Top Banner

of 65

Over voltage protection.pptx

Apr 14, 2018

Download

Documents

Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • 7/27/2019 Over voltage protection.pptx

    1/65

    Over voltages

    The insulation strength and characteristics ofvarious components of a system (including those ofvoltage limiting devices) must be selected relatingto those stresses.

    i. To reduce frequency of supply interruptionsii. To reduce component failures

    The selected level of voltage shall be low enoughto be operationally and economically acceptable

  • 7/27/2019 Over voltage protection.pptx

    2/65

    Causes of over voltage:

    Phase to earth faults ( it is assumed that resulting temporaryvoltages will not exceed

    1.4 Pu for solidly earthed networks1.7 Pu for resistance earthed networks

    2.0 Pu for reactance earthed networks Load rejection (supplying capacitive current through a large

    inductive reactance ex. A smaller generator connected to along cable or over head line)

    Ferro resonance ( inter change of stored energy for series orparallel combination of inductive and capacitive reactance)

  • 7/27/2019 Over voltage protection.pptx

    3/65

    Causes of over voltage: contd.

    Ferranti effect: (receiving end voltage greater thansending end voltage under no load or light load

    conditions)

    By care full design and natural earthing sustainedover voltages involving resonance and arcing ground

    faults are eliminated

    Below 145 kV method of earthing will normallydetermine the level temporary over voltages.

  • 7/27/2019 Over voltage protection.pptx

    4/65

    Switching surges

    They are of short duration and irregular form Typical switching impulse standard form is the 250/2500 sec.

    ( time to crest/ time to half value wave)

    The magnitude of internally operated switching surges is

    related to the system operating voltage In a system where CBS are not subjected to multi re strikingthe switching surges will rarely exceed 3 pu

    2.5 pu would be typical maximum based on which thedischarge duty of LA is assessed

    However in systems above 300 kV, it may be necessary tosuppress maximum switching surges to 2 pu or less by theinstallation of a shunt reactor and/or closing resistors on thecircuit breakers

  • 7/27/2019 Over voltage protection.pptx

    5/65

    Resonance effects

    For voltage level below 300 kV. Resonanceeffects occur

    i. When switching transformer

    ii. When switching cable and overhead line

    combination

    iii. Between lumped capacitive and reactive

    elements and over head linesiv. Charging long lines without shunt reactor

    compensation

  • 7/27/2019 Over voltage protection.pptx

    6/65

    Resonance effects-- contd

    Ferro resonance encountered on a transformerfeeder greater than 5 to 10 Km in length

    When one feeder/transformer on a double circuit is

    switched out but parallel feeder remains energized,the dead circuit draws energy by captive couplingfrom the parallel line circuit which resonates withtransformer impedance at a sub harmonic frequency

    (operation procedure such as opening the lineisolator at the transformer end on the disconnectedcircuit will eliminate the problem)

  • 7/27/2019 Over voltage protection.pptx

    7/65

    Mode of action of flash over on a line

    A lightning flash can impress over voltage ona over head line by

    a) Induction when it discharges to earth close to

    line

    b) By direct contact on the line either to the

    earthed structure or to the phase conductor

  • 7/27/2019 Over voltage protection.pptx

    8/65

    Induced Voltage Surge

    A close flash to ground up to about 14 m away caninduce a voltage rise on phase conductors

    The highest amplitude normally associated is in theregion of 200 kV

    Significant in case of low voltage lines

    At 11 kV estimated that it accounts for some 90%of all faults

    Little significance on lines of 275 kV and above

  • 7/27/2019 Over voltage protection.pptx

    9/65

    Direct stroke

    A direct stroke can be to the earthed tower topor on phase conductor

    Stroke on earthed lower top, for transmission ofshielded design, is innocuous

    Raise in potential caused by passage of current

    through tower impedance to earth will be lessthan with stand strength of line

  • 7/27/2019 Over voltage protection.pptx

    10/65

    Direct strokecontd.

