Joint research project: DC-INDUSTRIE2 Direct current for the factory of the future DC-INDUSTRIE2 | Sep. 2021 Contact: Dr. Hartwig Stammberger Prof. Dr.-Ing. Holger Borcherding (Eaton, Bonn, project coordinator) (TH OWL, Lemgo, scientific lead of the project) DC-INDUSTRIE2 open DC grid for sustainable factories
26

open DC grid for sustainable factories: DC-INDUSTRIE

Mar 16, 2022

Download

Documents

dariahiddleston
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: open DC grid for sustainable factories: DC-INDUSTRIE

Joint research project: DC-INDUSTRIE2 – Direct current for the factory of the future

DC-INDUSTRIE2 | Sep. 2021

Contact:

Dr. Hartwig Stammberger Prof. Dr.-Ing. Holger Borcherding

(Eaton, Bonn, project coordinator) (TH OWL, Lemgo, scientific lead of the project)

DC-INDUSTRIE2 – open DC grid for sustainable

factories

Page 2: open DC grid for sustainable factories: DC-INDUSTRIE

Page 2 © DC-INDUSTRIE2 & ZVEI, Sep. 2021

DC-INDUSTRIE2

Overview: research project DC-INDUSTRIE2

• Funded by the German Federal

Government, BMWi

• Funding codes: 03EI6002A-Q

• 3 years until Sep. 2022

• 39 industry and research partners

• Some 140 engineers & researchers

• Objectives:

• Safe and robust energy supply for production

• Mains-supporting connection to the supply grid

• Maximum use of decentralized, regenerative

energy

• Simple project planning

• Implementation and validation

• 7 model plants and transfer centers

Page 3: open DC grid for sustainable factories: DC-INDUSTRIE

Page 3 © DC-INDUSTRIE2 & ZVEI, Sep. 2021

DC-INDUSTRIE2

Status quo: Topology in an industrial AC grid

=

3~

-+

==

AC-distribution

Transformer Emergency power(extremely rare in industry)

=3~

3~=

Variable

speed drives

Fixed speed

drives (Mains-

synchronized)

Passive loads

(light, heat, …)

3~=

Machines and

robots

Energy flow

top-down

Auxiliary power

(PLC, I, O,

sensors,…)

24V

3~

1~ 230V /

3~ 400V

sockets

Page 4: open DC grid for sustainable factories: DC-INDUSTRIE

Page 4 © DC-INDUSTRIE2 & ZVEI, Sep. 2021

DC-INDUSTRIE2

Energy: Current situation with frequency converters (AC-AC)

Energy flow for motor operation

Basic wiring of frequency

converters is optimized

for motor applications

=

3~

3~

=AC grid

InverterDiode

rectifier

In braking mode, the inverter

needs to dispose of the stored

energy.

The most common method is

the dissipation of the energy

to heat in braking resistors

Energy flow in generator mode

AC grid=

3~

3~

=

InverterDiode

rectifierBraking resistor

Page 5: open DC grid for sustainable factories: DC-INDUSTRIE

Page 5 © DC-INDUSTRIE2 & ZVEI, Sep. 2021

DC-INDUSTRIE2

Electrical energy exchange with a DC grid

Energy flow

3~

= Generator

mode

DC grid

• Reduces effort

• Enables direct

energy exchange

– no additional

components

needed

=

3~

=

3~

Inverter

DC grid

Motor operation

AC grid

Infeed

rectifier

Page 6: open DC grid for sustainable factories: DC-INDUSTRIE

Page 6 © DC-INDUSTRIE2 & ZVEI, Sep. 2021

DC-INDUSTRIE2

Topology of an industrial DC grid

DC grid

Transformer

Supply and

feedback

DC 650 V

Energy storage

==

==

-+

==

Energy generation

3~=

Energy flow

bidirectional

==

Passive loads

(light, heat, …)

=3~

1~ 230V /

3~ 400V

sockets

24V

=

Auxiliary power

(PLC, I, O,

sensors,…)

=3~

Variable

speed

drives

Machines and

robots with DC-

supply

Page 7: open DC grid for sustainable factories: DC-INDUSTRIE

Page 7 © DC-INDUSTRIE2 & ZVEI, Sep. 2021

DC-INDUSTRIE2

Advantages of DC grid for industrial plants

• Energy efficiency

• Lower losses (typically 2-4% *)

• Total recovery of braking energy *

• Direct use of renewable energy sources *

• Peak power reduction through suitable storage (-80%) *

• Resource efficiency

• Reduction of copper use (cables)

