Page 1
©2016NetworkThermostat 240229-00
OccupancySensorHVACControl
1. Installthermostatbackplateandconnecttonetworkperthermostatinstallationinstructions
2. Pull4-conductorcable(orCAT5)fromthermostattooccupancysensorlocationandwireaccordingtothediagramsbelow.
a. SingleOccupancySensorConnectedtoThermostat
b. MultipleOccupancySensorsConnectedtoThermostat
Inadaisychainfashion,connectall24Vtogetherandthenall24Ctogetherasshown.Daisy-chainfromCLK2toCOMonthefirstsensor,thenNCtotheCOMofthesecondsensor,etc.Onthelastsensorinthechain,connecttheNCtoCLK1usingthefourthconductorbyconnectingeachsegmentwithawirenutasshownabove.*NOTE:Itmayberequiredtoaddaseparate(orlarger)24vactransformertopowermorethanoneoccupancysensor.Ifso,thermostatsandoccupancysensorsmusthavethesame24VAC/24V(c)polarityonallunits.75VAtransformerrecommended.
Page 2
©2016NetworkThermostat 240229-00
c. EnsurebothjumpersareatpositionAandperformWalkByTestperoccupancysensorinstallation
instructions
NT-OSCCeilingMountSensorWalkByTestJumperSettings
NT-OSWWallMountSensorWalkByTestJumperSettings
3. UpdateOccupancySensorandthermostatforHVACcontrol
a. RecommendsetthermostatOverrideTimerto10minutes,orlonger.OverrideTimermustNOTbe0:00.(inconfigurationpage)
Page 3
©2016NetworkThermostat 240229-00
4. UpdateOccupancySensorjumpersettingsforHVACcontrol
a. SetVerify(ON)(OccupancyDetection)tojumpersettingE(5minutes)
b. SetMinimumOccupied(OFF)(HVACRunTime)tojumpersettingsE(20minutes)orF(30minutes).
ThermostatoverridewillcontinuefordurationofMinOcc(OFF)time.
NOTES:WhenchangingOccupancySensorjumpersettings,recycleOccupancySensorpowerbyremovingandreattachingthethermostatfaceplate
5. Securecoveronoccupancysensor
6. SetdipswitchesonbackofthethermostatfaceplatetoturnoffAdaptiveRecovery(#2ON)ifdesired(but
notrequired)andengagetheLockout(#4ON)(required).
7. Placethermostatfaceplateonthermostatbackplate
8. SetOccupied&Unoccupiedschedulea. SetOccupiedscheduleto30minutesbeforeanticipatedoccupiedtime(orHVACruntimesothat
thespaceisatthedesiredoccupiedsetpoint).
b. SetanUnoccupiedscheduleto30minutesafteranticipatedoccupiedtime.UsesetbacksetpointsthatareeasyfortheHVACunittoobtainthedesiredoccupiedsetpointsduringnormaloccupiedhours.
OccupancyControlDipswitchSettings
Page 4
©2016NetworkThermostat 240229-00
c. Seta2ndUnoccupiedscheduleto30minutesafternormaloccupiedhours.Usesetpointsthatwillmaximizeenergysavingsduringunoccupiedhours.
Summary:TheprecedinginstructionsconfiguredtheHVACequipmentforoccupancysensorcontrol.Thisscenarioassumesaclassroomsettingwithastarttimeof8:15.Theteacherarrivesat8amsopreconditioningbegins30minutespriorat7:30am.Iftheroomremainsunoccupied,theschedulesetstheHVACto“light”setback(unoccupied)modeat8:30am.Attheendoftheday,thethermostatwillsettheHVACintoa“heavy”setback(unoccupied)modeat5:30pm.
1. TheareawillbepreconditionedtotheOccupiedSetPoints(cool=74oF,Heat=68oF)beginning30minutespriortoanticipatedroomoccupancyof8am.
2. Ifnooccupancyisdetectedduringnormaloccupiedhours,theschedulewillsettheHVACequipmentintoUnoccupied(orlightsetback)mode(cool=78oF,heat=65oF)30minutesafteranticipatedroomoccupancyof8am.UsealightsetbacksuchthattheHVACunitcaneasilyreachdesiredoccupiedsetpointsduringnormallyoccupiedhours.
3. Ifnooccupancyisdetectedduringnormalunoccupiedhours,theschedulewillsettheHVACequipmentintoUnoccupied(orheavysetback)mode(cool=85oF,heat=60oF)30minutesafteranticipatedroomoccupancyof5pm.Useaheavysetbacktomaximizeenergysavingsduringnormallyunoccupiedhours.
4. Ifoccupancyisdetectedatanytime,theHVACequipmentwillcontinueconditioningtheareainOverrideusingthatlastrunOccupiedsetpointsforthedurationofroomoccupancy.
5. TheOverride(Occupied)modewillcontinueforamaximumof20minutesaftertheroomisvacated.
Page 5
©2016NetworkThermostat 240229-00
6. IfthethermostatisinUnoccupiedMode,aminimumof6minutes(intheexample)ofcontinuousoccupiedtimeisnecessarybeforetheoccupancysensorwillplacethethermostatbackintoOverride(Occupied)Mode.
Notes:a. TheOccupancysensorwilltriggeranOverride(HVACconditionstoOccupiedsetpoints)whenthe
integratedoccupancysensorrelayOPENS.AnOverridewillconditionthespacetothelastrunoccupiedsetpoints.
b. ThethermostatmustrecognizethatanOccupancySensorisconnectedtotheCLK1&CLK2terminalsbydetectingashortbetweenCLK1&CLK2(i.e.theOccupancysensormustNOTdetectoccupancyatleastonetimewiththethermostatfaceplateONbeforethethermostatrecognizesthattheoccupancysensorisconnected).
c. Verify(ON)(occupancydetection)hasabuiltindelayof1minute.Thus,ifVerify(ON)issetto5
minutes,theOccupancySensorwillactivateanOverrideafter6minutesofcontinuousoccupiedtime.
d. Ifatimedelayrelayisbeingusedasadoorcontactorinconjunctionwiththeoccupancysensor,
ensurethattherelayisnormallyOPENwhenthedoorisclosed.