SUBMITTAL NUMBER: 233400-01.00 OCPS CLAY SPRINGS ES SUBMITTAL TRANSMITTAL SUBMITTAL DETAILS: REVIEWERS: SUBJECT: HVAC FANS PD (INCL. NOA FL PRODUCT APP)HVAC FANS PD (INCL. NOA FL PRODUCT APP) DATE RECIEVED: Oct 06, 2014 DISCIPLINE: Mechanical PRIMARY: KEVIN KING [email protected]TAD RIVENBARK [email protected]MATERN ENGINEERING PHN: (407) 740-5020 FAX: (407) 740-0365 MATERN ENGINEERING PHN: (407) 740-5020 FAX: (407) 740-0365 SECONDARY: PRIORITY STATUS: 2-STANDARD REVIEWER DUE DATE: 10/16/2014 SPECIFICATION REF: 23 34 00 DWG REF. NONE DWG TITLE: NO OF ITEMS: ITEM DESCRIPTI REVIEW STATUS: COMMENTS: CONTRACTOR/CM: : WILLIAMS COMPANY : BRAD KUBIN 2301 SILVER STAR RD. ORLANDO, FL, 32809 (407) 295-2530 FAX:(407) 297-0459 PLEASE SEE A/E COMMENTS FURNISH AS MARKED RETURNED ITEMS: DATE RETURNED TO CM: 10/9/2014 BUILDING REFERENCE: 1 Product Literature(s) PAGE 1 OF 1 RHODES + BRITO ARCHITECTS INC. : 605 E. ROBINSON STREET, SUITE 750 : ORLANDO, FL. : 32801 : 407.648.7288 : FAX.648.7289 cc: OWNER : CALVIN WOOLFOLK 6501 MAGIC WAY, BLDG. 200 ORLANDO, FL, 32809 (407) 317-3700 FAX:(407) 317-3768 R+B FILE: : 13017-0001.X6
65
Embed
OCPS CLAY SPRINGS ES SUBMITTAL TRANSMITTAL · Belt Drive Centrifugal Inline Fan Standard Construction Features: - Galvanized steel housing - Backward inclined aluminum wheel - Two
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
THIS SUBMITTAL IS ISSUED TO YOU FOR YOUR REVIEW. PLEASE RESPOND AND RETURN...WITH THIS COMPLETED SAM TRANSMITTAL...TO MICHELE BUDAY-URDANETA NO LATER THAN: 10/16/2014. PLEASE COMPLETE REVIEW STATUS AT RIGHT
SUBMITTAL CONTENTS:
NO OF ITEMS: ITEM DESCRIPTION
(please print)THIS SUBMITTAL WAS REVIEWED BY :
RE-SUBMIT WITH ITEMS
NOT REVIEWED
REJECTED
REVISE AND RESUBMIT
FURNISHED AS MARKED
REVIEWED
COMMENTS:
1 PRODUCT LITERATURE(S)
cc:
OWNER : CALVIN WOOLFOLK
6501 MAGIC WAY, BLDG. 200
ORLANDO, FL, 32809
R+B FILE: : 13017-0001.X6CONTR/CM: : WILLIAMS COMPANY
Class: Basis of Design (1) Equal (2) Substitution (3)
ACTION CODE A No exceptions taken. X B Make corrections noted. C Revise and Resubmit. D Submit Specified Item. E Rejected. N Review not required.
THE FOLLOWING COMMENTS SHALL BE CONSIDERED AN INTEGRAL PART OF THE SUBMITTAL DATA REVIEW. REVIEW OF THIS DATA IS ONLY FOR CONFORMANCE WITH THE DESIGN CONCEPT AS GIVEN IN THE CONTRACT DOCUMENTS. THE CONTRACTOR IS RESPONSIBLE FOR: QUANTITIES, FUNCTIONS, DIMENSIONS AND COORDINATION OF THE WORK WITH OTHER TRADES. 1. Coordinate all electrical requirements with The Electrical Contractor. Due to the
differing horsepower the installing contractor will be responsible for all modifications if any necessary for a complete installation.
