OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level

Produced under OSHA Susan Harwood GrantSH-19509-09

Page 2: OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level Produced under OSHA Susan Harwood Grant SH-19509-09.

• What SIZE of dust is Combustible?

• ANSWER: What is Dust less than 420 microns in size. (passing a #40 sieve).

HAZARD ASSESSMENTSHAZARD ASSESSMENTS

Page 3: OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level Produced under OSHA Susan Harwood Grant SH-19509-09.

• What is the BEST WAY to prevent, Fire Hazards, Deflagration, or Explosion?

• ANSWER: What is a Self-Assessment, Self-Scoring, INSPECTION CHECKLIST?

HAZARD ASSESSMENTSHAZARD ASSESSMENTS

Page 4: OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level Produced under OSHA Susan Harwood Grant SH-19509-09.

• What is the NFPA Code that serves as the GO-NO GO DECISION POINT for the Inspection Checklist?

• ANSWER: What is NFPA 91 & 654? IF ONLY non-combustible particulate solids are present, the “checklist” does not apply!

HAZARD ASSESSMENTSHAZARD ASSESSMENTS

Page 5: OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level Produced under OSHA Susan Harwood Grant SH-19509-09.

• What are the things OSHA looks for while on a Combustible Dust inspection?

• ANSWER: What is dust presence and accumulation? Dust that is present at greater than 5% of surface area, 1/32 of an inch accumulation, and accumulation on overhead surfaces will get you cited!

HAZARD ASSESSMENTSHAZARD ASSESSMENTS

Page 6: OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level Produced under OSHA Susan Harwood Grant SH-19509-09.

• What is a SECONDARY EXPLOSION?

• ANSWER: What is an explosion of dust that gets shaken loose from overhead accumulations because of the primary explosion?

HAZARD ASSESSMENTSHAZARD ASSESSMENTS

Page 7: OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level Produced under OSHA Susan Harwood Grant SH-19509-09.

• What’s a passive way to prevent dust accumulation on walls?

• ANSWER: What are OUTWARDLY SLOPING WALLS? They’re designed with a curve away from walls so that dust slides off.

PRACTICAL HOUSEKEEPING & IGNITION SOURCE CONTROL

PRACTICAL HOUSEKEEPING & IGNITION SOURCE CONTROL

Page 8: OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level Produced under OSHA Susan Harwood Grant SH-19509-09.

• What are the benefits of FREQUENT dust clean-up?

• ANSWER: What is preventing dust accumulation.

PRACTICAL HOUSEKEEPING & IGNITION SOURCE CONTROL

PRACTICAL HOUSEKEEPING & IGNITION SOURCE CONTROL

Page 9: OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level Produced under OSHA Susan Harwood Grant SH-19509-09.

• Name as many sources of mechanical friction that can generate heat very quickly?

• ANSWER: What are Conveyor Belts, or Metal on Metal or failing Bearings?

PRACTICAL HOUSEKEEPING & IGNITION SOURCE CONTROL

PRACTICAL HOUSEKEEPING & IGNITION SOURCE CONTROL

Page 10: OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level Produced under OSHA Susan Harwood Grant SH-19509-09.

• Name as many small and portable IGNITION SOURCES as you can remember…

• ANSWER: What is open flame from matches, lighters, space heaters, heat guns, and welding equipment?

PRACTICAL HOUSEKEEPING & IGNITION SOURCE CONTROL

PRACTICAL HOUSEKEEPING & IGNITION SOURCE CONTROL

Page 11: OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level Produced under OSHA Susan Harwood Grant SH-19509-09.

• Name as many ELECTRICAL sources of ignition as you can you remember…

• ANSWER: What are exposed electrical wires, damaged electrical equipment and wires, static electricity, or open breaker panels?

PRACTICAL HOUSEKEEPING & IGNITION SOURCE CONTROL

PRACTICAL HOUSEKEEPING & IGNITION SOURCE CONTROL

Page 12: OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level Produced under OSHA Susan Harwood Grant SH-19509-09.

• What is the National Fire Protection Association?

