ED-UAY-201401A
PathfinderAir-Cooled Single-Screw Chiller/Heat PumpSuper-high-efficiency series Model: UAY105-UAY348
Air-cooled water chiller/hot water units are the central air conditioning units with air as the cold (hot) source, and water as the heat transfer medium. The units need no additional equipment room, cooling tower, cooling pump, or cooling pipe and can be mounted on the building roof and outdoors. The heat pump units can provide heat as a hot water boiler. This series of units are applicable to various environments, such as hospitals, hotels, factories, and office buildings.As the first designer and manufacturer of large air-cooled heat pump units, DAIKIN has been committed to technical improvement and innovation and leads the development of the air-cooled heat pump technology. For the consideration of environment protection and energy saving, DAIKIN applies the advanced technology to the latest ultra-efficient air-cooled heat pump units. By using the R134a environment-friendly refrigerant, this series of units have a full-load COP of over 3.2. This value is higher than the energy saving product certification standard, which makes them one of the most efficient, energy-saving, and quiet environmental-friendly air conditioning units. Moreover, DAIKIN has built a large 1600 kW full performance lab to ensure the quality and performance of the units.
9601019
ISO9001:2008 ISO14001:2004 BS-OHSAS18001: 2007
EMS 80362 7644Test
CNAS L0778
Quality Management System Certification
Environment Management System Certification
Occupational Health and Safety Assessment Series
Certification
Certification of China National Accreditation Service for
Conformity Assessment (CNAS)
Obtained China National Industrial
Product Manufacture License
Specification
UAY 105 ST F AA E3 -
AA: Super-high-efficiency seriesBA: High-efficiency series
Literature No.: ED-UAY-201401A Supersedes: ED-UAY-201311A
DAIKIN Air-Cooled Screw Chiller/Heat Pump
3
■ DAIKIN adopts the latest R134a efficient single-screw compressor to greatly improve the efficiency.
■ New design of four-way valve lowers the pressure drop. Over-compress technology significantly improves the four-way valve reliability. This design avoids short circuit. In this way, units’ efficiency and stability is much better.
■ The new economizer design increases the unit sub-cooling, greatly promotes the unit’s cooling capacity and EER. Unit full load EER is up to 3.2, and higher EER under part load.
■ New high efficiency counter-flow shell & tube dry-expansion single pass evaporator (one or two internal independent refrigerant circuits)
■ The most advanced efficient single-screw compressor is adopted. The compressor can perform stepless adjustment within the range of 10% to 100% workload at maximum. Compared with the traditional compressors, this compressor has wider adjustment range and higher efficiency.
■ The temperature of outlet water is stable. The output ability meets the workload demand of the construction system. The units can regulate the output based on the actual workload and maintains high efficiency when running at partial workload. In addition, the accurate adjustment of the energy and water temperature brings more comfortable experience to customers.
Coo
ling
load
(%)
Coo
ling
load
(%)
Tem
pera
ture
of o
utle
t ch
illed
wat
er (º
C)
Tem
pera
ture
of o
utle
t ch
illed
wat
er (º
C)
Required load
Stepped energy adjustment
Time
Compressor load
Stepless energy adjustment
Time
■ No Chlorine No ODP Good Efficiency
■ New very high efficiency (full and part load) DAIKIN Single Screw compressor. (technology by DAIKIN)
Through meshing between metal and nonmetal, it eliminates the high frequency noise. And with fewer moving parts and rotor load balance, it decreases most vibrations. With a shock absorber, noise and vibrations are lowered further.
■ Integrated design and compact structure are adopted for the units. The base can balance the entire unit weight. The spring-damper on the units helps to eliminate the operation sound and vibration.
■ New high efficiency condenser fans (technology by DAIKIN)
Condenser using high efficiency, low noise resin spiral fan motor, direct drive, 3dB(A) noise lower compared with spiral blades.
■ Flexible installation without additional equipment room, cooling tower, or cooling pump.
■ The electric system of the units is integrated with the master unit, so an additional electric control cabinet is not required.
■ An intelligent control system monitors and controls the operating status of the units and indicates the fault cause for the convenience of maintenance.
■ An advanced electrical expansion valve enables the units to control the refrigerant flow accurately, adapt to various working conditions, and perform multiple control functions.
Features
Advanced design and excellent performance
Figure 1 Figure 2
Stepless adjustment, high efficiency, and energy saving
■ Automatic load/unload based on changes of the actual air conditioning load
■ Operating status display of the units■ Common fault alarm display■ Water temperature control to an accuracy to 0.5°C■ Output load PID control■ Balancing the operating duration of each compressor■ Compressor load control■ Three-level password protection■ Stepless load adjustment■ Failure history query
Multiple communication ports such as the Modbus, LonWorks, and BACnet can be added to the controller for integrated control or automatic building control to implement joint control of multiple units (optional).
■ The temperature of outlet chilled water is accurate to 0.5°C. In addition, various sensors in the system can transmit various kinds of signal data to the controller to implement timely protection for the unit components and ensure more reliable operation.
■ The mechanism of tree-level password protection ensures safe operation of the units and prevents misoperations of non-professional personnel.
Intelligent Network Controller
The units adopt the new-generation DAIKIN controller Micro Tech III. This controller integrates the heat pump applications and technologies of DAIKIN of more than 40 years and is equipped with programmable software. This enables compressors and fans to reach the highest COP.
Main components
Main Functions
Network control
■ Unit status■ Temperature of inlet/outlet water■ Compressor status■ Suction and discharge pressure■ Temperature and superheat of suction and discharge■ Openning of electrical expansion valve■ Oil pressure■ Ambient temperature
■ High pressure protection■ Low pressure protection■ Fan overload protection■ High discharge temperature protection■ Compressor overload protection■ Low compression ratio protection■ High oil pressure difference protection■ Sensor failure protection■ Compressor startup failure protection■ Phase protection■ Evaporator anti-freezing protection■ Water flow protection
External manual operator (optional)
Operating status query
Protection functions
■ Compressors start up one by one with a low startup current, to reduce the impact on the power grid.
■ Multiple protection functions ensure safe operation of the units.
DAIKIN Air-Cooled Screw Chiller/Heat Pump
5
DAIKIN leads the single-screw compressor technology. The Semi-hermetic compressor features high efficiency, energy saving, quiet operation, few moving components, and long service life.
■ Few moving componentsDAIKIN single-screw compressor consists of only five moving components: a screw rotor, two star wheels, and two energy adjustment slide valves. The screw rotor is a six-tooth aluminum coated steel component. The star wheel is an eleven-tooth component made of high-strength composite material.
■ Long duration and high reliabilityThe star wheels made of high-strength composite material can ensure the accuracy and the minimum gap and guarantee operation without wear and tear. The oil injection and liquid injection design of the compressor minimizes air superheat and eliminates the possibility of oil and refrigerant decomposition due to superheat.
■ Simple maintenanceThe removable side cover of the star wheel box simplifies the routine inspection without the need of removing and installing pipelines. Such a design facilitates the check of the internal components of the compressor.
■ Anticorrosion aluminum fins■ Ammeter and voltmeter■ High/low pressure gauge■ Soft starter■ External manual operator■ Building automation ports: Modbus, Lon Works, and
BACnet.
DAIKIN ultra-efficiency single-screw compressor (intended for R134a refrigerant)
Features
Options
■ Low operation sound and vibrationDAIKIN single-screw compressor can balance the load completely during its operation. Therefore, the vibration can be ignored because the noise value is lower than the industrial standard. The compressor does not contact with any metal during compression so that no high frequency noise is generated. The special-shaped air discharge cavity helps eliminate noises effectively.
■ Unique star wheel and rotor designThe star wheel of DAIKIN single-screw compressor is made of special materials that can avoid metal engagement between the star wheel and rotor. The small engagement gap and low engagement resistance implement “zero gap" engagement. The unique oil supply system that uses the oil pressure difference function enables more efficient sealing, lubrication, and cooling of the compressor. In this way, the engagement resistance is further reduced and the efficiency of entire units is improved.