Model: BSQ-160HP-3Belt Drive Centrifugal Inline Fan
DimensionalQuantity 1
Weight w/o Acc's (lb) 175
Weight w/ Acc's (lb) 212
Max T Motor Frame Size 184
Optional Damper (in.) 23 x 23
PerformanceRequested Volume (CFM) 900
Actual Volume (CFM) 900
External SP (in. wg) 0.6
Total SP (in. wg) 0.6
Fan RPM 885
Operating Power (hp) 0.19
Elevation (ft) 105
Airstream Temp.(F) 70
Air Density (ft3) 0.075
Drive Loss (%) 14.8
Tip Speed (ft/min) 3,853
Static Eff. (%) 52
MotorMotor Mounted Yes
Size (hp) 1/3
V/C/P 115/60/1
Enclosure ODP
Motor RPM 1725
Windings 1
NEC FLA* (Amps) 7.2
Notes:All dimensions shown are in units of in.*FLA - based on tables 150 or 148 of National ElectricalCode 2002. Actual motor FLA may vary, for sizing thermaloverload, consult factory.LwA - A weighted sound power level, based on ANSI S1.4dBA - A weighted sound pressure level, based on 11.5 dBattenuation per Octave band at 5 ft - dBA levels are notlicensed by AMCA InternationalSones - calculated using AMCA 301 at 5 ft
- Model WD-330 is a vertical mount exhaust damper and is constructed of galvanized steel with pre-punched mounting holes -Damper blades are 0.025 in. roll formed aluminum with vinyl seals on the closing edge - Steel axles are 0.188 in. diameter zincplated steel - Synthetic sleeve type bushings
Notes: All dimensions shown are in units of in.Width And height furnished approximately 0.125 in. undersize
Reference assembly view drawings for actualdimensions with mounted accessories
*Overall height may be greater depending on motor
*
19
28.38
4
23.75
1.75
Model: G-133-ADirect Drive Centrifugal Roof Exhaust Fan
DimensionalQuantity 1
Weight w/o Acc's (lb) 58
Weight w/ Acc's (lb) 99
Max T Motor Frame Size 56
Optional Damper (in.) 12 x 12
Roof Opening (in.) 14.5 x 14.5
PerformanceRequested Volume (CFM) 1,470
Actual Volume (CFM) 1,470
External SP (in. wg) 0.75
Total SP (in. wg) 0.75
Fan RPM 1392
Operating Power (hp) 0.31
Elevation (ft) 105
Airstream Temp.(F) 70
Air Density (ft3) 0.075
Tip Speed (ft/min) 4,781
Static Eff. (%) 55
MotorMotor Mounted Yes
Size (hp) 3/4
V/C/P 115/60/1
Enclosure ODP
Motor RPM 1725
Windings 1
NEC FLA* (Amps) 13.8
Notes:All dimensions shown are in units of in.*FLA - based on tables 150 or 148 of National ElectricalCode 2002. Actual motor FLA may vary, for sizing thermaloverload, consult factory.LwA - A weighted sound power level, based on ANSI S1.4dBA - A weighted sound pressure level, based on 11.5 dBattenuation per Octave band at 5 ft - dBA levels are notlicensed by AMCA InternationalSones - calculated using AMCA 301 at 5 ft
Model: G-133-ADirect Drive Centrifugal Roof Exhaust FanStandard Construction Features:Model G Centrifugal Roof Exhaust Fans are direct drive. These fans arespecifically designed for roof mounted applications exhausting relatively clean air.Fan wheels are centrifugal, backward inclined, and constructed of aluminum.
Options & Accessories:PSC MotorUL/cUL 705 Listed - "Power Ventilators"Switch, NEMA-1, Toggle, Junction Box Mounted & WiredHigh Wind Rated (+/- 150 PSF Rating)Florida Product Approval #FL13225.1 & Miami-Dade NOA #13-0220.08Texas Department of Insurance Product Evaluation RV-73Roof Curb-Galv., GPF-19-G18, Under Sized 1 in. TotalDamper, WD-100-PB-12X12, Gravity Operated (Loose), Not CoatedSolid State Speed Control, 10 Amp (PN 385205) Shipped LooseUnit Warranty: 1 Yr (Standard)
Limits of Use Approved for use in HVHZ: Yes Approved for use outside HVHZ: Yes Impact Resistant: Yes Design Pressure: +150/-150 Other: Not to be used within the ridge area
Installation Instructions FL13225_R3_II_13-0220.08 Spun Alum 150psf.pdf Verified By: Miami-Dade BCCO - EVL Created by Independent Third Party: Evaluation Reports FL13225_R3_AE_13-0220.08 Spun Alum 150psf.pdf
13225.2 Steel Rooftop Supply Fans Model RSF
Limits of Use Approved for use in HVHZ: Yes Approved for use outside HVHZ: Yes Impact Resistant: Yes Design Pressure: +100/-100 Other: Not to be used within the ridge area
Installation Instructions FL13225_R3_II_RSF NOA.pdf Verified By: Miami-Dade BCCO - EVL Created by Independent Third Party: Evaluation Reports FL13225_R3_AE_RSF NOA.pdf
Back Next
Contact Us :: 1940 North Monroe Street, Tallahassee FL 32399 Phone: 850-487-1824
The State of Florida is an AA/EEO employer. Copyright 2007-2013 State of Florida. :: Privacy Statement :: Accessibility Statement :: Refund Statement
Under Florida law, email addresses are public records. If you do not want your e-mail address released in response to a public-records request, do not send electronicmail to this entity. Instead, contact the office by phone or by traditional mail. If you have any questions, please contact 850.487.1395. *Pursuant to Section
455.275(1), Florida Statutes, effective October 1, 2012, licensees licensed under Chapter 455, F.S. must provide the Department with an email address if they haveone. The emails provided may be used for official communication with the licensee. However email addresses are public record. If you do not wish to supply a personaladdress, please provide the Department with an email address which can be made available to the public. To determine if you are a licensee under Chapter 455, F.S.,
please click here .
