Top Banner
Switch to perfection CS Outdoor Enclosures P OSSIBILITIES... Product Selection, Engineering And Configuration Guide
16

OSSIBILITIES CS Outdoor Enclosures - Steven Engineering · 2005. 1. 26. · 7 Heat Exchanger Options: • Optional rear mount external (shown) ... • All-aluminum ES-style design

Feb 09, 2021

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
  • Switch to perfection

    CS Outdoor EnclosuresPOSSIBILITIES...Product Selection,Engineering AndConfiguration Guide

  • RITTAL MODULAR TECHNOLOGY 1 Equipment Module Options:

    • 0600w x 1000h x 0500d, single bay

    • 0600w x 0800h x 0600d, single bay• 0600w x 1200h x 0500d, single bay• 0600w x 1200h x 0600d, single bay• 0800w x 1000h x 0500d, single bay• 0800w x 1200h x 0500d, single bay• 0800w x 1200h x 0600d, single bay (shown)• 0800w x 1600h x 0600d, single bay• 1200w x 1200h x 0500d, dual bay• 1600w x 1200h x 0600d, dual bay

    4 Doors Options:• RS hinged (shown)• Optional RS hinged rear door access

    6 Air Conditioner Options:• Optional rear mount external (shown)

    • Optional top mount external• Optional side mount external

    2

    7 Heat Exchanger Options:• Optional rear mount external (shown)

    • Optional top mount external• Optional side mount external• Optional door mount internal (shown)

    • ProEngineer 3D design technology

    • OEM custom design capability based onstandard Rittal design principles

    • Design based on “High-Volume” Rittalstandardization & manufacturing efficiency

    2 Structural Roof Options:• Standard front-rear access roof

    • Optional rear mount heat exchanger orair conditioner roof (shown)

    • Optional back-to-back module roof

    3 Base Plinth & Battery Module:• Optional 100mm mounting plinth

    • Optional 350mm battery modulewith pull-out shelf (shown)

    8 Power Module Options:• Optional 100/100A PTS module (shown)

    • Optional 200/100A PTS module

    5 Side Solar Panel Options:• Standard side solar shield (shown)

    • Standard side spanner (shown)• Optional bay side solar shields

    • Bellcore GR487 design compliance

    • Complete bolt-together modularity

    - Side-to-side or back-to-back equipmentmodule mounting capability

    - Equipment/power/termination modulemounting interchangeability

    RITTAL’S WIRELESS/WIRELINE ENCLOSURE SYSTEM DESIGN PHILOSOPHY. • All-aluminum construction techniques

    • Provides for regulatory & industrystandards compliance

    • Provides the ultimate cross-platform OEMenclosure & subrack packagingsolutions...

    1

    2

    3

    5

    6

    7

    8

    4

  • 3

    1 EquipmentModule

    2 StructuralRoof

    3 Battery Drawer& Base

    4 Doors

    5 Side SolarPanel

    BUILT TO YOUR SPECIFICATIONSEquipment Module• All-aluminum ES-style design• Unibody structural support frame

    - 2mm (.080”) aluminum- Standard powder paint (RAL 7035)

    • ES/PS 25mm mounting capabilityStandard features:• LS hinged front door (double wall)• Fixed rear panel (double wall)• Standard gland plate bottom access

    • Module-to-module mounting• Common intra-module cabling holes

    - (4) 3” protected cable openings each side• Common module mounting holes

    - (6) mounting hole locations each sideModule options:• EMI compliance• Side-to-side or back-to-back module mtg.• Front & rear door mounting (LS or RS)

    Custom enclosure options:• 25mm height, width & depth modifications• Custom customer specified paint

    Top Structural Roof• Environmental & structural support

    - 2mm (.080”) aluminum exterior covering- 3mm (.125”) aluminum C-channel structure

    • Top lifting-eye site placement access• Standard front & rear 50mm vented overhang• Optional rear mount heat exchanger/air

    conditioner• Optional back-to-back module roof• Standard powder paint (RAL 5018)• Standard side spanner (side overhang)

    - Vented 25mm side protection

    Base Mounting Plinth Option• 100mm structural mounting/transportation base• 3mm (.125”) aluminum C-channel structure

    - Standard powder paint (RAL 5018)Battery Module Option

    • 350mm structural battery compartment module- 3mm (.125”) aluminum C-channel structure- Internal structural steel slide mounting plate

    Door Features• Double-wall solar environmental protection

    - 2mm (.080”) aluminum- Standard powder paint (RAL 7035)

    • Front & rear mounting options• Rittal foamed-in-place gasket seal• EMI option available• 100° opening access

    Rear panel feature:• Rear fixed panel mounting

    - EMI option available- Back-to-back option available

    Side Solar Shield• Double wall solar environmental protection

    - 2mm (.080”) aluminum• Standard side solar shield

    - Used with standard side spanner overhang option- Sized for plinth, battery & roof CU options

    • Standard side spanner (side overhang)- Vented 25mm side protection

    Front-rear hinged door access options:• Ergoform flush mount handle

    - 3-point latching (standard)- Padlock clasp (standard)

