This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
ANSI/ACCA 12 QH ‐2014 Sec 3 and 4 replace RESNET Chapter 8 Section 807 and 808
Protocol Differences
• RESNET ‐ CO measurement
Added joints (in vent piping) as location for detection
Action levels for ambient CO > 9 and > 25 ppm
Direct vent tested under worst case Photo credit: Keith Williams
Protocol Similarities
No “natural” conditions testing
No draft measurements
No CAZ depressurization limits
• RESNET / BPI – Worst case and spillage
2/24/2016
4
Protocol Similarities
Sample after 5 minutes
CO Air free (as applicable)
Includes “vent free” and/or “gas log” appliances
• RESNET / BPI – CO measurements
CO Thresholds• ANSI “confluence”
Worst Case Testing Procedures and Potential Impacts
• Pre‐testing
• Baseline configuration
• Fans on
• Air handler impact
• Door position
2/24/2016
5
Pre‐Testing
• BPISample ambient air for CO (and combustible gases) upon entry and throughout the house
Inspect gas piping /fuel delivery systems for deficiencies/leakage
Inspect Combustion Appliance Zone (CAZ) and combustion appliances (including solid fuel appliances)
10% LEL
• BPIHouse in “Blower Door” testing mode except:
CAZ door(s) closed“Supplied air only” interior doors closed
Measure and record pressure in CAZ with respect to (WRT) outside*
Exhaust Fans On
Highest fan settingCheck/clean dryer filter/ext. ventDo not operate whole house cooling fan
• Measure and record CAZ pressure WRT outside (CAZ door remains closed)
2/24/2016
6
Air Handler On
If CAZ more negative WRT outsideBlower to remain on for spillage and CO test
If CAZ more positive WRT outsideBlower to be turned off for spillage and CO test
• Measure and record pressure in CAZ WRT outside (CAZ door remains closed)
Door Position
• Open interior door(s) directly leading to the CAZ
• Measure and record pressure in CAZ WRT outside
If CAZ more negative (WRT outside), after the door(s) are open, door(s) to remain open during spillage and CO test
Pre‐Testing
• RESNETTesting disclosure (for occupants with environmental sensitivities)
Operate CO detector continuously in CAZ during CO and depressurization testing
Check for combustible gases upon entry
2/24/2016
7
• RESNETClose all exterior windows, doors, attic hatches
Drain traps must be filled
Turn on all indoor (exhaust) fansIncluding powered attic ventilation fanExcluding whole house exhaust fan
NOT REQUIRED!
Air Handler On
If CAZ more negative WRT outsideLeave blower on
If CAZ more positive WRT outsideTurn blower off
• RESNET
Door Position
Interior door to CAZRooms with exhaust fansOther interior rooms
… to achieve the highest pressure differential in the CAZ WRT the outdoors
• RESNET (open or close):
Don’t Use Smoke
2/24/2016
8
ANSI/ACCA Worst Case Testing Procedures
• RESNETEnsure the vent is at room temperature
Fireplace damper closed OR a simulator must be operating in the fireplace with damper open
Check for spillage after 5 minutes of operation
Proper Vent DesignVisual Inspection
Appropriate vent materials
Pitch ¼” rise per 1’ run
6” to 8” initial rise
Photo credit: Keith Williams
Proper Vent Design
Vent connector length
Chimney height
Photo courtesy Cory Chovanec WECC
Photo courtesy Cory Chovanec WECC
Photo credit: Keith Williams
2/24/2016
9
Vent Inspection
Signs of corrosion
(Unusually) small or large vent connectors
Vent InspectionCommonly vented
Vent order: Small above larger appliance
Increased vent diameter after 2nd appliance
Photo courtesy of PA Weatherization Training Center Photo courtesy Cory Chovanec WECC
CAZ Inspection
• Excessive depressurization?
