Also available in three phase with Motor Control Center (MCC). Separate spec sheets are available for these configurations. The three phase P series quarter turn actuators have been designed for dependable performance in rugged industrial applications such as clean water and wastewater treatment, mining, process control, power and damper control. ProMation Engineering has an extensive stock of electric actuators and can ship product very rapidly, worldwide. The XMCC Series is a 3 Phase electric actuator with the same rugged industrial features ProMation is known for: • Clutchless Manual Override • Easy to see raised position indicator • Ruggedboard internal soldered connections • NEMA 4X enclosures The XMCC Series features a polyphase motor and is designed for use with your existing 3 phase motor control center (phase monitoring and motor control must be provided in any 3 phase installation). Product Notes: 1. The 3 Phase P Series can be ordered as an on/off (two position) model that can also be used in bump/jog applications. 2. It can also be ordered with a premium internal proportional control card that accepts a wide range of control signals, generates multiple feedback signals, and has look-ahead fault prevention. 3. Care must be taken during installation to make sure local phasing is correct for this actuator. SD15_P213_XMCC Ver D_050515 Page 1 of 4 P11/12 XMCC Series Actuator Specifications P11 P12 Torque “lb/Nm 26500”lbs/3000Nm 31000“lbs/3500Nm Supply Voltage 230/3/60 380/3/60 440/3/60 480/3/60 230/3/60 380/3/60 440/3/60 480/3/60 Max Inrush Current 3.5A 2.0A 2.0A 2.0A 4.8A 2.5A 2.6A 2.6A Running Current 1.3A 0.7A 0.7A 0.7A 1.5A 0.9A 0.8A 0.8A Motor Polyphase Runtime (90°@60Hz/vdc) 58 sec 58 sec Runtime (90°@50Hz) 70 sec 70 sec Duty Cycle On/Off/Jog: 25%, Proportional: Managed (75% maximum) Motor Starts 1200 per hour Weight 157lbs/72kg Mechanical Connections ISO5211 F16 Rnd 75mm Electrical Entry (2) 3/4” NPT Electrical Terminations 12-16ga Environmental Rating NEMA 4/4X Manual Override 15.6” Handwheel Control On/Off/Jog / Proportional Actuator Case Material Aluminum Alloy, Powder coated Motor Protection 230°F/110°C Thermal F* Class *Totally Enclosed Non-Ventilated Motors Ambient Temperature Operating Range -22°F to +125°F -30°C to +52°C Data Sheet P11/12 3 Phase XMCC On/Off/Jog/Proportional ISO5211 F16 R75
4
Embed
P11/12 XMCC N4 Data Sheet P11/12 3 Phase XMCC · Page 1 of 4 P11/12 XMCC Series P11/12 XMCC N4 Actuator Specifi cations P11 P12 Torque “lb/Nm 26500”lbs/3000Nm 31000“lbs/3500Nm
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Also available in three phase with Motor Control Center (MCC). Separate spec sheets are available for these configurations.
The three phase P series quarter turn actuators have been designed for dependable performance in rugged industrial applications such as clean water and wastewater treatment, mining, process control, power and damper control. ProMation Engineering has an extensive stock of electric actuators and can ship product very rapidly, worldwide.The XMCC Series is a 3 Phase electric actuator with the same rugged industrial features ProMation is known for:
• Clutchless Manual Override • Easy to see raised position indicator • Ruggedboard internal soldered connections • NEMA 4X enclosures
The XMCC Series features a polyphase motor and is designed for use with your existing 3 phase motor control center (phase monitoring and motor control must be provided in any 3 phase installation).
Product Notes:1. The 3 Phase P Series can be ordered as an on/off (two position) model that can also be used in bump/jog applications.2. It can also be ordered with a premium internal proportional control card that accepts a wide range of control
signals, generates multiple feedback signals, and has look-ahead fault prevention. 3. Care must be taken during installation to make sure local phasing is correct for this actuator.