• ANSWER: What is an Association that researches and publish standards based on industry experience and best practices?

NFPA ENGINEERING CONTROLS, BUILDING DESIGN, EXPLOSION PROTECTION

NFPA ENGINEERING CONTROLS, BUILDING DESIGN, EXPLOSION PROTECTION

Page 13: OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level Produced under OSHA Susan Harwood Grant SH-19509-09.

• Under NFPA, must engineering controls for Deflagration prevention be “Acceptance Tested”?

• ANSWER: What is YES

NFPA ENGINEERING CONTROLS, BUILDING DESIGN, EXPLOSION PROTECTION

NFPA ENGINEERING CONTROLS, BUILDING DESIGN, EXPLOSION PROTECTION

Page 14: OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level Produced under OSHA Susan Harwood Grant SH-19509-09.

• Should controls be on a periodic inspection and maintenance schedule?

• ANSWER: What is YES.

NFPA ENGINEERING CONTROLS, BUILDING DESIGN, EXPLOSION PROTECTION

NFPA ENGINEERING CONTROLS, BUILDING DESIGN, EXPLOSION PROTECTION

Page 15: OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level Produced under OSHA Susan Harwood Grant SH-19509-09.

• MUST engineering controls be checked against NFPA requirements for Operation, Maintenance, and Safety Requirements?

• ANSWER: What is YES

NFPA ENGINEERING CONTROLS, BUILDING DESIGN, EXPLOSION PROTECTIOn

NFPA ENGINEERING CONTROLS, BUILDING DESIGN, EXPLOSION PROTECTIOn

Page 16: OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level Produced under OSHA Susan Harwood Grant SH-19509-09.

• Name some types of deflagration engineering controls or components listed in the NFPA codes…

• ANSWER: What is 1-Oxidant reduction concentration (which prevents combustion), 2-Passive Isolation System (isolates system problems), Pre-Deflagration detection system , 4-Deflagration Suppression and Explosion venting.

NFPA ENGINEERING CONTROLS, BUILDING DESIGN, EXPLOSION PROTECTION

NFPA ENGINEERING CONTROLS, BUILDING DESIGN, EXPLOSION PROTECTION

Page 17: OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level Produced under OSHA Susan Harwood Grant SH-19509-09.

• What is a Deflagration Condition Assessment?

• ANSWER: What is analyzing conditions to see if you have a potential for a deflagration or dust explosion.

NFPA ENGINEERING CONTROLS, BUILDING DESIGN, EXPLOSION PROTECTION

NFPA ENGINEERING CONTROLS, BUILDING DESIGN, EXPLOSION PROTECTION

Page 18: OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level Produced under OSHA Susan Harwood Grant SH-19509-09.

• What MUST you do IF you are a wood processing location and you’re NOT SURE if you meet NFPA Code requirements relating to wood dust hazard controls?

• ANSWER: What is REVIEW NFPA CODES in detail, and DEVELOP A PLAN of ACTION to prevent hazards.

NFPA ENGINEERING CONTROLS, BUILDING DESIGN, EXPLOSION PROTECTION

NFPA ENGINEERING CONTROLS, BUILDING DESIGN, EXPLOSION PROTECTION

Page 19: OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level Produced under OSHA Susan Harwood Grant SH-19509-09.

• Name some NFPA Standards BY NUMBER and purpose...

• ANSWER What is NFPA:• 68 – Explosion Protection by Deflagration Venting• 69 – Explosion Prevention Systems• 70 – National Electrical Code • 77 – Recommended Practice on Static Electricity• 79 – Electrical Standard for Industrial Machinery• 499 – Combustible Dusts-Classified Locations-Chemical Process Areas• 654 – Prevention of Fire & Dust Explosions, Handling of Combustible

Solids• 664 – Prevention of Fires & Explosions in Wood Processing and Wood

Working Facilities.

NFPA ENGINEERING CONTROLS, BUILDING DESIGN, EXPLOSION PROTECTION

NFPA ENGINEERING CONTROLS, BUILDING DESIGN, EXPLOSION PROTECTION

Page 20: OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level Produced under OSHA Susan Harwood Grant SH-19509-09.

