    1

  • 7/27/2019 pagar_en2

    3/12

    2 The Installation of Electric Fence 3

    PARTIES WHO NEED TO KNOW ABOUT THE PROCEDURE OF

    INSTALLING THE ELECTRIC FENCE

    THE INSTALLATION OF ELECTRIC FENCE

    All Competent Persons: Engineer, Supervisor, Chargeman, Wireman

    All Registered Electrical Contractors with Energy Commission

    All Utilities: Electric, Water & Telecommunication

    All Government Departments: Federal & State

    All Premise Owners: Commercials or Industrial

    PURPOSEThis booklet is intended to enforce the method of installing the electric fence

    in order to improve the safety level of the installation according to MS IEC

    60335-2-76 standard. This booklet is also to inform of the procedures that

    must be complied with by the applicant in order to obtain approval from the

    Energy Commission on the installation of electric fence.

    BACKGROUND

    Previously the Energy Commission had issued a directive and a circular

    pertaining to the needs and method of installing the electric fence. In line

    with the current technology, the existing directive and previous circular of

    installing the electric fence need to be revised. Therefore, a conducive and

    comprehensive method of installing the electric fence concurrent to the

    international standards needs to be prepared.

    Generally the installation of electric fence installed by some parties is toprevent their properties from being trespassed by intruders either animal or

    human. The types of premises involved in the installation of electric fence are

    those that involve activities related to agriculture and security control such

    as military, power utility, water and others. Therefore, these installations of

    electric fence need to be installed in a control manner and safe in accordance

    to the Electricity Supply Act 1990, Electricity Regulations 1994 and other

    relevant standards so as to prevent the occurrence of on the part of the

    intruder/trespasser.

    COMPLIANCE WITH LEGISLATION

    The proper and safe method of installing the electric fence shall begin

    from the stage of design until the stages of construction, supervision,

    maintenance and monitoring. It needs to be implemented in accordance

    with the requirements of the Electricity Regulations 1994. The respective

    regulations that need to be complied with are as follows:-

    Regulation 15 : Requirement of any conductor for the purpose

    of connection to an installation which shall be constructed, installed,

    arranged, protected, worked and maintained shall be sufficient in size,

    power and number as to prevent danger.

    Regulation 65 : Requirement of competent persons (Part VI of the

    Second Schedule) who shall prepare and submit plans, drawings and

    specifications for voltage/ampere limit of an installation.

    Regulation 68 : Requirement to appoint competent person either an

    Electrical Services Engineer, Competent Electrical Engineer or Electrical

    Supervisor to inspect the electric fence installation.

    Regulation 75 : Requirement to appoint a registered electrical

    contractor with Energy Commission which hold a valid Certificate of

    Registration to perform or carry out the installation of electric fence.

    Regulation 110 : Electric fence installation shall be maintained in

    good, working order and safety precautions shall be observed at all times

    to prevent danger.

  • 7/27/2019 pagar_en2

    4/12

    4 The Installation of Electric Fence 5

    Regulation 111 : Requirement to appoint a competent person or

    a person acting under the control of a competent person who shall

    undertake to carry out any repair, replacement, servicing or cleaning of

    the installation.

    METHODS OF ELECTRIC FENCE INSTALLATION

    To ensure the installation of electric fence is continuously carried out in a

    proper and safe manner, the Energy Commission has provided the method of

    installing the electric fence which complies with standard of MS IEC 60335-

    2-76 Particular requirements for electric fence energizers.

    (Note: MS IEC 60335-2-76 standard can be purchased from SIRIM Berhad)

    Some of the main priorities that need to be emphasized during the construction

    stage of electric fence either of energizer type A, B, C, or D are as stated in

    the clauses and Annexes of MS IEC 60335-2-76 standard as follows:-

    i. Clause 22.108 - Energizer output characteristics shall be such that

    - the impulse repetition rate shall not exceed 1 Hz

    - the impulse duration of the impulse in the 500 component of the

    standard load shall not exceed 10 ms

    - for energy limited energizers the energy/impulse in the 500

    component of the standard load shall not exceed 5 Joule(J)

    Figure 1 : Measurement of voltage value at electric fence (pulse conductor) beingdone using Voltmeter.

    ii. Clause 22.109 -If the energizer is provided with more than one fence

    circuit (sometimes it defines zone), the output characteristics shall

    be within limits in 22.108 for any possible connection of the fence

    circuits. The impulses for the individual sets of output terminals shall

    be synchronized .

