PARADIP PORT TRUST INVITATION OF BUDGETARY OFFER FOR UP-GRADATION OF POWER SUPPLY NETWORK TO ADMINISTRATIVE BUILDING. SUBMISSION OF BUDGETARY OFFER ON OR BEFORE Dt.16/07/2019 EXECUTIVE ENGINER (ELECT.) PORT ELECTRICAL DIVISION – III PARADIP PORT TRUST, PARADIP, JAGATSINGHPUR, ODISHA – 754142 Contact No.9861244414 Email Id: [email protected]
21
Embed
PARADIP PORT TRUST INVITATION OF BUDGETARY OFFER FOR
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
PARADIP PORT TRUST
INVITATION OF BUDGETARY OFFER
FOR
UP-GRADATION OF POWER SUPPLY NETWORK TO ADMINISTRATIVE BUILDING.
Sub.: Up-gradation of Power Supply Network to Administrative Building.
Sl. No.
Description of Work Qty. Unit Rate (Rs.)
Amount (Rs.)
Remarks
(A) SUPPLY PART:
1 Supply of plinth mounted indoor type LT ACB panel board comprising of the followings switchgears and as per the specifications mentioned in the scope of work.
[i] As incoming:- one no. 2000 Amp, 4 Pole, 65 KA microprocessor based ACB with 4 nos. of Copper bus-bar of 2000 Amp. Rating.
[ii] As outgoing:- (a) One 1000 Amp., 4 Pole, ACB, (b) One 800 Amp., 4 Pole, ACB and (c) One 630 Amp., 4 Pole ACB.
Approximate size of panel: [3000 (L) X 550 (W) X 1800 (H)] mm
1 No.
2 Supply of plinth mounted indoor type LT Changeover panel comprising of the followings switchgears and as per the specifications mentioned in the scope of work.
[i] As incoming:- one no. 1250 Amp, 4 Pole, 415 volt, 50 Hz Changeover and 4 nos. of Copper bus-bar
[ii] As outgoing:- (a) 2 nos. 630 Amp, 4 Pole MCCB (b) 2 nos. 250 Amp, 4 Pole MCCB.
Approximate size of panel [2000 (L) X 700 (W) X 1800 (H)] mm.
1 No.
3 Supply of plinth mounted indoor type LT ACDB panel comprising of the followings switchgears and as per the specifications mentioned in the scope of work.
[i] As incoming:- one no. 800 Amp, 4 pole microprocessor based ACB with 4 nos. of Copper bus-bar.
[ii] As outgoing:- (a) 4 nos. of 250 Amp. 4 pole, MCCB; (b) 8 nos. of 125 Amp. 4 pole MCCB.
Approximate size of panel [1975 (L) X 550 (W) X 1875 (H)] mm.
1 No.
4 Supply of plinth mounted indoor type LT ACDB panel comprising of the followings switchgears and as per the specifications mentioned in the scope of work.
[i] As incoming:- one no. 630 Amp, 4 pole
microprocessor based ACB with 4 nos. of Copper bus-
bar.
[ii] As outgoing:- (a) 5 nos. of 250 Amp. 4 pole,
MCCB; (b) 5 nos. of 125 Amp. 4 pole, MCCB.
Approximate size of panel [2875 (L) X 550 (W) X 1750 (H)] mm.
1 No.
Sl. No.
Description of Work Qty. Unit Rate (Rs.)
Amount (Rs.)
Remarks
5
Supply of Plinth mounted indoor type LT ACDB panel comprising of the followings switchgears and as per the specifications mentioned in the scope of work.
[i] As incoming: - one no. 400 Amp, 4 pole MCCB with
4 nos. of Copper bus-bar.
[ii] As outgoing: - 4 nos. of 125 Amp. 4 pole, MCCB. Approximate size of panel [760 (L) X 650 (W) X 900 (H)] mm.
1 No.
6
Supply of Plinth mounted indoor type LT ACDB panel comprising of the followings switchgears and as per the specifications mentioned in the scope of work.