• Lower equipment costs and space savings in the field

• Grid stability

• Additional investments for mains filtering and compensation

can be omitted, and existing grids are supported

• Production failures through mains disturbances can be

prevented, reduced

• Industrial Smart DC-Grid , flexibility

• Infrastructure for intelligent control of energy flows enables

advantages in energy purchasing

• Supports modular machine concepts

*: Evaluated in model applications

Page 8: open DC grid for sustainable factories: DC-INDUSTRIE

Page 8 © DC-INDUSTRIE2 & ZVEI, Sep. 2021

DC-INDUSTRIE2

Simplified power calculation AC vs DC

• Power for AC

• Active power

• 𝑃 = 𝑈 · 𝐼 · cos(𝜑)

• Reactive power

• 𝑄 = σ𝑛=1∞ 𝑈 ⋅ 𝐼 ⋅ cos 𝜑𝑈𝑛 − 𝜑𝐼𝑛

• Distortion power

• 𝐷 = 𝑈 ⋅ 𝐼22 + 𝐼3

2 + … = U ⋅ σ𝑚=2∞ 𝐼𝑚

2

• And everything three times for three-phase

systems …

• Power for DC

• Active power 𝑃 = 𝑈 · 𝐼

• It really is that simple …

• In AC reactive power and distortion

power need to be transmitted to the

end user via cabling

• No such overhead in DC

Page 9: open DC grid for sustainable factories: DC-INDUSTRIE

Page 9 © DC-INDUSTRIE2 & ZVEI, Sep. 2021

DC-INDUSTRIE2

Operating voltage range

Two grid voltages depending on infeed method

• 650 V: For controlled supply and uncontrolled at 480V-mains

• 540 V: For uncontrolled supply at the 400V-AC-mains

• Rated operation

• Unlimited functionality of the units

• Stationary over, undervoltage

• Units can be operated permanently within this range

• The functionality should not be limited (e.g. power derating)

• Active participants counteract the voltage deviation

• Transient over, undervoltage

• Units may lose function, but must resume function after voltage recovery

• Voltage should only remain in this range for a limited time

• Switch-off limits: 400 V, 800 V

• Units switch off permanently

• Manufacturers can specify different rating data (e.g. rated power) for

both mains voltages

UDC,N =

485…625V

UDC,N =

600…750V

Uncontrolled Controlled, 480 V

400 VAC uncontrolled

Page 10: open DC grid for sustainable factories: DC-INDUSTRIE

Page 10 © DC-INDUSTRIE2 & ZVEI, Sep. 2021

DC-INDUSTRIE2

Voltage stability and droop curves

Grid voltage mirrors energy balance

a) Uncontrolled operation (basic network)• No active control of the DC-voltage (operation with diode rectifier)

b) Autonomous droop control• Active feeders regulate their power depending on the level of DC voltage

• The characteristic is defined by a non-linear characteristic curve

• No communication required

c) Droop control with communication• Setting of the characteristic curve can be changed by a central

control unit during operation

• Only slow communication required

d) Central voltage control• Central control unit provides the setup power values

• Fast communication required – real time control

Choosing the control method allows for simple as well as

complex DC-grids with several sources

600 650 700

DC voltage in Volt

Cu

rren

t

0

Droop control

Current-voltage characteristic

Active Infeed

Storage

PV system

Page 11: open DC grid for sustainable factories: DC-INDUSTRIE

Page 11 © DC-INDUSTRIE2 & ZVEI, Sep. 2021

DC-INDUSTRIE2

Resource efficiency – less copper for cables

• Example• Current for inverter driven three-phase

motor

• 7.5 kW, power factor 0.85, η=.887×.968 1)

• AC: L1, L2, L3, PE, 400 V• Current = 20 A 2)

• Wire cross section → 2.5 mm²

• Total copper: 4 ×2.5 mm² = 10 mm²

• DC: Plus, Minus, PE, 600 V 3)

• Current = 14.6 A (𝐼 = 𝑃/𝑈/𝜂 )

• Wire cross section → 1.5 mm²

• Total copper: 3 ×1.5 mm² = 4.5 mm²

• 55% less copper for same power!