    Figure 2 : The use of panel for synchronizing supply system if more than one

    energizer applies.

    Figure 3 : Area which is supplied by more than one different sources of energizershas been synchronized for supply to the electric fence.

  • 7/27/2019 pagar_en2

    5/12

    6 The Installation of Electric Fence 7

    iii. Annex BB Instructions for installation and connection of electric

    fences.

    Annex BB1 & BB2 Requirements for electric animal/securityfences:-

    - Any electric animal/security fence shall not be supplied from two

    separate energizers or from independent fence circuits of the same

    energizer.

    - For any two separate electric animal/security fences, each supplied

    from a separate energizer independently timed, the distances between

    the wires of the two electric animal/security fences shall be at least

    2.0/2.5 m. If this gap is to be closed, this shall be effected by means

    of electrically non-conductive material or an isolated metal barrier.

    Figure 5 : Earthing system for the installation of electric fence

    Figure 6 : Distance of physical barrier shall be at least 2.0 / 2.5 meters if

    receives two supplies from different energizers and both suppliesnot synchronised. (Note: 2.0 m for animal while 2.5 m for security)

    Figure 4 : Lightning protection system and component used

    iv. Annex CC Installation of electric security fences

    Annex CC.2 Location of electric security fence

    - The electric fence should be separated from the public access area

    by means of a physical barrier.

    - Where an electric fence is installed in an elevated position, such as on

    the inner side of a window or skylight, the physical barrier may be less

    than 1.5 m high where it covers the whole of the electric fences. If the

    bottom of the window or skylight is within a distance of 1.5 mfrom the

    floor or access level then the physical barrier need only extend up to

    a height of 1.5 m above the floor or access level.

    (Note: Refer to figures 7, 8 & 9 for examples of physical barrier)

    Figure 7 : A physical barrier type based on a combination of concrete wall andchain-link (wire) constructed at least 1.5 meter height. The pulse

    conductor is installed begins on the concrete wall.

  • 7/27/2019 pagar_en2

    6/12

    8 The Installation of Electric Fence 9

    REMINDER!

    A Competent Electrical Engineer must ensure the installation of electric

    fence under his responsibility is installed in compliance with the standard of

    MS IEC 60335-2-76.

    (Note: The latest version of the standard MS IEC 60335-2-76 needs to be referred to from

    time to time).

    Figure 8 : A physical barrier type of concrete wall constructed at least 1.5 meterheight. The pulse conductor installed begins on the concrete wall.

    Figure 9 : A physical barrier type made of chain-link (steel) been constructed at

    least 1.5 meter height. The pulse conductor installed begins on thesteel.

    OTHER INFORMATION RELATED TO THE INSTALLATION OF ELECTRIC

    FENCE(Figures 10 & 11)

    (Note: The electric fence owned by a premise owner is ONLY allowed to

    be commissioned when it has obtain in the written approval from Energy

    Commission via its regional offices. The procedure of application is as

    Attachment A).

    Figure 10 : The distance comply to the requirement of clauses as Annex CC1 &

    CC4

    Figure 11 : Other components used

  • 7/27/2019 pagar_en2

    7/12

    0 The Installation of Electric Fence 11

    PROCEDURES OF ELECTRIC FENCE APPLICATION

    1. Applicant is required to make application of installing the electric fence

    at the nearest Energy Commission regional office where the installation

    is located. Applicant need to complete the Application of Approval on

    Installation of Electric Fence Form (as Attachment B). This form can

    be downloaded from the ST website. The following are the documents

    required to be enclosed together :-

    i) Name premise / installation owner;

    ii) Address where the electric fence will be installed and the total perimeter

    of the installation

    iii) The registered electrical contractor with ST who will install the electric

    fence;

    iv) Diagrams and specification of the electric fence which shows the

    complete structure of the height, type of equipment, product, signage

    and others. All components and equipment in the diagrams need to

    be clearly labeled. These diagrams need to be signed at least by a

    Competent Electrical Engineer who has been engaged by the owner.

    v) Schematic drawing shows the sources of electric supply to the

    conductivity of wire of the fence, size and type of cable being used.