[i] As incoming:- one no. 250 Amp, 4 Pole MCCB with
4 nos. of Copper bus-bar.
[ii] As outgoing:- 5 nos. of 125 Amp. 4 pole MCCB. Approximate size of panel [1000 (L) X 300 (W) X 1760 (H)] mm.
3 No.
7 Supply of Plinth mounted indoor type LT ACDB panel comprising of the followings switchgears and as per the specifications mentioned in the scope of work.
[i] As incoming:- one no. 250 Amp, 4 Pole MCCB with
4 nos. of Copper bus-bar.
[ii] As outgoing :- (a) 2 nos. of 125 Amp. 4 pole MCCB; (b) 5 nos. of 20 Amp. 2 pole MCB.
Approximate size of panel [760 (L) X 210 (W) X 610 (H)] mm.
1
No.
8 Supply of Wall mounted indoor type LT ACDB panel comprising of the followings switchgears and as per the specifications mentioned in the scope of work.
[i] As incoming:- one no. 125 Amp, 415 volt, 50 Hz, 36
KA MCCB with 4 nos. of Copper bus-bar.
[ii] As outgoing:- (a) 8 nos. of 32 Amp. 2 pole MCB; (b) 8 nos. of 25 Amp. 2 pole MCB; (c) 8 nos. of 20 Amp. 2 pole, MCB; (d) 8 nos. of 16 Amp. 2 pole, MCB
Approximate size of panel [600 (L) X 300 (W) X 1200 (H)] mm.
3 No.
9 Supply of Wall mounted indoor type LT ACDB panel comprising of the followings switchgears and as per the specifications mentioned in the scope of work.
[i] As incoming: - one no. 63 Amp, 4 Pole MCCB with 4 nos. of Copper bus-bar.
[ii] MCB‟s as outgoing :- (a) 8 nos. of 36 Amp. 2 Pole;
(b) 8 nos. of 25 Amp. 2 Pole; (c) 8 nos. of 20 Amp. 2
pole; (d) 8 nos. of 16 Amp. 2 pole.
Approximate size of panel [600 (L) X 300 (W) X 450 (H)] mm.
9 No.
Sl. No.
Description of Work Qty. Unit Rate (Rs.)
Amount (Rs.)
Remarks
10 Supply of plinth mounted indoor type LT ACDB and Metering panel comprising of the followings switchgears and as per the specifications mentioned in the scope of work.
[i] As incoming :- one no. 630 Amp, 4 Pole MCCB with 4 nos. of Copper bus-bar and
[ii] As outgoing :- 4 nos. of 250 Amp. 4 pole MCCB and three phase digital energy meters with CTs for each out-going feeder.
Approximate size of panel [1800 (L) X 550 (W) X 1700 (H)] mm.
1 No.
11 Supply of plinth mounted indoor type LT Changeover panel comprising of the followings switchgears and as per the specifications mentioned in the scope of work.
[i] As incoming :- one no. 400 Amp, 4 Pole Changeover and 4 nos. of Copper bus-bar.
[ii] As outgoing :- 4 nos. 125 Amp, 4 Pole MCCB.
Approximate size of panel [1500 (L) X 550 (W) X 1700 (H)] mm.
1 No.
12 Supply of 3.5 C x 400 sq.mm, 1.1 KV grade, Galvanised steel strip armoured, XLPE insulated stranded and shaped aluminium conductor cable.
400 Mtr.
(B) EXECUTION PART:
13 Installation of plinth mounted indoor type LT ACB panel comprising of [i] one no. 2000 Amp, 4 Pole microprocessor based ACB as incoming with Copper bus-bar and [ii] (a) One 1000 Amp., 4 Pole ACB, (b) One 800 Amp, 4 Pole ACB and (c) One 630 Amp. 415 volt, 50 Hz, 4 Pole ACB as outgoing and connection of cables as per scope of work.
1
No.