    However the rise in potential can be severeand exceed with stand capability, if

    Tower footing resistance is high

    Rate of rise of current exceeds a certain level

    Flashover may occur

    Through the system voltage, losses is thefrequency of flash over

  • 7/27/2019 Over voltage protection.pptx

    11/65

    Direct strokecontd.

    Direct stroke on phase conductor

    May occur if there is a shielding failure i.e. stroke avoids earthwire and lands on line conductor. Discharge current flows equally in both directions. Impedance to earth is half the surge impedance (Z0) of the

    conductor. IN a 400 kV line Z0

    = 175 ohms

    Voltage rise is sufficient to cause failure of line insulation Minimum critical current for flash over Ic = 2 V I0

    Z0VI0 = minimum flash over voltage for 1/50 Wave

    At flash over the impedance through which the dischargecurrent flows drops abruptly from Z0/2 to impedance of tower, x-arm, tower footing

  • 7/27/2019 Over voltage protection.pptx

    12/65

    Surge propagation:

    Surge waves are propagated at the velocity of lightalong the conductor

    On arrival at substation, equipment there in getstressed. Rod gaps and surge arrestors provide necessary

    protection

    Waves are subjected to considerable attenuationsdue to losses both in the conductor (ohmic losses)and corona losses

  • 7/27/2019 Over voltage protection.pptx

    13/65

    Lightning discharges

    Clarification of lightning dischargesstroke (A)stroke (B)

    Stroke (A) : produced by the charged cloud which induces acharge on the stationery objects such as high buildings etc.

    Charge distribution causes concentration of potential at the topmost point

    Electro static stress being great at that point ionization ofsurrounding atmosphere takes place

    Dielectric strength of surrounding air decreases giving an easypath to lightning stroke.

    Decrease in dielectric strength of surrounding air takesconsiderable time

  • 7/27/2019 Over voltage protection.pptx

    14/65

    Lightning discharges

    Stroke B:

    A, B & C are three clouds with A and C positively charged andB negatively charged

    When there is a stroke between (A) and (B) the charge on (C)

    becomes free and immediately and indiscriminately strikeson any object on the ground

    For stroke (B) there is no time lag Stroke (B) may completely ignore highest building and strike

    bare ground.

    No protection can be arranged against stroke `B` Stroke `A` can be made safe by channelising the chargethrough a lightning conductor placed on the top of thebuilding

  • 7/27/2019 Over voltage protection.pptx

    15/65

    Static induced charges

    An over head conductor accumulates staticallyinduced charge when a charged cloud comes above

    When the cloud is swept away charge on the

    conductor is released The charge travels on either side giving rise to

    two travelling waves

    The earth wire does not prevent such surges

  • 7/27/2019 Over voltage protection.pptx

    16/65

    Lightning strokes

    Over voltage due to lightning strokessurge impedance of the line = ZsDischarge current = IdOver voltage due to direct stroke = Vd = Id x ZsHowever current travels in both directions

    over voltage = Vd = Id x Zs2

    when lightning strikes over earth wire or a tower

    Over voltage = Id x Ze + Lc didt

    Ze = impedance of earth wire

    Lc is the inductance of the line conductor

  • 7/27/2019 Over voltage protection.pptx

    17/65

    Protection against lightning

    1. Protection of transmission lines from

    direct strokes

    2. Protection of power stations and

    substations from direct strokes3. Protection of electrical equipment

    from traveling waves

  • 7/27/2019 Over voltage protection.pptx

    18/65

    Protection of transmission lines

    Against the direct strokes : Most harmful

    Effective protection required shielding to

    prevent lightning from striking the electricalconductors.

    There shall be adequate drain facilities so that

    the charge can be grounded without affectingInsulators or line conductors.

  • 7/27/2019 Over voltage protection.pptx

    19/65

    Design of transmission line against

    lightning

    Design shall consists of(a) General wire of adequate mechanical strength to provide shielding

    for line conductor. They shall also be noncorrosive

    Resistance of ground wire shall be low for better protection againstdirect stroke.