    • Bottom, tool or key lock options- Standard push-button access- Optional Telco #216 tool access- Optional Telco 7/16 tool access- Optional key access

    • Optional bay side solar shields- Full height solar shield protection- Not used with side spanner

    overhang option- Used for non-standard system

    mounting configuration- Sized for plinth, battery &

    roof CU options

    • Pull-out battery drawer access- 110v ac/200w thermostat controlled

    battery heaters- Generic battery clamp

    • Standard powder paint (RAL 5018)

  • 4

    6 AirConditioner (CU)

    7 HeatExchanger (HX) HX Heat Exchanger Features:

    • High-output outdoor design applications- Cross flow cassette design- 20, 60 and 90 watt/°K capacities

    (custom options available)

    Outdoor “Closed-Loop” Heat Exchanger Options

    Multiple Mounting options:• Roof mount• Rear external wallmount• Front internal door mount

    CU Air Conditioner Features:• High-output outdoor design applications

    - 3000, 5000, 8000 BTU standardavailability (custom options available)

    Outdoor “Closed-Loop” Air Conditioner OptionsMultiple mounting options:

    • Roof mount• Rear external wallmount

    Description 274148 9768032 9768012 9768042 9768052 9764012 9764022 9763012 9763032Mounting options Current Current Current Current Current Current 9/99 Current CurrentMounting options Interior door Exterior roof Exterior rear/side mountingMinimum module size 600wx650h 600wx1200h 800wx1200h 600w x 1200h 800wx1600h 600wx500d 800wx600d 600wx1200h 800wx1200hHousing construction AluminumCooling technology Cross-flow Counter-flow Cross-flowRegulatory compliance UL, In-process UL, CERated voltage -40-56vdcCooling output rating 21W/˚C 40W/˚C 60W/˚C 85W/˚C 130W/˚C 60W/˚C 85W/˚C 60W/˚C 90W/˚CPerformance summary 420W@48vdc 760W@48vdc 1140W@48vdc 1615W@48vdc 2470W@48vdc 1140W@48vdc 1615W@48vdc 1140W@48vdc 1710W@48vdc(Estimated watts @19˚∆t) 487W@54vdcTemperature range -33˚C-+65˚C (-28˚F-+149˚F)Rated current max (a) 3.5 5.3 5.3Power consumption max 76 140 140Blower MTBF TBD TBD TBD TBD TBD TBD TBD TBD TBDNoise level TBD TBD TBD TBD TBD TBD TBD TBD TBD110vac internal heater (w) 250 NA220vac internal heater (w) NA 400 400 NA 400 400 400 400 400Weight Size dependentExternal air thru-put @0 ∆P TBD TBD TBD TBD TBD TBD TBD TBD TBD(cfm)Internal air thru-put @0 ∆P TBD TBD TBD TBD TBD TBD TBD TBD TBD(cfm)External blower OFF (c/f) 27˚C (82˚F) TBD-48vdc power connector type 4-Pin mate-n-loc 3pin, 3W3 connector

    Pin: 1 & 2Alarms output Open collector Microprocessor controls

    NO-COM outputAlarm connector type 4-Pin mate-n-loc 15pin D-Sub connector

    Pin: 2 & 3Heater connector type 3pin, IEC-320 connectorOutdoor rated components Protected electronics

    Env rated external blower

    Heat Exchanger Technical Specifications

    Description 9768100 9762010 9761010 9761032 9761042Availability Current Current Current Current 9/99Mounting options Interior Door Exterior Roof Exterior Rear/Side MountingMinimum module size 600Wx1200D 600Wx500D 600Wx1200H 800Wx1200H 800Wx1200HHousing construction Aluminum/SSTRegulatory compliance CE In-processRated voltage 220vac, 50-60hzCooling output L35L35 900W(3071BTU) 900W(3071BTU) 900W(3071BTU) 1400W(4778BTU) 2300W(7850BTU)

    L35L50 650W(2218BTU) 750W(2560BTU) 750W(2560BTU) 1050W(3583BTU) 1940W(6621BTU)Temperature range +20˚C-+55˚C (68˚F-+131˚F)Rated current max (Amps) 4.0 4.0 3.5 5.5 9.5Starting current 11.6 10.7 10.8 15.5 16.5Power consumption (w) L35 470 460 450 900 1300

    L50 530 520 520 1000 1450Blower MTBF TBD TBD TBD TBD TBDRefrigerant R134Ap. max 24 barNoise level TBD TBD TBD TBD TBD220vac internal heater (w) TBD TBD TBD TBD TBDWeight Size dependentExt air thru-put @0 P (cfm) 252 335 470 470 735Int air thru-put @0 P (cfm) 341 335 470 647 735Temperature control Microprocessor Controller -

    Thermostat range (+20˚C-+55˚C), (Preset @ 35˚C)Alarms output Microprocessor optionAlarm connector type 15pin D-Sub connectorDoor switch connector type 9pin D-Sub connectorPower connector type 3pin, IEC-320 connectorOutdoor rated components Coated coils & refrigerant lines / Protected electronics / Env rated external blower

