7/27/2019 Over voltage protection.pptx
1/65
Over voltages
The insulation strength and characteristics ofvarious components of a system (including those ofvoltage limiting devices) must be selected relatingto those stresses.
i. To reduce frequency of supply interruptionsii. To reduce component failures
The selected level of voltage shall be low enoughto be operationally and economically acceptable
7/27/2019 Over voltage protection.pptx
2/65
Causes of over voltage:
Phase to earth faults ( it is assumed that resulting temporaryvoltages will not exceed
1.4 Pu for solidly earthed networks1.7 Pu for resistance earthed networks
2.0 Pu for reactance earthed networks Load rejection (supplying capacitive current through a large
inductive reactance ex. A smaller generator connected to along cable or over head line)
Ferro resonance ( inter change of stored energy for series orparallel combination of inductive and capacitive reactance)
7/27/2019 Over voltage protection.pptx
3/65
Causes of over voltage: contd.
Ferranti effect: (receiving end voltage greater thansending end voltage under no load or light load
conditions)
By care full design and natural earthing sustainedover voltages involving resonance and arcing ground
faults are eliminated
Below 145 kV method of earthing will normallydetermine the level temporary over voltages.
7/27/2019 Over voltage protection.pptx
4/65
Switching surges
They are of short duration and irregular form Typical switching impulse standard form is the 250/2500 sec.
( time to crest/ time to half value wave)
The magnitude of internally operated switching surges is
related to the system operating voltage In a system where CBS are not subjected to multi re strikingthe switching surges will rarely exceed 3 pu
2.5 pu would be typical maximum based on which thedischarge duty of LA is assessed
However in systems above 300 kV, it may be necessary tosuppress maximum switching surges to 2 pu or less by theinstallation of a shunt reactor and/or closing resistors on thecircuit breakers
7/27/2019 Over voltage protection.pptx
5/65
Resonance effects
For voltage level below 300 kV. Resonanceeffects occur
i. When switching transformer
ii. When switching cable and overhead line
combination
iii. Between lumped capacitive and reactive
elements and over head linesiv. Charging long lines without shunt reactor
compensation
7/27/2019 Over voltage protection.pptx
6/65
Resonance effects-- contd
Ferro resonance encountered on a transformerfeeder greater than 5 to 10 Km in length
When one feeder/transformer on a double circuit is
switched out but parallel feeder remains energized,the dead circuit draws energy by captive couplingfrom the parallel line circuit which resonates withtransformer impedance at a sub harmonic frequency
(operation procedure such as opening the lineisolator at the transformer end on the disconnectedcircuit will eliminate the problem)
7/27/2019 Over voltage protection.pptx
7/65
Mode of action of flash over on a line
A lightning flash can impress over voltage ona over head line by
a) Induction when it discharges to earth close to
line
b) By direct contact on the line either to the
earthed structure or to the phase conductor
7/27/2019 Over voltage protection.pptx
8/65
Induced Voltage Surge
A close flash to ground up to about 14 m away caninduce a voltage rise on phase conductors
The highest amplitude normally associated is in theregion of 200 kV
Significant in case of low voltage lines
At 11 kV estimated that it accounts for some 90%of all faults
Little significance on lines of 275 kV and above
7/27/2019 Over voltage protection.pptx
9/65
Direct stroke
A direct stroke can be to the earthed tower topor on phase conductor
Stroke on earthed lower top, for transmission ofshielded design, is innocuous
Raise in potential caused by passage of current
through tower impedance to earth will be lessthan with stand strength of line
7/27/2019 Over voltage protection.pptx
10/65
Direct strokecontd.
However the rise in potential can be severeand exceed with stand capability, if
Tower footing resistance is high
Rate of rise of current exceeds a certain level
Flashover may occur
Through the system voltage, losses is thefrequency of flash over
7/27/2019 Over voltage protection.pptx
11/65
Direct strokecontd.
