TFC Product data sheet Circular spigot with lip seal Internal measuring tube to sample particles for measurement Low-leakage shut-off damper, manually adjustable Damper unit for volume flow rate balancing (optional) H Y G I E N I S C H G E T E S T E T V D I 6 0 2 2 Tested to VDI 6022 Particulate filter air terminal devices TFC For critical air cleanliness and critical hygiene requirements, suitable for ceiling installation Ceiling mounted particulate filters as a final filter stage with Mini Pleat filter panels for the separation of suspended particles. Used in medicine, biology, the pharmaceuticals industry, and sensitive technical areas. ■ Easy, time-saving and secure filter change, can be completed by one person due to special press-in frame ■ Robust, welded construction ■ Compact construction, suitable for low ceilings, integration with all clean room ceiling systems of various manufacturers ■ Various air terminal devices to ideally meet individual requirements ■ Horizontal (circular, rectangular) or vertical (circular) connection ■ Choice of low-leakage shut-off damper or volume flow limiter for horizontal connection ■ Equipment for differential pressure measurement, sealing integrity testing, and particle sampling for measurement ■ For air cleanliness classes 5 to 8 according to ISO 14644-1 ■ Meets the hygiene requirements of VDI 6022 ■ Leakage class: DIN EN 1886 L1, DIN EN 15727 class D 1 / 25 PD-02/2022 - DE/en
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
TFCProduct data sheet
Circular spigot with lip seal
Internal measuring tube to sample particles for measurement
Low-leakage shut-off damper, manually adjustable
Damper unit for volume flow rate balancing (optional)
HYG
IENISCH GETESTET
VDI 6022
Tested to VDI 6022
Particulate filter air terminal devicesTFC
For critical air cleanliness and critical hygiene requirements, suitable for ceiling installation
Ceiling mounted particulate filters as a final filter stage with Mini Pleat filter panels for the separation of suspended particles. Used in medicine, biology, the pharmaceuticals industry, and sensitive technical areas.■ Easy, time-saving and secure filter change, can be completed by one person due
to special press-in frame■ Robust, welded construction■ Compact construction, suitable for low ceilings, integration with all clean room
ceiling systems of various manufacturers■ Various air terminal devices to ideally meet individual requirements■ Horizontal (circular, rectangular) or vertical (circular) connection■ Choice of low-leakage shut-off damper or volume flow limiter for horizontal
connection■ Equipment for differential pressure measurement, sealing integrity testing, and
particle sampling for measurement■ For air cleanliness classes 5 to 8 according to ISO 14644-1■ Meets the hygiene requirements of VDI 6022■ Leakage class: DIN EN 1886 L1, DIN EN 15727 class D
1 / 25 PD-02/2022 - DE/en
TFCProduct data sheet
General information 2Function 3Specification text 4Order code 5
Variants 6Dimensions 10Product details 24
General information
▪
▪
▪▪▪
▪
▪
▪▪
▪
▪
▪▪▪
▪▪
▪▪▪
▪▪▪▪▪▪▪▪
▪▪
▪▪▪▪▪▪
▪▪
▪
▪▪
▪
▪
▪
▪
▪
▪
▪
▪
▪▪
▪
ApplicationParticulate filter air terminal device for ceiling installation as a final filter stage and for air distributionFitting of filter elements for the separation of suspended particles such as aerosols, toxic dusts, viruses, bacteria from the supply or extract air.