■ High-efficiency oil separatorThe application of high-efficiency oil separator increases the oil separation rate to 99.7%. The “oil leakage" problem during the compression is resolved, and the reliability and efficiency of the compressor is improved.
DAIKIN Air-Cooled Screw Chiller/Heat Pump
6
DAIKIN Single-Screw Heat PumpSuper-high-efficiency series
Model Unit UAY-FAAE ST3 105 125 150 175 204 245 291 348
Unit DimensionsLength mm 3730 4630 5580 6480 6480 7380
Width mm 2260Height* mm 2385 2425
WeightTransport kg 3580 4405 5400 5770 5880 6620Operation kg 3650 4510 5550 5950 6130 6870
Standard accessories Unit installation and operation manual, certificate of conformity, warranty application form, spring shock absorber, water flow switch
Notes: ■ Nominal cooling conditions: EWT/LWT 12/7°C; ambient DB temperature is 35°C;
■ Nominal heating conditions: EWT/LWT 40/45°C; ambient DB temperature is 7°C, ambient WB temperature is 6°C;
■ Total heat recovery conditions: warm water inlet/outlet temperature 40/ 45°C, chilled water inlet/outlet temperature 12/ 7°C.
DAIKIN Air-Cooled Screw Chiller/Heat Pump
11
Cooling Capacity Variation Table (heat pump)Super-high-efficiency series
Note: The inlet/outlet water temperature on the air conditioning side corresponding to the capacity variation parameters on the heat recovery side is 12°C/7°C.
Capacity Variation Table for Total Heat Recovery
DAIKIN Air-Cooled Screw Chiller/Heat Pump
21
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)5 Control cabinet
Dimensions
UAY105ST3-FAAESuper-high-efficiency series
Unit: mm
UAY125ST3-FAAE
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)5 Control cabinet
Unit: mm
2460
22253000
395
1330
1
2
5
5530 2260
5400
3
4
2225
2460
2962 1346
427
1
2
5
5530 2260
5400
3
4
DAIKIN Air-Cooled Screw Chiller/Heat Pump
22
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)5 Control cabinet
Unit: mm
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)5 Control cabinet
Unit: mm
Super-high-efficiency seriesDimensions
UAY150ST3-FAAE
UAY175ST3-FAAE
2225
2460
2962
427
1339
1
2
5
6480 2260
6300
3
4
21423262
7380
7200
2260
2460
2225
1
2
3427
4
5
DAIKIN Air-Cooled Screw Chiller/Heat Pump
23
Dimensions
UAY204ST3-FAAE
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)5 Control cabinet
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 8" (OD219.1 mm)4 Size of outlet water pipe of the evaporator 8" (OD219.1 mm)5 Control cabinet
Unit: mm
Unit: mm
Super-high-efficiency series
UAY245ST3-FAAE
427
10860
2225
2460
2260
15
2
10730
34
62213562
2460
22253510 6347
1
2
5
465
2260
10730
34
10860
DAIKIN Air-Cooled Screw Chiller/Heat Pump
24
Dimensions
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 10" (OD273 mm)4 Size of outlet water pipe of the evaporator 10" (OD273 mm)5 Control cabinet
Unit: mm
Super-high-efficiency seriesUAY291ST3-FAAE
UAY348ST3-FAAE
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 8" (OD219.1 mm)4 Size of outlet water pipe of the evaporator 8" (OD219.1 mm)5 Control cabinet
Unit: mm
2225
2460
465
3510 7248
2260
15
2
12530
34
12690
87913130
540
14330
2460
2225
1
2
5
2260
34
14490
DAIKIN Air-Cooled Screw Chiller/Heat Pump
25
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 4" (OD114.3 mm)4 Size of outlet water pipe of the evaporator 4" (OD114.3 mm)5 Control cabinet
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 4" (OD114.3 mm)4 Size of outlet water pipe of the evaporator 4" (OD114.3 mm)5 Control cabinet
Dimensions
High-efficiency series
Unit: mm
Unit: mm
UAY105ST3-FBAE
UAY125ST3-FBAE
DAIKIN Air-Cooled Screw Chiller/Heat Pump
26
Dimensions
High-efficiency seriesUAY150ST3-FBAE
UAY175ST3-FBAE
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 5" (OD139.7 mm)4 Size of outlet water pipe of the evaporator 5" (OD139.7 mm)5 Control cabinet
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 5" (OD139.7 mm)4 Size of outlet water pipe of the evaporator 5" (OD139.7 mm)5 Control cabinet
Unit: mm
Unit: mm
DAIKIN Air-Cooled Screw Chiller/Heat Pump
27
Dimensions
High-efficiency seriesUAY204ST3-FBAE
UAY220ST3-FBAE
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)5 Control cabinet
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)5 Control cabinet
Unit: mm
Unit: mm
DAIKIN Air-Cooled Screw Chiller/Heat Pump
28
Dimensions
High-efficiency series
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)5 Control cabinet
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)5 Control cabinet
Unit: mm
Unit: mm
UAY245ST3-FBAE
UAY291ST3-FBAE
DAIKIN Air-Cooled Screw Chiller/Heat Pump
29
High-efficiency series
Dimensions
UAY348ST3-FBAE
UAY380ST3-FBAE
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)5 Control cabinet
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 8" (OD219.1 mm)4 Size of outlet water pipe of the evaporator 8" (OD219.1 mm)5 Control cabinet
Unit: mm
Unit: mm
DAIKIN Air-Cooled Screw Chiller/Heat Pump
30
Dimensions
2425
38223023
562
2396 1941
9710
452
9500
3471
2260
31
2
5
7 6
8
4
400
500
UAY266ST3-FBBE
1 Condenser2 Evaporator3 Main unit’s control cabinet4 Auxiliary unit’s control cabinet5 Size of inlet water pipe of the main unit’s evaporator 4"(OD114.3 mm)6 Size of outlet water pipe of the unit’s evaporator 4"(OD114.3 mm)7 Size of inlet water pipe of the auxiliary unit’s evaporator 5"(OD139.7 mm)8 Size of outlet water pipe of the auxiliary unit’s evaporator 5"(OD139.7 mm)
Unit: mm
UAY300ST3-FBBE
42002295
504
3480 1742
406
2425
11510
11300
2260
3115
31
2
5
7 6
8
4
400
500
1 Condenser2 Evaporator3 Main unit’s control cabinet4 Auxiliary unit’s control cabinet5 Size of inlet water pipe of the main unit’s evaporator 4"(OD114.3 mm)6 Size of outlet water pipe of the unit’s evaporator 4"(OD114.3 mm)7 Size of inlet water pipe of the auxiliary unit’s evaporator 5"(OD139.7 mm)8 Size of outlet water pipe of the auxiliary unit’s evaporator 5"(OD139.7 mm)
Unit: mm
DAIKIN Air-Cooled Screw Chiller/Heat Pump
31
UAY355ST3-FBBE
Dimensions
2425
3960 3234 1752
12460
475
475
2295
2260
2937
12200
31
2
5
7 6
8
4
500
400
UAY390ST3-FBBE
3900 132031363723
510
468
2893
2260
2425
13100
13360
31
2
5
7 6
8
4 400
500
1 Condenser2 Evaporator3 Main unit’s control cabinet4 Auxiliary unit’s control cabinet5 Size of inlet water pipe of the main unit’s evaporator 5"(OD139.7 mm)6 Size of outlet water pipe of the unit’s evaporator 5"(OD139.7 mm)7 Size of inlet water pipe of the auxiliary unit’s evaporator 5"(OD139.7 mm)8 Size of inlet water pipe of the auxiliary unit’s evaporator 5"(OD139.7 mm)
Unit: mm
1 Condenser2 Evaporator3 Main unit’s control cabinet4 Auxiliary unit’s control cabinet5 Size of inlet water pipe of the main unit’s evaporator 5"(OD139.7 mm)6 Size of outlet water pipe of the unit’s evaporator 5"(OD139.7 mm)7 Size of inlet water pipe of the auxiliary unit’s evaporator 6"(OD168.3 mm)8 Size of outlet water pipe of the auxiliary unit’s evaporator 6"(OD168.3 mm)
Unit: mm
DAIKIN Air-Cooled Screw Chiller/Heat Pump
32
Dimensions
2893
2260
2425
3136 174131363723
510
13100
13360
31
2
5
7 6
8
4
510
400
500
UAY400ST3-FBBE