Direct stroke on phase conductor
May occur if there is a shielding failure i.e. stroke avoids earthwire and lands on line conductor. Discharge current flows equally in both directions. Impedance to earth is half the surge impedance (Z0) of the
conductor. IN a 400 kV line Z0
= 175 ohms
Voltage rise is sufficient to cause failure of line insulation Minimum critical current for flash over Ic = 2 V I0
Z0VI0 = minimum flash over voltage for 1/50 Wave
At flash over the impedance through which the dischargecurrent flows drops abruptly from Z0/2 to impedance of tower, x-arm, tower footing
7/27/2019 Over voltage protection.pptx
12/65
Surge propagation:
Surge waves are propagated at the velocity of lightalong the conductor
On arrival at substation, equipment there in getstressed. Rod gaps and surge arrestors provide necessary
protection
Waves are subjected to considerable attenuationsdue to losses both in the conductor (ohmic losses)and corona losses
7/27/2019 Over voltage protection.pptx
13/65
Lightning discharges
Clarification of lightning dischargesstroke (A)stroke (B)
Stroke (A) : produced by the charged cloud which induces acharge on the stationery objects such as high buildings etc.
Charge distribution causes concentration of potential at the topmost point
Electro static stress being great at that point ionization ofsurrounding atmosphere takes place
Dielectric strength of surrounding air decreases giving an easypath to lightning stroke.
Decrease in dielectric strength of surrounding air takesconsiderable time
7/27/2019 Over voltage protection.pptx
14/65
Lightning discharges
Stroke B:
A, B & C are three clouds with A and C positively charged andB negatively charged
When there is a stroke between (A) and (B) the charge on (C)
becomes free and immediately and indiscriminately strikeson any object on the ground
For stroke (B) there is no time lag Stroke (B) may completely ignore highest building and strike
bare ground.
No protection can be arranged against stroke `B` Stroke `A` can be made safe by channelising the chargethrough a lightning conductor placed on the top of thebuilding
7/27/2019 Over voltage protection.pptx
15/65
Static induced charges
An over head conductor accumulates staticallyinduced charge when a charged cloud comes above
When the cloud is swept away charge on the
conductor is released The charge travels on either side giving rise to
two travelling waves
The earth wire does not prevent such surges
7/27/2019 Over voltage protection.pptx
16/65
Lightning strokes
Over voltage due to lightning strokessurge impedance of the line = ZsDischarge current = IdOver voltage due to direct stroke = Vd = Id x ZsHowever current travels in both directions
over voltage = Vd = Id x Zs2
when lightning strikes over earth wire or a tower
Over voltage = Id x Ze + Lc didt
Ze = impedance of earth wire
Lc is the inductance of the line conductor
7/27/2019 Over voltage protection.pptx
17/65
Protection against lightning
1. Protection of transmission lines from
direct strokes
2. Protection of power stations and
substations from direct strokes3. Protection of electrical equipment
from traveling waves
7/27/2019 Over voltage protection.pptx
18/65
Protection of transmission lines
Against the direct strokes : Most harmful
Effective protection required shielding to
prevent lightning from striking the electricalconductors.
There shall be adequate drain facilities so that
the charge can be grounded without affectingInsulators or line conductors.
7/27/2019 Over voltage protection.pptx
19/65
Design of transmission line against
lightning
Design shall consists of(a) General wire of adequate mechanical strength to provide shielding
for line conductor. They shall also be noncorrosive
Resistance of ground wire shall be low for better protection againstdirect stroke.
(b) Adequate clearance between1. Line conductor and tower
2. Line conductor and earth
3. Clearance between line conductor and ground wire all throughthe span including mid Span or point of lowest sag.
(c) Tower footing resistance shall be low(d) Angle of protection (shielding angle) angle between the normal
passing through the ground wire and line joining the supportedcenter points of outer conductor and ground wire. It shall be 30for 132 & 220 kV lines 20 for 400 kV lines
7/27/2019 Over voltage protection.pptx
20/65
Effect of number of earth wires In the absence of a ground wire: When there is a charge cloud over a transmission line without
any ground wire
There will be two capacitances(1) Between cloud and conductor C2(2) Between conductor and earth C1Induced voltage on the line
V L1 = C1 x EcC1+C2
When ground wire is present it increases capacitance betweenconductor and earth i.e. C1 Decreases induced voltage on theline.
It is observed that presence of a ground wire reduces inducedvoltage on line to half.
For two ground wires the induced voltage comes down to onethird
Presence of two ground wires also provides better shielding
7/27/2019 Over voltage protection.pptx
21/65
Earth wires
Disadvantages with ground wire:
(a) higher line cost
(b) Probable direct shorting between lineconductor and ground wire when the later
gets cut
In 400kV system transmission line towers will
have twu earth wires.
