On-load tap-changer VACUTAP® VRD, VRF, VRG Technical Data TD 237/02 www.reinhausen.com
On-load tap-changer VACUTAP® VRD, VRF, VRGTechnical Data TD 237/02
www.reinhausen.com
2 TD 237/02 237/02/01/0
Table of Contents
1 General / Technical data ............................................................................................................................................................................. 3
1.1 On-load tap-changer designations .............................................................................................................................................. 3
1.2 Summary of the technical data ...................................................................................................................................................... 4
1.2.1 Step capacity diagram ........................................................................................................................................................ 5
1.2.2 Step capacity diagram EAF/LF operation ....................................................................................................................... 5
1.3 Rated insulation level ....................................................................................................................................................................... 6
1.4 Rated withstand voltages of the internal insulation ................................................................................................................ 7
2 Special designs – On-load tap-changer combination VACUTAP® VRF I/VRF II for delta connection ......................... 9
3 Appendix ..................................................................................................................................................................................................... 10
3.1 Dimension drawings / connection diagrams ....................................................................................................................... 10
3.2 Installation drawings .................................................................................................................................................................. 10
Table of Contents
NOTE
These technical data are intended for the calculator and designer of the transformer. These type-specific data areonly valid in connection with the information contained in the general section (TD 61) since this section containsimportant information on such subjects as potential connection of the tap winding, leakage inductance, currentdivision, and so on.
Changes may have been made to a product after going to press with this documentation.
We expressly reserve the right to make changes to a product’s technical data and design as well as changesto the scope of delivery.
In all cases, the information submitted and agreements concluded during processing of the quotation and orderin question shall be binding.
Since the on-load tap-changer is delivered to the specifications of the transformer manufacturer, the transformermanufacturer is responsible for selecting the correct properties of the on-load tap-changer so that the requirementsof the transformer are met.
3TD 237/02237/02/01/0
Example VRF III 1300 Y - 72,5 / C - 10 19 1W R
- / -
VRDVRFVRG
IIIIII
100013002600
1230
Applications Y72,5123170245300362CDE
1012141618
1012141618
1923273135
013
WG
Tie-in measures tie-in resistor Rpotential switch S
P
Number of max. operatingpositions withchange-over selector
1012141618
1923
35
Change-over selector
reversing change-over selectorcoarse change-over selector
Number of max. operatingpositions withoutchange-over selector
Mid-positions 0 mid-positions (without change-over selector)1 mid-position3 mid-positions
2731
Contacts 1012141618
Tap selector size VRD, VRFVRD, VRFVRG
For neutral connection only
Um (in kV) VRD, VRF, VRGVRD, VRF, VRGVRD, VRF, VRGVRD, VRF, VRGVRD, VRF, VRGVRF, VRG
Number of configured sectors
1 sector2 sectors
3 sectors (Y)3 sectors
Ium (in A) VRD, VRF, VRGVRD, VRF, VRGVRF, VRG
potential switch with tie-in resistor
Basic connection diagram
Type VACUTAP ® VRDVACUTAP ® VRFVACUTAP ® VRG
Number of phases 1 phase2 phases3 phases
1 General / Technical Data
1.1 On-load tap-changer designations
1 General / Technical Data
4 TD 237/02 237/02/01/0
1 General / Technical Data
1.2 Summary of the technical data
Note: 1) Neutral point
2) Forced current division by two parallel winding branches required
3) The maximum rated step voltage may be exceeded by 10 % due to overexcitation of the transformer if thestep capacity is limited to its rated value.
Oil compartment: Pressure-tight up to 0.3 bar permanent differential pressure (test pressure 0.6 bar), head and cover ofthe diverter switch oil compartment are vacuum-proof.
Temperature The on-load tap-changer VACUTAP® VR can be operated in the rated load range at temperatures of therange: surrounding oil between -25° and + 105 °C and with overload up to 115 °C according to IEC 60214-1.
Dimensions: Weight, displacement volume, oil content of the diverter switch oil compartment are shown in therelevant dimension drawings.
