Page 1: Overview of Liquid Cooling Systems Peter Rumsey, Rumsey Engineers.

Overview of Liquid Cooling SystemsPeter Rumsey, Rumsey Engineers

Page 2: Overview of Liquid Cooling Systems Peter Rumsey, Rumsey Engineers.

Outline

• What is liquid cooling?

• Energy Benefits

• What is water side economizer

• Combined benefits

Page 3: Overview of Liquid Cooling Systems Peter Rumsey, Rumsey Engineers.

Why Liquid Cooling?

Heat Capacity of this much air

=

Heat Capacity of this much water

Page 4: Overview of Liquid Cooling Systems Peter Rumsey, Rumsey Engineers.

Fans move energy less efficiently

Page 5: Overview of Liquid Cooling Systems Peter Rumsey, Rumsey Engineers.

Liquid Cooling

Closer coupling between cooling source and server

Page 6: Overview of Liquid Cooling Systems Peter Rumsey, Rumsey Engineers.

Liquid Cooled Racks

Racks with integral coils

Page 7: Overview of Liquid Cooling Systems Peter Rumsey, Rumsey Engineers.
Page 8: Overview of Liquid Cooling Systems Peter Rumsey, Rumsey Engineers.
Page 9: Overview of Liquid Cooling Systems Peter Rumsey, Rumsey Engineers.

Yesterday

Page 10: Overview of Liquid Cooling Systems Peter Rumsey, Rumsey Engineers.

Today

Page 11: Overview of Liquid Cooling Systems Peter Rumsey, Rumsey Engineers.
Page 12: Overview of Liquid Cooling Systems Peter Rumsey, Rumsey Engineers.

Comparison of Conventional Cooling to Liquid Cooling – 1,000 kW data center load

  Cooling Towers

and Pumps

Chiller Chilled Water

Pumps

Fans Other Total Power (kW)

% SAVINGS

Traditional System - 45 Deg F Chilled Water

70 500 50 150 n/a 770 N/A

Liquid Cooled with Fans in the Rack - 55 Deg F Chilled Water

70 425 50 100 n/a 645 16%

Liquid Cooled without fans in the rack - 55 Deg F Chilled Water

70 425 50 0 n/a 545 29%

Liquid Cooled directly couple with CPU - 70 to 80 deg F Chilled Water

70 0 50 0 Room A/C - 245

365 53%

Page 13: Overview of Liquid Cooling Systems Peter Rumsey, Rumsey Engineers.

Free Cooling

Use cooling towers and heat exchanger to produce chilled water

Turn off chiller

Page 14: Overview of Liquid Cooling Systems Peter Rumsey, Rumsey Engineers.
Page 15: Overview of Liquid Cooling Systems Peter Rumsey, Rumsey Engineers.

Three – Well Suited For 24 hr Load

Facility B Data Center

Chiller 4 Power, Load and Efficiency - Oct 5 and 6

0

200

400

600

800

1000

1200

1400

1600

1800

10/4/2002 12:00 10/5/2002 0:00 10/5/2002 12:00 10/6/2002 0:00 10/6/2002 12:00 10/7/2002 0:00 10/7/2002 12:00

Time

Power (kW), Tons

0.0

0.2

0.4

0.6

0.8

1.0

1.2

1.4

Efficiency (kW/Ton)

Chiller kW Tons kW/Ton

Page 16: Overview of Liquid Cooling Systems Peter Rumsey, Rumsey Engineers.

Put in series with chiller free cooling can improve reliability

Page 17: Overview of Liquid Cooling Systems Peter Rumsey, Rumsey Engineers.

Free Cooling

RH = 20%

h = 20 Btu/lb ???

= 30 /h Btu lb ???

= 40 /h Btu lb ???

= 50 /h Btu lb ???

0.0000

0.0020

0.0040

0.0060

0.0080

0.0100

0.0120

0.0140

0.0160

0.0180

0.0200

0.0220

0.0240

0.0260

0.0280

0.0300

30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120

( )Dry Bulb Temperature F

50° F Wetbulb Line3200 hours minimum of free cooling

Page 18: Overview of Liquid Cooling Systems Peter Rumsey, Rumsey Engineers.
Page 19: Overview of Liquid Cooling Systems Peter Rumsey, Rumsey Engineers.

Comparison of Conventional Cooling to Liquid Cooling – 1,000 kW data center loadWith Free Cooling

  Cooling Towers

and Pumps

Chiller Chilled Water

Pumps

Fans Other Total Power

% SAVINGS

Traditional System - 45 Deg F Chilled Water

70 500 50 150 n/a 770 N/A

Liquid Cooled with Fans in the Rack - 55 Deg F Chilled Water

70 255 50 100 n/a 475 38%

Liquid Cooled without fans in the rack - 55 Deg F Chilled Water

70 255 50 0 n/a 375 51%

Liquid Cooled directly couple with CPU - 70 to 80 deg F Chilled Water

70 0 50 0 Room A/C - 150

270 65%

Page 20: Overview of Liquid Cooling Systems Peter Rumsey, Rumsey Engineers.

Take Aways

• Liquid has greater heat removal capacity

• Pumps are more efficient than fans

• Coupling heat removal to the source eliminates mixing

• Commercially available liquid solutions are available

• Water side free cooling provides cooling with reduced chiller operation for much of the year in California

Page 21: Overview of Liquid Cooling Systems Peter Rumsey, Rumsey Engineers.