 20 / 18 = 1.11 < 3 (OK)
Dalam arah-y : H/By = 20 / 29 = 0,69 < 3 (OK)
Berarti untuk kedua arah tidak ada beban sebesar 0,1V pada lantai atapnya