AC-cable 3~ AC 400 V

4 conductor system

DC-cable DC 650 V

3 conductor system

Wiring type B1

Number of wires

simultaneously

loaded

2 3

Wire cross section

in mm2

current in A

1.5 17.5 15.5

2.5 24 21

4 32 28

6 41 36

Permitted current in A

@ 30°C ambient temperature

acc. to DIN VDE 0298-41) Efficiency factor η for motor and inverter, respectively2) Data from Lenze manual for i550 inverter3) Lowest DC voltage in nominal voltage band

Page 12: open DC grid for sustainable factories: DC-INDUSTRIE

Page 12 © DC-INDUSTRIE2 & ZVEI, Sep. 2021

DC-INDUSTRIE2

System concept: Division into DC sectors

DC sectors

➢ Build a logical unit

➢ Include components with

strong functional

dependencies to each other

➢ Provide sufficient capacity to

suppress switch-frequency

compensation processes

from the DC-grids

➢ Are protected with a smart

DC breaker

DC grid

DC 650 V

==

==

-+

==

3~= Energy

==

=3~24V

==

3~

Page 13: open DC grid for sustainable factories: DC-INDUSTRIE

Page 13 © DC-INDUSTRIE2 & ZVEI, Sep. 2021

DC-INDUSTRIE2

Smart DC Breakers: fast and reliable protection

• Requirements• Fast operation – avoid voltage dips

• Mechanical breakers too slow

• Power semiconductors• IGBT + Diode

• Bi-directional

• Functions• Switching

• Overcurrent protection

• Isolation

• Detection of over- & undervoltage

• Pre-charging

• Properties• Fast (< 100 µs switch-off time)

• Low fault energy (<< 1% of mechanical breaker)

DC

grid

Lo

ad

Isolation

Shunt

IGBT

module (s)

Varistor

Semiconductor breaker

+

+

Main-

tenance

Page 14: open DC grid for sustainable factories: DC-INDUSTRIE

Page 14 © DC-INDUSTRIE2 & ZVEI, Sep. 2021

DC-INDUSTRIE2

Smart Hybrid Breaker reduces power loss

• Mechanical contact

conducts current

→ low power loss

• Power semiconductors

interrupt → Fast

• Switch-Off procedure:• Actor opens mechanical contact

→ short arc

• IGBT picks up the current

(forward voltage < arc voltage)

and switches off →

• Varistor limits voltage

• Isolation contacts open load- less

and isolate

• Coil limits current increase during

short-circuit

+

Main-

tenance

DC

-Bu

s

Coil

Lo

ad

Isolation

Shunt

IGBT-

Modul

Mechanical

contactVaristor

Hybrid Breaker

+

Page 15: open DC grid for sustainable factories: DC-INDUSTRIE

Page 15 © DC-INDUSTRIE2 & ZVEI, Sep. 2021

DC-INDUSTRIE2

Insulating materials for DC cables and wires

• Basics electrical field E

• AC: E-field dependent on voltage and geometry

• DC: Electric field is subject to pronounced temperature influence, since

polarity influence of the insulator depends on temperature T and conductivity

(~ 10-14 … 10-16 S/m)

• Impacts

• Higher stress on the insulating material possible with DC compared to AC

(with same voltage, same current, same geometry)

• Other ageing processes in the insulating material due to rectified E-field.

➔ Causes: Conduction processes and force effects on molecular chains in

insulation

• DC-Industrie2

• Investigation of the ageing behavior of selected

typical AC insulating materials under DC stress 𝐼, 𝑈

rela

tive e

lectr

ic fie

ld s

trength

Cable with insulation

conditions:

𝑈eff, AC= 𝑈DC,𝐼AC= 𝐼DC

(T↓ σ↓ E↑)

insulation

inner sideinsulation

outer side

Cable for

DC applicationSource: LAPP

(T↑ σ↑ E↓)

Page 16: open DC grid for sustainable factories: DC-INDUSTRIE

Page 16 © DC-INDUSTRIE2 & ZVEI, Sep. 2021

DC-INDUSTRIE2

Model applications of DC-INDUSTRIE (2016 – 2019)

• Mercedes-Benz• Production cell

with 4 robots

• Challenging

energy demand

(Al-welding)

• Continued from EU project AREUS

• Mercedes-Benz

• Suspension track

• 5 individual carriers with slip rings

• Coupling of twoapplications

• KHS

• Beverage

container handling

• Open concept

• > 30 drives

• Homag

• Wood working machines

• Many loads

• Sensors &

actors

• Integrated

energy storage

Page 17: open DC grid for sustainable factories: DC-INDUSTRIE

Page 17 © DC-INDUSTRIE2 & ZVEI, Sep. 2021

DC-INDUSTRIE2

Model applications of DC-INDUSTRIE (2016 – 2019)

• Mercedes-Benz• Production cell

with 4 robots

• Challenging

energy demand

(Al-welding)