1 Condenser2 Evaporator3 Main unit’s control cabinet4 Auxiliary unit’s control cabinet5 Size of inlet water pipe of the main unit’s evaporator 6"(OD168.3 mm)6 Size of outlet water pipe of the unit’s evaporator 6"(OD168.3 mm)7 Size of inlet water pipe of the auxiliary unit’s evaporator 6"(OD168.3 mm)8 Size of outlet water pipe of the auxiliary unit’s evaporator 6"(OD168.3 mm)
Unit: mm
UAY415ST3-FBBE
2225
226024
25
3000
360
132024122940
392
14000
14260
31
2
5
7 6
8
4
500
400
1 Condenser2 Evaporator3 Main unit’s control cabinet4 Auxiliary unit’s control cabinet5 Size of inlet water pipe of the main unit’s evaporator 5"(OD139.7 mm)6 Size of outlet water pipe of the unit’s evaporator 5"(OD139.7 mm)7 Size of inlet water pipe of the auxiliary unit’s evaporator 6"(OD168.3 mm)8 Size of outlet water pipe of the auxiliary unit’s evaporator 6"(OD168.3 mm)
Unit: mm
DAIKIN Air-Cooled Screw Chiller/Heat Pump
33
UAY424ST3-FBBE
Dimensions
2225
2260
2425
2412 1340
392
24122940
392
14000
14260
31
2
5
7 6
8
4
500
400
UAY450ST3-FBBE
2412 216324122940
392
392
2225
226024
25
15160
14900
1
2
5
3
7 6
4
8
500
400
1 Condenser2 Evaporator3 Main unit’s control cabinet4 Auxiliary unit’s control cabinet5 Size of inlet water pipe of the main unit’s evaporator 6"(OD168.3 mm)6 Size of outlet water pipe of the unit’s evaporator 6"(OD168.3 mm)7 Size of inlet water pipe of the auxiliary unit’s evaporator 6"(OD168.3 mm)8 Size of outlet water pipe of the auxiliary unit’s evaporator 6"(OD168.3 mm)
Unit: mm
1 Condenser2 Evaporator3 Main unit’s control cabinet4 Auxiliary unit’s control cabinet5 Size of inlet water pipe of the main unit’s evaporator 6"(OD168.3 mm)6 Size of outlet water pipe of the unit’s evaporator 6"(OD168.3 mm)7 Size of inlet water pipe of the auxiliary unit’s evaporator 6"(OD168.3 mm)8 Size of outlet water pipe of the auxiliary unit’s evaporator 6"(OD168.3 mm)
Unit: mm
DAIKIN Air-Cooled Screw Chiller/Heat Pump
34
Dimensions
High-efficiency series
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 4" (OD114.3 mm)4 Size of outlet water pipe of the evaporator 4" (OD114.3 mm)5 Control cabinet
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 4" (OD114.3 mm)4 Size of outlet water pipe of the evaporator 4" (OD114.3 mm)5 Control cabinet
Unit: mm
Unit: mm
UAA105ST3-FBAE
UAA125ST3-FBAE
2460
2260
2225
3530
3400
2
3
1 5
4
1536 1244
365
2260
22252486 1244
4300
4430
3
2
1
4
365
5
2460
DAIKIN Air-Cooled Screw Chiller/Heat Pump
35
High-efficiency series
Dimensions
UAA150ST3-FBAE
UAA175ST3-FBAE
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 5" (OD139.7 mm)4 Size of outlet water pipe of the evaporator 5" (OD139.7 mm)5 Control cabinet
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 5" (OD139.7 mm)4 Size of outlet water pipe of the evaporator 5" (OD139.7 mm)5 Control cabinet
Unit: mm
Unit: mm
2260
2460
22255200
395
2450 1353
3
2
1 5
4
5380
395
3000 1320
6100 2225
2460
2260
3
2
1
4
5
6280
DAIKIN Air-Cooled Screw Chiller/Heat Pump
36
Dimensions
High-efficiency series
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)5 Control cabinet
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)5 Control cabinet
Unit: mm
Unit: mm
UAA204ST3-FBAE
UAA220ST3-FBAE
2
3
1 5
4
6280
6100
134024122225
2260
2460
427
427
2412 2163
7000 2225
2460
22607180
1
2
3
4
5
DAIKIN Air-Cooled Screw Chiller/Heat Pump
37
High-efficiency series
Dimensions
UAA245ST3-FBAE
UAA291ST3-FBAE
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)5 Control cabinet
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)5 Control cabinet
Unit: mm
Unit: mm
2260
2460
2225
2412
427
3
4
2
1 5
8530
5467
8660
23
4
1 5
427
3262 5371
9430
2460
2260
2225
9560
DAIKIN Air-Cooled Screw Chiller/Heat Pump
38
Dimensions
High-efficiency series
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 8" (OD219.1 mm)4 Size of outlet water pipe of the evaporator 8" (OD219.1 mm)5 Control cabinet
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 6" (OD168.3 mm)4 Size of outlet water pipe of the evaporator 6" (OD168.3 mm)5 Control cabinet
Unit: mm
Unit: mm
UAA348ST3-FBAE
UAA380ST3-FBAE
1 5
23
4
427
3262 627110330
2260
2460
2225
10490
1
5
23
4
2260
2225
2460
73022360
12130
465
12290
DAIKIN Air-Cooled Screw Chiller/Heat Pump
39
High-efficiency series
Dimensions
UAA400ST3-FBAE
UAA450ST3-FBAE
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 8" (OD219.1 mm)4 Size of outlet water pipe of the evaporator 8" (OD219.1 mm)5 Control cabinet
1 Condenser2 Evaporator3 Size of inlet water pipe of the evaporator 8" (OD219.1 mm)4 Size of outlet water pipe of the evaporator 8" (OD219.1 mm)5 Control cabinet
Unit: mm
Unit: mm
1 5
3 2
2260
3210 7297
12130
465
4
2460
2225
12290
1 5
3 2
4
465
3210 8197
13930 2225
2460
226014090
DAIKIN Air-Cooled Screw Chiller/Heat Pump
40
Dimensions
UAY105SR3-FBAE
UAY125SR3-FBAE
1 Condenser2 Control cabinet3 Evaporator4 Size of inlet water pipe of the evaporator 4"(OD114.3 mm)5 Size of outlet water pipe of the evaporator 4"(OD114.3 mm)6 Heat recovery exchanger7 Size of outlet water pipe of the heat recovery exchanger 3"(OD88.9 mm)8 Size of inlet water pipe of the heat recovery exchanger 3"(OD88.9 mm)
1 Condenser2 Control cabinet3 Evaporator4 Size of inlet water pipe of the evaporator 4"(OD114.3 mm)5 Size of outlet water pipe of the evaporator 4"(OD114.3 mm)6 Heat recovery exchanger7 Size of outlet water pipe of the heat recovery exchanger 3"(OD88.9 mm)8 Size of inlet water pipe of the heat recovery exchanger 3"(OD88.9 mm)
Unit: mm
Unit: mm
DAIKIN Air-Cooled Screw Chiller/Heat Pump
41
Dimensions
UAY150SR3-FBAE
UAY175SR3-FBAE
1 Condenser2 Control cabinet3 Evaporator4 Size of inlet water pipe of the evaporator 5"(OD139.7 mm)5 Size of outlet water pipe of the evaporator 5"(OD139.7 mm)6 Heat recovery exchanger7 Size of outlet water pipe of the heat recovery exchanger 3"(OD88.9 mm)8 Size of inlet water pipe of the heat recovery exchanger 3"(OD88.9 mm)
1 Condenser2 Control cabinet3 Evaporator4 Size of inlet water pipe of the evaporator 5"(OD139.7 mm)5 Size of outlet water pipe of the evaporator 5"(OD139.7 mm)6 Heat recovery exchanger7 Size of outlet water pipe of the heat recovery exchanger 4"(OD114.3 mm)8 Size of inlet water pipe of the heat recovery exchanger 4"(OD114.3 mm)
Unit: mm
Unit: mm
DAIKIN Air-Cooled Screw Chiller/Heat Pump
42
Dimensions
UAY204SR3-FBAE
UAY220SR3-FBAE
1 Condenser2 Control cabinet3 Evaporator4 Size of inlet water pipe of the evaporator 6"(OD168.3 mm)5 Size of outlet water pipe of the evaporator 6"(OD168.3 mm)6 Heat recovery exchanger7 Size of outlet water pipe of the heat recovery exchanger 4"(OD114.3 mm)8 Size of inlet water pipe of the heat recovery exchanger 4"(OD114.3 mm)
1 Condenser2 Control cabinet3 Evaporator4 Size of inlet water pipe of the evaporator 6"(OD168.3 mm)5 Size of outlet water pipe of the evaporator 6"(OD168.3 mm)6 Heat recovery exchanger7 Size of outlet water pipe of the heat recovery exchanger 4"(OD114.3 mm)8 Size of inlet water pipe of the heat recovery exchanger 4"(OD114.3 mm)
Notes: ■ The maximum operating current in the above table refers to the maximum operating current during cooling or heating within the operation range.
