222 TECHNICAL DATA SHEETS RCD INCOMER PANELS | DISTRIBUTION PANELS DESCRIPTION RCD Incomer Panels allow the attachment of modular equipment and the Power Control Device (RCD). In accordance with Standards: EN 62208 / EN 61439-3. Insulation Class: II. White - RAL 9003. Reversible door. Rotary Lever Lock or Keylock option. Distribution Panels allow the attachment of modular equipment. In accordance with Standards: EN 62208 / EN 61439-3. Insulation Class: II. White - RAL 9003. Reversible door. Rotary Lever Lock or Keylock option. DIMENSIONS (mm) FLUSH MOUNTING BOXES FOR PANELS REF. L (mm) A (mm) P (mm) L1 (mm) A1 (mm) P1 (mm) 60004 192 255 113 170 188 92 60008 264 255 113 242 188 92 60012 336 255 113 314 188 92 60016 264 380 113 242 313 92 60024 336 380 113 314 313 92 60032 408 380 113 386 313 92 60040 480 380 113 458 313 92 60048 552 380 113 530 313 92 60060 480 505 113 458 438 92 60080 480 630 113 458 563 92 A A1 L L1 P1 P CHARACTERISTICS Flush Mounting Boxes for Panel Boards were designed to be stackable, fitting into each other to enable each stack of four boxes to occupy the space of two. IP40 IK07 PANELBOARDS General Catalogue 2019/2020
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
222
TECHNICAL DATA SHEETS
RCD INCOMER PANELS | DISTRIBUTION PANELS
DESCRIPTION
� RCD Incomer Panels allow the attachment of modular equipment and the Power Control Device (RCD).
� In accordance with Standards: EN 62208 / EN 61439-3.
� Insulation Class: II.
� White - RAL 9003.
� Reversible door.
� Rotary Lever Lock or Keylock option.
� Distribution Panels allow the attachment of modular equipment.
� In accordance with Standards: EN 62208 / EN 61439-3.
� Insulation Class: II.
� White - RAL 9003.
� Reversible door.
� Rotary Lever Lock or Keylock option.
DIMENSIONS (mm)
FLUSH MOUNTING BOXES FOR PANELS
REF. L (mm) A (mm) P (mm) L1 (mm) A1 (mm) P1 (mm)
60004 192 255 113 170 188 92
60008 264 255 113 242 188 92
60012 336 255 113 314 188 92
60016 264 380 113 242 313 92
60024 336 380 113 314 313 92
60032 408 380 113 386 313 92
60040 480 380 113 458 313 92
60048 552 380 113 530 313 92
60060 480 505 113 458 438 92
60080 480 630 113 458 563 92
AA1
L
L1
P1
P
CHARACTERISTICS
� Flush Mounting Boxes for Panel Boards were designed to be
stackable, fitting into each other to enable each stack of four boxes
to occupy the space of two.
IP40 IK07
PANELBOARDS
General Catalogue 2019/2020
223
TECHNICAL DATA SHEETS
i
RCD INCOMER PANELS | DISTRIBUTION PANELS
MOUNTING DIAGRAM
RCD IN THE RIGHT SIDE RCD IN THE LEFT SIDE
DIN RAIL FIXATION BRASS TERMINALS FIXATION
N - REF. 60904- REF. 60905
L - REF. 60901N - REF. 60902
- REF. 60903
CABLE TIDYING
PANELBOARDS
224
TECHNICAL DATA SHEETS
RCD INCOMER PANELS | DISTRIBUTION PANELS
MOUNTING DIAGRAM
MASKS
ASSEMBLY AND DISMANTLING OF THE DOOR FRAME AND DOOR
1.
2.
90º
Click
Click
ASSEMBLY OF THE ROTARY LEVER LOCK AND KEYLOCK
REF. 60900
REF. 60910
225
TECHNICAL DATA SHEETS
i
RCD INCOMER PANELS | DISTRIBUTION PANELS
� CLASSIFICATION - EN 62208 STANDARD
SECTION 4 CLASSIFICATION PANELBOARDS
a Type of material Insulating
b Means of fixing
Recessed mounting
Not for installation in hollow walls
c Installation Location Interior
d Protection degree
IP40 in accordance with IEC 60529
IK07 in accordance with IEC 62262
e Isolation voltage Ui=400V; nominal intensity: In ≤ 63A with 230/400 V
SECTION 6.3 DOCUMENTATION PANELBOARDS
Permissible loads
Maximum permissible load within the housing is 200 kg/m3
Do not apply loads to the cover.
Lifting devices, where necessary Not applicable
Devices for protection from electrical shock Not applicable, plastic casing
Applicable conditions of use Interior installation: Temperatures between -5º C e +40º C
Data on ability to dissipate thermal energy Maximum interior thermal charge 40W
� SPECIFIC CLASSIFICATION - EN 61439-3 STANDARD
SECTION 5.6 DOCUMENTATION PANELBOARDS
Nominal Frequency (fn) 50Hz
Level of pollution 2
Earth systems TN
Users For use by people without training
EMF environment Type B
Protection for people Isolated command body and insulated casing - class ll insulation
Note:
Should not be mounted in areas of special risk, such as, places subject to variations in temperature and high pressure, with strong magnetic fields, and atmospheres subject to explosions, fires or vibrations and exceptional voltage flluctuations.