7/27/2019 Over voltage protection.pptx
22/65
Alternative method of line protection
Even after providing ground and reducing the likelyinduced voltages, harmful voltages can still develop
Lightning arrestors act as additional protectivedevices by by-passing the surges to ground
Protector tube is a fiber tube with electrode at earthend.
Fitted directly below the conductor
The arc type electrode on the top of the tube forms aseries gap with conductor
7/27/2019 Over voltage protection.pptx
23/65
Alternative method of line protection
The lower electrode is solidly grounded In case of surge on the conductor, an arc develops
between conductor and top electrode of the tube.
Arc shifts within the tube and vaporises some of thefiber of tube wall to emit gases which will quench thearc
This tube successfully prevents re-striking
The break down voltage of tube shall be less thanflash over voltage of the insulation.
7/27/2019 Over voltage protection.pptx
24/65
Protection against traveling waves
The traveling waves cause the following damages:i. High peak voltage of surge may cause flash over in the
internal winding or external flashover between theterminals of the equipment.
ii. steep wave front may cause internal flash over betweenturns of the transformer
iii. Steep wave front resulting into resonance and highvoltage may cause internal or external flash over causingbuilding up of oscillations in the equipment
Protective equipment : LAs and Surge diverters They are connected between line and earth
7/27/2019 Over voltage protection.pptx
25/65
Action of the Surge diverter
A traveling wave reaches surge diverter and attains aprefixed voltage
A spark is formed across the gap
The diversion provides a low impedance path to earth
The surge impedance of the line limits the amplitude ofthe current flowing to earth to prevent break down of
insulation
Important aspect is that the surge diverter shallprovide low impedance path to earth only when
traveling surge reaches the surge diverters
7/27/2019 Over voltage protection.pptx
26/65
Action of the Surge diverter It shall absorb any current during normal operation
for over voltage surges.
It means that it shall not function at powerfrequencies but function only when abnormalfrequencies are applied
When there is a discharge through them they shall becapable of carrying the discharge current for sometime interval.
After the over voltage discharge it must be capableinterrupting normal frequency current from flowing toearth as soon as the voltage reaches below the breakdown value
7/27/2019 Over voltage protection.pptx
27/65
Switching over voltage protection in a
substation
Operation of breakers causes transient over voltages Over voltage value varying between 1.1 Pu to 6 Pu based on
switching duty and the type of circuit breaker Over voltage occurs mainly due to exchange of energy
between system inductance LI2 and system capacitance
CV2
Over voltage occurs during the opening of circuits and closingof long EHV lines
Most severe over voltages occurs during the closing unloadedtransmission line
Preventive measure Provision of Pre insertion resistors ( 400 to 800 ohms per
phase) Simultaneous closing of lines at both ends Using shunt reactors, surge arresters etc.
7/27/2019 Over voltage protection.pptx
28/65
Switching Over voltages in Substations
Switching duty of
C.B.
Applications and
Remedial Actions
Phenomena
Opening of capacitor
bank currents, cable
charging circuits, filter
banks
Switching of shunt
capacitor banks used for
p.f. correction.
- Use of re strike free C.B.
for capacitor switching
duty.
Re strike in circuit
breakers giving over
voltage.
EHV lines
* Closing unloaded
lines* Closing charged
lines
* Auto re closing of
C.B.
* Long EHV transmission.
- Use of pre-closing
resistors with circuitbreakers. Use of lightning
arresters. Use of shunt
reactors in transmission
lines.
Traveling waves
travel to and fro
giving rise to a
switching surge.
7/27/2019 Over voltage protection.pptx
29/65
Methods of Reducing Switching Over
Voltages
Switching operation
causing over voltage
Method to reduce
switching over voltage
Energising an uncharged
line
High voltage shunt reactors
are connected to line toreduce power frequency
over voltages.
Elimination of trapped
charged on the line
Line shunting after opening
by means of earthing switchReduction of current
chopping
Opening resistors (
Resistance switching with
CB) used only with ABCB
7/27/2019 Over voltage protection.pptx
30/65
Methods of Reducing Switching Over
Voltages
Switching operationcausing over voltage
Method to reduceswitching over voltage
Reducing the switching over
voltages due to closing
Single stage pre closing resistor
insertion with CB.