Product Approval Accepts:
DAMPER TYP. SECTION VIEW
1212
2.56.6
Standard Construction Features:
- Model WD-100 is a horizontal mount exhaust damper (air flow up) and is constructed of 18 ga galvanized steel with pre-punched mounting holes - Damper blades are 0.025 in. roll formed aluminum with vinyl seals on the closing edge, and springassisted for ease of opening - Steel axles are 0.188 in. diameter zinc plated mounted in acetal bushings - Synthetic axlebearings
Notes: All dimensions shown are in units of in.Width And height furnished approximately 0.125 in. undersize
Standard Construction Features:- Roof Curb fits between the building roof and the fan mounted directly to the roof support structure - Constructed of either 18ga galvanized steel or 0.064 in. aluminum - Straight Sided without a cant - 5 in. mounting flange - 1 in. thick 3 lb densityinsulation - Height - Available from 8 in. to 42 in. as specified in 0.5 in. increments.
Notes:- The maximum roof opening dimension should not be greater than the "Actual" top outside dimension minus 2 in..- The minimum roof opening dimension should be at least 2.5 in. more than the damper dimension or recommended duct size.- The Roof Opening Dimension may NOT be the Structural Opening Dimension.- Damper Tray is optional and must be specified. Tray size is same as damper size.- Security bars are optional and must be specified. Frames and gridwork are all 10 ga steel. Gridwork is welded to the frameand the frame is welded to the curb. To prevent corrosion, they are coated with Greenheck’s high performance Permatectorcoating.
Notes:All dimensions shown are in units of in.*FLA - based on tables 150 or 148 of National ElectricalCode 2002. Actual motor FLA may vary, for sizing thermaloverload, consult factory.LwA - A weighted sound power level, based on ANSI S1.4dBA - A weighted sound pressure level, based on 11.5 dBattenuation per Octave band at 5 ft - dBA levels are notlicensed by AMCA InternationalSones - calculated using AMCA 301 at 5 ft
- Model WD-330 is a vertical mount exhaust damper and is constructed of galvanized steel with pre-punched mounting holes -Damper blades are 0.025 in. roll formed aluminum with vinyl seals on the closing edge - Steel axles are 0.188 in. diameter zincplated steel - Synthetic sleeve type bushings
Notes: All dimensions shown are in units of in.Width And height furnished approximately 0.125 in. undersize
Reference assembly view drawings for actualdimensions with mounted accessories
*Overall height may be greater depending on motor
*
19
24.38
4.38
23.75
1.75
Model: G-123-BDirect Drive Centrifugal Roof Exhaust Fan
DimensionalQuantity 1
Weight w/o Acc's (lb) 51
Weight w/ Acc's (lb) 92
Max T Motor Frame Size 56
Optional Damper (in.) 12 x 12
Roof Opening (in.) 14.5 x 14.5
PerformanceRequested Volume (CFM) 765
Actual Volume (CFM) 765
External SP (in. wg) 0.6
Total SP (in. wg) 0.6
Fan RPM 1099
Operating Power (hp) 0.12
Elevation (ft) 105
Airstream Temp.(F) 70
Air Density (ft3) 0.075
Tip Speed (ft/min) 3,757
Static Eff. (%) 59
MotorMotor Mounted Yes
Size (hp) 1/4
V/C/P 115/60/1
Enclosure ODP
Motor RPM 1140
Windings 1
NEC FLA* (Amps) 5.8
Notes:All dimensions shown are in units of in.*FLA - based on tables 150 or 148 of National ElectricalCode 2002. Actual motor FLA may vary, for sizing thermaloverload, consult factory.LwA - A weighted sound power level, based on ANSI S1.4dBA - A weighted sound pressure level, based on 11.5 dBattenuation per Octave band at 5 ft - dBA levels are notlicensed by AMCA InternationalSones - calculated using AMCA 301 at 5 ft
Model: G-123-BDirect Drive Centrifugal Roof Exhaust FanStandard Construction Features:Model G Centrifugal Roof Exhaust Fans are direct drive. These fans arespecifically designed for roof mounted applications exhausting relatively clean air.Fan wheels are centrifugal, backward inclined, and constructed of aluminum.
Options & Accessories:PSC MotorUL/cUL 705 Listed - "Power Ventilators"Switch, NEMA-1, Toggle, Junction Box Mounted & WiredHigh Wind Rated (+/- 150 PSF Rating)Florida Product Approval #FL13225.1 & Miami-Dade NOA #13-0220.08Texas Department of Insurance Product Evaluation RV-73Roof Curb-Galv., GPF-19-G18, Under Sized 1 in. TotalDamper, WD-100-PB-12X12, Gravity Operated (Loose), Not CoatedSolid State Speed Control, 5 Amp (PN 385031) Shipped LooseUnit Warranty: 1 Yr (Standard)
- Model WD-100 is a horizontal mount exhaust damper (air flow up) and is constructed of 18 ga galvanized steel with pre-punched mounting holes - Damper blades are 0.025 in. roll formed aluminum with vinyl seals on the closing edge, and springassisted for ease of opening - Steel axles are 0.188 in. diameter zinc plated mounted in acetal bushings - Synthetic axlebearings
Notes: All dimensions shown are in units of in.Width And height furnished approximately 0.125 in. undersize
Standard Construction Features:- Roof Curb fits between the building roof and the fan mounted directly to the roof support structure - Constructed of either 18ga galvanized steel or 0.064 in. aluminum - Straight Sided without a cant - 5 in. mounting flange - 1 in. thick 3 lb densityinsulation - Height - Available from 8 in. to 42 in. as specified in 0.5 in. increments.