31)31) 1 31) 2 1 1
1000 1300 1300 1300 1300 1300 2600
On-load tap-changer
Max. rated through-currentIum(in A)
Rated short-time withstandcurrent (in kA)
Rated short-circuit duration(in s)
Rated peak withstand current(in kA)
Max. rated step voltageUim (in V)3)
Step capacity (PStN)(in kVA)
Rated frequency (in Hz)
Operating positions
50 ... 60
Without change-over selector: max. of 18 With change-over selector: max. of 35
12 15 15 15 15 15 26
3 3 3 3 3 3 3
30 37.5 37.5 37.5 37.5 37.5 65
3300 3300 3300 4000 4000 4000 4000
1500 1500 1500 3000 3000 3000 6000
No. of phases and application
VRD
III 1
000
Y
VRD
III 1
300
Y
VRD
I 130
1
VRF
III 1
000
YVR
G II
I 100
0 Y
VRF
III 1
300
YVR
G II
I 130
0 Y
VRF
II 13
02VR
G II
130
2
VRF
I 130
1VR
G I
1301
VRF
I 260
22)
VRG
I 26
022)
VRF
I 100
1VR
G I
1001
31) 1
1000 1000
1212
3 3
30 30
4000 4000
3000 3000
5TD 237/02237/02/01/0
Rated through-current Iu (A)
Rate
d st
ep v
olta
ge U
i (V)
1.2.1 Step capacity diagram1)
1 General / Technical Data
1.2.2 Step capacity diagram EAF/LF operation3)
Rate
d st
ep v
olta
ge U
i (V)
Rated through-current Iu (A)
Fig. 1Step capacities (Rated step voltage Ui, Rated through-current Iu).
Note: 1) When used for electrical arc furnace (EAF) and ladle furnace transformers (LF), refer to step capacity diagram chap. 1.2.2.2) Forced current division by two parallel winding branches required.
Fig. 2Step capacities electrical arc furnace and ladle furnace operation (EAF/LF), rated step voltage Ui, ratedthrough-current Iu.
Note: 3) Please contact MR.
VRG: Identical versions as VRF but with tap selector size „E“
0
500
1000
1500
2000
2500
3000
3500
4000
4500
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600
3000 kVA 6000 kVA
1500 kVA
VR
D III 1
000Y
VR
D III 1
300Y
VR
D I 1
301
VR
F I 2
602
2)
VR
F III 1
300Y
VR
F II 1302
VR
F I 1
301V
RF
III 1
000Y
VR
F I 1
001
0
500
1000
1500
2000
2500
3000
3500
4000
4500
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600
VRF I 1001
1500 kVA1820 kVA
2400 kVA
1360 kVA
VR
D III 1
000Y
VR
D III 1
300Y
VR
D I 1
301
VRF I 1301
VRF III 1300YVRF III 1000Y
6 TD 237/02 237/02/01/0
1.3 Rated insulation level
Rated insulation level On-load tap-changer
72.5 to 362 kV VRF/VRG I 1001; VRF/VRG II 1302; VRF/VRG I 1301;VRF/VRG I 2602
72.5 to 300 kV VRD I 1301
72.5 to 245 kV VRD III 1000 Y; VRD III 1300 Y; VRF/VRG III 1000 Y;VRF/VRG III 1300 Y
1 General / Technical Data
Note: 1) According to IEC 60214-1, chapter 3.57: highest r.m.s. phase-to-phase voltage in a three-phase system for which aon-load tap-changer is designed with respect to its insulation.
Highest voltage forequipment Um (in kV)1)
72.5
Rated lightning impulse with-stand voltage (in kV, 1.2/50 µs)
123 170 245 300 362
Rated switching impulsewithstand voltage (in kV)
Rated short-duration powerfrequency withstand voltage(in kV, 50 Hz, 1 min.)