■ Working conditions for the nominal operating current: During cooling, the ambient temperature for dry bulb is 35°C, and the temperature of inlet/outlet chilled water is 12°C/7°C. During heating, the ambient temperature for dry bulb is 7°C, the temperature for wet bulb is 6°C, and the temperature of inlet/outlet hot water is 40°C/45°C.
■ Inter-phase unbalance range: ≤ 2%
■ Power supply voltage: 380 V±10%
Electrical specifications
Model
Compressor Fan Nominal operating currentMaximum operating current (A)
Notes: ■ The maximum operating current in the above table refers to the maximum operating current during cooling or heating within the operation range.
■ Working conditions for the nominal operating current: During cooling, the ambient temperature for dry bulb is 35°C, and the temperature of inlet/outlet chilled water is 12°C/7°C. During heating, the ambient temperature for dry bulb is 7°C, the temperature for wet bulb is 6°C, and the temperature of inlet/outlet hot water is 40°C/45°C.
1 Unit failure Passive dry contact output For failure signal output of the unit (Figure 1)
2 Water pump control output Passive dry contact output For water pump control output (Figures 2 and 3)
3 Water flow switch Passive dry contact input For detecting water flow of the unit (Figure 4)
4 Remote startup/shutdown Passive dry contact input For remote startup/shutdown of the unit (Figure 5)
5 Remote mode selection Passive dry contact input For remote mode selection of the unit (Figure 6)
6 System failure signal 1 Passive dry contact output For failure signal output of the unit (Figure 7)
7 System failure signal 2 Passive dry contact output For failure signal output of the unit (Figure 8)
8 Heat recovery auxiliary electric heating signal Passive dry contact output Used to output the auxiliary electric heating signal
for units. For details, see Figures 9 and 10.
9 Dry-steam auxiliary electric heater signal Passive dry contact output Used to output the auxiliary electric heating signal
for units. For details, see Figures 9 and 10.
10 Heat recovery pump control output Passive dry contact output Used to output the heat recovery pump control signal for units. For details, see Figures 2 and 3.
11 Heat recovery water switch Passive dry contact output Used to detect the heat recovery water flow of the unit. For details, see Figures 11.
Notes: ■ The wiring of the dashed part must be completed by the customer. ■ The customer is advised to configure an outdoor incoming circuit breaker. ■ The selected external wires and circuit breakers for all units must be larger than the maximum operating current of the units, and furthermore, they will not cause malfunction conditions due to start current. ■ Due to the impact of layout and length, supplies cannot provide details about the main power wiring. Please refer to relevant materials.
Auxiliary unit's control cabinet
Outlet water temperature
sensor of main unit
Outlet water temperature sensor
of auxiliary unit
Shielded twisted pairAll exposed wires must be protected with conduits.
Main unit's control cabinetNotes: 1. Wirings for main unit's and auxiliary unit's
control cabinets showed in the left figure are applicable only to the following unit models: UAY266ST3-FBBE UAY300ST3-FBBE UAY355ST3-FBBE UAY390ST3-FBBE UAY400ST3-FBBE UAY415ST3-FBBE UAY424ST3-FBBE UAY450ST3-FBBE
2. The preceding models adopt twin power supply wiring.
DAIKIN Air-Cooled Screw Chiller/Heat Pump
65
Notes:
■ * This function is not available for cooling-only and total heat recovery units.
■ For the terminal blocks in figures 2 and 3, M3(401) and M3(402) indicate the output contacts for pump control on the air conditioning side; M3(90) and M3(91) indicate the output contacts for pump control on the heat recovery side.
■ For the terminal blocks in figures 9 and 10, M3(53) and M3(54) indicate the signal contacts for auxiliary electric heating on the air conditioning side; M3(28A) and M3(28E) indicate the signal contacts for auxiliary electric heating on the heat recovery side.
■ Operating signals of the unit come from the operating signals of the water pump. If M3 (401) and M3 (402) are externally connected to a water pump contactor, the operating signals of unit come from the normally-open contact of the contactor.
■ When the unit is in the remote mode control, switch Q8 must be set to “Heating". It can be controlled by connecting a remote switch to M3 (60) and M3 (61). The short contact tag between M3 (60) and M3 (61) must be removed.
■ The failure, water pump output and electric heater contact can bear an AC voltage of only 230 V. If the water pump contactor uses a 380 V coil, conversion is required. See Figure 3/10.
■ Since the units are under constant improvement, use the drawing delivered with the related unit for reference.
M3(8)
M3(23)
Control cabinet
Terminal block
F116 Water flow switch
Figure 4
Control cabinet
Terminal block AC power supply 220V~/50HzIntermediate
relay
AC power supply 380V~/50Hz
Constantly closed point for electric heating protection
M3(53)
M3(54)
Control cabinet
Terminal block 220 V alarm indicator
AC power 220V~/50Hz
Figure 1
M3(25)
M3(26)~
Control cabinet
Terminal block
M3(401)
M3(402)
AC power 220V~/50Hz
Normally-close point of water pump overload relay
Water pump contactor(with a coil voltage of 220 V) Figure 2
~
Control cabinet
M3(402)
M3(401)
Terminal block AC power 220V~/50HzIntermediate
relay
AC power 380V~/50Hz
Normally-close point of water pump overload relay
Water pump contactor(with a coil voltage of 380 V) Figure 3
~
~
Control cabinet
M3(59)
M3(58)
Terminal block
Remote switch of the unit
Figure 5
Figure 6
Control cabinet
M3(61)
M3(60)
Terminal block
Remote mode selection switch
Control cabinet
M3(60+)
M3(50)
Terminal block 220 V alarm indicator
AC power 220V~/50Hz
Figure 7
~
Control cabinet
Terminal block AC power supply 220V~/50Hz
Constantly closed point for electric heating protection
Electric heating contactorThe voltage of the coil on
the contactor is 220 V. Figure 9
M3(53)
M3(54)
Control cabinet
M3(73)
M3(50)
Terminal block 220 V alarm indicator
AC power 220V~/50Hz
Figure 8
~
~
~
~
Electric Heater contactorThe voltage of the coil on
the contactor is 380 V. Figure 10
Control cabinet
Terminal block
M3(197)
M3(198)
F116
Heat recovery water switch
Figure 11
DAIKIN Air-Cooled Screw Chiller/Heat Pump
66
Requirements for Water System Installation
Components of Water System
Recommended water systemInstallation illustration for the water system of a single unit:
Components recommended for the water system:
2-way valve
Water replenishing valve
Heater
Fan coil
Water pump
Gate valve
Softconnector
Expansion tank
Auto air discharge valve
Sewage discharge
valve
Pressure gauge
Thermometer
Differential pressurebypass valve
Filter
Water flow switch
Relief valve
Gate valve
Softconnector
Gate valve
Gate valve
Pressure gauge
Thermometer
Gate valve
Fan coil
Fan coil
Fan coil
Softconnector
2-way valve
2-way valve
2-way valve
No. Recommended Components
1 All pipes must be as level and simple as possible to reduce water resistance.
2 It is recommended to install manual stop valve for a component that requires manual maintenance.
3 Install a thermometer and pressure gauge at water inlets and outlets.
4 Install a water tank to increase the capacity of the water system.
5 Install hoses at the water inlets and outlets of a unit to prevent vibration from being transmitted to buildings.
DAIKIN Air-Cooled Screw Chiller/Heat Pump
67
On-site wiring diagram
Mandatory components for the water system:
No. Mandatory Components
1 A heat insulation layer with a thickness of at least 10 millimeter must be wrapped around the chilled water pipe.
2 A water filter with at least 25 meshes per square inch must be installed at the inlet of the water-side heat exchanger.