    Air Conditioner Technical Specifications

  • 5

    Power Transfer Module Design• All-aluminum ES-style design construction• Unibody structural support frame

    - 2mm (.080”) aluminum construction- Standard powder paint (RAL 7035)

    • Front ES/PS 25mm mounting capability • Standard power transfer features - 100/100 or 200/100 transfer - 12-position loadcenter - Surge protection -100a generator receptacle

    • Rear mount internal outlet box- (2) 110V 15A duplex receptacles- (1) 110V 15A GFIC receptacle

    Door features: • Double-wall solar protection

    - 2mm (.080”) aluminum- Standard powder paint (RAL 7035)

    • Front & rear mounting options • Rittal foamed-in-place gasket seal

    • Ergoform flush mount door access- 3-point latching (standard)- Pad lock clasp (standard)- 100° opening access

    8 PowerModule

    PolemountCabinet

    Polemount Cabinet Design• All-aluminum ES-style design

    - Front access configuration • Unibody structural support frame

    - 2mm (.080”) aluminum- ES/PS 25mm mounting capability- Standard powder paint, or plated EMI option (RAL 7035)- Custom gland plate bottom access

    • Custom 25mm WxHxD size optionsDoor features: • Double-wall solar protection

    - 2mm (.080”) aluminum- Standard powder paint (RAL 7035)

    • Front & rear mounting options • Rittal foamed-in-place gasket seal

    • Ergoform flush mount door handle- 3-point latching (standard)- Pad lock clasp (standard)- 100° opening access

    • Bottom, tool or key lock options- Standard push-button access- Optional Telco #216 tool access- Optional Telco 7/16 tool access- Optional key access

    Roof features:• Non-structural environmental protection

    - 2mm (.080”) aluminum- Standard powder paint (RAL 5018)

    • Front vented access overhang

    • Bottom, tool or key lock options- Standard push-button access- Optional Telco #216 tool access- Optional Telco 7/16 tool access- Optional key access

    Standard PTS configuration: • 100/100A PTS module option - 100/100 amp main/emergency transfer - Joslyn AC voltage surge protection - 100a 12-position load center distribution - 100a Hubbell generator connector • 200/100A PTS module option - 200/100 amp main/emergency transfer - Joslyn AC voltage surge protection - 100a 12-position load center distribution - 100a Hubbell generator connectionRoof features:• Non-structural environmental protection

    - 2mm (.080”) aluminum- Standard powder paint (RAL 5018)

    • Includes side spanner overhangprotection

    AnchorPlates

    Anchor Plate Design• Provides embedded concrete anchoring• Padmount mounting location

    - Design based on module size• Locating frame support

    - 2mm (.080”) aluminum frame- SST anchor sleeve mounting

  • 6

    STANDARD PRODUCT CONFIGURATIO

    2 StructuralRoof

    1 BaseModuleIncludes front door(double wall), rearpanel (double wall)

    3 Battery Drawer& Base

    4 Doors

    5 Side SolarPanels

    ❏ 100mm base plinth + equipment module❏ 350mm battery module + equipment module❏ 100mm base plinth + top heat exchanger + equipment module❏ 350mm battery module + top heat exchanger + equipment module❏ 100mm base plinth + equipment module❏ 350mm battery module + equipment module❏ 100mm base plinth + top heat exchanger + equipment module❏ 350mm battery module + top heat exchanger + equipment module

    ❏ Other

    ❏ Standard front & rear vented overhang roof❏ Rear mounted heat exchanger/air conditioner mounting roof❏ Back-to-back module mounting roof❏ Standard side spanner (overhang)

    - Used with standard side solar shield ONLY

    ❏ Other

    ❏ 100mm base plinth❏ 350mm battery module

    - Pull-out battery drawer- 120 VAC/200w thermostat controlled heater

    ❏ 350mm cable management module- Removable front panel

    ❏ Other

    ❏ RS hinged door❏ LS hinged door❏ RS EMI hinged door❏ Back-to-back rear panel❏ Back-to-back EMI rear panel

    ❏ Other

    Width: 0600 (23.63)Height: 1000 (39.37)Depth: 0500 (19.69)

    Width: 0600 (23.63)Height: 0800 (31.50)Depth: 0600 (23.63)

    Width: 0600 (23.63)Height: 1200 (47.24)Depth: 0500 (19.69)

    Width: 0600 (23.63)Height: 1200 (47.24)Depth: 0600 (23.63)

    Width: 0800 (31.50)Height: 1000 (39.37)Depth: 0500 (19.69)

    ❏ ❏ ❏ ❏ ❏

    Part No: 9751075 Part No: 9751015 Part No: 9751095 Part No: 9751025 Part No: 9751085