    (b) Adequate clearance between1. Line conductor and tower

    2. Line conductor and earth

    3. Clearance between line conductor and ground wire all throughthe span including mid Span or point of lowest sag.

    (c) Tower footing resistance shall be low(d) Angle of protection (shielding angle) angle between the normal

    passing through the ground wire and line joining the supportedcenter points of outer conductor and ground wire. It shall be 30for 132 & 220 kV lines 20 for 400 kV lines

  • 7/27/2019 Over voltage protection.pptx

    20/65

    Effect of number of earth wires In the absence of a ground wire: When there is a charge cloud over a transmission line without

    any ground wire

    There will be two capacitances(1) Between cloud and conductor C2(2) Between conductor and earth C1Induced voltage on the line

    V L1 = C1 x EcC1+C2

    When ground wire is present it increases capacitance betweenconductor and earth i.e. C1 Decreases induced voltage on theline.

    It is observed that presence of a ground wire reduces inducedvoltage on line to half.

    For two ground wires the induced voltage comes down to onethird

    Presence of two ground wires also provides better shielding

  • 7/27/2019 Over voltage protection.pptx

    21/65

    Earth wires

    Disadvantages with ground wire:

    (a) higher line cost

    (b) Probable direct shorting between lineconductor and ground wire when the later

    gets cut

    In 400kV system transmission line towers will

    have twu earth wires.

  • 7/27/2019 Over voltage protection.pptx

    22/65

    Alternative method of line protection

    Even after providing ground and reducing the likelyinduced voltages, harmful voltages can still develop

    Lightning arrestors act as additional protectivedevices by by-passing the surges to ground

    Protector tube is a fiber tube with electrode at earthend.

    Fitted directly below the conductor

    The arc type electrode on the top of the tube forms aseries gap with conductor

  • 7/27/2019 Over voltage protection.pptx

    23/65

    Alternative method of line protection

    The lower electrode is solidly grounded In case of surge on the conductor, an arc develops

    between conductor and top electrode of the tube.

    Arc shifts within the tube and vaporises some of thefiber of tube wall to emit gases which will quench thearc

    This tube successfully prevents re-striking

    The break down voltage of tube shall be less thanflash over voltage of the insulation.

  • 7/27/2019 Over voltage protection.pptx

    24/65

    Protection against traveling waves

    The traveling waves cause the following damages:i. High peak voltage of surge may cause flash over in the

    internal winding or external flashover between theterminals of the equipment.

    ii. steep wave front may cause internal flash over betweenturns of the transformer

    iii. Steep wave front resulting into resonance and highvoltage may cause internal or external flash over causingbuilding up of oscillations in the equipment

    Protective equipment : LAs and Surge diverters They are connected between line and earth

  • 7/27/2019 Over voltage protection.pptx

    25/65

    Action of the Surge diverter

    A traveling wave reaches surge diverter and attains aprefixed voltage

    A spark is formed across the gap

    The diversion provides a low impedance path to earth

    The surge impedance of the line limits the amplitude ofthe current flowing to earth to prevent break down of

    insulation

    Important aspect is that the surge diverter shallprovide low impedance path to earth only when

    traveling surge reaches the surge diverters

  • 7/27/2019 Over voltage protection.pptx

    26/65

    Action of the Surge diverter It shall absorb any current during normal operation

    for over voltage surges.

    It means that it shall not function at powerfrequencies but function only when abnormalfrequencies are applied

    When there is a discharge through them they shall becapable of carrying the discharge current for sometime interval.

    After the over voltage discharge it must be capableinterrupting normal frequency current from flowing toearth as soon as the voltage reaches below the breakdown value

  • 7/27/2019 Over voltage protection.pptx

    27/65

    Switching over voltage protection in a

    substation

    Operation of breakers causes transient over voltages Over voltage value varying between 1.1 Pu to 6 Pu based on

    switching duty and the type of circuit breaker Over voltage occurs mainly due to exchange of energy

    between system inductance LI2 and system capacitance

    CV2

    Over voltage occurs during the opening of circuits and closingof long EHV lines

    Most severe over voltages occurs during the closing unloadedtransmission line

    Preventive measure Provision of Pre insertion resistors ( 400 to 800 ohms per

    phase) Simultaneous closing of lines at both ends Using shunt reactors, surge arresters etc.