3 The chilled water pipe must be cleaned by using a bypass pipe. It’s prohibited to clean the water pipes through the water-side heat exchanger.
4A water flow switch must be installed at the water outlet of the water-side heat exchanger. The distance of the level straight pipe between both ends of the flow swith must be five times more than the diameter at least.The water flow direction in the
water flow switch must be the same as that in the water system.
5 A relief valve with a opening pressure less than 1.0 MPa must be installed.
6 An automatic water replenishment device must be installed to ensure sufficient water in the water system.
7 A pump with a proper water flow and lift must be installed at the water inlet of the water-side heat exchanger to ensure that the actual water flow is between 70% - 130% of the rated water flow for the unit when the unit is working.
8 Sufficient maintenance space must be reserved.
9 Stop valves must be installed at the water inlet and outlet of the unit.
10 An automatic relief valve must be installed at the top of water pipes to ensure that air in the water system can be discharged when the unit is working.
11An auxiliary heater or other heating devices must be installed to ensure that water in the water system does not freeze when the environment temperature drops below zero (this requirement only applies to areas where the environment temperature
may drop below 0°C).
12 The chilled water pipe must comply with the local piping engineering regulations and rules.
13 The water used in the water system must comply with related industry standards.
Water Flow
Water Volume
The design water flow of water system should be the same as rated water flow of unit. Of course, the unit is able to operate at condition of 70%~130% rated water flow. However, water flow out of this range may cause unit alarm, or even reduce the unit life expectancy.
It is very important to design the water system with suitable water volume. With too much low water volume, air conditioning terminal device will not be able to operate at stable condition, then the user may feel uncomfortable. Moreover, the chiller with lower water volume may be frequently on/off, then may cause the chiller alarm, or even damage evaporator and system.
Minimum water volume: To avoid the above happened, water volume of water system must be at least more than the minimum water volume
Minimum water volume (m3) = Rated cooling capacity of chiller (kW) × 0.0068
DAIKIN Air-Cooled Screw Chiller/Heat Pump
68
The workload of a DAIKIN water chiller is controlled by the outlet water temperature which can be set by using the unit controller.
By default, the outlet water temperature is set to 7°C. It can be set from 4~15°C. Out of this range, some other parameters are needed to be changed as well. Please contact local DAIKIN office or distributor to have professional technician to do the setting accordingly.
Setting the Outlet Water Temperature
Cleaning the Water System
Requirements on Water Quality
While installing the water system, it may create a lot of welding slag, dirt or other impurity. It may damage the evaporator if the chiller is connected directly to the water system without cleaning. Please do not run the water into chiller until the water is clean and qualified.
Water quality directly affects the performance and life expectancy of the unit. Therefore, the water quality must be tested and properly managed for the unit to work properly.
DAIKIN recommends a water quality that meets the following standards:
Item Standard Item Standard
pH pH:7.5~9 Conductivity <800µS/cm
Total hardness CaCO3: 40~85mg/L Chloride CI-<300mg/L
SO2- SO2-<70mg/L Alkalinity HCO- : 70~300mg/L
NH+ NH+<2mg/L H2S H2S<0.05mg/L
CI2 CI2<1mg/L CO2 CO2<5mg/L
NH- NH-<100mg/L Solid impruities Diameter of solid impurities<1mm
Al/Fe Al/Fe<0.2mg/L Mn Mn<0.1mg/L
4 4 3
4 4
3 3
DAIKIN Air-Cooled Screw Chiller/Heat Pump
69
1 2 3 45
Turn Anticlockwise Turn Clockwise Press
Screen Alarm Query Shortcut key Return Up Down Enter
MT3006
2
3
4
5 1
Control panel and function
Main controller
DAIKIN Air-Cooled Screw Chiller/Heat Pump
70
Operation Panel
EMERGENCY
4 1
Q0 (UNIT SWITCH) 0 1
OFF ON
Q1 (1#SYS SW.) 0 1
OFF ON
2
Q2 (2#SYS SW.) 0 1
OFF ON
3
I1
I2
I3
CM2
6
A
I1
I2
I3
CM1
A
5
1 2 3 4 5 6
UNIT SWITCH 1#SYS SW. 2#SYS SW. EMERGENCYSTOP
Programmable ammeter of 1#
Programmable ammeter of 2#
DAIKIN Air-Cooled Screw Chiller/Heat Pump
71
Control functions
Alarm Query Press the key to enter alarm menu
Turn button
Turn Anticlockwise Up Page up while checking or reduce value while parameter setting
Turn Clockwise Down Page down while checking or increase value while parameter setting
Press Enter Confirm operation
Shortcut key Return to main menu
Return Return to the upper-layer menu
EMERGENCY STOP Turn off the unit in case of emergency
UNIT SWITCH Q0
OFF Turn off the unit
ON Turn on the unit
1#SYS SW. Q1
OFF Turn off the 1#SYS
ON Turn on the 1#SYS
1#SYS SW. Q2
OFF Turn off the 2#SYS
ON Turn on the 2#SYS
ON 1#SYS manual defrosting
Programmable ammeter of CM1 Indicating the working current of 1#SYS
Programmable ammeter of CM2 Indicating the working current of 2#SYS
Unit start / shutdown
Start the unit
Please follow the procedure to start the unit: (1) Check before start a. Confirm the unit has been commissioned and ready for operation. b. Check whether the unit status meet the requirements of startup. (2) Startup procedure Step 1: Supply power to the unit; Step 2: Turn the “EMERGENCY STOP” clockwise until it springs up; Step 3: Turn “Breaker” Q12 of the control circuit to “ON”. The following main menu displays in 30 seconds.
Main Menu 1/12 Enter Password ► Unit Status=
Auto: Evap Recirc Active Setpt = 7.0°C
Main Menu 1/12
Enter Password ► Unit Status= Off: Unit Sw Active Setpt= 7.0°C
After the unit and water circulation started, confirm whether the water system works properly. If the controller does not display “Auto: Evap Recirc”, see 10.1. Step 5: Turn the “1#SYS SW.” Q1 and “2#SYS SW.” Q2 to “ON”, then unit will start and adjust load automatically.
If it need circuit 1 or circuit 2 run alone, just turn the respective switch to “ON”.
Shutdown procedure
(1) Shutdown the Circuit To shutdown circuit 1# or circuit 2#, turn the switch of the corresponding circuit to “OFF”. After these operations,
the circuit will shutdown automatically.(2) Shutdown the Unit Step 1: Turn “1#SYS SW.” and “2#SYS SW.” to “OFF”; Step 2: Turn “UNIT SWITCH” to “OFF”. After these operations, the unit will shutdown automatically.
Setting Temperature
Enter the user password and choose “View/Set Unit” in main menu then choose “Temperatures”. The following screen displays:
Main Menu 1/12 Enter Password ► Unit Status=
Auto: Evap Recirc Active Setpt = 7.0°C
Main Menu 1/12
Enter Password ► Unit Status= Off: Unit Sw Active Setpt= 7.0°C
“Cool LWT 1” indicates the setpoint of evaporator leaving water temperature in cooling mode. The value range is (4.0°C, 15.0°C). “Cool LWT 2” indicates the double setpoint temperature of leaving water in cooling mode. The value range is (4.0°C, 15.0°C).For example, to set "Cool LWT 1", select the item and press the knob. The following interface displays:
Main Menu 1/12 Enter Password ► Unit Status=
Auto: Evap Recirc Active Setpt = 7.0°C
Main Menu 1/12
Enter Password ► Unit Status= Off: Unit Sw Active Setpt= 7.0°C
Turn the knob clockwise to increase the value and turn it anticlockwise to decrease the value, and press the knob to confirm the setting. Then the previous menu displays and the parameter setting takes effect. Other parameters can be set in the same way.