  • 7

    ON GUIDELINE OPTIONS

    6 AirConditioner

    7 HeatExchanger

    8 PowerModule

    9 AnchorPlates

    ❏ 60w/c, 1140w external roof mount heat exchanger❏ 85w/c, 1615w external roof mount heat exchanger❏ 60w/c, 1140w external rear mount heat exchanger❏ 90w/c, 1710w external rear mount heat exchanger❏ 21w/c, 0420w internal door mount heat exchanger❏ 40w/c, 760w internal door mount heat exchanger❏ 60w/c, 1145w internal door mount heat exchanger❏ 85w/c, 1615w internal door mount heat exchanger❏ 130w/c, 2470w internal door mount heat exchanger

    ❏ Other

    ❏ 0900w (3000btu) internal door mount air conditioner❏ 0900w (3000btu) external roof mount air conditioner❏ 0900w (3000btu) external rear mount air conditioner❏ 1400w (5000btu) external rear mount air conditioner❏ 2300w (8000btu) external rear mount air conditioner❏ 0900w (3000btu) external side mount air conditioner❏ Optional 205-250vac transformer (max ac voltage input)

    ❏ Other

    ❏ 100/100 power transfer module- 100/100A ac transfer, surge, LC, generator connection

    ❏ 200/100 power transfer module- 200/100A ac transfer, surge, LC, generator connection

    ❏ Other

    ❏ Embedded concrete anchor plate❏ Pad mount shim kit

    ❏ Other

    Width: 0800 (31.50)Height: 1200 (47.24)Depth: 0500 (19.69)

    Width: 0800 (31.50)Height: 1200 (47.24)Depth: 0600 (23.63)

    Width: 0800 (31.50)Height: 1600 (62.99)Depth: 0600 (23.63)

    Width: 1200 (47.24)Height: 1200 (47.24)Depth: 0500 (19.69)

    Width: 1600 (62.99)Height: 1200 (47.24)Depth: 0600 (23.63)

    ❏ ❏ ❏ ❏ ❏ Width:Height:Depth:

    Special SizePart No: 9751045 Part No: 9751055 Part No: 9751065 Part No: 9752015 Part No: 9752035

  • RS View

    AC PowerModule

    Equipment Module

    B

    A

    A

    B

    Gland PlateConfiguration STD

    Optional AC Power Module100/100 Configuration

    Rear FixedWall STD

    Optional Cable-EntryKO Ports

    Optional Mechanical InterlockMain/Generator Breaker-100A Main-100A Emergency

    DK 7688 EIA FixedRails 23" Mounting

    Ergoform 3-PT Flush MountLatch LS Hinged Door 100Degree Opening

    Rittal 25mmMountingHole Pattern(Not ShownFor Clarity)

    Battery ModuleBottom Rear CableOpening

    100A Gen PlugHubbell Shown

    Load-CenterSQ-D 200A,12-Pos

    STD Surge-ProtJoslyn #1265-21

    Cable Pull-Area

    LS View(Door Removed For Clarity)

    Battery ModuleSpecial Mod Pull-Out Drawer(4) 12-FA-100C&D Batteries

    8

    Technical SpecificationsSingle-Bay Sample Configuration With Power Transfer Module & Battery Drawer

  • Optional SmallTermination Module

    Optional AC PowerModule 100/100Configuration

    Common Cabling &Mounting Holes STD

    SM TermModule

    AC PowerModule

    Optional Mechanical InterlockMain/Generator Breaker-100/100-200/200

    100A Gen PlugHubbell Shown

    Load-CenterSQ-D 200A, 12-PosFeed- Thru Mains

    STD Surge-ProtJoslyn #1265-21

    Cable Pull-Area

    Dual Module Base

    LS View(Door Removed For Clarity)

    Rear-PanelOpening

    (STD) Battery ModuleBattery Slide-out Shelf(4) 90AH BatteriesIntegrated Heater CNTL

    Bay-2Bay-1

    (STD) Battery ModuleBattery Slide-out Shelf(6) 80AH BatteriesIntegrated Heater CNTL

    Individual LS/RS Hinged-3-PT Flush Latch

    RS View

    Expansion Module

    Termination-EquipModule

    Expansion Module

    Optional Door Mount HX60W/Degree C RatingApprox 1300 W W/Solar

    Rittal 25mm MountingHole Pattern (Not ShownFor Clarity)

    9

    Technical SpecificationsSix-Bay Back-To-Back/Side-To-Side Sample Configuration With Power Transfer Module & Battery Drawer

  • 10

    Technical SpecificationsSingle-Bay Equipment Module Sample Configuration With Heat Exchanger & Battery Drawer

    Door mount heatexchanger20w/°k capacitySlim-line design

    Section A-A

    Bay Side SolarShield 2X

    Front View(Door Mounted HX View)

    Rittal 25mm Mounting HoleConfiguration (Not ShownFor Clarity)

    Section B-B

    Optional BatteryModule Pull-OutBattery Shelf-110v Heater

  • Rear View

    Battery Module Pull-OutShelf 110VAC Bat Heater

    Bottom View (Pad Mounting)