Notes:- The maximum roof opening dimension should not be greater than the "Actual" top outside dimension minus 2 in..- The minimum roof opening dimension should be at least 2.5 in. more than the damper dimension or recommended duct size.- The Roof Opening Dimension may NOT be the Structural Opening Dimension.- Damper Tray is optional and must be specified. Tray size is same as damper size.- Security bars are optional and must be specified. Frames and gridwork are all 10 ga steel. Gridwork is welded to the frameand the frame is welded to the curb. To prevent corrosion, they are coated with Greenheck’s high performance Permatectorcoating.
Notes:All dimensions shown are in units of in.*FLA - based on tables 150 or 148 of National ElectricalCode 2002. Actual motor FLA may vary, for sizing thermaloverload, consult factory.LwA - A weighted sound power level, based on ANSI S1.4dBA - A weighted sound pressure level, based on 11.5 dBattenuation per Octave band at 5 ft - dBA levels are notlicensed by AMCA InternationalSones - calculated using AMCA 301 at 5 ft
- Model WD-330 is a vertical mount exhaust damper and is constructed of galvanized steel with pre-punched mounting holes -Damper blades are 0.025 in. roll formed aluminum with vinyl seals on the closing edge - Steel axles are 0.188 in. diameter zincplated steel - Synthetic sleeve type bushings
Notes: All dimensions shown are in units of in.Width And height furnished approximately 0.125 in. undersize
Reference assembly view drawings for actualdimensions with mounted accessories
*Overall height may be greater depending on motor
*
19
24.38
4.38
23.75
1.75
Model: GB-121-4Belt Drive Centrifugal Roof Exhaust Fan
DimensionalQuantity 1
Weight w/o Acc's (lb) 56
Weight w/ Acc's (lb) 97
Max T Motor Frame Size 56
Optional Damper (in.) 12 x 12
Roof Opening (in.) 14.5 x 14.5
PerformanceRequested Volume (CFM) 825
Actual Volume (CFM) 825
External SP (in. wg) 0.4
Total SP (in. wg) 0.4
Fan RPM 987
Operating Power (hp) 0.12
Elevation (ft) 105
Airstream Temp.(F) 70
Air Density (ft3) 0.075
Drive Loss (%) 20.9
Tip Speed (ft/min) 3,374
Static Eff. (%) 56
MotorMotor Mounted Yes
Size (hp) 1/4
V/C/P 115/60/1
Enclosure ODP
Motor RPM 1725
Windings 1
NEC FLA* (Amps) 5.8
Notes:All dimensions shown are in units of in.*FLA - based on tables 150 or 148 of National ElectricalCode 2002. Actual motor FLA may vary, for sizing thermaloverload, consult factory.LwA - A weighted sound power level, based on ANSI S1.4dBA - A weighted sound pressure level, based on 11.5 dBattenuation per Octave band at 5 ft - dBA levels are notlicensed by AMCA InternationalSones - calculated using AMCA 301 at 5 ft
- Model WD-100 is a horizontal mount exhaust damper (air flow up) and is constructed of 18 ga galvanized steel with pre-punched mounting holes - Damper blades are 0.025 in. roll formed aluminum with vinyl seals on the closing edge, and springassisted for ease of opening - Steel axles are 0.188 in. diameter zinc plated mounted in acetal bushings - Synthetic axlebearings
Notes: All dimensions shown are in units of in.Width And height furnished approximately 0.125 in. undersize
Standard Construction Features:- Roof Curb fits between the building roof and the fan mounted directly to the roof support structure - Constructed of either 18ga galvanized steel or 0.064 in. aluminum - Straight Sided without a cant - 5 in. mounting flange - 1 in. thick 3 lb densityinsulation - Height - Available from 8 in. to 42 in. as specified in 0.5 in. increments.
Notes:- The maximum roof opening dimension should not be greater than the "Actual" top outside dimension minus 2 in..- The minimum roof opening dimension should be at least 2.5 in. more than the damper dimension or recommended duct size.- The Roof Opening Dimension may NOT be the Structural Opening Dimension.- Damper Tray is optional and must be specified. Tray size is same as damper size.- Security bars are optional and must be specified. Frames and gridwork are all 10 ga steel. Gridwork is welded to the frameand the frame is welded to the curb. To prevent corrosion, they are coated with Greenheck’s high performance Permatectorcoating.