    This schematic drawing need to be signed at least by a Competent

    Electrical Engineer who has been engaged by the owner.

    vi) The submission of certification and test report for the energizer (type A,

    B, C or D) must comply with the IEC 60335-2-76:2006 standard from

    IEC CB Scheme laboratories or APLAC.

    (Note : Energizer is not a regulated equipment therefore once it imported toMalaysia the importer needs to obtain a release letter from the Customs

    office issued by Energy Commission)

    vii) Once the installation of electric fence ready, it needs to be supervised

    and tested by the competent person who has been engaged by the

    owner. Therefore, the engaged competent person shall submit to

    the Energy Commission the Form G (Supervision and Completion

    Certificate) and Form H (Test Certificate) as required by Regulation 14,

    Electricity Regulations 1994.

    viii) An inspection will be carried out by Energy Commission officers once

    the installation of electric fence is completed. The visit will be carried

    out together with the engaged electrical contractor, the responsible

    Electrical Supervisor/Competent Electrical Engineer and the owner/

    representative of the installation.

    ix) Once the Energy Commissions regional office satisfied on the

    compliance of installing the electric fence, a written approval will be

    issued to the owner. Once the owner has obtained the approval from

    the Energy Commission, the electric fence can start operation or

    commission.

    x) The owner of the electric fence installation shall engage a competent

    person with a minimum of an Electrical Supervisor level to inspect the

    installation at least once every two(2) years. This is to ensure installation

    is always safe. The inspection report needs to be submitted to Energy

    Commission.

    xi) There is no fee imposed for the approval.

    xii) The Energy Commission will cancel the approval letter on the electric

    fence installation if the installation is either :-

    a. no longer being used; or/and

    b. found to be unsafe

    ATTACHMENT A

  • 7/27/2019 pagar_en2

    8/12

    2 The Installation of Electric Fence 13

    2. The flow chart of the summarised procedure for the application on

    installation of electric fence is shown below

    FLOW CHART ON THE PROCEDURE OF ELECTRIC FENCE APPLICATION

    APPLICATION OF APPROVAL ON INSTALLATION OF ELECTRIC FENCE

    UNDER REGULATION 15, ELECTRICITY REGULATION 1994

    ATTACHMENT B

    Name of the owner

    (Either an individual/representative of company

    or agency. If company/agency, name of the

    responsible officer)

    Identification Card No.

    (please submit a photocopy of NRIC)

    No. of Company Registration(only if applicable)

    Address of the owner

    Address of Electric Fence

    Installation(if different from the address of the owner)

    Purpose of installing the electric

    fence

    Duration of the installation

    I understand and acknowledge that the installation of electric fence at the above premise need to

    comply with the Electricity Supply Act 1990 & Electricity Regulations 1994 and the requirements set

    by the Energy Commission.

    Signature of the owner & companys / agencys stamp:

    Date:

    Name of the Company

    Certificate of Registration No. with

    Energy Commission(please submit a copy of vali d certificate)

    Validity date of the certificate

    Part A: INFORMATION ON INSTALLATION

    Part B: INFORMATION ON ELECTRICAL CONTRACTOR

  • 7/27/2019 pagar_en2

    9/12

    4 The Installation of Electric Fence 15

    Approval Application on Installation of Electric Fence under Regulation 15, Electricity Regulations 1994 Approval Application on Installation of Electric Fence under Regulation 15, Electricity Regulations 1994

    Part C: INFORMATION ON ELECTRIC FENCE Part D: APPROVAL / CANCELLATION

    APPROVAL by Energy Commission:

    CANCELLATION of Approval Letter:

    ST Regional Office

    ____________________________________

    ST Regional Office

    __________________

    __________________

    Reasons for cancellation: _______________________________________________________________________________________________________________________

