SEQUENCE OPERATION FOR STEAM ADDMISSION
(BOILER BED 130 T/H JERANJANG 1X25MW)
Jl
J
GEDUNG WASA, Jl. Raya Cakung Cilincing KM 1 No. 11Jakarta Timur 13910 – IndonesiaTelp. : 021 – 4619381 & 021 4604958 (Operator)Facs. : 021 – 4619382 Email : [email protected], [email protected]
- jacking oil difungsikan untuk mengangkat rotor turbine ke center bearing sehingga waktu turbine berputar, rotor / bearing tidak bersinggungan langsung & memudahkan untuk berputar.
- jacking di operasikan sebelum turning di running
PT. BUMIMITRA ADIPERSADA
04
LUBE OIL TURBINE
03
- HP lube oil pump / centrifugal pump sudah running
- AC lube oil pump sudah running
- check pressure & flow tidak ada kebocoran
- inspect rotation gear motor turning
- turning gear motor sudah di no load test
- protection turning gear sudah dilakukan simulasi interlock test
- load test
PT. BUMIMITRA ADIPERSADA
05
04
TURNING GEAR
- Test buka tutup valve inlet & outlet condenser circulating water
- Pipe circulating water harus sudah selesai di hydro test
- start travelling screen
- check water level CWP / sea water
- level water harus sudah inter lock dengan CWP pump
- semua protection CWP pump harus sudah selesai di simulasi & interlock protection
- CWP pump juga harus interlock dengan hydraulick valve untuk isolation
PT. BUMIMITRA ADIPERSADA
06
05
CONDENSING SYSTEM
START CIRCULATING WATER SYSTEM
- buka valve inlet & outlet condenser
- start CWP 1 dan bersamaan dengan dibukanya valve hydraulic 1
--check water inlet & outlet di condenser
- start rabber ball cleaning
Untuk CWP 2 prosesnya sama dengan CWP 1
- inlet dari main steam pipe dan di control dengan PCV valve
- fungsi equalizing system ini adalah untuk steam seal menjaga kebocoran di seal turbine pada waktu ada tekanan tinggi di sisi seal bagian dalam ( seal antara bagian yg ikut berputar dengan bagian yang diam) & menetralisir udara bebas / atmispher contaminasi kedalam turbine.
- equalizing juga dapat supply steam dari deaerator disisi steam sebagai balance steam.
- equalizing di control dengan PCV valve maksudnya valve tersebut buka / tutupnya berdasarkan pressure yang masuk bukan electric. Kalau ada pressure akan buka & bila tidak ada pressure akan tutup dengan sendirinya.
- equalizing system juga ada line menuu condenser dengan tujuan mengurangi steam di equalizing tank., untuk balance antara steam yang masuk ke equalizing dengan yang harus di keluarkan.
- equalizing juga ada line pipe dari feed water system dengan tujuan untuk water spray (kalau terjadi high temperature maka water spray difungsikan untuk mengurangi temperature tersebut)
apabila temperature di equalizing tank mencapai 300ºC buka valve feed water untuk spray. Adjust presure spray antara 0.097ºC ~ 0.099 Mpa.
PT. BUMIMITRA ADIPERSADA
07
06
EQUALIZING TANK/ SURGE TANK
- fungsi gland seal system ini adalah untuk steam seal menjaga kebocoran di seal turbine pada waktu ada tekanan tinggi di sisi seal bagian luar ( seal antara bagian yg ikut berputar dengan bagian yang diam) & menetralisir udara bebas / atmispher contaminasi kedalam turbine.
- gland seal mengambil supply steam dari vacuum pump / jet pump condenser dipakai ke seal turbine bagian luar dan sisa steam di balance dengan exhaust fan yang ada di gland seal untuk membuang steam yang berlebihan.
- gland seal juga dapat supply water dari condensate pump dengan tujuan sebagai cooler / pendingin
- sedangkan steam yang ada di gland seal tank yang sudah menjadi water karena condensasi dikembalikan ke condensor.
PT. BUMIMITRA ADIPERSADA
08
07
GLAND SEAL STEAM SYSTEM
WARMING-UP
- check initial temperature & pressure steam condition
- check semua valve main steam sampai dengan main stop valve & yakinkan tidak ada kebocoran.
- yakinkan valve main stop valve posisi close
- yakinkan valve drain mulain dari auxiliari steam header, main line pipe steam yang menuju ke turbine & di cahing turbine semua harus terbuka untuk meminimais water yang terbawa steam pada condisi steam basah / cold start-up. Karena untuk mencegah terjadinya corrosive turbine.
- buka isolation valve yang menuju ke equalizing valve sehingga steam di control dengan PCV valve & by pass harus tertutup. Tetapi sebelumnya valve drain dari equalizing tank menuju ke condensor harus di buka.
- buka manual valve untuk gland seal & buka valve drain lalu operasikan fan.
- yakinkan semua valve yang untuk indicator instrument sudah terbuka & instrument sudah berfungsi dengan baik.