• Continued from EU project AREUS

• Mercedes-Benz

• Suspension track

• 5 individual carriers with slip rings

• Coupling of twoapplications

• KHS

• Beverage

container handling

• Open concept

• > 30 drives

• Homag

• Wood working machines

• Many loads

• Sensors &

actors

• Integrated

energy storage

Page 18: open DC grid for sustainable factories: DC-INDUSTRIE

Page 18 © DC-INDUSTRIE2 & ZVEI, Sep. 2021

DC-INDUSTRIE2

Model applications of DC-INDUSTRIE2

• BMW

• Car body production cell

• Focus

• Energy distribution & storage

• Energy feedback to grid

• Switching and protection

• KUKA

• Test cell with 4 robots • Focus: robot control

• Fraunhofer IISB• DC infrastructure in office building, EV charging

Building A Building B

Exterior

Page 19: open DC grid for sustainable factories: DC-INDUSTRIE

Page 19 © DC-INDUSTRIE2 & ZVEI, Sep. 2021

DC-INDUSTRIE2

Model applications of DC-INDUSTRIE2

Mercedes-Benz

Factory 56

• Large distances &

power

• 222.000 m2

production area

• 2 MW DC grid for

hall infrastructure

• 1 MW solar

energy, 5.7 MW

peak

• Goal: CO₂-neutral

production

8 air condition units

1 MW solar panels

2 × AC connection

with AICsStorage units

DC bus bars

524 m long

Page 20: open DC grid for sustainable factories: DC-INDUSTRIE

Page 20 © DC-INDUSTRIE2 & ZVEI, Sep. 2021

DC-INDUSTRIE2

Model applications of DC-INDUSTRIE2

• Homag

• Wood working machines

• Three applications spread out in a factory hall

• Setup

• Multiple connections to AC grid

• Several storage options• Flywheel

• Capacitors

• Batteries

• Focus

• Influence of long cables on voltage dips

during supply failure or faults

• Coordination between several

active infeed converters

20

Page 21: open DC grid for sustainable factories: DC-INDUSTRIE

Page 21 © DC-INDUSTRIE2 & ZVEI, Sep. 2021

DC-INDUSTRIE2

Model applications of DC-INDUSTRIE2

• Fraunhofer IPA

• Industrial power

distribution

• AC-DC

transformation

• Protection concept

• Parallel operation

of AICs

• TH OWL

• Model electro-mechanical loads, up to 11 axes

• Storage • Several infeed rectifiers

• Focus

• Model dynamic behavior in real time

• Test virtual machines in a DC environment

• Test of multiple failure scenarios

Which adaptations are necessary for machines and systems for DC?

Page 22: open DC grid for sustainable factories: DC-INDUSTRIE

Page 22 © DC-INDUSTRIE2 & ZVEI, Sep. 2021

DC-INDUSTRIE2

More information and publications (examples)

• DC-Industrie-Homepage www.dc-

industrie.de

• Publications (excerpt)

• White paper

• Several technical reports and papers

• Textbook Die Gleichstromfabrik

im Hanser Verlag,

https://www.hanser-fachbuch.de/

buch/Die+Gleichstromfabrik/

9783446465817

• English language edition to

come – 2nd quarter of 2021

• Computer & Automation

• 4 article technical paper series

Page 23: open DC grid for sustainable factories: DC-INDUSTRIE

Page 23 © DC-INDUSTRIE2 & ZVEI, Sep. 2021

DC-INDUSTRIE2

Hannover Messe 2019 Presentations

https://experience.dc-industrie.zvei.org

Click for

more

info

Page 24: open DC grid for sustainable factories: DC-INDUSTRIE

Page 24 © DC-INDUSTRIE2 & ZVEI, Sep. 2021

DC-INDUSTRIE2

Why direct current and DC-INDUSTRIE?

1. Open system

2. Efficient integration of green energy

3. Lower energy consumption

4. Reduced feed-in power

5. Increased system availability

Page 25: open DC grid for sustainable factories: DC-INDUSTRIE

Page 25 © DC-INDUSTRIE2 & ZVEI, Sep. 2021

DC-INDUSTRIE2

DC-INDUSTRIE team engaged for the DC factory

Page 26: open DC grid for sustainable factories: DC-INDUSTRIE

Page 26 © DC-INDUSTRIE2 & ZVEI, Sep. 2021

DC-INDUSTRIE2

Assoziierte Partner: ABB Stotz-Kontakt; AMK Arnold Müller; Audi; Bauer Gear Motor; Bender; Danfoss; DEHN; ESR Pollmeier; Gerotor; Harting;

JEAN MÜLLER; KUKA; LEONI; Maschinenfabrik Reinhausen; Paul Vahle; Puls; Rittal; SEW-PowerSystems; Siemens; TU Ilmenau; Wöhner

Project partners – www.dc-industrie.de