  • 7/27/2019 Over voltage protection.pptx

    28/65

    Switching Over voltages in Substations

    Switching duty of

    C.B.

    Applications and

    Remedial Actions

    Phenomena

    Opening of capacitor

    bank currents, cable

    charging circuits, filter

    banks

    Switching of shunt

    capacitor banks used for

    p.f. correction.

    - Use of re strike free C.B.

    for capacitor switching

    duty.

    Re strike in circuit

    breakers giving over

    voltage.

    EHV lines

    * Closing unloaded

    lines* Closing charged

    lines

    * Auto re closing of

    C.B.

    * Long EHV transmission.

    - Use of pre-closing

    resistors with circuitbreakers. Use of lightning

    arresters. Use of shunt

    reactors in transmission

    lines.

    Traveling waves

    travel to and fro

    giving rise to a

    switching surge.

  • 7/27/2019 Over voltage protection.pptx

    29/65

    Methods of Reducing Switching Over

    Voltages

    Switching operation

    causing over voltage

    Method to reduce

    switching over voltage

    Energising an uncharged

    line

    High voltage shunt reactors

    are connected to line toreduce power frequency

    over voltages.

    Elimination of trapped

    charged on the line

    Line shunting after opening

    by means of earthing switchReduction of current

    chopping

    Opening resistors (

    Resistance switching with

    CB) used only with ABCB

  • 7/27/2019 Over voltage protection.pptx

    30/65

    Methods of Reducing Switching Over

    Voltages

    Switching operationcausing over voltage

    Method to reduceswitching over voltage

    Reducing the switching over

    voltages due to closing

    Single stage pre closing resistor

    insertion with CB.

    Two stage pre closing resistor

    insertion with CB.

    Closing resistors in between circuit

    breaker and shunt reactor

    Reducing switching over voltages

    by improved switching sequence

    Synchronous switching of three

    poles.Simultaneous operation of circuit

    breakers at both ends of line,

    Use of surge arrestors While closing of line

    While disconnecting reactor

  • 7/27/2019 Over voltage protection.pptx

    31/65

    Rod gaps or coordinating gaps

    They are used on insulators, equipment and bushings

    Conducting rods are provided between line terminaland earth terminal with an adjustable gap ( Airinsulation)

    Rods are of 12mm dia approx.

    The gap is adjusted to break down at about 20% belowthe flash over voltage of the insulation. Spark over causes dead Short circuit Voltage of phase with respect to ground falls very low

    The rod gaps are no more used consequent todevelopment of surge arrestors.

    O lt i N t k d R di

  • 7/27/2019 Over voltage protection.pptx

    32/65

    Over-voltage in Network and Remedies

    Phenomena Causes Effect Remedies

    Surges Lightning strokes on

    overhead lines orsubstation

    Line insulation flash

    over or puncture.The traveling wave

    reaches substations.

    The insulation of

    equipment is

    stressed by impulse

    surge

    -Use of Ground

    wire

    - Surge Diverters

    -Earthing of

    towers

    -Lightning Masts

    Switching

    surges

    Breaking inductive circuit,

    the energy stored

    inductance gives rise a

    voltage rise across

    capacitor.

    Switching of capacitive,

    line charging currents give

    rise to a over voltage due

    to restrike. Closing of EHV

    lines

    Wave travels from

    C.B. to both sides

    Transmission line

    insulator, stressed.

    Terminal apparatus

    insulation stressed

    -Use of opening

    resistors with C.B.

    - Use of restrike

    free C.B.

    -Use pre-insertion

    resistors with C.B.

  • 7/27/2019 Over voltage protection.pptx

    33/65

    Over-voltage in Network and Remedies

    Phenomena Causes Effect Remedies

    Resonance The fault causingresonance between

    inductance and

    capacitance in a part of

    the circuit

    Very high, voltagesurges occur.