Two stage pre closing resistor
insertion with CB.
Closing resistors in between circuit
breaker and shunt reactor
Reducing switching over voltages
by improved switching sequence
Synchronous switching of three
poles.Simultaneous operation of circuit
breakers at both ends of line,
Use of surge arrestors While closing of line
While disconnecting reactor
7/27/2019 Over voltage protection.pptx
31/65
Rod gaps or coordinating gaps
They are used on insulators, equipment and bushings
Conducting rods are provided between line terminaland earth terminal with an adjustable gap ( Airinsulation)
Rods are of 12mm dia approx.
The gap is adjusted to break down at about 20% belowthe flash over voltage of the insulation. Spark over causes dead Short circuit Voltage of phase with respect to ground falls very low
The rod gaps are no more used consequent todevelopment of surge arrestors.
O lt i N t k d R di
7/27/2019 Over voltage protection.pptx
32/65
Over-voltage in Network and Remedies
Phenomena Causes Effect Remedies
Surges Lightning strokes on
overhead lines orsubstation
Line insulation flash
over or puncture.The traveling wave
reaches substations.
The insulation of
equipment is
stressed by impulse
surge
-Use of Ground
wire
- Surge Diverters
-Earthing of
towers
-Lightning Masts
Switching
surges
Breaking inductive circuit,
the energy stored
inductance gives rise a
voltage rise across
capacitor.
Switching of capacitive,
line charging currents give
rise to a over voltage due
to restrike. Closing of EHV
lines
Wave travels from
C.B. to both sides
Transmission line
insulator, stressed.
Terminal apparatus
insulation stressed
-Use of opening
resistors with C.B.
- Use of restrike
free C.B.
-Use pre-insertion
resistors with C.B.
7/27/2019 Over voltage protection.pptx
33/65
Over-voltage in Network and Remedies
Phenomena Causes Effect Remedies
Resonance The fault causingresonance between
inductance and
capacitance in a part of
the circuit
Very high, voltagesurges occur.
Insulation failure
likely to occur.
Filters toeliminate
harmonics
Travelingwaves
High voltage waves getreflected on reachinga junction or end.
Reflected wavesgets superimposed
for initial wave.
Voltage may rise to
several time the
normal voltage.
-Properswitching
sequence.
Sustained
Power
frequency
over
voltage
Poor voltage control Failure of
transformers and
Rotating Machines
-Proper Voltage
control
7/27/2019 Over voltage protection.pptx
34/65
Protective Devices Against Lightning Over voltages
Device Where applied Remarks
Rod gaps Across insulator string,bushing insulators -Difficult to coordinate-Create dead short
circuit
-Cheap
Overhead Ground
Wires (earthed)
-Above overhead lines
-Above the substationarea
-Provide effective
protection againstdirect strokes on line
conductors towers sub
station equipment
Vertical Masts in
substations
-- in sub stations -instead of providing
overhead shieldingwires
Lightning Masts/Rods
(earthed)
- Above tall buildings Protect buildings
against direct strokes.
Angle of Protection
= 300
7/27/2019 Over voltage protection.pptx
35/65
Protective Devices Against Lightning Over voltages
Device Where applied Remarks
Surge Arresters -- on incoming lines in each
substation
-Near terminals of
Transformers and
generators
-Near motor and
generators terminals
-- Diverts over voltage to
earth without causing
short circuit
-Used at every voltage
level in every sub-station and for each line.
Surge Absorbers -- near rotating machines
connected between phaseand ground
-Resistance
CapacitanceCombination absorbs
the over voltage surge
and reduces steepness
of wave
7/27/2019 Over voltage protection.pptx
36/65
Lightning arrester selection
1. To determine the magnitude of the power frequency phase to ground voltageexpected at the proposed arrester location during phase to ground fault, or otherabnormal conditions which cause higher voltages to ground than normal.
2. To make a tentative selection of the power frequency voltage rating of thearrester. This selection may have to be reconsidered after step (6) is completed.
3. To select the impulse current likely to be discharged through the arrester.
4. To determine the maximum arrester discharge voltage for the impulse currentand type of arrester selected. 5. To establish the full-wave impulse voltage withstand level of the equipment to
be protected.