Reference assembly view drawings for actualdimensions with mounted accessories
*Overall height may be greater depending on motor
*
17
21.75
4
14.63
1.75
Model: G-095-DDirect Drive Centrifugal Roof Exhaust Fan
DimensionalQuantity 1
Weight w/o Acc's (lb) 20
Weight w/ Acc's (lb) 56
Optional Damper (in.) 10 x 10
Roof Opening (in.) 12.5 x 12.5
PerformanceRequested Volume (CFM) 225
Actual Volume (CFM) 225
External SP (in. wg) 0.3
Total SP (in. wg) 0.3
Fan RPM 1031
Operating Power (hp) 0.03
Elevation (ft) 105
Airstream Temp.(F) 70
Air Density (ft3) 0.075
Tip Speed (ft/min) 2,936
Static Eff. (%) 36
MotorMotor Mounted Yes
Size (hp) 1/8
V/C/P 115/60/1
Enclosure ODP
Motor RPM 1550
Windings 1
NEC FLA* (Amps) NA
Notes:All dimensions shown are in units of in.*FLA - based on tables 150 or 148 of National ElectricalCode 2002. Actual motor FLA may vary, for sizing thermaloverload, consult factory.LwA - A weighted sound power level, based on ANSI S1.4dBA - A weighted sound pressure level, based on 11.5 dBattenuation per Octave band at 5 ft - dBA levels are notlicensed by AMCA InternationalSones - calculated using AMCA 301 at 5 ft
Model: G-095-DDirect Drive Centrifugal Roof Exhaust FanStandard Construction Features:Model G Centrifugal Roof Exhaust Fans are direct drive. These fans arespecifically designed for roof mounted applications exhausting relatively clean air.Fan wheels are centrifugal, backward inclined, and constructed of aluminum.
Options & Accessories:UL/cUL 705 Listed - "Power Ventilators"Switch, NEMA-1, Toggle, Junction Box Mounted & WiredHigh Wind Rated (+/- 150 PSF Rating)Florida Product Approval #FL13225.1 & Miami-Dade NOA #13-0220.08Texas Department of Insurance Product Evaluation RV-73Roof Curb-Galv., GPF-17-G18, Under Sized 1 in. TotalDamper, WD-100-PB-10X10, Gravity Operated (Loose), Not CoatedSolid State Speed Control, 5 Amp (PN 385031) Shipped LooseUnit Warranty: 1 Yr (Standard)
- Model WD-100 is a horizontal mount exhaust damper (air flow up) and is constructed of 18 ga galvanized steel with pre-punched mounting holes - Damper blades are 0.025 in. roll formed aluminum with vinyl seals on the closing edge, and springassisted for ease of opening - Steel axles are 0.188 in. diameter zinc plated mounted in acetal bushings - Synthetic axlebearings
Notes: All dimensions shown are in units of in.Width And height furnished approximately 0.125 in. undersize
Standard Construction Features:- Roof Curb fits between the building roof and the fan mounted directly to the roof support structure - Constructed of either 18ga galvanized steel or 0.064 in. aluminum - Straight Sided without a cant - 5 in. mounting flange - 1 in. thick 3 lb densityinsulation - Height - Available from 8 in. to 42 in. as specified in 0.5 in. increments.
Notes:- The maximum roof opening dimension should not be greater than the "Actual" top outside dimension minus 2 in..- The minimum roof opening dimension should be at least 2.5 in. more than the damper dimension or recommended duct size.- The Roof Opening Dimension may NOT be the Structural Opening Dimension.- Damper Tray is optional and must be specified. Tray size is same as damper size.- Security bars are optional and must be specified. Frames and gridwork are all 10 ga steel. Gridwork is welded to the frameand the frame is welded to the curb. To prevent corrosion, they are coated with Greenheck’s high performance Permatectorcoating.
Reference assembly view drawings for actualdimensions with mounted accessories
*Overall height may be greater depending on motor
*
19
24.38
4.38
23.75
1.75
Model: GB-101-4Belt Drive Centrifugal Roof Exhaust Fan
DimensionalQuantity 1
Weight w/o Acc's (lb) 60
Weight w/ Acc's (lb) 102
Max T Motor Frame Size 56
Optional Damper (in.) 12 x 12
Roof Opening (in.) 14.5 x 14.5
PerformanceRequested Volume (CFM) 500
Actual Volume (CFM) 500
External SP (in. wg) 0.25
Total SP (in. wg) 0.25
Fan RPM 877
Operating Power (hp) 0.06
Elevation (ft) 105
Airstream Temp.(F) 70
Air Density (ft3) 0.075
Drive Loss (%) 37.4
Tip Speed (ft/min) 2,556
Static Eff. (%) 51
MotorMotor Mounted Yes
Size (hp) 1/4
V/C/P 115/60/1
Enclosure EXP
Motor RPM 1725
Windings 1
NEC FLA* (Amps) 5.8
Notes:All dimensions shown are in units of in.*FLA - based on tables 150 or 148 of National ElectricalCode 2002. Actual motor FLA may vary, for sizing thermaloverload, consult factory.LwA - A weighted sound power level, based on ANSI S1.4dBA - A weighted sound pressure level, based on 11.5 dBattenuation per Octave band at 5 ft - dBA levels are notlicensed by AMCA InternationalSones - calculated using AMCA 301 at 5 ft
- Model WD-100 is a horizontal mount exhaust damper (air flow up) and is constructed of 18 ga galvanized steel with pre-punched mounting holes - Damper blades are 0.025 in. roll formed aluminum with vinyl seals on the closing edge, and springassisted for ease of opening - Steel axles are 0.188 in. diameter zinc plated mounted in acetal bushings - Synthetic axlebearings
Notes: All dimensions shown are in units of in.Width And height furnished approximately 0.125 in. undersize
Standard Construction Features:- Roof Curb fits between the building roof and the fan mounted directly to the roof support structure - Constructed of either 18ga galvanized steel or 0.064 in. aluminum - Straight Sided without a cant - 5 in. mounting flange - 1 in. thick 3 lb densityinsulation - Height - Available from 8 in. to 42 in. as specified in 0.5 in. increments.