    Insulation failure

    likely to occur.

    Filters toeliminate

    harmonics

    Travelingwaves

    High voltage waves getreflected on reachinga junction or end.

    Reflected wavesgets superimposed

    for initial wave.

    Voltage may rise to

    several time the

    normal voltage.

    -Properswitching

    sequence.

    Sustained

    Power

    frequency

    over

    voltage

    Poor voltage control Failure of

    transformers and

    Rotating Machines

    -Proper Voltage

    control

  • 7/27/2019 Over voltage protection.pptx

    34/65

    Protective Devices Against Lightning Over voltages

    Device Where applied Remarks

    Rod gaps Across insulator string,bushing insulators -Difficult to coordinate-Create dead short

    circuit

    -Cheap

    Overhead Ground

    Wires (earthed)

    -Above overhead lines

    -Above the substationarea

    -Provide effective

    protection againstdirect strokes on line

    conductors towers sub

    station equipment

    Vertical Masts in

    substations

    -- in sub stations -instead of providing

    overhead shieldingwires

    Lightning Masts/Rods

    (earthed)

    - Above tall buildings Protect buildings

    against direct strokes.

    Angle of Protection

    = 300

  • 7/27/2019 Over voltage protection.pptx

    35/65

    Protective Devices Against Lightning Over voltages

    Device Where applied Remarks

    Surge Arresters -- on incoming lines in each

    substation

    -Near terminals of

    Transformers and

    generators

    -Near motor and

    generators terminals

    -- Diverts over voltage to

    earth without causing

    short circuit

    -Used at every voltage

    level in every sub-station and for each line.

    Surge Absorbers -- near rotating machines

    connected between phaseand ground

    -Resistance

    CapacitanceCombination absorbs

    the over voltage surge

    and reduces steepness

    of wave

  • 7/27/2019 Over voltage protection.pptx

    36/65

    Lightning arrester selection

    1. To determine the magnitude of the power frequency phase to ground voltageexpected at the proposed arrester location during phase to ground fault, or otherabnormal conditions which cause higher voltages to ground than normal.

    2. To make a tentative selection of the power frequency voltage rating of thearrester. This selection may have to be reconsidered after step (6) is completed.

    3. To select the impulse current likely to be discharged through the arrester.

    4. To determine the maximum arrester discharge voltage for the impulse currentand type of arrester selected. 5. To establish the full-wave impulse voltage withstand level of the equipment to

    be protected.

    6. To make certain that the maximum arrester discharge voltage is below the fullwave impulse, withstand level of the equipment insulation to be protected, byadequate margin.

    7. To establish the separation limit between the arrester and the equipment to beprotected.

  • 7/27/2019 Over voltage protection.pptx

    37/65

    Types of Earthing

    For purpose of selection of voltage rating of a LA threetypes of earthing are considered

    (I) Effective earthed system: a system is effectively earthed

    if under any fault condition the line to earth voltages of

    healthy phases do not exceed 80 % of the system line toline voltage

    If in a system all transformers have star connectedwinding with neutrally solidly earthed then the system

    is effectively earthed

    However if only few transformers are earthed like that,it is not effectively earthed system

  • 7/27/2019 Over voltage protection.pptx

    38/65

    Types of Earthing - conted.

    (II) Non effectively earthed system:

    a) if the line to earth voltage in healthy phases in case of afault exceed 80% of the line to line voltage but does not exceed100% of it, the system is called non effectively earthed system

    b) System with few solidly earthed neutrals

    c) Systems with neutral Earthed through resistors orreactors of low ohmic value or arc suppression coil

    (III) Isolated or un earthed neutral systems :-

    system neutrals are not earthed. Line to earth voltage of healthyphases exceed 100% of the line to line voltage.