Special featuresCompact constructionEasy operationHigh operational reliability
ClassificationVariants SC, TC, and SR conform to hygiene requirements
Nominal sizes400, 500, 600, 625, 680 [mm]
VariantsSC: Side entry circular spigotSC00H: Side entry circular spigot, manually adjustable shut-off damperSCTN0: Side entry circular spigot, shut-off damper with pneumatic actuatorSCBR0: Side entry circular spigot, shut-off damper with electric actuator 24 – 240 V ACSCVFL: Side entry circular spigot, volume flow limiterTC: Top entry circular spigotSR: Side entry rectangular spigot
ConstructionSPC: Powder-coated steel, RAL 9010, pure whiteSTA: Stainless steel (only for SC, TC, SR)
Parts and characteristicsPneumatic actuator: control pressure 0.6 – 1.0 barElectric actuator: mains connection 24 – 240 V, 50 HzVolume flow limiter: factory set to a reference flow rate, can be readjusted within a volume flow rate range of > 5 : 1
Air terminal devicesADLQ: Ceiling diffuserDLQ: Ceiling diffuserFD: Ceiling swirl diffuserTDF: Ceiling swirl diffuserFDF: Ceiling swirl diffuserVDW: Ceiling swirl diffuserDLQLF: Ceiling diffuserDLQL: Ceiling swirl diffuser with baffle element made of acoustic fleecePCD: PROCONDIF® air terminal deviceAIRNAMIC: Ceiling swirl diffuser
OptionsD: Spigot diameterM: Damper unit for volume flow rate balancing2: Installation subframe with 2 fixing points4: Installation subframe with 4 fixing pointsT: Top suspension and measurement pointsS: Side suspension and measurement points
Useful additionsMini Pleat filter panels (MFP)Suitable filter elements to be ordered separately
Construction featuresClamping mechanism with 2 fixing points for filter elements; 4 fixing points as an optionSealing integrity test facility to check the filter functionPressure measurement points to monitor the differential operating pressure
Materials and surfacesCasing made of either sheet steel, powder-coated, RAL 9010, pure white, or of stainless steel for variants SC, TC and SRAir terminal devices made of sheet steel, powder-coated, RAL 9010 (pure white), types DLQ, FD, TDF, VDW, DLQLF, DLQL, made from extruded aluminium sections type ADLQ with anodised finish, or from stainless steel type FDFAir terminal device made of sheet steel, powder-coated RAL 9010 (pure white, matt); type PCD with internal part made of PP plastic, RAL 9010 (pure white)Air terminal device made of high-quality ABS plastic, RAL 9010 (pure white), type AIRNAMIC
Standards and guidelinesHygiene meets the requirements of VDI 6022, VDI 3803, DIN 1946 Part 4, ÖNORM H 6021 and ÖNORM H 6020, SWKI VA 104-01 and SWKI 99-3, and EN 13779Leakage class: DIN EN 1886 L1, DIN EN 15727 class D
MaintenanceFor constructions with shut-off damper, the filter change and other maintenance work can be carried out without disturbance to the system operationAir terminal devices with central fixing facilitate removal for filter change and decontamination
Installation and commissioningFitting of filter elements with flat seal or fluid sealThe filter element is pressed into place using 2 or 4 (optional) easy-to-handle clampsAir terminal device with central fixing (to be provided by others)
2 / 25 PD-02/2022 - DE/en
TFCProduct data sheet
Function
Schematic illustration of TFC-SCBR0
①
⑥
⑤
②
③
④
① Top pressure measurement point② Top suspension③ Filter element with flat seal④ Clamping mechanism for the filter element⑤ Internal measuring tube⑥ Spigot with lip seal
3 / 25 PD-02/2022 - DE/en
TFCProduct data sheet
Specification text
This specification text describes the general characteristics of the product. Texts for variants can be generated with our Easy Product Finder design program.
▪▪▪
▪
▪
▪
▪
▪▪
Specification textParticulate filter air terminal device type TFC for ceiling installation as final filter stage and for air distribution. Fitting of filter elements for the separation of suspended particles such as aerosols, toxic dusts, viruses and bacteria from the supply or extract air.Casing with side entry or top entry spigot. As standard, ceiling mounted particulate filters with circular spigots are fitted with a lip seal. With optional manually adjustable low-leakage shut-off damper, pneumatic or electric actuator, or volume flow limiter.The filter elements are pressed into place by an installation subframe with two or four (optional) fixing points. As standard, the casings are equipped with a sealing integrity test facility, internal measuring tube, and pressure measurement point for monitoring the operating differential pressure. Suspension and pressure measurement points either at the side or at the top. For fitting Mini Pleat filter panels with a flat seal or a fluid seal. Leakage test for each casing.