    _______________________________________________________________________

    _______________________________________________________________________

    _______________________________________________________________________

    _______________________________________________________________________

    _______________________________________________________________________

    ______________________________________________________________________

    Date:_________

    Date:_________

    Diagram & specification of electric

    fence structure(please submit each diagram & brochure if

    available)

    Structure of the electric fence Type of energizer (Type A, B, C or D) Wire of fence Certication / test report & STs

    Release Letter on energizeraccording to IEC 60335-2-76:2006or MS IEC 60335-2-76 standard

    Conguration of wiring Conguration of earthing

    Reference:Reference:Reference:Reference:

    Reference:Reference:

    Drawing of site layout(please submit each diagram)

    Fencing layout

    Photos of fence & warning

    signage

    Single-line schematic drawing for

    supply source to energizer

    Single-line schematic drawing for

    output of each energizer circuit

    Reference:

    Reference:

    Reference:

    Reference:

    Signature of Competent Electrical

    Engineer who endorsed the diagram

    & drawing.

    Complete / Incomplete

    Certificate of Competency No.

    Form G (Supervision and

    Completion)need stamp & signature of competent person

    Complete / Incomplete

    Form H (Test)need stamp & signature of competent person

    Complete / Incomplete

    The site visit by ST together with

    electrical contractor and the

    responsible competent person has

    been conducted on the date as

    below:-

    ________________________

    Satisfy / Not satisfy(If not satisfy, please improve the conditions as

    follows:

    (........................

    .......................................................)

    (use attachment if the space is insufficient)

  • 7/27/2019 pagar_en2

    10/12

    6 The Installation of Electric Fence 17

    Regional Office (Pulau Pinang, Kedah & Perlis)

    Tingkat 10, Bangunan KWSP

    13700 Seberang Jaya, Butterworth

    PULAU PINANG

    Tel: 04-398 8255

    Fax: 04-390 0255

    Regional Office (Perak)

    Tingkat 1, Bangunan KWSP

    Jalan Greentown

    30450 Ipoh

    PERAK

    Tel: 05-253 5413

    Fax: 05-255 3525

    Regional Office (Kelantan & Terengganu)

    Tingkat 6, Bangunan KWSP

    Jalan Padang Garong

    15000 Kota Bharu

    KELANTAN

    Tel: 09-748 7390

    Fax: 09-744 5498

    Regional Office (Pahang)

    Tingkat 7, Kompleks Teruntum

    Jalan Mahkota

    25000 Kuantan

    PAHANG

    Tel: 09-514 2803

    Fax: 09-514 2804

    List of Energy Commission Regional Offices and Address

    Regional Office (Selangor, Kuala Lumpur & Putrajaya)

    Tingkat 10, Menara PKNS

    No.17, Jalan Yong Shook Lin

    46050 Petaling Jaya

    SELANGOR

    Tel: 03-7955 8930

    Fax: 03-7955 8939

    Regional Office (Johor)

    Suite 18A, Aras 18

    Menara ANSAR 65

    Jalan Trus

    80000 Johor Bharu

    JOHOR

    Tel: 07-224 8861

    Fax: 07-224 9410

    Regional Office (West Coast of Sabah)

    Tingkat 7, Bangunan BSN

    Jalan Kemajuan

    88000 Kota Kinabalu

    SABAH

    Tel: 088-232 447

    Fax: 088-232 444

    Regional Office (East Coast of Sabah)

    Tingkat 3, Wisma Saban KM12

    W.D.T. No.25

    90500 Sandakan

    SABAH

    Tel: 089-666 695

    Fax: 089-660 279

  • 7/27/2019 pagar_en2

    11/12

    8 The Installation of Electric Fence 19

    Regional Office(Negeri Sembilan & Melaka)

    Tingkat 4, Wisma Perkeso

    Jalan Persekutuan, MITC

    75450 Ayer Keroh

    MELAKA

    Tel: 06-231 9594

    Fax: 06-231 9620

    Note

  • 7/27/2019 pagar_en2

    12/12

    20 The Installation of Electric Fence

    Note