8/11/2019 Operation of Bus Bar Protection
1/18
MISOPERATION OF BUSBAR
PROTECTION DURINGCLOSE-IN EXTERNAL FAULTS
May 18, 2010
Steve TurnerSenior Applications Engineer
BECKWITH ELECTRIC CO., UPS.
8/11/2019 Operation of Bus Bar Protection
2/18
INTRODUCTION
Typical Substation Configuration & FaultLocation
Delta
Wye Grounded
(Distribution Sub)
8/11/2019 Operation of Bus Bar Protection
3/18
INTRODUCTIONTwo Misoperations in 2004
Transformer Differential Protection
Fast Bus Trip Protection Scheme
8/11/2019 Operation of Bus Bar Protection
4/18
Part One
Numerical Transformer Differential Protection
MisoperationMulti-winding transformer relay protects:
Parallel 23 MVA Banks
23 kV Distribution Bus
8/11/2019 Operation of Bus Bar Protection
5/18
Part OneNumerical Transformer Differential Protection
Misoperation
Delta
Wye Grounded
115 kV
23 kV
23 MVA 23 MVA
C800 C800
C200 C200 C200 C200
C800 C800
T1 T2
Wndg1 (87) Wndg2 (87)
Wndg3 (87)
A-B
Wndg4 (51N)
8/11/2019 Operation of Bus Bar Protection
6/18
Part OneNumerical Transformer Differential Protection
Misoperation
Intense lightning storm passed through the area
Distribution feeder subjected to several heavy faults
Faulted feederCT developed significant remanence flux?
8/11/2019 Operation of Bus Bar Protection
7/18
C200 Excitation Characteristic
8/11/2019 Operation of Bus Bar Protection
8/18
C200 CT on faulted feeder saturated -> low knee pointC200 CTs are connected in parallel
All C200 CTs saturate
Therefore ->Total exc i tat ion c urrent appears in th e operat ing coi l!
VSAT
ieieie
Why Did Transformer Relay Trip?
8/11/2019 Operation of Bus Bar Protection
9/18
IWNDG3vs. IWNDG4
8/11/2019 Operation of Bus Bar Protection
10/18
Dual Slope Characteristic
IOP
IBIAS
25%
50%
A-PhB-Ph
C-Ph
INTERNAL EXTERNAL
8/11/2019 Operation of Bus Bar Protection
11/18
Solution
1. Match C-ratings for CTs
2. Do not connect CTs in parallel(i.e., low impedance differential protection)
3. Separate protection for transformer & bus
4. Use high impedance differential protectionfor bus
8/11/2019 Operation of Bus Bar Protection
12/18
Solution
Delta
Wye Grounded
115 kV
23 kV
23 MVA 23 MVA
C800 C800
C400 C400 C400 C400
C800 C800
T1 T2
Wndg1 (87T) Wndg2 (87T)
87B
Wndg4 (87T)Wndg3 (87T)
8/11/2019 Operation of Bus Bar Protection
13/18
Part TwoNumerical Fast Bus Protection Scheme
MisoperationFeeder overcu rrent relays block high -side quic k tr ip
Delta
Wye Grounded
230 kV
23 kV
23 MVA
T1
50FT
50B
F
50B50B
Blocking Signal50FT Fast Trip Element
50B
Blocking Element
8/11/2019 Operation of Bus Bar Protection
14/18
Some Customers Uses Directional Elements
Delta
Wye Grounded
230 kV
23 kV
23 MVA
T1
50FT
50B & !32R
F
50B & !32R50B & !32R
*No Blocking Signal*
50FT Fast Trip Element
50B Blocking Element
32R Adaptive Directional Element
Yg DIG
Directional element inhibits blocking for bus ground faults
8/11/2019 Operation of Bus Bar Protection
15/18
32R, Adaptive Directional
ElementUse most prevalent signal (+, -, or 0) for
polarizing
Negative-seq. voltage is the most commonchoice
V2& I2equal zero during balanced three-phase faults
8/11/2019 Operation of Bus Bar Protection
16/18
Evolving Faults Fool DirectionalElementNo signal while fault evolves fromPh-Ph to
Three-Phase!
F32Q = Negative-Seq. Directional Element
F32P = Positive-Seq. Directional Element
67P2 = Blocking Element
Hole = Trip!
8/11/2019 Operation of Bus Bar Protection
17/18
Solution
Add two cycle time delay on dropout toblocking signal
Blocking
Signal
0
2
Rides through momentary ho les
Blocking Signal
w. Time Delay on Dropout
8/11/2019 Operation of Bus Bar Protection
18/18
CONCLUSIONS
Dont parallel CTs for low impedance differentialprotection
Use properly rated CTs
Use zones of protection
Fast bus trippingschemes require coordination