Notes:- The maximum roof opening dimension should not be greater than the "Actual" top outside dimension minus 2 in..- The minimum roof opening dimension should be at least 2.5 in. more than the damper dimension or recommended duct size.- The Roof Opening Dimension may NOT be the Structural Opening Dimension.- Damper Tray is optional and must be specified. Tray size is same as damper size.- Security bars are optional and must be specified. Frames and gridwork are all 10 ga steel. Gridwork is welded to the frameand the frame is welded to the curb. To prevent corrosion, they are coated with Greenheck’s high performance Permatectorcoating.
Reference assembly view drawings for actualdimensions with mounted accessories
*Overall height may be greater depending on motor
*
19
24.38
4.38
23.75
1.75
Model: G-123-ADirect Drive Centrifugal Roof Exhaust Fan
DimensionalQuantity 1
Weight w/o Acc's (lb) 57
Weight w/ Acc's (lb) 98
Max T Motor Frame Size 56
Optional Damper (in.) 12 x 12
Roof Opening (in.) 14.5 x 14.5
PerformanceRequested Volume (CFM) 1,050
Actual Volume (CFM) 1,050
External SP (in. wg) 0.85
Total SP (in. wg) 0.85
Fan RPM 1364
Operating Power (hp) 0.24
Elevation (ft) 105
Airstream Temp.(F) 70
Air Density (ft3) 0.075
Tip Speed (ft/min) 4,666
Static Eff. (%) 58
MotorMotor Mounted Yes
Size (hp) 1/2
V/C/P 115/60/1
Enclosure ODP
Motor RPM 1725
Windings 1
NEC FLA* (Amps) 9.8
Notes:All dimensions shown are in units of in.*FLA - based on tables 150 or 148 of National ElectricalCode 2002. Actual motor FLA may vary, for sizing thermaloverload, consult factory.LwA - A weighted sound power level, based on ANSI S1.4dBA - A weighted sound pressure level, based on 11.5 dBattenuation per Octave band at 5 ft - dBA levels are notlicensed by AMCA InternationalSones - calculated using AMCA 301 at 5 ft
Model: G-123-ADirect Drive Centrifugal Roof Exhaust FanStandard Construction Features:Model G Centrifugal Roof Exhaust Fans are direct drive. These fans arespecifically designed for roof mounted applications exhausting relatively clean air.Fan wheels are centrifugal, backward inclined, and constructed of aluminum.
Options & Accessories:PSC MotorUL/cUL 705 Listed - "Power Ventilators"Switch, NEMA-1, Toggle, Junction Box Mounted & WiredHigh Wind Rated (+/- 150 PSF Rating)Florida Product Approval #FL13225.1 & Miami-Dade NOA #13-0220.08Texas Department of Insurance Product Evaluation RV-73Roof Curb-Galv., GPF-19-G18, Under Sized 1 in. TotalDamper, WD-100-PB-12X12, Gravity Operated (Loose), Not CoatedSolid State Speed Control, 10 Amp (PN 385205) Shipped LooseUnit Warranty: 1 Yr (Standard)
- Model WD-100 is a horizontal mount exhaust damper (air flow up) and is constructed of 18 ga galvanized steel with pre-punched mounting holes - Damper blades are 0.025 in. roll formed aluminum with vinyl seals on the closing edge, and springassisted for ease of opening - Steel axles are 0.188 in. diameter zinc plated mounted in acetal bushings - Synthetic axlebearings
Notes: All dimensions shown are in units of in.Width And height furnished approximately 0.125 in. undersize
Standard Construction Features:- Roof Curb fits between the building roof and the fan mounted directly to the roof support structure - Constructed of either 18ga galvanized steel or 0.064 in. aluminum - Straight Sided without a cant - 5 in. mounting flange - 1 in. thick 3 lb densityinsulation - Height - Available from 8 in. to 42 in. as specified in 0.5 in. increments.
Notes:- The maximum roof opening dimension should not be greater than the "Actual" top outside dimension minus 2 in..- The minimum roof opening dimension should be at least 2.5 in. more than the damper dimension or recommended duct size.- The Roof Opening Dimension may NOT be the Structural Opening Dimension.- Damper Tray is optional and must be specified. Tray size is same as damper size.- Security bars are optional and must be specified. Frames and gridwork are all 10 ga steel. Gridwork is welded to the frameand the frame is welded to the curb. To prevent corrosion, they are coated with Greenheck’s high performance Permatectorcoating.