    Johnson-CNTL #TEL12-9090AH Batteries

    Solid Bottom

    MTG Base

    26x13.5 Slot 4X

    See Detail A6-Pos Gnd Bar2-Hole Lug1.25" Sp

    ProposedElectrical-BoxLocation

    Bay 1 Bay 2

    1.25" Insulator

    RF Entry ModuleRemovable FrontCover

    Right SideSection View

    CableInput

    Modified 1.75"EIA 75mmC-Channel4X

    ErgoformExternal FlangePadlock/Key/Toll3-PT Latch4X

    Rittal 25mm Mounting HoleConfiguration (Not ShownFor Clarity)

    Structural Top VentedLifting Roof

    Side Mount CUAir Conditioner1400W (5000btu)L35L35 Rating

    Rear Mount 23" Swingframe

    STD Gland PlateConfiguration

    Open Bottom AreaEquip Module

    Side SolarShield

    11

    Technical SpecificationsTwo-Bay Equipment Module Sample Configuration With Side Mount Air Conditioner & Battery Drawer

  • Product Configuration Guide

    Section Modular Options Description Width 0600mm (23.63") 0600mm (23.63")Height 1000mm (39.37") 0800mm (31.50")Depth 0500mm (19.69") 0600mm (23.63")

    1 Base Modules Equipment Module(Generic) -Standard front RS/LS hinged door & fixed rear panel 9751075 9651015

    Equipment Module, EMI-Standard front RS/LS hinged door & fixed rear panel 9751076 9751016

    2 Equipment Modules Equipment Module 0274001 0274000Equipment Module, EMI 0274082 0274081

    3 Doors & Panels Door, RS hinged 0274011 0274010Door, LS hingedDoor, RS hinged, EMI 0274092 0274091Door, LS hinged, EMIDoor, RS hinged, 21W-HX 0274099 0274098Door, RS hinged, EMI, 21W-HX 0040780 0040400Door, RS hinged, 40W-HX NA NADoor, RS hinged, EMI, 40W-HX NA NADoor, RS hinged, 60W-HX NA NADoor, RS hinged, EMI, 60W-HX NA NADoor, RS hinged, 85W-HX NA NADoor, RS hinged, EMI, 85W-HX NA NADoor, RS hinged, 130W-HX NA NADoor, RS hinged, EMI, 130W-HX NA NARear Panel, Fixed 0274018 0274017Rear Panel, Fixed EMI 0274099 0274098Rear Panel, Back-to-back mounting 0040737 0040794Rear Panel, Back-to-back mounting, EMI 0040742 0040795

    12

    CS Standard Product Selection Matrix

    8

    2

    5 6

    7

    1

    3

    12

    10

    9

    3

    4

    9

    Description 9768100 9762010Availability Current CurrentMounting options Interior Door Exterior RoofMinimum module size 600Wx1200D 600Wx500DHousing constructionRegulatory compliance Rated voltageCooling output L35L35 900W(3071BTU) 900W(3071BTU) L35L50 650W(2218BTU) 750W(2560BTU)Temperature range Rated current max (Amps) 4.0 4.0Starting current 11.6 10.7Power consumption (w) L35 470 460 L50 530 520Blower MTBF TBD TBDRefrigerantp. maxNoise level TBD TBD220vac internal heater (w) TBD TBDWeightExt air thru-put @0 P (cfm) 252 335Int air thru-put @0 P (cfm) 341 335Temperature control

    Thermostat range Alarms output Alarm connector type Door switch connector type Power connector type Outdoor rated components Coated coils & refrigerant lines /

    Air Conditioner Technical Specifications

  • Description 274148 9768032 9768012 9768042 9768052 9764012 9764022 9763012 9763032Mounting options Current Current Current Current Current Current 9/99 Current CurrentMounting options Interior door Exterior roof Exterior rear/side mountingMinimum module size 600wx650h 600wx1200h 800wx1200h 600w x 1200h 800wx1600h 600wx500d 800wx600d 600wx1200h 800wx1200hHousing construction AluminumCooling technology Cross-flow Counter-flow Cross-flowRegulatory compliance UL, In-process UL, CERated voltage -40-56vdcCooling output rating 21W/˚C 40W/˚C 60W/˚C 85W/˚C 130W/˚C 60W/˚C 85W/˚C 60W/˚C 90W/˚CPerformance summary 420W@48vdc 760W@48vdc 1140W@48vdc 1615W@48vdc 2470W@48vdc 1140W@48vdc 1615W@48vdc 1140W@48vdc 1710W@48vdc(Estimated watts @19˚∆t) 487W@54vdcTemperature range -33˚C-+65˚C (-28˚F-+149˚F)Rated current max (a) 3.5 5.3 5.3Power consumption max 76 140 140Blower MTBF TBD TBD TBD TBD TBD TBD TBD TBD TBDNoise level TBD TBD TBD TBD TBD TBD TBD TBD TBD110vac internal heater (w) 250 NA220vac internal heater (w) NA 400 400 NA 400 400 400 400 400Weight Size dependentExternal air thru-put @0 ∆P TBD TBD TBD TBD TBD TBD TBD TBD TBD(cfm)Internal air thru-put @0 ∆P TBD TBD TBD TBD TBD TBD TBD TBD TBD(cfm)External blower OFF (c/f) 27˚C (82˚F) TBD-48vdc power connector type 4-Pin mate-n-loc 3pin, 3W3 connector