- pada pressure 0.2 ~ 0.3 Mpa dan semua drain di atas terbuka amati temperature akan naik beransur ansur 5ºC / min.,tahan selama 20 ~ 30 menit untuk warming-up.
- setelah temperature steam mencapai 130ºC ~ 150ºC stop warming-up.
PT. BUMIMITRA ADIPERSADA
09
08
START-UP TURBINE
BOOSTING WARMING-UP
- boosting warming-up harus mengikuti tahapberikut:
4) KALAU ADA KELAINAN DI EXPANSION SEGERA STOP ACCELERATION & CHECK-UP
5) PERBEDAAN TEMPERATURE CASING TURBINE:
a. TEMPERATURE CASING WALL < 4ºC/MIN
b. TEMPERATURE UPPER & LOWER CASING < 50ºC
c. TEMPERATURE INNER & OUTER FLANGE INLET STEAM < 100ºC
6) LAKUKAN PENGUJIAN SAFETY TRIP OFF (MSV, GOVERNOR & EXTRACTION VALVE HARUS CLOSE.
7) LAKUKAN PENGUJIAN OVER SPEED TEST (ROTOR SPEED MENUJU KE 3270 R/MIN EHC OVER SPEED PROTECTION HARUS TRIP).
8) LAKUKAN PENGUJIAN OVER SPEED TEST (TURBINE SPEED MENUJU KE 3300 ~ 3360 R/MIN EMERGENCY GOVERNOR HARUS TRIP. KALAU TIDAK TRIP TEKAN EMERGENCY PILOT GOVERNOR UNT SHUT-DOWN (SYSTEM AKAN SHUT DOWN SETELAH SPEED TURBINE MENCAPAI 3390 R/MIN)
9) SETELAH SPEED TURBINE MENCAPAI 3060 ~ 3030 R/MIN RESET EMERGENCY GOVERNOR PILOT
10) YAKINKAN SEMUA SUDAH DALAM KONDISI NORMAL SEBELUM GENERATOR MASUK POWER.
SAAT STEAM MASUK TURBINE
PT. BUMIMITRA ADIPERSADA
16
15
PERSIAPAN SEBELUM BOILER BURNING UNTUK STEAM ADDMISSIONYANG HARUS DILAKUKAN DIBAWAH INI:
1) BUKA VALVE MAIN STEAM OUTLET BOILER, AUXILARY STEAM HEADER, ISOLATION VALVE SAMPAI KE MSV (MAIN STOP VALVE) TERMASUK BY PASS STEAM
2) TUTUP MSV & GOVERNOR VALVE
3) BUKA DRAIN VALVE SEMUA JALUR STEAM SAMPAI TURBINE DRAIN JUGA HARUS DI BUKA.
4) CIRCULATING WATER SYSTEM HARUS DIOPERASIKAN (SECARA OTOMATIS CWP HARUS RUNNING & CIRCULATING)
9) URUTAN SEQUENCE KEMBALI KE WARMING-UP & START UP TURBINE
10) SETELAH STEAM YANG MASUK TURBINE MENCAPAI1.5Mpa DENGAN TEMPERATURE 250 ~ 300ºC BUKA VALVE YANG MENUJU KE EQUALIZING TANK UNTUK GLAND SHAFT SEAL & OPERASIKAN GLAND SEAL. TUJUANNYA UNTUK MEMINIMAIS KEBOCORAN SEAL TURBINE & MAINTAIN VACUUM CONDENSOR MENJADI 0.06 ~ 0.067Mpa (450 ~ 500mmHg) DI CONDENSOR.
11) OPERASIKAN WATER SPRAY DI EQUALIZING TANK SETELAH STEAM YANG MASUK EQUALIZING TANK MENCAPAI 300ºC.
12) BUKA MSV DAN GOVERNOR.
13) PADA SAAT GOVERNOR OPEN & TURBINE PRESSURE 5% TUTUP BY PASS STEAM
14) SETELAH PRESSURE TURBINE NAIK MENCAPAI 0.2 ~ 0.3 Mpa / Min & TEMPERATURE NAIK 2 ~ 3ºC/Min, LOAD-UP RATE 250KW/Min.