Reference assembly view drawings for actualdimensions with mounted accessories
*Overall height may be greater depending on motor
*
19
24.38
4.38
23.75
1.75
Model: G-123-ADirect Drive Centrifugal Roof Exhaust Fan
DimensionalQuantity 1
Weight w/o Acc's (lb) 57
Weight w/ Acc's (lb) 98
Max T Motor Frame Size 56
Optional Damper (in.) 12 x 12
Roof Opening (in.) 14.5 x 14.5
PerformanceRequested Volume (CFM) 1,050
Actual Volume (CFM) 1,050
External SP (in. wg) 0.85
Total SP (in. wg) 0.85
Fan RPM 1364
Operating Power (hp) 0.24
Elevation (ft) 105
Airstream Temp.(F) 70
Air Density (ft3) 0.075
Tip Speed (ft/min) 4,666
Static Eff. (%) 58
MotorMotor Mounted Yes
Size (hp) 1/2
V/C/P 115/60/1
Enclosure ODP
Motor RPM 1725
Windings 1
NEC FLA* (Amps) 9.8
Notes:All dimensions shown are in units of in.*FLA - based on tables 150 or 148 of National ElectricalCode 2002. Actual motor FLA may vary, for sizing thermaloverload, consult factory.LwA - A weighted sound power level, based on ANSI S1.4dBA - A weighted sound pressure level, based on 11.5 dBattenuation per Octave band at 5 ft - dBA levels are notlicensed by AMCA InternationalSones - calculated using AMCA 301 at 5 ft
Model: G-123-ADirect Drive Centrifugal Roof Exhaust FanStandard Construction Features:Model G Centrifugal Roof Exhaust Fans are direct drive. These fans arespecifically designed for roof mounted applications exhausting relatively clean air.Fan wheels are centrifugal, backward inclined, and constructed of aluminum.
Options & Accessories:PSC MotorUL/cUL 705 Listed - "Power Ventilators"Switch, NEMA-1, Toggle, Junction Box Mounted & WiredHigh Wind Rated (+/- 150 PSF Rating)Florida Product Approval #FL13225.1 & Miami-Dade NOA #13-0220.08Texas Department of Insurance Product Evaluation RV-73Roof Curb-Galv., GPF-19-G18, Under Sized 1 in. TotalDamper, WD-100-PB-12X12, Gravity Operated (Loose), Not CoatedSolid State Speed Control, 10 Amp (PN 385205) Shipped LooseUnit Warranty: 1 Yr (Standard)
- Model WD-100 is a horizontal mount exhaust damper (air flow up) and is constructed of 18 ga galvanized steel with pre-punched mounting holes - Damper blades are 0.025 in. roll formed aluminum with vinyl seals on the closing edge, and springassisted for ease of opening - Steel axles are 0.188 in. diameter zinc plated mounted in acetal bushings - Synthetic axlebearings
Notes: All dimensions shown are in units of in.Width And height furnished approximately 0.125 in. undersize
Standard Construction Features:- Roof Curb fits between the building roof and the fan mounted directly to the roof support structure - Constructed of either 18ga galvanized steel or 0.064 in. aluminum - Straight Sided without a cant - 5 in. mounting flange - 1 in. thick 3 lb densityinsulation - Height - Available from 8 in. to 42 in. as specified in 0.5 in. increments.
Notes:- The maximum roof opening dimension should not be greater than the "Actual" top outside dimension minus 2 in..- The minimum roof opening dimension should be at least 2.5 in. more than the damper dimension or recommended duct size.- The Roof Opening Dimension may NOT be the Structural Opening Dimension.- Damper Tray is optional and must be specified. Tray size is same as damper size.- Security bars are optional and must be specified. Frames and gridwork are all 10 ga steel. Gridwork is welded to the frameand the frame is welded to the curb. To prevent corrosion, they are coated with Greenheck’s high performance Permatectorcoating.
Notes:All dimensions shown are in units of in.*FLA - based on tables 150 or 148 of National ElectricalCode 2002. Actual motor FLA may vary, for sizing thermaloverload, consult factory.LwA - A weighted sound power level, based on ANSI S1.4dBA - A weighted sound pressure level, based on 11.5 dBattenuation per Octave band at 5 ft - dBA levels are notlicensed by AMCA InternationalSones - calculated using AMCA 301 at 5 ft
Standard Construction Features:- Roof Curb fits between the building roof and the fan mounted directly to the roof support structure - Constructed of either 18ga galvanized steel or 0.064 in. aluminum - Straight Sided without a cant - 5 in. mounting flange - 1 in. thick 3 lb densityinsulation - Height - Available from 8 in. to 42 in. as specified in 0.5 in. increments.
Notes:- The maximum roof opening dimension should not be greater than the "Actual" top outside dimension minus 2 in..- The minimum roof opening dimension should be at least 2.5 in. more than the damper dimension or recommended duct size.- The Roof Opening Dimension may NOT be the Structural Opening Dimension.- Damper Tray is optional and must be specified. Tray size is same as damper size.- Security bars are optional and must be specified. Frames and gridwork are all 10 ga steel. Gridwork is welded to the frameand the frame is welded to the curb. To prevent corrosion, they are coated with Greenheck’s high performance Permatectorcoating.