DAIKIN Air-Cooled Screw Chiller/Heat Pump
73
WARNING
Parameter setting must be in accord with this operation manual. Improper setting can cause erratic chiller operation and damage to the chiller.
!
Parameter setting must be in accord with this operation manual. Improper setting can cause erratic chiller operation and damage to the chiller.
After entering the user password, you can view and modify parameters at the user level. The default user password is 1990. The procedure is as follows: Step 1: Press the shortcut key to go to the main menu:
Main Menu 1/12 Enter Password ► Unit Status=
Auto: Evap Recirc Active Setpt = 7.0°C
Main Menu 1/12
Enter Password ► Unit Status= Off: Unit Sw Active Setpt= 7.0°C
Step 3: Press the knob and enter the highest digit of the password, and press the knob to confirm the entry. Enter other digits in turn in the same way. If the user password is correct, you can view and modify parameters at the user level. After you enter the password, the main menu displays as below and “6” displays at the upper-left corner.
Main Menu 1/12 Enter Password ► Unit Status=
Auto: Evap Recirc Active Setpt = 7.0°C
Main Menu 1/12
Enter Password ► Unit Status= Off: Unit Sw Active Setpt= 7.0°C
Choose the quick menu in the main menu, press the knob and enter the quick menu to view major operation parameters of the unit. Step 1: Choose the quick menu:
6 Main Menu 8/15
Unit Status= Off: Unit Sw
Active Setpt= 7.0°CEvap LWT= 20.0°C
6 Main Menu 12/15
Unit Capacity = 00.0% Unit Mode = Cool Time Until Restart Alarms
► ►
6 Main Menu 15/15
Alarms ► Scheduled Maintenance ► About Chiller ► Language Selection ►
View the current operation status of the unit. Auto: Off: Ice Mode TmrOff: OAT Lockout Off: All Cir DisabledOff: Unit AlarmOff: Keypad DisableOff: Remote Sw Off: BAS DisableOff: Unit SwOff: Time ScheduleOff: Test ModeAuto: Noise ReductionAuto: Wait For LoadAuto: Evap RecircAuto: Wait For FlowAuto: PumpdnAuto: Max PulldnAuto: Unit Cap LimAuto: Current LimOff: Cfg Chg,Rst CtlrOff : Mfg Loc Not SetOff: Comm Cfg Tmr
2 Active Setpt R °C View the actual setpoint of evaporator leaving water temperature
3 Evap LWT R °C View the evaporator leaving water temperature4 Evap EWT R °C View the evaporator entering water temperature5 Unit Capacity R % View the capacity of the unit6 Unit Current R A View the current of the unit7 Softload Limit R % View the softload capacity limitation of the unit8 Network Limit R % View the network capacity limitation of the unit9 Demand Limit R % View the demand capacity limitation of the unit
10 Unit Mode R -- View the current mode of the unit
11 Control Source R/W --
View and set the control source of the unit. The options are as follows: Local: The unit is controlled by control panel Network: The unit is controlled by local panel and network
12 Current Limit R/W A View or set the current limitation of the unit
Note: In the “Property” column, “R” indicates that the item can be read by user. R/W indicates that the item can be read and written (changed) by user. The same below.
Turn the knob clockwise or anticlockwise to view other parameters in the quick menu.
DAIKIN Air-Cooled Screw Chiller/Heat Pump
76
View/Set Unit
Choose the View/Set Unit menu in the main menu; press the knob to view or set operation parameters for the unit. Step 1: The View/Set Unit menu is as follows:
6 Main Menu 8/15
Unit Status= Off: Unit Sw
Active Setpt= 7.0°CEvap LWT= 20.0°C
6 Main Menu 12/15
Unit Capacity = 00.0% Unit Mode = Cool Time Until Restart Alarms
► ►
6 Main Menu 15/15
Alarms ► Scheduled Maintenance ► About Chiller ► Language Selection ►
No. Menu Description1 Status/Settings ► Enter the menu. For details, see 9.3.2.12 Set-Up ► Enter the menu. For details, see 9.3.2.23 Temperatures ► Enter the menu. For details, see 9.3.2.3 4 Date/Time/ Schedules ► Enter the menu. For details, see 9.3.2.4 5 Power Conservation ► Enter the menu. For details, see 9.3.2.5 6 Ctrlr IP Setup ► Enter the menu. For details, see 9.3.2.6 7 Design Conditions ► Enter the menu. For details, see 9.3.2.7 8 Menu Password ► Enter the menu. For details, see 9.3.2.8
Status/Settings
After entering the Status/Settings menu, you can view and set the following parameters:
No. Menu Property Unit Description1 Unit Status R -- View the current operation status of the unit2 Next Crkt On R -- View the next circuit to be started3 Next Crkt Off R -- View the next circuit to be stopped
4 Chiller Enable R --Used to enable the unitEnable: Allow the unit to be started Disable: Prohibit the unit to be started
5 Control Source R --View and set the control source of the unit. The options are as follows: Local: The unit is controlled by control panel Network: The unit is controlled by local panel and network
6 Netwrk En SP R -- View the status of BAS switch7 Netwrk Mode SP R -- View the mode setting of BAS 8 Netwrk Cool SP R °C View the BAS cooling setpoint9 Netwrk Ice SP R °C View the BAS ice storage setpoint
10 Netwrk Cap Lim R % View the network capacity limitation of the unit11 Stg Up Dly Rem R s View remaining time before next compressor start12 Stg Dn Dly Rem R s View remaining time before next compressor stop13 Ice Cycle Rem R min View the remaining time of an ice storage cycle 14 Evap Pmp 1Hrs R hour View the running time of pump 1 15 Evap Pmp 2Hrs R hour View the running time of pump 2 16 Remote Srv En R/W -- Reserved
DAIKIN Air-Cooled Screw Chiller/Heat Pump
77
Set-Up
After entering the Set-Up menu, setting the following parameters:
Temperatures
No. Menu Property Unit Description
1 Available Modes R --
Set the available modes for the unit:Cool: Cooler only Cool/Ice w/Glycol: Cooler only, Ice Storage, GlycolCool/Heat: Heat PumpCool/Ice/Heat w/Glycol: Heat Pump Unit, Ice Storage, Glycol Test: Test mode
2 Start Up DT R °C View the startup temperature difference3 Shut Dn DT R °C View the stop temperature difference 4 Stg Up DT R °C View the temperature difference for starting next compressor 5 Stg Dn DT R °C View the temperature difference for stopping next compressor
6 Max Pulldn R °C/min View the evaporator entering water temperature maximum pull down rate for cooling mode
7 Stg Up Delay R min View the remaining time for starting the next compressor 8 Stg Dn Delay R min View the remaining time for stopping the next compressor 9 Unit En Init R -- Reserved
10 Ice Cycle Dly R hour View the cycle time of ice storage mode
No. Menu Property Unit Description1 Evap LWT R °C Current evaporator leaving water temperature2 Evap EWT R °C Current evaporator entering water temperature
3 Evap Delta T R °C View the current difference between the leaving and entering water temperatures of evaporator
4 Active Setpt R °C View the current actual setpoint for leaving water temperature of the evaporator
5 Outside Air R °C View the current ambient temperature
6 Cool LWT 1 R/W °C View or set the first temperature setpoint for evaporator leaving water in cooling mode
7 Cool LWT 2 R/W °C View or set the double setpoint for evaporator leaving water in cooling mode
8 Ice LWT R/W °C View or set the temperature setpoint for evaporator leaving water in ice storage mode
DAIKIN Air-Cooled Screw Chiller/Heat Pump
78