  • 7/27/2019 Over voltage protection.pptx

    39/65

    Selection of lightening arrestors

    Tentative selection of arrestor Voltage:

    Arrestor Voltage rating shall not be less thanproduct of system highest voltage x co-

    efficient of earthing

    Co-efficient of earthing : Effectively earthed system 80%

    Non effectively earthed system - 100 %

    and isolated earth system

  • 7/27/2019 Over voltage protection.pptx

    40/65

    Selection of lightening arrestors

    In a 220 kV effectively earthed system Highest system voltage = 245 kV Co-efficient of earthing = 80%

    Arrestor voltage rating >= 245x0.8 = 196 kV As per IS 3070 (partI) 1965 the rating is 198 kV

    By going for a higher voltage rating for a surge

    arrestor, the degree of protection forequipment gets reduced.

  • 7/27/2019 Over voltage protection.pptx

    41/65

    Selection of arrestor discharge current

    This can be calculated from(a) Spark over voltage of transmission line insulation

    (b) Surge impedance of the line

    (c) Residual discharge voltage of LAIa = 2E- Ea

    Z

    Ia = Arrestor discharge current

    E = Magnitude of incoming surge voltage

    Ea = Residual discharge voltage of an arrestor

    Z = Surge impedance of the line

  • 7/27/2019 Over voltage protection.pptx

    42/65

    Selection of arrestor discharge current

    In a 220 kV system using 11 insulators Transmissionline will not permit a traveling wave of a value morethan 1025 kVp

    As per IS 3010 (Part 1) -1965 the residual voltages of

    LA at a discharge current of 10kA is 649 kV. Considering the surge impedance as 450 ohms Maximum value of discharge current of LA =

    2(1025000)-649000 = 3100 Amps

    450 The LAs normally in 200 kV system have a discharge

    current rating of 10 kA.

  • 7/27/2019 Over voltage protection.pptx

    43/65

    Selection of arrestor discharge Voltage

    Most important characteristic of LA determining the protectionlevel being offered

    The arrestor discharge voltage shall be less than BIL ofequipment for effective protection

    Discharge voltage depends on(I) discharge current

    (II) rate of rise of current applied(III) Wave shape of current applied

    Discharge voltage of LA increases with discharge current. Butincrease is much restricted due to nonlinear resistanceproperty.

    Increase in discharge from 5 kA to 20 kA produces only 25% risein discharge voltage. Increase in rate of current from 1000 to 5000 Amps per micro

    second increases discharge voltage by only 35%.

  • 7/27/2019 Over voltage protection.pptx

    44/65

    Protective margin of LA

    Protective margin of LA = BIL of the equipment---maximum discharge voltage of LA

    While determining protection level offered by a LA 10%allowances towards drop in lead length and manufacturingtolerance shall be allowed.

    Protective margin shall be 20% of the BIL of the equipmentwhen closely located

    In a 220 kV systemDischarge voltage of LA = 649 kV

    Allowing 10 % margin protection level = 713 kVBIL of equipment = 900 kVp

    Protection margin = 900-713 = 187 kVp

    There is more than 20 % of the BIL of 180 kV

  • 7/27/2019 Over voltage protection.pptx

    45/65

    Protective margin of LA-Continue.

    In American system

    Average discharge voltage x 1.25 +40 kV = BIL

    protected

    When adequate margin is not available LAs

    with lower rating shall be chosen taking risk.

  • 7/27/2019 Over voltage protection.pptx

    46/65

    Insulation Co-ordination Scheme

    For 220 KV system. L.A. Voltage rating=system highest voltage x co-efficient of earthing =245x.8=196Kv. Selecting standard rating from Table 12.1 column 1,L.A. voltage rating=198 Kv Discharge current rating= 10KA (assumed) Residual voltage, from column 3 of table 12.1,=649Kv (peak) Protection level of the L.A. =649x1.1=714Kv For a margin of 20% between the B.I.L. and the protection level of L.A., the B.I.L. should be

    =714x1.2=857Kv.

    Choose standard B.I.L. Table 14.3 (b) Col. 4=900 Kv, The corresponding power freq. I minute test voltage =395kv Switching surge flashover voltage =220 x6.5=825kv 3 Check it is less than B.I.L. of 900kv.