Notes:All dimensions shown are in units of in.*FLA - based on tables 150 or 148 of National ElectricalCode 2002. Actual motor FLA may vary, for sizing thermaloverload, consult factory.LwA - A weighted sound power level, based on ANSI S1.4dBA - A weighted sound pressure level, based on 11.5 dBattenuation per Octave band at 5 ft - dBA levels are notlicensed by AMCA InternationalSones - calculated using AMCA 301 at 5 ft
Standard Construction Features:- Roof Curb fits between the building roof and the fan mounted directly to the roof support structure - Constructed of either 18ga galvanized steel or 0.064 in. aluminum - Straight Sided without a cant - 5 in. mounting flange - 1 in. thick 3 lb densityinsulation - Height - Available from 8 in. to 42 in. as specified in 0.5 in. increments.
Notes:- The maximum roof opening dimension should not be greater than the "Actual" top outside dimension minus 2 in..- The minimum roof opening dimension should be at least 2.5 in. more than the damper dimension or recommended duct size.- The Roof Opening Dimension may NOT be the Structural Opening Dimension.- Damper Tray is optional and must be specified. Tray size is same as damper size.- Security bars are optional and must be specified. Frames and gridwork are all 10 ga steel. Gridwork is welded to the frameand the frame is welded to the curb. To prevent corrosion, they are coated with Greenheck’s high performance Permatectorcoating.
FGRHooded Gravity ReliefSTANDARD CONSTRUCTION FEATURES• Precision formed locked rib construction. • Available in aluminum orgalvanized steel construction. • 0.5 in. galvanized steel mesh birdscreens. •Heavy gauge galvanized steel support members. • Hood can be removedcompletely from the base or hinged open.• Units with a throat size exceeding 60 in. x 120 in. will have 12 in. galvanizedbases as standard.• Recommended roof opening dimension is at least 2.5 in. larger than thedamper size.
STANDARD CONSTRUCTION FEATURES• Welded Aluminum (0.064 in.) or galvanized (18 ga) construction •Straight sided • 5 in. roof mounting / flashing flange • 1 in. 3 lb densityinsulationRoof Opening - The Maximum roof opening dimension should not begreater than the "Actual" top outside dimension minus 2 in.. With dampers,the Minimum roof opening dim. should be at least 2.5 in. more than thedamper dim.NOTES:* The Roof Opening Dim. may NOT be the Structural Opening Dim.* Tray - Damper Tray is optional and must be specified. Tray size is sameas damper size.* Height - Available from 8 in. to 42 in. as specified in 0.5 in. increments.* Security Bars are optional & must be specified. Frames & gridwork are all10 ga steel. Gridwork is welded to the frame & the frame is welded to thecurb. To prevent corrosion, they are coated w/Greenheck's high...
NOTES: All dimensions shown are in units of inches
Mark Qty. CapW x L
ActualW x L
FlangeW x L
Height Damper TrayW x L
FGR - 1 1 34 x 34 33 x 33 43 x 43 18FGR - 2 1 30 x 30 29 x 29 39 x 39 18
Limits of Use Approved for use in HVHZ: Yes Approved for use outside HVHZ: Yes Impact Resistant: Yes Design Pressure: +150/-150 Other: Not to be used within the ridge area
Installation Instructions FL13225_R3_II_13-0220.08 Spun Alum 150psf.pdf Verified By: Miami-Dade BCCO - EVL Created by Independent Third Party: Evaluation Reports FL13225_R3_AE_13-0220.08 Spun Alum 150psf.pdf
13225.2 Steel Rooftop Supply Fans Model RSF
Limits of Use Approved for use in HVHZ: Yes Approved for use outside HVHZ: Yes Impact Resistant: Yes Design Pressure: +100/-100 Other: Not to be used within the ridge area
Installation Instructions FL13225_R3_II_RSF NOA.pdf Verified By: Miami-Dade BCCO - EVL Created by Independent Third Party: Evaluation Reports FL13225_R3_AE_RSF NOA.pdf
Back Next
Contact Us :: 1940 North Monroe Street, Tallahassee FL 32399 Phone: 850-487-1824
The State of Florida is an AA/EEO employer. Copyright 2007-2013 State of Florida. :: Privacy Statement :: Accessibility Statement :: Refund Statement
Under Florida law, email addresses are public records. If you do not want your e-mail address released in response to a public-records request, do not send electronicmail to this entity. Instead, contact the office by phone or by traditional mail. If you have any questions, please contact 850.487.1395. *Pursuant to Section
455.275(1), Florida Statutes, effective October 1, 2012, licensees licensed under Chapter 455, F.S. must provide the Department with an email address if they haveone. The emails provided may be used for official communication with the licensee. However email addresses are public record. If you do not wish to supply a personaladdress, please provide the Department with an email address which can be made available to the public. To determine if you are a licensee under Chapter 455, F.S.,