14 Installation of plinth mounted indoor type LT Changeover panel comprising of [i] one no. 1250 Amp, 4 Pole, 415 volt, 50 Hz Changeover and Copper bus-bar [ii] (a) 2 nos. 630 Amp, 4 Pole MCCB; (b) 2 nos. 250 Amp, 4 Pole MCCB as outgoing and connection of cables as per scope of work.
1 No.
15 Dismantling of old panel & installation of new plinth mounted indoor type LT ACDB panel comprising of [i] one no. 800 Amp microprocessor based ACB as incoming with Copper bus-bar and [ii] (a) 4 nos. of 250 Amp. MCCB; (b) 8 nos. of 125 Amp. 4 pole, MCCB as outgoing and connection of cables as per scope of work.
1 No.
16 Dismantling of old panel & installation of plinth mounted indoor type ACDB panel comprising of [i] one no. 630 Amp, microprocessor based ACB as incoming with Copper bus-bar and [ii] (a) 5 nos. of 250 Amp. 4 pole, MCCB; (b) 5 nos. of 125 Amp. 4 pole, MCCB as outgoing and connection of cables as per scope of work.
1 No.
Sl. No.
Description of Work Qty. Unit Rate (Rs.)
Amount (Rs.)
Remarks
17 Dismantling of old panel & installation of Plinth mounted indoor type ACDB panel comprising of [i] one no. 400 Amp, MCCB as incoming with Copper bus-bar and [ii] 4 nos. of 125 Amp. 4 pole, MCCB as outgoing and connection of cables as per scope of work.
1 No.
18 Dismantling of old panel & installation of Plinth mounted indoor type ACDB panel comprising of [i] one no. 250 Amp, MCCB as incoming with Copper bus-bar and [ii] 5 nos. of 125 Amp. 4 pole, MCCB as outgoing and connection of cables as per scope of work.
3 No.
19 Dismantling of old panel & installation of Plinth mounted indoor type ACDB panel comprising of [i] one no. 250 Amp, MCCB as incoming with Copper bus-bar and [ii] (a) 2 nos. of 125 Amp. 4 pole, MCCB; (b) 5 nos. of 20 Amp. 2 pole „C‟ Curve MCB as outgoing and connection of cables as per scope of work.
1 No.
20 Dismantling of old panel & installation of Wall mounted indoor type ACDB panel comprising of [i] one no. 125 Amp MCCB as incoming with Copper bus-bar and [ii] (a) 8 nos. of 32 Amp. 2 pole MCB; (b) 8 nos. of 25 Amp. 2 pole MCB; (c) 8 nos. of 20 Amp. 2 pole MCB; (d) 8 nos. of 16 Amp. 2 pole MCB as outgoing and connection of cables as per scope of work.
3 No.
21 Dismantling of old panel & installation of Wall mounted indoor type ACDB panel comprising of [i] one no. 63 Amp, MCCB as incoming with Copper bus-bar and [ii] (a) 8 nos. of 36 Amp. 2 pole MCB; (b) 8 nos. of 25 Amp. 2 pole MCB; (c) 8 nos. of 20 Amp. 2 pole MCB; (d) 8 nos. of 16 Amp. 2 pole MCB as outgoing and connection of cables as per scope of work.
9 No.
22 Installation of plinth mounted indoor type Metering panel comprising of [i] one no. 630 Amp, MCCB as incoming with Copper bus-bar and [ii] 4 nos. of 250 Amp. 4 pole, MCCB as outgoing and connection of cables as per scope of work.
1 No.
23 Dismantling of old panel & installation of plinth mounted indoor type Changeover panel having one no. 400 Amp, 4 Pole, Changeover and Copper bus-bar along with 4 nos. 125 Amp, 4 Pole MCCB as outgoing and connection of cables as per scope of work.
1 No.
24 Laying of 3.5 C x 400 sq.mm, 1.1 KV grade, Galvanised steel strip armoured, XLPE insulated aluminium conductor cable as per scope of work.