    Power frequency over voltage=220x3=228kv rms 3 This is less than 395kv. B.I.L. of CBs, instrument transformer, disconnect switches etc,.=900x1.1=990kv. Choose standard B.I.L.=1175kv.

  • 7/27/2019 Over voltage protection.pptx

    47/65

    The L.A. voltage rating

    Rated system

    voltage KV

    Highest system

    voltage KV

    Arrester rating

    in KV

    132 145 120/132

    220 245 198/216

    400 420 336

  • 7/27/2019 Over voltage protection.pptx

    48/65

    Establishment of Separation Limit

    When arrestor are to be located away from equipment. A traveling wave coming into the station to location to the discharge voltage of the arrestor. Proximity to transformer or breakers.

    - Transformer is most expensive price.

    - Repair to transformer is costly and with higher revenue loss.

    - Transformers are always at the end of a circuit where voltage regulation.

    . For circuit breakers and disconnecting switches flash over distance between terminals when inopen position in grater than between terminals and ground.

    . Surge in excess to insulation strength will flash over to ground with out damaging theequipment.

    . At best there can be only outage .

    . By reducing BIL of transformer savings in the cost of insulation can be obtained.

    . Not possible incase of CB or disconnections switches.

    . Hence a set of LAS shall be closer to transformers.

  • 7/27/2019 Over voltage protection.pptx

    49/65

    Location of Lightning Arresters:

    The electrical circuit length between L.A. and the transformer bushingterminal (inclusive of lead length in metes for effectively earthed) should

    not exceed the limits given below:

    Rated syst.voltage KV BIL KVPeak Max.distance

    132kV 550

    650

    35.0

    45.0

    220kV

    400kV

    900/1050

    1425/1550

    Closer

    to

    Trans.

  • 7/27/2019 Over voltage protection.pptx

    50/65

    Definition:- Flash over voltages

    Impulse flash over voltage:-

    The voltage which will cause flash over of anInsulation When subjected to a 1.2x50s

    impulse

    (British standards1x50 sec)

    (American standards 1.5 x 40sec)

  • 7/27/2019 Over voltage protection.pptx

    51/65

    Definition:- Flash over voltages

    Basic Insulation level :-The crest voltage of standard wave that will notcause flashover of the insulation is referred to asBasic insulation level

    (Basic impulse insulation voltages are levelsexpressed in impulse crest voltage with a standardwave not longer than 1.2x50 s.

    Equipment insulation as tested shall be equal or

    above the BIL

  • 7/27/2019 Over voltage protection.pptx

    52/65

    Impulse spark over volt- time characteristic

    This characteristic is obtained by plotting--Time which elapses between the moment the voltage wave

    is applied and the moment of spark over -- on abscissa

    -Voltage at the moment of spark over

    (i) Occurring on the wave front(ii) Occurring on the wave peaks

    (iii) Crest of the voltage for spark overoccurring on the wave tail

  • 7/27/2019 Over voltage protection.pptx

    53/65

    LINE INSULATION

    Extra high voltage line can be made lightning proofby

    1 Efficient shielding

    2 Low tower footing resistance equal to or less than10 ohms

    shielding angle

    Transmission lines up to 220kV 30400 kV at and above 20

  • 7/27/2019 Over voltage protection.pptx

    54/65

  • 7/27/2019 Over voltage protection.pptx

    55/65

    Line insulation -contd.

    Line insulation shall be sufficient to prevent aflashover from the power-frequency over

    voltages and Switching Surges.

    It shall take into consideration the local unfavourable circumstances which decrease the

    flash over voltage (rain, dirt, Insulation

    pollution etc.,)

  • 7/27/2019 Over voltage protection.pptx

    56/65

    OVER VOLTAGE FACTORS

    Line

    Voltages

    Switching

    Surge flash

    over

    Power frequency flash

    over (Dry & Wet)

    220kV 6.5 V pn 0.3

    400kV 5.0 V pn 3.3

    Vpn = Phase to Neutral Voltage (rms)

    Add one or two more Insulators for each string.

  • 7/27/2019 Over voltage protection.pptx

    57/65

    OVER VOLTAGE FACTORSContd.