    Pin: 1 & 2Alarms output Open collector Microprocessor controls

    NO-COM outputAlarm connector type 4-Pin mate-n-loc 15pin D-Sub connector

    Pin: 2 & 3Heater connector type 3pin, IEC-320 connectorOutdoor rated components Protected electronics

    Env rated external blower

    Heat Exchanger Technical Specifications

    0600mm (23.63") 0600mm (23.63") 0800mm (31.50") 0800mm (31.50") 0800mm (31.50") 0800mm (31.50") 1200mm (47.24") 1600mm (62.99")1200mm (47.24") 1200mm (47.24") 1000mm (39.37") 1200mm (47.24") 1200mm (47.24") 1600mm (62.99") 1200mm (47.24") 1200mm (47.24")0500mm (19.69") 0600mm (23.63") 0500mm (19.69") 0500mm (19.69") 0600mm (23.63") 0600mm (23.63") 0500mm (19.69") 0600mm (23.63")

    9751095 9751025 9751085 9751045 9751055 9751065 9752015(2) 9752035(2)

    9751096 9751026 9751086 9751046 9751056 9751066 9752016(2) 9752036(2)0274107 0274002 0274004 0274005 0274006 0274007 0274008 02741080274083 0274109 0274085 0274086 0274087 0274088 0274089 00407270274012 0274012 0274014 0274015 0274015 0274016 0274012(2) 0274015(2)

    0274093 0274093 0274095 0274096 0274096 0274097 0274093(2) 0274096(2)

    0274100 0274100 0274102 0274103 0274103 0274104 0274100(1/2) 0274103(1/2)0040412 0040412 0040781 0040782 0040782 0040783 0040412 0040782

    NANA

    NA NA NA 0040772 0040772 0040773 NA 0040772NA NA NA 0040784 0040784 0040785 NA 0040784

    NANA

    NA NA NA NA NA NA NANA NA NA NA NA NA NA0274019 0274019 0274021 0274022 0274022 0274023 0274019(2) 0274022(2)0274100 0274100 0274102 0274103 0274103 0274104 0274100(2) 0274103(2)0040738 0040738 0040739 0040740 0040740 0040741 0040738(2) 0040740(2)0040743 0040743 0040744 0040745 0040745 0040746 0040743(2) 0040745(2)

    13

    9761010 9761032 9761042Current Current 9/99

    Exterior Rear/Side Mounting600Wx1200H 800Wx1200H 800Wx1200HAluminum/SST

    CE In-process220vac, 50-60hz900W(3071BTU) 1400W(4778BTU) 2300W(7850BTU)750W(2560BTU) 1050W(3583BTU) 1940W(6621BTU)

    +20˚C-+55˚C (68˚F-+131˚F)3.5 5.5 9.5

    10.8 15.5 16.5450 900 1300520 1000 1450TBD TBD TBD

    R134A24 barTBD TBD TBDTBD TBD TBD

    Size dependent470 470 735470 647 735

    Microprocessor Controller - (+20˚C-+55˚C), (Preset @ 35˚C) Microprocessor option 15pin D-Sub connector 9pin D-Sub connector3pin, IEC-320 connector Protected electronics / Env rated external blower

  • 4 Battery and Base Plinth 100mm Base Plinth structure 0274105 9755015350mm Battery Module 9754015 9754025350mm Cable Management Module 9759015 9759025

    5 Structural Roof Generic Roof Module, Basic/Top CU/HX 9759015 9759025Generic Roof Module, Rear mounted HX/CU 9759055 9759065Generic Roof Module, Back-to-back mounting 9759095 9759105Standard Side Spanner (Overhang)-Used with Standard Side Solar Shield ONLY 9766015 9766025

    6 Standard Side Solar Panels 100mm Base Plinth + Equip Module 9753075 9753015350mm Battery Module + Equip Module 9753195 9753095100mm Base Plinth + Top HX + Equip Module 9753185 9753055350mm Battery Module + Top HX + Equip Module 9753205 9753135

    Bay Side Solar Panels 100mm Base Plinth + Equip Module 0040747 0040748350mm Battery Module + Equip Module 0040757 0040758100mm Base Plinth + Top HX + Equip Module 0040752 0040753350mm Battery Module + Top HX + Equip Module 0040762 0040763

    7 Anchor Plates Anchor Plate Kit, (Imbedded concrete) 9970206 9970207Shim Kit, Pad Mount 9970214 9970214

    8 Power Modules 100/100 Power Transfer Module-100/100A AC Transfer, Surge, LC, Generator Conn 9749015 NA200/100 Power Transfer Module-200/100A AC Transfer, Surge, LC, Generator Conn 9749115 NA