350 550 750 1050 1050 1175
850 850 950
140 230 325 460 460 510
7TD 237/02237/02/01/0
1.4 Rated withstand voltages of the internal insulation
Fig. 2 shows diagrams of the voltage stress present on the tap winding of the three primary basic connections of three-poleon-load tap-changers and single-pole on-load tap-changers.When selecting the on-load tap-changer, a check must be made to determine whether the highest stress on the tap selectordoes not exceed the related rated withstand voltages.
a0 = Between selected and preselected tapping on the diverter switch and tap selector
a1 = Between tap selector contacts of the winding of one tap position (connected or not connected)
a = Between beginning and end of a tapped winding and, with coarse tap winding, between beginning and end of a coarse tap winding.Note for coarse tapping arrangement in (-) - position of the change-over selector:When stressed with impulse voltage, the permissible withstand voltage „a“ must be adhered to between the end of a coarse tap windingconnected with the K tap selector contact and the tap selector contact at the end of the tapped winding of the same phase
b = Between the tap selector contacts of different phases and between change-over selector contacts of different phases, which are connectedwith the beginning/end of a tapped winding or with a tap selector contact
f = Between diverter switch terminal and ground
Additional for coarse tapping arrangement in (+) - position of the change-over selector:c1 = From one (-) - change-over selector contact to terminal of the same phasec2 = Between (-) - change-over selector contacts of different phases
CAUTIONAdhere to maximum ratedlightning impulse withstandvoltage stress on a0in mid-position.
8997560E
Fig. 2 Rated withstand voltages
With coarse change-over selector in (+) – position With coarse change-over selector in (–) – position
With reversing change-over selectorWithout change-over selector
1 General / Technical Data
8 TD 237/02 237/02/01/0
Note:1) Tap selectors according to basic circuit diagram 10 09 1 W, 12 11 1W, 14 13 1 W are designed as 18 09 1 W, 18 11 1 W,
18 13 1 W.Tap selectors according to basic circuit diagram 16 15 1 W and 18 17 1 W are not available.
2) Higher values up to 550 kV on request.3) Insulation distance omitted for single-pole on-load tap-changers
The tap selector size (ID letters C,D,E) characterizes the internal insulation of the tap selector, whose rated withstand voltages mustbe matched to the requirements of the transformer winding. The admissible maximum operating voltage on the individual tapselector distances complies to half the value of the above mentioned rated short-duration power frequency withstand voltages.
1 General / Technical Data
On-load tap-changer VRD III 1000 Y ... VRG I 2602, rated withstand voltages of the internal on-load tap-changer insulation.
Insulation Tap selector size C Tap selector size D1) Tap selector size Edistances
kV 1.2/50 µs kV, 50 Hz, 1 min kV 1.2/50 µs kV, 50 Hz, 1 min kV 1.2/50 µs kV, 50 Hz, 1 min
a0
a1 150 30 150 30 150 30
a 400 85 5002) 110 670 180
b3) 400 100 5002) 150 670 180
c1 550 180 590 210 820 250
c23) 550 195 590 225 820 280
Power frequency withstand voltage test (50 Hz/60 s): 20 kV 50 Hz 1 min; Response voltage at 1 mA-leakage current: 44 kV 1.2/50 µs;3 kA-residual voltage (= lightning impulse protection level): 70 kV 1.2/50 µs with ZnO
9TD 237/02237/02/01/0
The VRF II 1302 on-load tap-changer can also be used withthe single-phase on-load tap-changer VRF I 1301 as a two-column on-load tap-changer combination VRF I 1301/VRF II1302 for adjusting the voltage of transformer windings in adelta connection.The tap windings should correspond to those in fig. 3.
2 Special designs – On-load tap-changer combinationVACUTAP® VRF I/VRF II for delta connection
2 Special designs –On-load tap-changer combination VACUTAP® VRF I/VRF IIfordelta connection
KHW 352-3
Fig. 3On-load tap-changer combination VRF I 1301/VRF II 1302(a – VRF I 1301, b – VRF II 1302) for delta connection.