PT. BUMIMITRA ADIPERSADA
17
16
I. START-UP TURBINE ADA 2 YAITU COLD STARTUP & HOT START-UP (COLD START-UP TEMPERATURE INNER CASING DIBAWAH 150ºC & HOT START-UP TEMPERATURE INNER CASING MENCAPAI DIATAS 150ºC)
II. SAAT TURBINE OPERASI NORMAL & SHUT DOWN 24 HOURS TURBINE INNER CASING MENCAPAI 300ºC
III. SAAT TURBINE SHUT DOWN 48 HOURS TURBINE INNER CASING MENCAPAI KURANG LEBIH 150ºC
IV. SEBELUM HOT START-UP TURBINE YANG HARUS DI PERHATIKAN ANTARA LAIN:
a. BENDING ROTOR TIDAK SAMPAI 0.06mm
b. PERBEDAAN / DIFFERENTIAL TEMPERATURE UPPER & LOWWER TIDAK LEBIH 50ºC
c. OPERASIKAN EQUALIZING SYSTEM UNTUK GLAN SEAL
d. OPERASIKAN VACUUM PUMP / JET PUMP SAMPAI MENCAPAI 0.067Mpa (500mmHg)
e. OPERASIKAN GLAND SEAL
f. LUBE OIL TURBINE SETELAH COOLER TIDAK LEBIH DARI 40ºC
g. DIFFERENTIAL FILTER LUB OIL TURBINE TIDAK MELEWATI 0.05Mpa
h. TEMPERATURE OIL BEARING 35ºC ~ 40ºC KALAU ADA KENAIKAN GAK LEBIH ANTARA 10ºC ~ 15ºC
i. PRESSURE OIL TURBINE 0.08 ~ 0.12Mpa
HOT START-UP TURBINE
PT. BUMIMITRA ADIPERSADA
18
17I. START-UP LUBE OIL TURBINE PERTAMA LIHAT COOLING WATER CIRCUATING SUDAH
SEMPURNA / BELUM YANG MELEWATI OIL COOLER.
II. START HP LUBE OIL & CHECK SEMUA LINE YANG DI LEWATI ANTARA LAIN:
a. LUBE OIL BEARING PRESSURE 0.08 ~ 012 Mpa
b. LUBE OIL TURNING GEAR 0.08 ~ 0.12 Mpa (PRESSURE LUBE OIL LOW DI 0.055 Mpa HARUS STOP)
d. CHECK LUBE OIL DI OIL INJECT TEST VALVE HARUS READY
e. CHECK OIL DI EMERGENCY GOVERNOR PILOT HARUS READY
f. CHECK OILDI EMERGENCY QUICK CLOSE VALVE HARUS READY
g. CHECK EXTRACTION VALVE HARUS OPEN
h. CHECK MSV 1 & 2 VALVE HARUS CLOSED
i. CHECK GOVERNOR VALVE HARUS CLOSED
j. CHECK EHC (ELECTRICAL HYDRAULIC CONVERTER HARUS SUDAH ADA PRESSURE OIL
k. CHECK REGULATOR SLIDE HP / LP HARUS ADA PRESSURE & MEMBUTUHKAN SETTING PRESSURE UNTUK KEBUTUHAN PRESSURE YANG DIBUTUHKAN GOVERNOR OPEN & START UP VALVE.
l. START UP VALVE HARUS DI FUNGSIKAN KARENA SEBAGAI SUPPLY CONTROL MSV VALVE & EMERGENCY CONTROL LUBE OIL
III. SEQUENCE LUBE OIL TURBINE SEBAGAI BERIKUT:
a. START HP LUBE OIL TURBINE PRESSURE 1 Mpa (UNTUK MENGOPERASIKAN JACKING OIL, MENGOPERASIKAN TURNING GEAR, LUBRICATION BEARING TURBINE & CONTROL VALVE HYDRAULIC SYSTEM)
b. KALAU TURBINE SUDAH BERPUTAR MAKA MAIN OIL PUMP SUDAH BISA PRODUCT PRESSURE SENDIRI KURANG LEBIH 2 Mpa
c. PADA SAAT MAIN OIL PUMP OPERASI PRESSUREKALAU SUDAH MENCAPAI 1.9 Mpa HP LUBE OIL AKAN STOP.
d. KALAU SEANDAINYA ADA PENURUNAN PRESSURE MAIN OIL PUMP SAMPAI DENGAN 1.7 Mpa MAKA HP LUBE OIL AKAN RUNING AUTOMATIC
e. PRESURE TERJADI PENURUNAN SAMPAI 0.05 Mpa AC LUBE OIL AKAN START
f. PRESSURE TERJADI PENURUNAN TERUS MENCAPAI 0.04 DC LUBE OIL AKAN START AUTO, ITU SAMA DENGAN TERJADI POWER BLACK OUT.
g. KALAU PRESSURE TURUN TERUS SAMPAI DENGAN 0.03 Mpa MAKA LUBE OIL SHUT DOWN.
START LUBE OIL TURBINE
PT. BUMIMITRA ADIPERSADA
19
18
CONTROL REGULATOR SLIDE, START-UP VALVE, EMERGENCY SOLENOID VALVE SHUT DOWN, MANUAL SHUT DOWN & MSV 1 & 2
START LUBE OIL TURBINE
GOVERNOR VALVE, EMERGENCY GOVERNOR PILOT & QUICK CLOSE VALVE
OIL INJECTOR CONTROL NORMAL & OIL INJECTOR
EMERGENCY
TURNING GEAR
PT. BUMIMITRA ADIPERSADA
20
19 BEBERAPA SET POINT YANG PERLU DI PERHATIAN:
a. GOVERNOR SHUT DOWN KALAU LUBE OIL PRESSURE 0.8 Mpa
b. REGULATOR SLIDE VALVE SETTING 3 ~ 6%
c. SPEED VARIATION ≤ 0.25%
d. RANGE GOVERNOR 0 ~ 3390 R / MIN
e. ELECTRO GOVERNOR OVER SPEED PROTECTION 3270 R / MIN