Presenters

Bernd Schuessler Gary Tapperson

Page 3: Pepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentation

Introduction

Trunk to spur coupling solutions using the new Fieldbus

H1 card with integrated power

Agenda

New integrated Fieldbus power supply

High Power Trunk: One concept for all applications

Segment Protectors in general purpose and Class I,

Div.2/Zone 2 areas

FieldBarriers in Class I, Div.1/Zone 1/0 areas

Summary

Page 4: Pepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentation

Preferred Partner Solutions

... Emerson considers Pepperl+Fuchs a "preferred

partner" for Foundation Fieldbus projects.

Emerson prefers to use technologies from P+F,

whether internal to Emerson products or as

integrated stand-alone P+F products.

Page 5: Pepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentation

Trunk to Spur Coupling with Internal Ff Power

Control Room Field

Internal Ff power

(this product is a combined

Emerson P+F solution)

P+F Ff

Segment Protectors

P+F Ff

FieldBarriers

SE4017P0/37P0

Safe or Class I, Div.2 Area

Class I, Div.1

Page 6: Pepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentation

Trunk to Spur Coupling with External Ff Power

OPTION 2: Offer external power and the P+F stand-alone Ff ADM module Control Room Field

Optional P+F Ff ADM (Advanced Diagnostics Module)

24V Bulk

Power

Emerson DeltaV SE4017P0/37P0 with

external Pepperl+Fuchs Ff Power Supplies

P+F Ff

Power

Supplies

Safe or Class I, Div.2 Area

Page 7: Pepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentation

High Power TrunkOne Concept - All applications

Zone 1Zone 2/

Div.2Div.1

Zone 2/

Div.2

General Purpose

NI and IS protection is done in the field

-Segment Protectors

-FieldBarrier

-Distributed architecture

Reliable Fieldbus Power:

-2 powered FF segments

-Simplex or redundant

-Ext. Advanced P.L. Diagnostics optional

-Robust communication

High Power Trunk:

-Up to 30V/400 mA

-Longer cable runs

-Max. number of instruments

per segment - even for IS

Page 8: Pepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentation

High Power Trunk (HPT) vs FISCO

HPT enables utilization of same DCS and FF segment architecture for both general purpose and I.S. applications

Over 25,000 FieldBarriers installed in the field

HPT eliminates the short-comings of FISCO (Fieldbus Intrinsically Safe COncept)

– High system installation cost

– Reduced FF cable length (1000m max)

– Potentially increased number of DCS H1 interfaces

– Large cabinet space requirements for DCS H1 interfaces, wiring, and FF FISCO power

– Limited power => reduced number of field devices on a segment

HPT supports FF segment power conditioner redundancy, providing load sharing and not requiring “switch-over”

Smaller size in the control room:

– ½ the footprint of a simplex FISCO

– ¼ the footprint of redundant FISCO

Page 9: Pepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentation

Field Equipment

Pepperl+Fuchs Trunk to Spur Couplers

– Segment Protectors for Field Devices on Spurs

in General Purpose Environments or Spurs in

some specific Hazardous Environments

(Zone 2 / Div 2)

– FieldBarriers for Field Devices on Spurs in

Hazardous Environments

(Zone 1/0 or Div 1)

Page 10: Pepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentation

High Power Trunk in General Purpose and Class I, Div.2/Zone 2 Area

Internal FF power

(this product is a combined

Emerson P+F solution)

Control Room

Page 11: Pepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentation

Short circuit protected spurs (<58mA)

Over voltage protection

Trunk in/out T-connector

LED’s for power, com., short

Nonincendive spurs =>

live maintenance in Div.2!

4,6,8,10 and 12 spur versions

For general purpose and Class I, Div.2 appl.

Built in, selectable terminator

DIN-rail mountable

P+F offers a variety of different

field junction box enclosure styles and materials

Complies with Foundation FF- 846 Device Coupler Spec.

Segment Protectors

Page 12: Pepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentation

Reliable Operation

Replace or add field devices

during normal operation

Plug-in terminals with

retaining screws

LED’s indicate status

Test points at trunk and spurs

One pre-commissioned, high

available Fieldbus terminator

- Redundant layout

- EMC Class A compliant

Page 13: Pepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentation

High Power Trunk in Class I, Div.1/Zone 1/0

Internal FF power

(this product is a combined

Emerson P+F solution)

Class I, Div.2 or Zone1

Class I, Div.1/Zone 1/0

Page 14: Pepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentation

FieldBarrier for Intrinsic Safety

4 short circuit protected, current limited IS outputs

Same control room design for IS and non-IS

Connects 4 IS (Entity or FISCO) field devices

Up to 12 devices/segment (3 FieldBarriers)

Galvanic isolation between non-IS trunk and IS

spurs

40 mA per spur (typically 1 device)

120 m (393 ft) max. spur length

Built-in selectable terminator

Div.2/Zone 1 mountable

DIN rail/cabinet mountable version

Custom enclosures

Page 15: Pepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentation

OPTION 2: Offer external power and the P+F stand-alone Ff ADM module

Control Room Field Safe or Class I, Div.2 Area

Y-Purge with FieldBarrier

*FieldBarrier in Y-

Purge enclosure

General purpose

wiring

Fieldbus Trunk in

conduit with poured

seals

Intrinsically safe

Instruments (live

work permitted)

*FieldBarrier offers non-IS

trunk connections and

intrinsically safe spurs

Class I, Div.1 Area

Page 16: Pepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentation

OPTION 2: Offer external power and the P+F stand-alone Ff ADM module

Control Room Field Safe or Class I, Div.2 Area

Class I, Div.1 Area

Explosion Proof/Flame Proof Installation

FieldBarriers in Explosion

Proof enclosure

Intrinsically Safe

Spurs

Fieldbus Trunk in conduit

with poured seals

Intrinsically safe

Instruments (live

work permitted)

Page 17: Pepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentation

Business Results Achieved

Fieldbus Trunk to Spur Coupling

Reduces project risk during start up and operation

Increases plant uptime

Reduces installation cost when used together with High Power Trunk in hazardous locations

Page 18: Pepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentation

Summary

Trunk to spur coupling solutions like segment

protectors and FieldBarriers are critical to assure a

reliable, error free fieldbus installation

They protect the entire network from a single short

In combination with a High Power Trunk approach,

they can bring the same benefits from using FF in

safe areas to hazardous locations

Page 19: Pepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentation

Where To Get More Information

White papers and additional information on Trunk to spur

coupling and other P+F solutions:

www.pepperl-fuchs.us

Question about this presentation, feel fee to contact:

Bernd Schuessler

Gary Tapperson

[email protected]

[email protected]