No. Menu Property Unit Description1 Actual Time R/W -- View or set the current time2 Actual Date R/W -- View or set the current date
3 En Schedule R/W --View or set the function of time schedule. The options are as follows: Disable: No time scheduleEnable: Time schedule function is enabled
4 Time Schedule R/W --
When time schedule function is enabled, the menu uses to set the start and stop time for three time periods. In every period, it is time schedule “ON”Set the start and stop time for days from Monday to FridayStart time1:Set the first start timeStop time1:Set the first stop timeStart time2:Set the second start timeStop time2:Set the second stop timeStart time3:Set the third start timeStop time3:Set the third stop timeSet the start and stop time for days from Saturday To Sunday Start time1:Set the first start timeStop time1:Set the first stop timeStart time2:Set the second start timeStop time2:Set the second stop timeStart time3:Set the third start timeStop time3:Set the third stop time
5 Holiday Schedule R/W --
When time schedule function is enabled, the menu use to set the holidays, in holidays, the unit will be offHoliday1:Set the first holidayHoliday2:Set the second holidayHoliday3:Set the third holidayHoliday4:Set the fourth holidayHoliday5:Set the fifth holidayHoliday6:Set the sixth holidayHoliday7:Set the seventh holidayHoliday8:Set the eighth holidayHoliday9:Set the ninth holidayHoliday10:Set the tenth holiday
6 UTC diff R/W min View or set the UTC time difference. UTC refers to Universal Time Coordinated
7 DLS Enable R/W -- View or set the daylight saving time mode 8 DLS strt Month R/W -- View or set the month when the daylight saving time mode takes effect 9 DLS Strt Week R/W -- View or set the week when the daylight saving time mode takes effect
10 DLS End Month R/W -- View or set the month when the daylight saving time mode finishes11 DLS End Week R/W -- View or set the week when the daylight saving time mode finishes 12 Quiet Mode R/W -- View or set the quiet mode13 QM Start Hr R/W -- View or set the hour when the quiet mode takes effect 14 QM Start Min R/W -- View or set the minute when the quiet mode takes effect 15 QM End Hr R/W -- View or set the hour when the quiet mode finishes 16 QM End Min R/W -- View or set the minute when the quiet mode finishes 17 QM Cond Offset R/W °C View or set the condenser temperature difference for the quiet mode
Date/Time/ Schedules
DAIKIN Air-Cooled Screw Chiller/Heat Pump
79
No. Menu Property Unit Description1 Unit Capacity R % View the current capacity of the unit 2 Unit Current R A View the working current of the unit 3 Demand Lim En R -- View whether demand capacity limitation is enabled 4 Demand Limit R/W % View or set demand capacity limitation of the unit 5 Current @ 20mA R A View the current for 20mA 6 Current Limit R A View the current limitation of the unit
7 Setpoint Reset R/W --
Adjust the evaporator leaving water temperature setpoint: None: No adjust to the setpoint 4-20mA: Adjust the settings based on external current signal Return: Adjust the settings based on evaporator water temperature Oat: Adjust the settings based on ambient temperature
8 Max Reset R/W °C View or set the maximum reset
9 Start Reset DT R/W °C View or set the temperature difference between evaporator entering and leaving water using “Return” to adjust the evaporator leaving water temperature setpoint
10 Max Reset OAT R/W °C View or set the ambient temperature when it is the maximum adjustment using “Oat” to adjust the evaporator leaving water temperature setpoint
11 Strt Reset OAT R/W °C View or set the ambient temperature when adjustment starts using “Oat” to adjust the evaporator leaving water temperature setpoint
12 Softload En R/W -- View or set the softload function 13 Softload Ramp R/W min View or set the softload time 14 Starting Cap R/W % View or set the capacity for softload function
Power Conservation
Ctrlr IP Setup
Design Conditions
Menu Password
No. Menu Property Unit Description1 Apply Changes R/W -- Any change in this menu would be effective after confirmed here2 DHCP R/W -- View or set the function of dynamically obtaining the controller IP address 3 Act IP R -- View the current IP address of the controller 4 Act Msk R -- View the current subnet mask of the controller 5 Act Gwy R -- View the current gateway of the controller 6 Gvn IP R/W -- View or set the IP address 7 Gvn Msk R/W -- View or set the subnet mask 8 Gvn Gwy R/W -- View or set the gateway
No. Menu Property Unit Description1 Evap Dsn EWT R °C Reserved2 Evap Dsn LWT R °C Reserved3 Rated Cap R Tons Reserved
No. Menu Property Unit Description1 Pwd Disable R -- View whether the menu password function is disabled
DAIKIN Air-Cooled Screw Chiller/Heat Pump
80
View/Set Circuit
Data
Choose the View/Set Circuit menu in the main menu, press the knob to view and set operation parameters for the circuit. Step 1: The View/Set Circuit menu is as follows:
6 Main Menu 4/15
Enter Password ► Quick menu ► View/Set Unit ► View/Set Circuit ►
6 View/Set Circuit 1/2
Circuit #1 ► Circuit #2 ►
6 Main Menu 11/15
Evap LWT= 20.0°C Unit Capacity = 00.0% Unit Mode = Cool Time Until Restart ►
6 Time Until Restart 1/2
C1 Cycle Tm Left 0s
C2 Cycle Tm Left 0s
6 Main Menu 13/15 Unit Mode = cool Time Until Restart ► Alarms ► Scheduled Maintenance ►
6 Scheduled Maintenance 1/3
Next Maint= Nov 2010
Support Reference= 999+555-5555
6 Main Menu 14/15
Time Until Restart ► Alarms ► Scheduled Maintenance ► About Chiller ►
Step 2: Press the knob to enter the View/Set Circuit menu:
6 Main Menu 4/15
Enter Password ► Quick menu ► View/Set Unit ► View/Set Circuit ►
6 View/Set Circuit 1/2
Circuit #1 ► Circuit #2 ►
6 Main Menu 11/15
Evap LWT= 20.0°C Unit Capacity = 00.0% Unit Mode = Cool Time Until Restart ►
6 Time Until Restart 1/2
C1 Cycle Tm Left 0s
C2 Cycle Tm Left 0s
6 Main Menu 13/15 Unit Mode = cool Time Until Restart ► Alarms ► Scheduled Maintenance ►
6 Scheduled Maintenance 1/3
Next Maint= Nov 2010
Support Reference= 999+555-5555
6 Main Menu 14/15
Time Until Restart ► Alarms ► Scheduled Maintenance ► About Chiller ►
After selecting circuit #1 or #2, then the key parameters or status of the circuit show. See the following table:
No. Menu Unit Description1 Data ► View key operation parameters of circuit #1 and #2. For details, see 9.3.3.1 2 Status/Settings ► View the status and parameter settings of circuit #1 and #2. For details, see 9.3.3.2 3 Comp 1/2 ► View parameter settings for compressor 1/2. For details, see 9.3.3.3 4 Condenser 1/2 ► View parameter settings for condenser 1/2. For details, see 9.3.3.4
No. Menu Property Unit Description1 Evap Pressure R kPa View the evaporating pressure of circuit #1 or #2. 2 Cond Pressure R kPa View the condensing pressure of circuit #1 or #2. 3 Suction temp R °C View the suction temperature of circuit #1 or #2. 4 Discharge temp R °C View the discharge temperature of circuit #1 or /#2. 5 Suction SH R °C View the suction gas superheat of circuit #1 or /#2. 6 Discharge SH R °C View the discharge gas superheat of circuit #1 or /#2. 7 Oil Pressure R kPa View the oil pressure of circuit #1 or #2.
8 Oil Pr Diff R kPa View the oil pressure difference between circuit #1 or /#2, namely discharge pressure minus oil pressure.