Motor Protection 230°F/110°C Thermal F* Class*Totally Enclosed Non-Ventilated Motors
Ambient Temperature Operating Range
-22°F to +125°F-30°C to +52°C
Data Sheet
P11/12 3 Phase XMCCOn/Off/Jog/Proportional
ISO5211 F16 R75
P Series Exploded View
Easily distinguishable yellow/red position
indicator
Worm Drive
Heavy Duty Drive Motor
Easily accessible switch &
cam stacks
Modular ControlCards
Clutchless OverrideHandwheel
Aluminum Casting4X Protection
Mechanical Stop Screws (2)
Epicyclic Gearing
Aluminum Casting4X Protection
NEMA 4Cover Seal
(Typical)
Application Notes:1. These actuators are to be mounted ONLY between a horizontal and upright position.2. When installing conduit, use proper techniques for entry into the actuator. Use drip loops to prevent
conduit condensate from entering the actuator. 3. Both NPT conduit ports MUST use proper equipment to protect the NEMA 4X integrity of the housing. 4. The anti-condensate heater is to be used in ALL applications. 5. Do not install or store the actuator outdoors or in humid environments without power to the heater.6. Use proper wire size to prevent actuator failure (see wire sizing chart). 7. Mechanical travel stops exist to prevent over-rotation for manual override only. They are not intended
to stop motor driven rotation.8. Do not parallel wire multiple actuators together without utilizing isolation relays! If this is your
intention, please contact ProMation Engineering for a multiple actuator parallel wiring diagram.
Switch Logic Map and Switch/Cam Arrangement
Term
inal
ID#
12
11
10
9
8
7
-5° 0°CW CCW
85°5° 90° 95°
SW3 CCW AUX(Factory Set - Adj)
SW4 CW AUX(Factory Set - Adj)}
}Closed Common
Open Common
}Used by Controller
Open
Not Closed
Closed
Not Open
Switch sequencing data is provided in the table below to show the change-of-state points during the rotation of the actuator from OPEN to CLOSED and back again. The red bar indicates when that terminal makes with it’s respective common.
SW1 and SW2 are set at the factory and should NOT be changed. The INCLUDED auxiliary switches SW3 & SW4 are forterminals7thru12andthosesetpointsmaybemodifiedifneed be. When so optioned, SW5 & SW6 auxiliary switches are initially set to function the same as auxiliary switches SW3 & SW4.
X.XX ± .13 [X.XXX ± .005]ALL TOLERANCE FEATURES IN mm
458 mm18.0 in 285 mm
11.2 in
402 mm15.8 in
262 mm10.3 in
398 mm15.7 in
220 mm8.7 in
552 mm21.7 in
Add 254mm
[10"] to allowfor coverremoval
165 mm6.5 inBHC
(4) M20x2.5
30mm1.2"
F16 ISO Flange75.00 mm
2.953 in
218 mm8.6 in
184 mm7.2 in
(2) 3/4" NPTEMT Entry
Drive Coupling Fabrication Data
12.00 mm.472 in
10.00 mm.394 in
75.00 - .13.00+ mm
2.953 - 0.0050.000+ in
100.00 mm3.937 inDepth
31.50 mm1.240 in KEY
12.00 mm.472 inKeyway
P11/12 Series Dimensional Data
Existing Switchgear
Existing Switchgear
Wire sizing data is provided in the table below to assist in the selection of the proper wire size for these actuators using various wire sizes over distance.
Please make sure to reference the correct voltage and do not exceed the indicated length of the wire run for each model.
• Field Control Device may be relay contact, Switch or Triac type.
• Pilot device 10A MAX. Auxiliary switches are rated 10A @ 250vac MAX.
• Terminals 7-12 are dry type Form C.
• Terminals accept 12-16ga solid/stranded wire.
SAMPLE DIAGRAMSRefer to the proper IOM for your actuator for the correct wiring diagram or visit www.promationei.com.
On/Off/Jog Control
Proportional Control
• See page 4 for Control Input/Outputs
• Pilot device 10A MAX. Auxiliary switches are rated 10A @ 250vac MAX.
• Terminals 7-12 are dry type Form C.
• Terminals accept 12-16ga solid/stranded wire.
Product is shipped at MID-STROKE position to allow up to 6 seconds run time after power up to determine if the actuator is running in the correct direction. If it is not, immediately remove power to avoid possible damage to the actuator end stops.
SD
15_P213_X
MC
C Ver D
_050515
Page 3 of 4 P11/12 XMCC Series
Wiring Diagrams for P11/12 Series
NOT OPEN*
OPEN COM*
OPEN*
NOT CLOSED*
CLOSED COM*
CLOSED*
C
B
12
11
10
9
8
7
LINE IN
480/3Ø
* CONNECTIONSOPTIONAL
GND Screw
GND
6
5
4
3
2
1
GRN
SW3
SW4
AUXILIARYSWITCH
(STANDARD)
ALL SWITCHESSHOWN WITHACTUATOR IN
FULL OPENPOSITION
AUXILIARYSWITCH
(STANDARD)
E1E2
Actuator ships in Mid-Stroke position!
