Top Banner
LOGO “ Add your company slogan DUCTING DESIGN
30

Perancangan Ducting

Nov 16, 2015

Download

Documents

Arga Benny

Perancangan Instalasi Ducting Dalam Gedung
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • EQUAL FRICTION METHOD EXAMPLEDuct system for general office ;

    Total air quantity5400 cfm18 air terminals300 cfm eachOperating pressure for all terminals-0.15 in.wgRadius elbowsR/D = 1.25

    Find ;Initial duct velocity, area, size and friction rate in the ductTotal equivalent length of duct run, with highest resistance Total static pressure required at Fan discharge

  • DUCT LAYOUT

  • SELECT AN INITIAL VELOCITYRECOMMENDED MAX DUCT VELOCITIES FOR LOW VELOCITY SYSTEMS

  • Velocity dipilih 1700 fpm

  • Duct area : 5400 cfm/1700 fpm = 3.18 sq.ft

  • Duct size (TABLE 6)

  • Duct size : 22 in x 22 in

  • Circular equiv. diameter

  • Initial friction rate

  • Friction rate ; 0.145 in wg per 100 ft of eauivalent length

  • Percent section area in branches

  • Percent of cfm = air quantity in duct section/ total air quantity

  • It appears that the duct run from the Fan to terminal 18 has the highest resistance

  • Friction of rectangular Elbow

  • The total friction loss in the ductwork frfom the Fan to terminal 18 :

    Loss= total equiv length x friction rate

    = 229 ft x (0.145/100 ft) = 0.332 in. wg

  • Total pressure at Fan DischargeThe sum of the terminal operating pressure and the loss in the ductwork

    0.332 in. wg + 0.15 in.wg = 0.482 in.wg

  • Friction losses