6. To make certain that the maximum arrester discharge voltage is below the fullwave impulse, withstand level of the equipment insulation to be protected, byadequate margin.
7. To establish the separation limit between the arrester and the equipment to beprotected.
7/27/2019 Over voltage protection.pptx
37/65
Types of Earthing
For purpose of selection of voltage rating of a LA threetypes of earthing are considered
(I) Effective earthed system: a system is effectively earthed
if under any fault condition the line to earth voltages of
healthy phases do not exceed 80 % of the system line toline voltage
If in a system all transformers have star connectedwinding with neutrally solidly earthed then the system
is effectively earthed
However if only few transformers are earthed like that,it is not effectively earthed system
7/27/2019 Over voltage protection.pptx
38/65
Types of Earthing - conted.
(II) Non effectively earthed system:
a) if the line to earth voltage in healthy phases in case of afault exceed 80% of the line to line voltage but does not exceed100% of it, the system is called non effectively earthed system
b) System with few solidly earthed neutrals
c) Systems with neutral Earthed through resistors orreactors of low ohmic value or arc suppression coil
(III) Isolated or un earthed neutral systems :-
system neutrals are not earthed. Line to earth voltage of healthyphases exceed 100% of the line to line voltage.
7/27/2019 Over voltage protection.pptx
39/65
Selection of lightening arrestors
Tentative selection of arrestor Voltage:
Arrestor Voltage rating shall not be less thanproduct of system highest voltage x co-
efficient of earthing
Co-efficient of earthing : Effectively earthed system 80%
Non effectively earthed system - 100 %
and isolated earth system
7/27/2019 Over voltage protection.pptx
40/65
Selection of lightening arrestors
In a 220 kV effectively earthed system Highest system voltage = 245 kV Co-efficient of earthing = 80%
Arrestor voltage rating >= 245x0.8 = 196 kV As per IS 3070 (partI) 1965 the rating is 198 kV
By going for a higher voltage rating for a surge
arrestor, the degree of protection forequipment gets reduced.
7/27/2019 Over voltage protection.pptx
41/65
Selection of arrestor discharge current
This can be calculated from(a) Spark over voltage of transmission line insulation
(b) Surge impedance of the line
(c) Residual discharge voltage of LAIa = 2E- Ea
Z
Ia = Arrestor discharge current
E = Magnitude of incoming surge voltage
Ea = Residual discharge voltage of an arrestor
Z = Surge impedance of the line
7/27/2019 Over voltage protection.pptx
42/65
Selection of arrestor discharge current
In a 220 kV system using 11 insulators Transmissionline will not permit a traveling wave of a value morethan 1025 kVp
As per IS 3010 (Part 1) -1965 the residual voltages of
LA at a discharge current of 10kA is 649 kV. Considering the surge impedance as 450 ohms Maximum value of discharge current of LA =
2(1025000)-649000 = 3100 Amps
450 The LAs normally in 200 kV system have a discharge
current rating of 10 kA.
7/27/2019 Over voltage protection.pptx
43/65
Selection of arrestor discharge Voltage
Most important characteristic of LA determining the protectionlevel being offered
The arrestor discharge voltage shall be less than BIL ofequipment for effective protection
Discharge voltage depends on(I) discharge current
(II) rate of rise of current applied(III) Wave shape of current applied
Discharge voltage of LA increases with discharge current. Butincrease is much restricted due to nonlinear resistanceproperty.
Increase in discharge from 5 kA to 20 kA produces only 25% risein discharge voltage. Increase in rate of current from 1000 to 5000 Amps per micro
second increases discharge voltage by only 35%.
7/27/2019 Over voltage protection.pptx
44/65
Protective margin of LA
Protective margin of LA = BIL of the equipment---maximum discharge voltage of LA
While determining protection level offered by a LA 10%allowances towards drop in lead length and manufacturingtolerance shall be allowed.
Protective margin shall be 20% of the BIL of the equipmentwhen closely located
In a 220 kV systemDischarge voltage of LA = 649 kV
Allowing 10 % margin protection level = 713 kVBIL of equipment = 900 kVp
Protection margin = 900-713 = 187 kVp
There is more than 20 % of the BIL of 180 kV
7/27/2019 Over voltage protection.pptx
45/65
Protective margin of LA-Continue.