Special featuresCompact constructionEasy operationHigh operational reliability
Materials and surfacesCasing made of either sheet steel, powder-coated RAL 9010, pure white, or of stainless steel for variants SC, TC and SRAir terminal devices made of sheet steel, powder-coated RAL 9010 (pure white), types DLQ, FD, TDF, VDW, DLQLF, DLQL, made from extruded aluminium sections type ADLQ with anodised finish, or from stainless steel type FDFAir terminal device made of sheet steel, powder-coated RAL 9010 (pure white, matt); type PCD with internal part made of PP plastic, RAL 9010 (pure white)Air terminal device made of high-quality ABS plastic, RAL
ConstructionsSPC: Steel, powder-coated RAL 9010, pure whiteSTA: Stainless steel (only for SC, TC, SR)
TFC–SC–SPC–VDW/600×24×248×344/M/2/SVariant Side entry circular spigotCasing material Steel, powder-coated, RAL 9010, pure whiteAir terminal device VDWNominal size 600 mm × 24 bladesSpigot diameter 248 mmCasing height 344 mmDamper unit For volume flow rate balancingFixing points Installation subframe with 2 fixing pointsSuspension/measurement points Side arrangement
5 / 25 PD-02/2022 - DE/en
TFCProduct data sheet
Variants
▪▪
Ceiling mounted particulate filter, variant TFC-SC with air terminal device AIRNAMIC
Casing with circular spigotSide entry spigot
▪▪▪
Ceiling mounted particulate filter, variant TFC-SC00Hwith air terminal device VDW
Casing with circular spigotSide entry spigotShut-off damper, manually adjustable
6 / 25 PD-02/2022 - DE/en
TFCProduct data sheet
▪▪▪▪
Ceiling mounted particulate filter, variant TFC-SCTN0 with air terminal device DLQLF
Casing with circular spigotSide entry spigotShut-off damper with pneumatic actuatorControl pressure 0.6 to 1.0 bar
▪▪▪▪
Ceiling mounted particulate filter, variant TFC-SCBR0 with air terminal device FD
Casing with circular spigotSide entry spigotShut-off damper with electric actuatorSupply voltage 24 to 240 V AC
7 / 25 PD-02/2022 - DE/en
TFCProduct data sheet
▪▪▪▪▪
Ceiling mounted particulate filter, variant TFC-SCVFL with air terminal device TDF
Casing with circular spigotSide entry spigotVolume flow limiter, Type VFLFactory set to a reference volume flow rateCan be adjusted within a volume flow rate range of >5 : 1
▪▪
Ceiling mounted particulate filter, variant TFC-TC with air terminal device PCD
Casing with circular spigotTop entry spigot
8 / 25 PD-02/2022 - DE/en
TFCProduct data sheet
▪▪
Ceiling mounted particulate filter, variant TFC-SRwith air terminal device DLQ
Casing with rectangular spigotSide entry spigot
9 / 25 PD-02/2022 - DE/en
TFCProduct data sheet
Product specific data TFC-SCAll weights are net, without packaging
G1, S, G + 40 mm for air terminal devices DLQL and PCD① Nominal size ② Filter size ③ Spigot diameter ④ Casing height ⑤ Overall dimensions of air terminal device ⑥ Overall dimensions of casing ⑦ Overall dimensions of casing flange ⑧ Top suspension, screw hole pitch ⑨ Flange width ⑩ Casing overhang ⑪ Distance to casing flange ⑫ Dimensions to centre line of spigot ⑬ ~ Weight
Dimensions
TFC-SC
X
□L
□M
G1
□J
F
TFC-SC, side view
U 40
G
SØ
D
10 / 25 PD-02/2022 - DE/en
TFCProduct data sheet
Product specific data TFC-SC for AIRNAMICAll weights are net, without packaging
① Nominal size ② Filter size ③ Spigot diameter ④ Casing height ⑤ Overall dimensions of air terminal device ⑥ Overall dimensions of casing ⑦ Overall dimensions of casing flange ⑧ Top suspension, screw hole pitch ⑨ Flange width ⑩ Casing overhang ⑪ Distance to casing flange ⑫ Dimensions to centre line of spigot ⑬ ~ Weight
11 / 25 PD-02/2022 - DE/en
TFCProduct data sheet
Product specific data TFC-SC00HAll weights are net, without packaging