10 TD 237/02 237/02/01/0
3 Appendix
3.1 Dimension drawings / connection diagrams
On-load tap-changer VACUTAP® VRD, VRG, VRF, survey of types ................................................................ 727016_1/2 Page 12/13
On-load tap-changer VACUTAP® VR, basic connection diagrams, designation oftap selector terminal contacts according to MR standard .............................................................................. 899906_1/2 Page14/15
On-load tap-changer VACUTAP® VRD III 1300 Y–C/D, connection diagram 10 19 1 W ........................ 1599588 Page16
On-load tap-changer VACUTAP® VRG III 1300 Y–E, connection diagram 14 27 1 G .............................. 1599592 Page 17
On-load tap-changer VACUTAP® VRD III 1000/1300 Y - VRF III 1000/1300 Y,dimension drawing ..................................................................................................................................................... 899803_1/2 Page 18/19
On-load tap-changer VACUTAP® VRG III 1000/1300 Y, dimension drawing ............................................. 899804_1/2 Page 20/21
On-load tap-changer VACUTAP® VRF II 1302, dimension drawing .............................................................. 899814_1/2 Page 22/23
On-load tap-changer VACUTAP® VRF II 1302 (Um 362 kV), dimension drawing ..................................... 899815_1/2 Page 24/25
On-load tap-changer VACUTAP® VRG II 1302, dimension drawing ............................................................. 899816_1/2 Page 26/27
On-load tap-changer VACUTAP® VRG II 1302 (Um 362 kV), dimension drawing .................................... 899817_1/2 Page 28/29
On-load tap-changer VACUTAP® VRD I 1301 - VRF I 1001/1301, dimension drawing .......................... 899805_1/2 Page 30/31
On-load tap-changer VACUTAP® VRF I 1001/1301 (Um 362 kV), dimension drawing .......................... 899806_1/2 Page 32/33
On-load tap-changer VACUTAP® VRG I 1001/1301, dimension drawing ................................................... 899810_1/2 Page 34/35
On-load tap-changer VACUTAP® VRG I 1001/1301 (Um 362 kV), dimension drawing ......................... 899811_1/2 Page 36/37
On-load tap-changer VACUTAP® VRF I 2602, dimension drawing ............................................................... 727033_1/2 Page 38/39
On-load tap-changer VACUTAP® VRF I 2602 (Um 362 kV), dimension drawing ...................................... 727034_1/2 Page 40/41
On-load tap-changer VACUTAP® VRG I 2602, dimension drawing ............................................................. 727035_1/2 Page 42/43
On-load tap-changer VACUTAP® VRG I 2602 (Um 362 kV), dimension drawing ..................................... 727036_1/2 Page 44/45
3.2 Installation drawings
On-load tap-changer VACUTAP® VRD, VRF, tap selector size C/D, installation drawing ......................... 899898_1/2 Page 46/47
On-load tap-changer VACUTAP® VRG, tap selector size E, installation drawing ....................................... 899945_1/2 Page 48/49
On-load tap-changer VACUTAP® VR, on-load tap-changer head ................................................................. 899944 Page 50
On-load tap-changer VACUTAP® VR, on-load tap-changer head withflange for pressure-relief device ............................................................................................................................. 899946 Page 51
On-load tap-changer VACUTAP® VR, special design for bell-type tank ...................................................... 720781 Page 52
On-load tap-changer VACUTAP® VRD, VRF, VRG, tap selector andchange-over selector terminal ................................................................................................................................. 899941 Page 53
On-load tap-changer VACUTAP® VRD, VRF, tap selector size C/D, representation of thetap selector bottom showing the lowest parts to be energized ..................................................................... 899968 Page 54
On-load tap-changer VACUTAP® VRG, tap selector size E, representation of the tap selectorbottom showing the lowest parts to be energized ............................................................................................ 899969 Page 55
On-load tap-changer VACUTAP® VR, versions of the on-load tap-changer head,swivelling range and drive direction of the gear unit ....................................................................................... 728471 Page 56
On-load tap-changer VACUTAP® VR, versions of the on-load tap-changer head,swivelling range and drive direction of the gear unit ....................................................................................... 728474 Page 57
On-load tap-changer VACUTAP® VR, horizontal drive shaft, tap selector size C/D ................................... 899958 Page 58
3 Appendix
11TD 237/02237/02/01/0
2 Appendix
On-load tap-changer VACUTAP® VR, horizontal drive shaft, tap selector size E ....................................... 899959 Page 59
On-load tap-changer VACUTAP® VRD, VRF, basic arrangement of potential switchand tie-in resistors ....................................................................................................................................................... 899950 Page 60
On-load tap-changer VACUTAP® VRD, VRF I ... WP, tap selector size C/D,tie-in resistor cylinder and potential switch ........................................................................................................ 899951 Page 61