In American system
Average discharge voltage x 1.25 +40 kV = BIL
protected
When adequate margin is not available LAs
with lower rating shall be chosen taking risk.
7/27/2019 Over voltage protection.pptx
46/65
Insulation Co-ordination Scheme
For 220 KV system. L.A. Voltage rating=system highest voltage x co-efficient of earthing =245x.8=196Kv. Selecting standard rating from Table 12.1 column 1,L.A. voltage rating=198 Kv Discharge current rating= 10KA (assumed) Residual voltage, from column 3 of table 12.1,=649Kv (peak) Protection level of the L.A. =649x1.1=714Kv For a margin of 20% between the B.I.L. and the protection level of L.A., the B.I.L. should be
=714x1.2=857Kv.
Choose standard B.I.L. Table 14.3 (b) Col. 4=900 Kv, The corresponding power freq. I minute test voltage =395kv Switching surge flashover voltage =220 x6.5=825kv 3 Check it is less than B.I.L. of 900kv.
Power frequency over voltage=220x3=228kv rms 3 This is less than 395kv. B.I.L. of CBs, instrument transformer, disconnect switches etc,.=900x1.1=990kv. Choose standard B.I.L.=1175kv.
7/27/2019 Over voltage protection.pptx
47/65
The L.A. voltage rating
Rated system
voltage KV
Highest system
voltage KV
Arrester rating
in KV
132 145 120/132
220 245 198/216
400 420 336
7/27/2019 Over voltage protection.pptx
48/65
Establishment of Separation Limit
When arrestor are to be located away from equipment. A traveling wave coming into the station to location to the discharge voltage of the arrestor. Proximity to transformer or breakers.
- Transformer is most expensive price.
- Repair to transformer is costly and with higher revenue loss.
- Transformers are always at the end of a circuit where voltage regulation.
. For circuit breakers and disconnecting switches flash over distance between terminals when inopen position in grater than between terminals and ground.
. Surge in excess to insulation strength will flash over to ground with out damaging theequipment.
. At best there can be only outage .
. By reducing BIL of transformer savings in the cost of insulation can be obtained.
. Not possible incase of CB or disconnections switches.
. Hence a set of LAS shall be closer to transformers.
7/27/2019 Over voltage protection.pptx
49/65
Location of Lightning Arresters:
The electrical circuit length between L.A. and the transformer bushingterminal (inclusive of lead length in metes for effectively earthed) should
not exceed the limits given below:
Rated syst.voltage KV BIL KVPeak Max.distance
132kV 550
650
35.0
45.0
220kV
400kV
900/1050
1425/1550
Closer
to
Trans.
7/27/2019 Over voltage protection.pptx
50/65
Definition:- Flash over voltages
Impulse flash over voltage:-
The voltage which will cause flash over of anInsulation When subjected to a 1.2x50s
impulse
(British standards1x50 sec)
(American standards 1.5 x 40sec)
7/27/2019 Over voltage protection.pptx
51/65
Definition:- Flash over voltages
Basic Insulation level :-The crest voltage of standard wave that will notcause flashover of the insulation is referred to asBasic insulation level
(Basic impulse insulation voltages are levelsexpressed in impulse crest voltage with a standardwave not longer than 1.2x50 s.
Equipment insulation as tested shall be equal or
above the BIL
7/27/2019 Over voltage protection.pptx
52/65
Impulse spark over volt- time characteristic
This characteristic is obtained by plotting--Time which elapses between the moment the voltage wave
is applied and the moment of spark over -- on abscissa
-Voltage at the moment of spark over
(i) Occurring on the wave front(ii) Occurring on the wave peaks
(iii) Crest of the voltage for spark overoccurring on the wave tail
7/27/2019 Over voltage protection.pptx
53/65
LINE INSULATION
Extra high voltage line can be made lightning proofby
1 Efficient shielding
2 Low tower footing resistance equal to or less than10 ohms
shielding angle
Transmission lines up to 220kV 30400 kV at and above 20
7/27/2019 Over voltage protection.pptx
54/65
7/27/2019 Over voltage protection.pptx
55/65
Line insulation -contd.
Line insulation shall be sufficient to prevent aflashover from the power-frequency over
voltages and Switching Surges.