• What are some PRACTICAL WAYS to control Deflagrations?

• ANSWER What are ENGINEERED SYSTEMS that ISOLATE, REDIRECT, CONTAIN, or EXTINGUISH deflagrations within enclosed process equipment?

NFPA ENGINEERING CONTROLS, BUILDING DESIGN, EXPLOSION PROTECTION

NFPA ENGINEERING CONTROLS, BUILDING DESIGN, EXPLOSION PROTECTION

Page 21: OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level Produced under OSHA Susan Harwood Grant SH-19509-09.

• What is the MOST CRITICAL component for ANY engineered system?

• ANSWER: What is OPERATOR TRAINING! Employees who control and interpret the information from engineering controls MUST know how to properly operate the system for start-up, operation, shut-down, and ANY other condition!

NFPA ENGINEERING CONTROLS, BUILDING DESIGN, EXPLOSION PROTECTION

NFPA ENGINEERING CONTROLS, BUILDING DESIGN, EXPLOSION PROTECTION

Page 22: OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level Produced under OSHA Susan Harwood Grant SH-19509-09.

• What is a THERMOGRAPHIC IMAGER?

• ANSWER: What is an Infrared Camera. (Remember that the detection of infrared radiation is converted to visual images with a temperature scale. This analytical method allows you to detect sources of ignition using visual means).

DETECTING HAZARDOUS CONDITIONS with THERMOGRAPHIC IMAGERY

DETECTING HAZARDOUS CONDITIONS with THERMOGRAPHIC IMAGERY

Page 23: OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level Produced under OSHA Susan Harwood Grant SH-19509-09.

• What is the AUTO-IGNITION temperature of WOOD DUST?

• ANSWER: What is 399 *F to 500 *F. (Remember, contact with wood dust at this temperature will cause it to ignite)!

DETECTING HAZARDOUS CONDITIONS with THERMOGRAPHIC IMAGERY

DETECTING HAZARDOUS CONDITIONS with THERMOGRAPHIC IMAGERY

Page 24: OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level Produced under OSHA Susan Harwood Grant SH-19509-09.

• What is the surface temperature range of a Metal Halide Lamp?

• ANSWER: What is 400 *F to 700 *F. Also, failure of this type of light source is “catastrophic”, it can shatter and explode.

DETECTING HAZARDOUS CONDITIONS with THERMOGRAPHIC IMAGERY

DETECTING HAZARDOUS CONDITIONS with THERMOGRAPHIC IMAGERY

Page 25: OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level Produced under OSHA Susan Harwood Grant SH-19509-09.

• A Halogen lamp is uncovered and wood dust is suspended in air. Using TI, the lamp’s surface temperature was determined to be at 552 degrees Fahrenheit – Is this ABOVE or BELOW the auto-ignition temperature of wood dust?

• ANSWER: What is ABOVE it? The auto-ignition temperature for wood dust is 399 to 500 degrees Fahrenheit, and this is an IGNITION SOURCE. With dust suspended in air, DEFLAGRATION CONDITIONS exist.

DETECTING HAZARDOUS CONDITIONS with THERMOGRAPHIC IMAGERY

DETECTING HAZARDOUS CONDITIONS with THERMOGRAPHIC IMAGERY

Page 26: OVERVIEW COMBUSTIBLE DUST QUIZ: Management Level Produced under OSHA Susan Harwood Grant SH-19509-09.

• Wood dust has accumulated next to an electrical panel, and a Thermographic Image of the panel shows a surface temperature of 700 degrees Fahrenheit. Is it a cause for concern?

• ANSWER: What is YES! In this case, the surface temperature alone is enough to auto-ignite the dust! You have FIRE TRIANGLE conditions at this point, and will have a deflagration hazard if dust becomes suspended in air.

DETECTING HAZARDOUS CONDITIONS with THERMOGRAPHIC IMAGERY

DETECTING HAZARDOUS CONDITIONS with THERMOGRAPHIC IMAGERY