9 EXV Position R % View the EXV opening of circuit #1 or #2.
DAIKIN Air-Cooled Screw Chiller/Heat Pump
81
Status/Settings
Comp 1/2
Time Until Restart
Condenser 1/2
No. Menu Property Unit Description
1 Circuit Status R --
View the status of circuit #1 or #2: Off: ReadyOff: Stage Up DelayOff: Cycle TimerOff : BAS DisableOff: Keypad DisableOff : Circuit Switch Off: Refr In Oil SumpOff: AlarmOff: Test ModeEXV: Preopen Run: PumpdownRun: NormalRun: Disch SH LowRun: Evap Press LowRun: Cond Press High Run: High LWT LimitRun: Defrost
2 Circuit Mode R -- View the mode of circuit #1 or #2. The default value is “Enable”, it means the corresponding circuit can start
3 Circuit Cap R % View the capacity of circuit #1 or #2
No. Menu Property Unit Description1 Size R -- View the model of the compressor2 Run Hours R hour View the running hours of compressor 1/2 3 No. Of Starts R -- View the number of starts of compressor 1/2 4 Capacity R % View the capacity of compressor 1/2
No. Menu Property Unit Description1 No. Of Fans running R -- View the number of running fans of the circuit.2 No. Of Fans R -- View the number of total fans of the circuit.
Choose the Time Until Restart menu in the main menu, press the knob to view the remaining time to restart for the system. Step 1: The Remaining time to restart is as follows:
6 Main Menu 4/15
Enter Password ► Quick menu ► View/Set Unit ► View/Set Circuit ►
6 View/Set Circuit 1/2
Circuit #1 ► Circuit #2 ►
6 Main Menu 11/15
Evap LWT= 20.0°C Unit Capacity = 00.0% Unit Mode = Cool Time Until Restart ►
6 Time Until Restart 1/2
C1 Cycle Tm Left 0s
C2 Cycle Tm Left 0s
6 Main Menu 13/15 Unit Mode = cool Time Until Restart ► Alarms ► Scheduled Maintenance ►
6 Scheduled Maintenance 1/3
Next Maint= Nov 2010
Support Reference= 999+555-5555
6 Main Menu 14/15
Time Until Restart ► Alarms ► Scheduled Maintenance ► About Chiller ►
DAIKIN Air-Cooled Screw Chiller/Heat Pump
82
Step 2: Press the knob to enter the Time Until Restart menu:
6 Main Menu 4/15
Enter Password ► Quick menu ► View/Set Unit ► View/Set Circuit ►
6 View/Set Circuit 1/2
Circuit #1 ► Circuit #2 ►
6 Main Menu 11/15
Evap LWT= 20.0°C Unit Capacity = 00.0% Unit Mode = Cool Time Until Restart ►
6 Time Until Restart 1/2
C1 Cycle Tm Left 0s
C2 Cycle Tm Left 0s
6 Main Menu 13/15 Unit Mode = cool Time Until Restart ► Alarms ► Scheduled Maintenance ►
6 Scheduled Maintenance 1/3
Next Maint= Nov 2010
Support Reference= 999+555-5555
6 Main Menu 14/15
Time Until Restart ► Alarms ► Scheduled Maintenance ► About Chiller ►
No. Menu Property Unit Description1 C1 Cycle Tm Left R s View the remaining time before compressor 1 can be restarted 2 C2 Cycle Tm Left R s View the remaining time before compressor 2 can be restarted
Scheduled Maintenance
Choose the Scheduled Maintenance in the main menu, press the knob to check the information about scheduled maintenance. Step 1: The Scheduled Maintenance is as follows:
6 Main Menu 4/15
Enter Password ► Quick menu ► View/Set Unit ► View/Set Circuit ►
6 View/Set Circuit 1/2
Circuit #1 ► Circuit #2 ►
6 Main Menu 11/15
Evap LWT= 20.0°C Unit Capacity = 00.0% Unit Mode = Cool Time Until Restart ►
6 Time Until Restart 1/2
C1 Cycle Tm Left 0s
C2 Cycle Tm Left 0s
6 Main Menu 13/15 Unit Mode = cool Time Until Restart ► Alarms ► Scheduled Maintenance ►
6 Scheduled Maintenance 1/3
Next Maint= Nov 2010
Support Reference= 999+555-5555
6 Main Menu 14/15
Time Until Restart ► Alarms ► Scheduled Maintenance ► About Chiller ►
Step 2: Press the knob to enter the Scheduled Maintenance menu:
6 Main Menu 4/15
Enter Password ► Quick menu ► View/Set Unit ► View/Set Circuit ►
6 View/Set Circuit 1/2
Circuit #1 ► Circuit #2 ►
6 Main Menu 11/15
Evap LWT= 20.0°C Unit Capacity = 00.0% Unit Mode = Cool Time Until Restart ►
6 Time Until Restart 1/2
C1 Cycle Tm Left 0s
C2 Cycle Tm Left 0s
6 Main Menu 13/15 Unit Mode = cool Time Until Restart ► Alarms ► Scheduled Maintenance ►
6 Scheduled Maintenance 1/3
Next Maint= Nov 2010
Support Reference= 999+555-5555
6 Main Menu 14/15
Time Until Restart ► Alarms ► Scheduled Maintenance ► About Chiller ►
No. Menu Property Unit Description1 Next Maint R/W -- View the next maintance time 2 Support Reference R -- View the telephone number of technical support personnel
About Chiller
Choose the About Chiller in the main menu, press the knob to check the relevant data of the unit. Step 1: The About Chiller is as follows:
6 Main Menu 4/15
Enter Password ► Quick menu ► View/Set Unit ► View/Set Circuit ►
6 View/Set Circuit 1/2
Circuit #1 ► Circuit #2 ►
6 Main Menu 11/15
Evap LWT= 20.0°C Unit Capacity = 00.0% Unit Mode = Cool Time Until Restart ►
6 Time Until Restart 1/2
C1 Cycle Tm Left 0s
C2 Cycle Tm Left 0s
6 Main Menu 13/15 Unit Mode = cool Time Until Restart ► Alarms ► Scheduled Maintenance ►
6 Scheduled Maintenance 1/3
Next Maint= Nov 2010
Support Reference= 999+555-5555
6 Main Menu 14/15
Time Until Restart ► Alarms ► Scheduled Maintenance ► About Chiller ►
DAIKIN Air-Cooled Screw Chiller/Heat Pump
83
Step 2: Press the knob to enter the About Chiller menu:
6 About Chiller 1/6
BSP version = 9.20
App Version = MHS010V1.12
6 Main Menu 15/15
Alarms ► Scheduled Maintenance ► About Chiller ► Language Selection ►
6 Language Selection 1/1
Current Language English
No. Menu Property Unit Description
1 BSP version R -- View the BSP version. BSP refers to Board Support Package. The version number must be 9.20 or higher.
2 App Version R -- View the application program version.
Language Selection
Choose the Language Selection in the main menu, press the knob to select a language. It supports two languages, English and Chinese. Step 1: The Language Selection is as follows:
6 About Chiller 1/6
BSP version = 9.20
App Version = MHS010V1.12
6 Main Menu 15/15
Alarms ► Scheduled Maintenance ► About Chiller ► Language Selection ►
6 Language Selection 1/1
Current Language English
Step 2: Press the knob to enter the Language Selection menu:
6 About Chiller 1/6
BSP version = 9.20
App Version = MHS010V1.12
6 Main Menu 15/15
Alarms ► Scheduled Maintenance ► About Chiller ► Language Selection ►
6 Language Selection 1/1
Current Language English
Press the knob to confirm the setting. Then return to previous level menu.
● Daikin Industries, Ltd.’s products are manufactured for export to numerous countries throughout the world. Daikin Industries, Ltd. does not have control over which products are exported to and used in a particular country. Prior to purchase, please therefore confirm with your local authorized importer, distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for use, in the region where the product will be used. This statement does not purport to exclude, restrict or modify the application of any local legislation.
● Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
● Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorized parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.
● Read the User’s Manual carefully before using this product. The User’s Manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
Warning
The air conditioners manufactured by Daikin Industries have received ISO 9001 series certification for quality assurance.
Certificate Number. 9601019
The airconditioning factories of Daikin Industries have received environmental management system standard ISO 14001 certification.
Certificate Number. EMS80362
Cautions on product corrosion 1. The units should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced. 2. If the unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the
unit close to the sea shore, contact your local distributor.