It shall take into consideration the local unfavourable circumstances which decrease the
flash over voltage (rain, dirt, Insulation
pollution etc.,)
7/27/2019 Over voltage protection.pptx
56/65
OVER VOLTAGE FACTORS
Line
Voltages
Switching
Surge flash
over
Power frequency flash
over (Dry & Wet)
220kV 6.5 V pn 0.3
400kV 5.0 V pn 3.3
Vpn = Phase to Neutral Voltage (rms)
Add one or two more Insulators for each string.
7/27/2019 Over voltage protection.pptx
57/65
OVER VOLTAGE FACTORSContd.
-To take care of one disc in the string
becoming defective.
-Facilitate hot line maintenanceUp to 220 kV Line 1 disc for each string
400 kV Line 2 discs for each string
RECOMMENDED INSULATION LEVEL OF
7/27/2019 Over voltage protection.pptx
58/65
RECOMMENDED INSULATION LEVEL OF
LINE
Normal
system
Voltage
Vpn
In kV
(Vph/3)
Switching over
volt. (Wet) kV *
No of
discs
required
132kV 76 76 x6.5=495 5
220kV 127 127x6.5=825 9400kV 231 231x5=1755 13
* Compared with Impulse FOV (Value)
RECOMMENDED INSULATION LEVEL OF
7/27/2019 Over voltage protection.pptx
59/65
RECOMMENDED INSULATION LEVEL OF
LINEcontd.
Normal
system
Voltage
Vpn
In kV
Power freq.
over volt
(wet)
(kVrms)
No.
of
discs
req.
No. of
discs
recom.
As per
practice
132kV 76 76x3=228 6 7 9/10
220kV 127 127x3=381 10 11 13/14
400kV 231 231x3=762 20 22 23/24
7/27/2019 Over voltage protection.pptx
60/65
Tower forting resistance 10ohms severest lightning discharge 50kA (rms) Impulse strength of
Insulation=2x50x10x10=700kV
As per the table for 7 discs, the impulse FOV (kVp =695kVp)
For better performance tower fortingresistance shall be brought down.
For 132kV best is 7 ohms
C di ti f li I l ti d S b
7/27/2019 Over voltage protection.pptx
61/65
Co-ordination of line Insulation and Sub-
Station Insulation
Line Insulation is not directly related to theInsulation of equipment within the Sub-Station.
Impulse flash over voltage of line Insulation
determine the highest surge voltage that can travelinto the sub-station.
Current through lighting arrestor can be calculatedfrom
1 Surge impudence of line
2 Surge voltage arriving over the line
Co ordination of line Ins lation and S b
7/27/2019 Over voltage protection.pptx
62/65
Co-ordination of line Insulation and Sub-
Station Insulation
Discharge voltage of the LA on that current isthe basic protective level of the substation
equipment.
Discharge voltage across LA varies with surgecurrent.
BASIC INSULATION LEVEL AS PER IS (2165
7/27/2019 Over voltage protection.pptx
63/65
BASIC INSULATION LEVEL AS PER IS (2165
1962)
Nominalsystem
volt kV
(rms)
Highestsystem
volt kV
(rms)
Impulse withstandvolt kVp for test
One minute powerfrequent volt kV (rms)
Full
insulation
Reduced
insulation
Full
insulation
Reduced
insulation
132 kV 145 650 550 275 230
220 kV 245 1050 900 460 395
400 kV 420 1550 680
1425 630Reduced insulation is used where system is effectively earthed.
7/27/2019 Over voltage protection.pptx
64/65
INSULATION LEVELS OF EQUIPMENT
Transformers, Isolators, Instrument Transformers aremanufactured for the standard Insulation level.
Some times transformers, are manufactured for onestep lower insulation level for the sake of economy.
(LAs will be designed for a still lower level)
Where LAs are provided right on the top of thetransformer, some of the equipment may lie well outside the protective zone of the LA.
7/27/2019 Over voltage protection.pptx
65/65
INSULATION LEVELS OF EQUIPMENT
Protective zone is determined based on
A With stand level of equipment
B Discharge volt of LA
C Distance between LA and equipment.
Such equipment shall be designed for one stephigher Bil.
Generally BIL of substation equipment other thantransformer are designed for10% higher BIL than thatof Transformer .