G1, S, G + 40 mm for air terminal devices DLQL and PCD① Nominal size ② Filter size ③ Spigot diameter ④ Casing height ⑤ Overall dimensions of air terminal device ⑥ Overall dimensions of casing ⑦ Overall dimensions of casing flange ⑧ Top suspension, screw hole pitch ⑨ Flange width ⑪ Distance to casing flange ⑫ Dimensions to centre line of spigot ⑬ ~ Weight
TFC-SC00H
□L
□MG
1
□J
F
X
TFC-SC00H, side view
120
ØD
G
S
37
X
12 / 25 PD-02/2022 - DE/en
TFCProduct data sheet
Product specific data TFC-SC00H for AIRNAMICAll weights are net, without packaging
① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ ⑪ ⑫ ⑬TFC B × H × T ∅D G₁ K M J L F S G kg600 535 × 535 × 78/91 200 423 598 561 563 520 49 308 32625 575 × 575 × 78/91 200 428 623 601 603 560 54 313 33
① Nominal size ② Filter size ③ Spigot diameter ④ Casing height ⑤ Overall dimensions of air terminal device ⑥ Overall dimensions of casing ⑦ Overall dimensions of casing flange ⑧ Top suspension, screw hole pitch ⑨ Flange width ⑪ Distance to casing flange ⑫ Dimensions to centre line of spigot ⑬ ~ Weight
13 / 25 PD-02/2022 - DE/en
TFCProduct data sheet
Product specific data TFC-SCTN0All weights are net, without packaging
G1, S, G + 40 mm for air terminal devices DLQL and PCD① Nominal size ② Filter size ③ Spigot diameter ④ Casing height ⑤ Overall dimensions of air terminal device ⑥ Overall dimensions of casing ⑦ Overall dimensions of casing flange ⑧ Top suspension, screw hole pitch ⑨ Flange width ⑫ Dimensions to centre line of spigot ⑬ ~ Weight
TFC-SCTN0
□L
□MG
1
□J
F
X
TFC-SCTN0, side view
ØD
47
G
TFC-SCTN0, construction for filter size 345 × 345
□L
□M
G1
□J
F
65
X
TFC-SCTN0, construction for filter size 345 × 345, side view
ØD
47
G89
X
14 / 25 PD-02/2022 - DE/en
TFCProduct data sheet
Product specific data TFC-SCTN0 for AIRNAMICAll weights are net, without packaging
① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ ⑫ ⑬TFC B × H × T ∅D G₁ K M J L F G kg600 535 × 535 × 78/91 200 423 598 561 563 520 308 34625 575 × 575 × 78/91 200 428 623 601 603 560 313 35
① Nominal size ② Filter size ③ Spigot diameter ④ Casing height ⑤ Overall dimensions of air terminal device ⑥ Overall dimensionsof casing ⑦ Overall dimensions of casing flange ⑧ Top suspension, screw hole pitch ⑨ Flange width ⑫ Dimensions to centre line of spigot ⑬ ~ Weight
15 / 25 PD-02/2022 - DE/en
TFCProduct data sheet
Product specific data TFC-SCBR0All weights are net, without packaging
G1, S, G + 40 mm for air terminal devices DLQL and PCD① Nominal size ② Filter size ③ Spigot diameter ④ Casing height ⑤ Overall dimensions of air terminal device ⑥ Overall dimensionsof casing ⑦ Overall dimensions of casing flange ⑧ Top suspension, screw hole pitch ⑨ Flange width ⑫ Dimensions to centre line of spigot ⑬ ~ Weight
TFC-SCBR0
□L
□MG
1
□J
F
X
TFC-SCBR0, side view
ØD
47
G
TFC-SCBR0, construction for filter size 345 × 345
□L
□M
G1
□J
F
65
X
TFC-SCBR0, construction for filter size 345 × 345, side view
ØD
47
G89
16 / 25 PD-02/2022 - DE/en
TFCProduct data sheet
Product specific data TFC-SCBR0 for AIRNAMICAll weights are net, without packaging
① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ ⑫ ⑬TFC B × H × T ∅D G₁ K M J L F G kg600 535 × 535 × 78/91 200 423 598 561 563 520 308 34625 575 × 575 × 78/91 200 428 623 601 603 560 313 35
① Nominal size ② Filter size ③ Spigot diameter ④ Casing height ⑤ Overall dimensions of air terminal device ⑥ Overall dimensions of casing ⑦ Overall dimensions of casing flange ⑧ Top suspension, screw hole pitch ⑨ Flange width ⑫ Dimensions to centre line of spigot ⑬ ~ Weight
17 / 25 PD-02/2022 - DE/en
TFCProduct data sheet
Product specific data TFC-SCVFLAll weights are net, without packaging