On-load tap-changer VACUTAP® VRD, VRF I ... WP, tap selector size C/D,tie-in resistor cylinder and potential switch ........................................................................................................ 899952 Page 62
On-load tap-changer VACUTAP® VRD, VRF I ... WP, tap selector size C/D,tie-in resistor cylinder and potential switch ........................................................................................................ 899953 Page 63
On-load tap-changer VACUTAP® VRD, VRF I ... WP, tap selector size C/D,tie-in resistor cylinder and potential switch ........................................................................................................ 899954 Page 64
On-load tap-changer VACUTAP® VRD, VRF I ... WR, tap selector size C/D,tie-in resistor cylinder ................................................................................................................................................ 899955 Page 65
On-load tap-changer VACUTAP® VRD, VRF I ... WR, tap selector size C/D,tie-in resistor cylinder ................................................................................................................................................ 899956 Page 66
On-load tap-changer VACUTAP® VRD, VRF I ... WR, tap selector size C/D,tie-in resistor cylinder ................................................................................................................................................ 899960 Page 67
On-load tap-changer VACUTAP® VRD, VRF I ... WR, tap selector size C/D,tie-in resistor cylinder ................................................................................................................................................ 899961 Page 68
On-load tap-changer VACUTAP® VRD, VRF III ... WP, tap selector size C/D,tie-in resistor cylinder and potential switch ........................................................................................................ 899962 Page 69
On-load tap-changer VACUTAP® VRD, VRF III ... WP, tap selector size C/D,tie-in resistor cylinder and potential switch ........................................................................................................ 899963 Page 70
On-load tap-changer VACUTAP® VRD, VRF III ... WR, tap selector size C/D,tie-in resistor cylinder ................................................................................................................................................ 899964 Page 71
On-load tap-changer VACUTAP® VRD, VRF III ... WR, tap selector size C/D,tie-in resistor cylinder ................................................................................................................................................ 899965 Page 72
On-load tap-changer VACUTAP® VRD, VRF I/III ... WS, tap selector size C/D,potential switch ........................................................................................................................................................... 899966 Page 73
On-load tap-changer VACUTAP® VRG I/III ... WS, tap selector size E,potential switch ........................................................................................................................................................... 899967 Page 74
12 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRD, VRF, VRGSurvey of types
7270163E_1
13TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRD, VRF, VRGSurvey of types
7270163E_2
14 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRBasic connection diagramsDesignation of tap selector terminal contacts according to MR standard
8999060E_1
15TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRBasic connection diagramsDesignation of tap selector terminal contacts according to MR standard
8999060E_2
16 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRD III 1300 Y-C/D-10 19 1 WConnection diagram
1599588
17TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRG III 1300 Y-E-14 27 1 GConnection diagram
1599592
18 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRD III 1000/1300 Y -VRF III 1000/1300 YDimension drawing
8998033E_1
19TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRD III 1000/1300 Y -VRF III 1000/1300 YDimension drawing
8998033E_2
20 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRG III 1000/1300 YDimension drawing
8998043E_1
21TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRG III 1000/1300 YDimension drawing
8998043E_2
22 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRF II 1302Dimension drawing
8998144E_1
23TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRF II 1302Dimension drawing
8998144E_2
24 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRF II 1302 (Um 362 kV)Dimension drawing
8998154E_1
25TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRF II 1302 (Um 362 kV)Dimension drawing
8998154E_2
26 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRG II 1302Dimension drawing
8998164E_1
27TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRG II 1302Dimension drawing
8998164E_2
28 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRG II 1302 (Um 362 kV)Dimension drawing
8998174E_1
29TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRG II 1302 (Um 362 kV)Dimension drawing
8998174E_2
30 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRD I 1301 - VRF I 1001/1301Dimension drawing