    9 Air Conditioners, Roof 0900W (3000BTU) External Roof mount Air Conditioner1 9762012 9762012Air Conditioners, Rear 0900W (3000BTU) External Rear mount Air Conditioner2 NA NA

    0900W (3000BTU )External Side mount Air Conditioner3 NA NA1400W (5000BTU) External Rear mount Air Conditioner2 NA NA2300W (8000BTU) External Rear mount Air Conditioner2 NA NA

    Air Conditioners, Door 0900W (3000BTU) Internal Door mount Air Conditioner3 NA NA10 Heat Exchangers, Roof 60w/k, 1140W External Roof mount heat exchanger1 9764012 9764012

    85w/k, 1710W E0xternal Roof mount heat exchanger1 NA NAHeat Exchangers, Rear 60w/k, 1140W External Rear mount heat exchanger2 NA NA

    60w/k, 1140W External Side mount heat exchanger3 NA NA90w/k, 1710W External Rear mount heat exchanger2 NA NA

    Heat Exchangers, Door 21w/k, 0420W Internal Door mount heat exchanger4 0274148 027414840w/k, 0760W Internal Door mount heat exchanger4 NA NA60w/k, 1140W Internal Door mount heat exchanger4 NA NA85w/k, 1615W Internal Door mount heat exchanger4 NA NA130w/k, 2470W Internal Door mount heat exchanger4 NA NA

    11 CU/HX Options CU Test unit 9765050 9765050Cable, Door Switch, 2.5m 0242080 0242080Cable, Alarm, 2.5m 0242079 0242079Cable, AC Power, IEC-320, 2.5m 0242078 0242078Cable, DC Power, 3w3 3-pole, 2.5m 0242077 0242077

    12 CS Accessories Alarm, Lo-Temp 9970202 9970202Alarm, Hi-Temp 9970203 997020319" Rails (Plated), 800mm NA DK768519" Rails (Plated), 1000mm DK7686 NA19" Rails (Plated), 1200mm NA NA19" Rails (Plated), 1600mm NA NA19" Rail Installation Bracket, 600mm, CTR DK7696 DK769619" Rail Installation Bracket, 800mm, LH DK7697 NA19" Rail Installation Bracket, 800mm, CTR DK7698 NA23" Rail Installation Bracket, 800mm, LH NA NA23" Rail Installation Bracket, 800mm, CTR NA NAGND Rail Kit DK7113 DK7113Door Switch PS4127 PS4127Door Entry Alarm Kit, Telco Pull-to-Detent 9970216 9970216

    Product Configuration Guide

    14

    CS Standard Product Selection Matrix

    Notes: 1Top mount CU/HX Hood Cover is included with Roof CU/HX option.2Specify LS Hinged Door or Fixed Panel mounting for rear mount CU/HX option (cover shroud included).3External cover shroud separately included with side mount CU/HX option.4HX door ordered separately.

  • 0274105 9755015 9755025 9755025 9755035 9755035 0274105(2) 9755035(2)9754015 9754025 9754035 9754035 9754045 9754045 9754015(2) 9754045(2)9759015 9759025 9759035 9759035 9759045 9759045 9759015(2) 9759045(2)9759015 9759025 9759035 9759035 9759045 9759045 9759015(2) 9759045(2)9759055 9759065 9759075 9759075 9759085 9759085 9759055(2) 9759085(2)9759095 9759105 9759115 9759115 9759125 9759125 9759095(2) 9759125(2)

    9766015 9766025 9766015 9766015 9766025 9766025 9766015 97660259753025 9753035 9753075 9753025 9753035 9753045 9753025 97530359753105 9753115 9753195 9753105 9753115 9753125 9753105 97531159753065 9753075 9753185 9753065 9753075 9753085 9753065 97530759753145 9753155 9753205 9753145 9753155 9753165 9753145 97531550040749 0040750 0040747 0040749 0040750 0040751 0040749 00407500040759 0040760 0040757 0040759 0040760 0040761 0040759 00407600040754 0040755 0040752 0040754 0040755 0040756 0040754 00407550040764 0040765 0040762 0040764 0040765 0040766 0040764 00407659970206 9970207 9970208 9970208 9970209 9970209 9970206(2) 9970209(2)9970214 9970214 9970214 9970214 9970214 9970214 9970214 9970214