G1, S, G + 40 mm for air terminal devices DLQL and PCD① Nominal size ② Filter size ③ Spigot diameter ④ Casing height ⑤ Overall dimensions of air terminal device ⑥ Overall dimensions of casing ⑦ Overall dimensions of casing flange ⑧ Top suspension, screw hole pitch ⑨ Flange width ⑫ Dimensions to centre line of spigot ⑬ ~ Weight
TFC-SCVFL
□L
□MG
1
□J
F
X
TFC-SCVFL, side view
ØD
50
G
18 / 25 PD-02/2022 - DE/en
TFCProduct data sheet
Product specific data TFC-SCVFL for AIRNAMICAll weights are net, without packaging
① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ ⑫ ⑬TFC B × H × T ∅D G₁ K M J L F G kg600 535 × 535 × 78/91 250 473 598 561 563 520 333 33625 575 × 575 × 78/91 250 478 623 601 603 560 338 34
① Nominal size ② Filter size ③ Spigot diameter ④ Casing height ⑤ Overall dimensions of air terminal device ⑥ Overall dimensions of casing ⑦ Overall dimensions of casing flange ⑧ Top suspension, screw hole pitch ⑨ Flange width ⑫ Dimensions to centre line of spigot ⑬ ~ Weight
19 / 25 PD-02/2022 - DE/en
TFCProduct data sheet
Product specific data TFC-TCAll weights are net, without packaging
G1, S, G + 40 mm for air terminal devices DLQL and PCD① Nominal size ② Filter size ③ Spigot diameter ④ Casing height ⑤ Overall dimensions of air terminal device ⑥ Overall dimensionsof casing ⑦ Overall dimensions of casing flange ⑧ Top suspension, screw hole pitch ⑨ Flange width ⑬ ~ Weight
TFC-TC
□L
□MG
1
□J
F
X
TFC-TC, side view
ØD
20 / 25 PD-02/2022 - DE/en
TFCProduct data sheet
Product specific data TFC-TC for AIRNAMICAll weights are net, without packaging
G1, S, G + 40 mm for air terminal devices DLQL and PCD① Nominal size ② Filter size ③ Spigot diameter ④ Casing height ⑤ Overall dimensions of air terminal device ⑥ Overall dimensionsof casing ⑦ Overall dimensions of casing flange ⑧ Top suspension, screw hole pitch ⑨ Flange width ⑫ Dimensions to centre line of spigot ⑬ ~ Weight ⑭ Overall dimensions of flange ⑮ Number of flange screw holes × screw hole pitch ⑯ Overall dimensions over spigot
TFC-SR
□L
□M
G1
□J
F
A
X
TFC-SR, side view
E
98 148
G
X
TFC-SR flange dimensions
n x t
A 25
124
98 148
Ø6,5n x t
A
M25
25
124
98 148
Ø6.8
22 / 25 PD-02/2022 - DE/en
TFCProduct data sheet
Product specific data TFC-SR for AIRNAMICAll weights are net, without packaging
① ② ④ ⑤ ⑥ ⑦ ⑧ ⑨ ⑫ ⑬ ⑭ ⑮ ⑯TFC B × H × T G₁ K M J L F G kg A n × t E600 535 × 535 × 78/91 294 598 561 563 520 244 22 608 4 × 146 591600 535 × 535 × 150 366 598 561 564 520 316 22 608 4 × 146 591625 575 × 575 × 78/91 299 623 601 603 560 249 23 648 4 × 156 631625 575 × 575 × 150 371 623 601 604 560 321 23 648 4 × 156 631
① Nominal size ② Filter size ③ Spigot diameter ④ Casing height ⑤ Overall dimensions of air terminal device ⑥ Overall dimensions of casing ⑦ Overall dimensions of casing flange ⑧ Top suspension, screw hole pitch ⑨ Flange width ⑫ Dimensions to centre line of spigot ⑬ ~ Weight ⑭ Overall dimensions of flange ⑮ Number of flange screw holes × screw hole pitch ⑯ Overall dimensions over spigot
23 / 25 PD-02/2022 - DE/en
TFCProduct data sheet
Product details
▪▪▪
Fitting of filter elements with flat seal or fluid sealThe filter element is pressed into place using 2 or 4 (optional) easy-to-handle clampsAir terminal device with central fixing (to be provided by others)
Detail X – AIRNAMIC air terminal device
□K
□J
□M
Detail X – various air terminal devices
□J
□M
□K
Sealing integrity test facility
①
②
③
① Test groove② Filter seal③ Connection for sealing integrity testing
Internal measuring tube
①
②
① Measuring tube Ø 8 x 1.5 mm② Cheese head screw M6 x 10 mm
24 / 25 PD-02/2022 - DE/en
TFCProduct data sheet
Top suspension and measurement points
50① ③ ②
① Suspension② Measurement point on upstream side (plus)③ Measurement point on downstream side (minus)
Side suspension and measurement points
①
②
③
① Suspension② Measurement point on upstream side (plus)③ Measurement point on downstream side (minus)