8998055E_1
31TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRD I 1301 - VRF I 1001/1301Dimension drawing
8998055E_2
32 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRF I 1001/1301 (Um 362 kV)Dimension drawing
8998065E_1
33TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRF I 1001/1301 (Um 362 kV)Dimension drawing
8998065E_2
34 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRG I 1001/1301Dimension drawing
8998105E_1
35TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRG I 1001/1301Dimension drawing
8998105E_2
36 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRG I 1001/1301 (Um 362 kV)Dimension drawing
8998115E_1
37TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRG I 1001/1301 (Um 362 kV)Dimension drawing
8998115E_2
38 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRF I 2602Dimension drawing
7270334E_1
39TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRF I 2602Dimension drawing
7270334E_2
40 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRF I 2602 (Um 362 kV)Dimension drawing
7270343E_1
41TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRF I 2602 (Um 362 kV)Dimension drawing
7270343E_2
42 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRG I 2602Dimension drawing
7270353E_1
43TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRG I 2602Dimension drawing
7270353E_2
44 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRG I 2602 (Um 362 kV)Dimension drawing
7270363E_1
45TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRG I 2602 (Um 362 kV)Dimension drawing
7270363E_2
46 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRD, VRFTap selector size C/D, installation drawing
8998985E_1
47TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRD, VRFTap selector size C/D, installation drawing
8998985E_2
48 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRGTap selector size E, installation drawing
8999454E_1
49TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRGTap selector size E, installation drawing
8999454E_2
50 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VROn-load tap-changer head
8999444E
51TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VROn-load tap-changer head with flange for pressure-relief device
8999462E
52 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRSpecial design for bell-type tank
7207810E
53TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRD, VRF, VRGTap selector and change-over selector terminal
8999411E
54 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRD, VRFTap selector size C/D, representation of the tap selector bottomshowing the lowest parts to be energized
8999682E
55TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRGTap selector size E, representation of the tap selector bottom showingthe lowest parts to be energized
8999691E
56 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRVersions of the on-load tap-changer headSwivelling range and drive direction of the gear unit
7284711E
57TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRVersions of the on-load tap-changer headSwivelling range and drive direction of the gear unit
7284740E
58 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRHorizontal drive shaft, tap selector size C/D,
8999583E
59TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRHorizontal drive shaft, tap selector size E,
8999593E
60 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRD, VRFBasic arrangement of potential switch and tie-in resistors
8999501E
61TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRD, VRF I ... WP
Tap selector size C/D, tie-in resistor cylinder and potential switch8999513M
62 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRD, VRF I ... WP
Tap selector size C/D, tie-in resistor cylinder and potential switch8999523M
63TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRD, VRF I ... WP
Tap selector size C/D, tie-in resistor cylinder and potential switch8999533M
64 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRD, VRF I ... WP
Tap selector size C/D, tie-in resistor cylinder and potential switch8999543M
65TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRD, VRF I ... WR
Tap selector size C/D, tie-in resistor cylinder8999553M
66 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRD, VRF I ... WR
Tap selector size C/D, tie-in resistor cylinder8999563M
67TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRD, VRF I ... WR
Tap selector size C/D, tie-in resistor cylinder8999603M
68 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRD, VRF I ... WR
Tap selector size C/D, tie-in resistor cylinder8999613M
69TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRD, VRF III ... WP
Tap selector size C/D, tie-in resistor cylinder and potential switch8999623M
70 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRD, VRF III ... WP
Tap selector size C/D, tie-in resistor cylinder and potential switch8999633M
71TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRD, VRF III ... WR
Tap selector size C/D, tie-in resistor cylinder8999644M
72 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRD, VRF III ... WR
Tap selector size C/D, tie-in resistor cylinder8999653M
73TD 237/02237/02/01/0
On-load tap-changer VACUTAP® VRD, VRF I/III ... WSTap selector size C/D, potential switch
8999663M
74 TD 237/02 237/02/01/0
On-load tap-changer VACUTAP® VRG I/III ... WSTap selector size E, potential switch
8999674M