    -To take care of one disc in the string

    becoming defective.

    -Facilitate hot line maintenanceUp to 220 kV Line 1 disc for each string

    400 kV Line 2 discs for each string

    RECOMMENDED INSULATION LEVEL OF

  • 7/27/2019 Over voltage protection.pptx

    58/65

    RECOMMENDED INSULATION LEVEL OF

    LINE

    Normal

    system

    Voltage

    Vpn

    In kV

    (Vph/3)

    Switching over

    volt. (Wet) kV *

    No of

    discs

    required

    132kV 76 76 x6.5=495 5

    220kV 127 127x6.5=825 9400kV 231 231x5=1755 13

    * Compared with Impulse FOV (Value)

    RECOMMENDED INSULATION LEVEL OF

  • 7/27/2019 Over voltage protection.pptx

    59/65

    RECOMMENDED INSULATION LEVEL OF

    LINEcontd.

    Normal

    system

    Voltage

    Vpn

    In kV

    Power freq.

    over volt

    (wet)

    (kVrms)

    No.

    of

    discs

    req.

    No. of

    discs

    recom.

    As per

    practice

    132kV 76 76x3=228 6 7 9/10

    220kV 127 127x3=381 10 11 13/14

    400kV 231 231x3=762 20 22 23/24

  • 7/27/2019 Over voltage protection.pptx

    60/65

    Tower forting resistance 10ohms severest lightning discharge 50kA (rms) Impulse strength of

    Insulation=2x50x10x10=700kV

    As per the table for 7 discs, the impulse FOV (kVp =695kVp)

    For better performance tower fortingresistance shall be brought down.

    For 132kV best is 7 ohms

    C di ti f li I l ti d S b

  • 7/27/2019 Over voltage protection.pptx

    61/65

    Co-ordination of line Insulation and Sub-

    Station Insulation

    Line Insulation is not directly related to theInsulation of equipment within the Sub-Station.

    Impulse flash over voltage of line Insulation

    determine the highest surge voltage that can travelinto the sub-station.

    Current through lighting arrestor can be calculatedfrom

    1 Surge impudence of line

    2 Surge voltage arriving over the line

    Co ordination of line Ins lation and S b

  • 7/27/2019 Over voltage protection.pptx

    62/65

    Co-ordination of line Insulation and Sub-

    Station Insulation

    Discharge voltage of the LA on that current isthe basic protective level of the substation

    equipment.

    Discharge voltage across LA varies with surgecurrent.

    BASIC INSULATION LEVEL AS PER IS (2165

  • 7/27/2019 Over voltage protection.pptx

    63/65

    BASIC INSULATION LEVEL AS PER IS (2165

    1962)

    Nominalsystem

    volt kV

    (rms)

    Highestsystem

    volt kV

    (rms)

    Impulse withstandvolt kVp for test

    One minute powerfrequent volt kV (rms)

    Full

    insulation

    Reduced

    insulation

    Full

    insulation

    Reduced

    insulation

    132 kV 145 650 550 275 230

    220 kV 245 1050 900 460 395

    400 kV 420 1550 680

    1425 630Reduced insulation is used where system is effectively earthed.

  • 7/27/2019 Over voltage protection.pptx

    64/65

    INSULATION LEVELS OF EQUIPMENT

    Transformers, Isolators, Instrument Transformers aremanufactured for the standard Insulation level.

    Some times transformers, are manufactured for onestep lower insulation level for the sake of economy.

    (LAs will be designed for a still lower level)

    Where LAs are provided right on the top of thetransformer, some of the equipment may lie well outside the protective zone of the LA.

  • 7/27/2019 Over voltage protection.pptx

    65/65

    INSULATION LEVELS OF EQUIPMENT

    Protective zone is determined based on

    A With stand level of equipment

    B Discharge volt of LA

    C Distance between LA and equipment.

    Such equipment shall be designed for one stephigher Bil.

    Generally BIL of substation equipment other thantransformer are designed for10% higher BIL than thatof Transformer .