    9749025 9749035 9749015 9749025 9749035 9749045 9749025 9749035

    9749125 9749135 9749115 9749125 9749135 9749145 9749125 97491359762012 9762012 9762012 9762012 9762012 9762012 9762012(1/2) 9762012(1/2)9761012 9761012 NA 9761012 9761012 9761012 9761012(1/2) 9761012(1/2)NA 9761012 NA NA 9761012 9761012 NA 9761012NA NA NA 9761032 9761032 9761032 NA 9761032(1/2)NA NA NA Avail-99 Avail-99 Avail-99 NA Avail-999768100 9768100 NA 9768100 9768100 9768100 9768100(1/2) 9768100(1/2)9764012 9764012 9764012 9764012 9764012 9764012 9764012(1/2) 9764012(1/2)NA NA 9764022 9764022 9764022 9764022 NA 9764022(1/2)9763012 9763012 NA 9763012 9763012 9763012 NA 9763012(1/2)NA 9763012 NA NA 9763012 9763012 NA 9763012NA NA NA 9763032 9763032 9763032 NA 9763032(1/2)0274148 0274148 0274148 0274148 0274148 0274148 0274148(1/2) 0274148(1/2)9768032 9768032 NA 9768032 9768032 9768032 9768032(1/2) 9768032(1/2)NA NA NA 9768012 9768012 9768012 NA 9768012(1/2)9768042 9768042 NA 9768042 9768042 9768042 9768042(1/2) 9768042(1/2)NA NA NA NA NA 9768052 NA NA9765050 9765050 9765050 9765050 9765050 9765050 9765050 97650500242080 0242080 0242080 0242080 0242080 0242080 0242080 02420800242079 0242079 0242079 0242079 0242079 0242079 0242079 02420790242078 0242078 0242078 0242078 0242078 0242078 0242078 02420780242077 0242077 0242077 0242077 0242077 0242077 0242077 02420779970202 9970202 9970202 9970202 9970202 9970202 9970202 99702029970203 9970203 9970203 9970203 9970203 9970203 9970203 9970203NA NA NA NA NA NA NA NANA NA DK7686 NA NA NA NA NADK7688 DK7688 NA DK7688 DK7688 NA DK7688(2) DK7688(2)NA NA NA NA NA DK7690 NA NADK7696 DK7696 NA NA NA NA DK7696 NANA NA DK7697 DK7697 DK7697 DK7697 NA DK7697(2)NA NA DK7698 DK7698 DK7698 DK7698 NA DK7698(2)NA NA 7697951 7697951 7697951 7697951 NA 7697951NA NA 7698951 7698951 7698951 7698951 NA 7698951DK7113 DK7113 DK7113 DK7113 DK7113 DK7113 DK7113 DK7113PS4127 PS4127 PS4127 PS4127 PS4127 PS4127 PS4127 PS41279970216 9970216 9970216 9970216 9970216 9970216 9970216 9970216

    15

  • Midwest Regional Office28800-A Beck RoadWixom, MI 48393TEL: (248) 669-7133FAX: (248) 669-9021

    Canadian HeadquartersRittal Systems Ltd.7320 Pacific CircleMississauga, Ontario L5T IV7TEL: (905) 795-0777FAX: (905) 795-9548

    Eastern Regional Office377 Research ParkwayMeriden, CT 06450-7188TEL: (203) 235-2300FAX: (203) 235-4879

    U. S. HeadquartersOne Rittal PlaceSpringfield, OH 45504TEL: (937) 399-0500FAX: (937) 390-5599

    Southern Regional Office1300 Cobb International Blvd.Kennesaw, GA 30152TEL: (770) 424-5195FAX: (770) 424-5394

    Mexican HeadquartersRittal, S.A. de C.V.Prolongación 5 de Mayo No. 29Parque Industrial Naucalpan, 53489Naucalpan, MéxicoTEL: 525-300-2570FAX: 525-300-0495

    Western Regional Office16840 Valley ViewLa Mirada, CA 90638TEL: (714) 690-0393FAX: (714) 690-0399

    Central Region Office1600 Shore Road, Unit KNaperville, IL 60563TEL: (630) 548-2240FAX: (630) 548-3934

    To get connected with Rittal, just contact your local

    Rittal representative anywhere in North America. They

    can provide you with information, expert advice and

    Get directly in touch with the Rittal Telecommuni-cations Team for product, design and applicationengineering services. This experienced groupof sales and engineering professionals puts theirmany years of experience with wireless andwireline design to work for you in helping addressyour system challenges.

    Rittal Telecommunications Group1912 Eastchester Dr., Ste. 201High Point, NC 27265Tel: (336) 812-3370Fax: (336) 812-3377

    sales support for Rittal’s complete range of enclosure

    and enclosure climate control solutions, no matter

    what your application.

    C S E N G I N E E R I N G G R O U P

    R I T T A L I N N O R T H A M E R I C A

    In USA: Rittal Corporation • One Rittal Place • Springfield, OH 45504 • Phone: (937) 399-0500Fax: (937) 390-5599 • Toll-Free: 1-800-477-4000 • Email: [email protected] • Internet: www.rittal-corp.com

    In Canada: Rittal Systems Ltd. • 7320 Pacific Circle • Mississauga, Ontario L5T 1V1 • Toll-Free: 1-800-399-0748Tel: (905) 795-0777 • Internet: [email protected]

    In México: Rittal, S.A. de C.V. • Prolongación 5 de Mayo No. 29 • Parque Industrial Naucalpan • 53489 Naucalpan, MéxicoPhone: (525) 300-2570 • Fax: (525) 300-0495

    CONNECTIONS

    Switch to perfectionHCG 5/99 PP 5M #9045.999b