J1
HEATER
SW2
SW1
J2
E1E2J3
112
43
Items within dotted line locatedinside actuator housing
430-10100 Switch Card
SW1
SW2
SW3
SW4
Switch StackDetail
A
5 6
21 22
3 4
1 2
A1 A2MC1
MC2
ØA
ØB
ØC NO
C
NC
REV Ø RELAY
120VAC COIL
120VAC COIL
5 6
21 22
3 4
1 2
A1 A2
ABCDEF WHT
BLU
RED
Correct Phase errors within 20 sec after power-up.
Supplied by others
410-50100TL25-1800
Heater is 25W120V
120vac Control ONLY
M410-95483480V/3Ø
120VAC
480VAC
T1 480/120
FB OUT
INSignal OUT+
Signal IN+
430-10102Controller
Signal COMCOM
48
0/3
/60
P9
~1
3 M
OD
CO
NT
RO
L - X
MC
C
P9~13-483PN4-XMCC
C
Use For:
123
BLU
GRY
P9~13 POTDETAIL
BRN
RED
BLK
WD
-85
0-5
82
42
NOT OPEN*
OPEN COM*
OPEN*
NOT CLOSED*
CLOSED COM*
CLOSED*
RUN CW
RUN CCW
C
B
12
11
10
9
8
7
LINE IN
480/3Ø
* CONNECTIONSOPTIONAL
FIELDCONTROL
DEVICE
GND Screw
GND
6
5
4
3
2
1
GRN
SW3
SW4
AUXILIARYSWITCH
(STANDARD)
ALL SWITCHESSHOWN WITHACTUATOR IN
FULL OPENPOSITION
AUXILIARYSWITCH
(STANDARD)
E1E2
Actuator ships in Mid-Stroke position!
J1
HEATER
SW2
SW1
J2
E1E2J3
112
43
Items within dotted line locatedinside actuator housing
ProMation Engineering follows a policy of continual product updates and enhancements. Our website is the best place to obtain the latest product documentation, including the wiring diagrams for these controllers. Visit us at www.promationei.com or use the QR code below to link to the site.
ProMation Product Line
PL SeriesLinear Drive
Up to 4400lbs down/up force.
P SeriesNon-Spring Return
55”lbs through 40,000”lbs.
PA~PD Series Spring Return
445”lbs through 2300”lbs.
PBU Battery Back-Up Systems
Provides battery power to drive open
The Premium controller offers a full array of features - such as various control and feedback signals, alphanumeric readout, several fault indicators for operational diagnostics,
Control Signal Inputs(selectable using program menu):0-10vdc, 1-5vdc, 2-10vdc, 4-20mA
Factory set with common isolated from ground. Ground reference is possible.
ProMation Premium Controller:
Signal Input Impedance Sensitivity
0-10vdc 140k ohms 50mV
1-5vdc 250k ohms 20mV
2-10vdc 140k ohms 40mV
4-20mA 250 ohms 80µA
Feedback Signal Output (Can be different than input): 0-10vdc, 1-5vdc, 2-10vdc, 4-20mA
Max Load: 250 ohms
extensive data logging that provides full proportional control for all industrial applications. ModBus communications are also an option on this controller.
Full Proportional Control Featuring:• Autocalibration• Programmable• High resolution• Alarm Outputs• Data logging• Simple User Interface• Field Selection Friendly• Thermal Management
Auxi l iary Signal Output (programmable):A larm Contacts a l low for signaling of 5 different fault conditions. 2 Position ControlContacts and capability for 2 position (only) override of the actuator.
Proportional Control
• Premium Proportional Controller Option. Converts 2 position to proportional control.• Mechanical Torque Switch Assembly• IP68 Protection, tested to 0.7kgf/cm2 for 72 hours. P2~P8 only.• 1k ohm position feedback potentiometer.• 5k ohm position feedback potentiometer.• 10k ohm position feedback potentiometer.• 4-20mA feedback generator for On/Off/Jog actuators.• Auxiliary Switch set. Provides 3rd and 4th auxiliary switches (Form C x 2).• Integral Thermostat for Heater Control - turns on at 32°F, turns off at 50°F.• Cold weather auxiliary heater option. Thermostatically controlled, On 32°F, Off
at 50°F, auto reset, hermetically sealed, 120/230vac On/Off/Jog type actuators. 175W Internal Heater, 2A power consumption.
• Chain wheel override for applications where an actuator is mounted some distancefromthefloor.(UsewithLCS).
• Epoxy coating for increased environmental protection.• Nylon coating for increased environmental protection.• Stainless Steel actuator enclosure. P2~P6 Only.
Cold Weather Heater Option keeps your actuator operational in cold weather applications. Automatically compensates internal temperatures in response to severe external conditions.