Photo credit: Keith Williams
2/24/2016
10
BPI Requirements• If CO measurements exceed threshold limits:
Advise occupant that appliance(s) should be serviced immediately
• If appliance(s) fail spillage, address causeAir handler onCAZ door closedFans on
• If both, recommend appliance(s) be shut down
RESNET Requirements
• If CO measurements exceed threshold limits: Notify client of need to call qualified technician and;Document appliance is unsafe for use; andDocument client was informed of this condition
• Shall not perform air sealing (or any other tasks*) onhome (until address)
RESNET Requirements
• If appliance(s) fail spillage remediation must be in work scope via:
Combustion Safety Testing:What we learn from Standards and
Research
Better Buildings Better Business ConferenceMarch 2016
2/29/2016
1
Combustion Products Spillage from
Gas Water HeatersMonitoring Results
Dan CautleySeventhwave
B4 Wisconsin Dells, March 4, 2016
What’s this “Spillage”?
2
Why Building America interest?
• Prior work suggesting spillage in normal operation isn’t well predicted by current testing methods• Building America Hazard Test Methods Cautley• LBNL Combustion Appliance Venting Rapp
• Prior work suggesting venting problems are responsible for much spillage under normal operation• CEE Ventilation Depressurization Bohac & Cheple
3
2/29/2016
2
Building America project objective
4
Can we develop a simplified test procedure that: • Is easier to perform & more repeatable• Reduces “failures” for acceptable situations• Still finds hazardous situations
Source: Larry Brand, GTI
Simplified Test Conditions
5
Test ProcedureComprehensive BPI 2015 Simplified
Dryer & Kitchen On On OnNext Largest Exhaust Fan On On On
Other Exhaust Fans On On Off
CAZ Door Check Check ClosedOther Doors Check Open= exhaust
fan or return register in room
Open= exhaust fan or return
register in room
Air Handler Check Check Check
Check= which ever produces lowest CAZ pressure
Source: CEE
Simplified and BPI Test Methods
• Maximum spillage duration• Water heaters & warm vent furnace/boiler = 2
minutes• Cold vent furnace/boiler = 5 minutes
• Draft pressure not used for pass/fail
• CAZ depressurization not used for pass/fail
6
Source: CEE
2/29/2016
3
Our Field Study• 11 homes, MN and WI• Atmospheric draft natural gas water heaters in
basements• FAILED simplified spillage test,
PASSED with one fan less depressurization• Depressurization very similar compared to WCD
• Monitored operation, spillage, driving forces• Collected data for 3 to 6+ months, 1500 days
total
7
Monitoring setupCO2 near vent used to identify spillage
8
Basic factors affecting spillage
• Minutes into burner cycle (spillage more likely at start)
• Outdoor temperature (spillage more likely in warm weather)
• Depressurization• Venting configuration
Two of these factors were dominant in our field study results
9
2/29/2016
4
Spillage by minute of operation, by site
10
What caused this?
Two sites showed excessive spilling;both had venting defects
11
• MN_04 had an undersized water heater vent (vent capacity = 75% of burner input)
• WI_01 had a large opening downstream of the water heater (unused, partially repaired connection for a furnace)
3” vent, 6’ run, 4 elbows
Water heater and unused furnace vent
Images courtesy CEE
Effect of first minute of operation and outdoor temperature
• BPI-1200-S is almost identical to our Simplified Test Procedure
• Current test methods are probably conservative, tend to fail systems that generally operate safely
• Typical systems as monitored don’t spill excessively
• Vent defects are an important cause, perhaps the largest cause, of excessive spillage. Vent inspection is critically important in evaluating safe operation.
17
Conclusions, cont’d
• Downdraft formation remains somewhat mysterious, is not addressed in current testing, and needs more work
• Carbon monoxide is a serious risk, identifying high levels is a priority
• Carbon monoxide alarms can offer protection in the case of:• Future CO production from a burner problem or
replacement water heater• Future venting problems, e.g. a collapsed chimney• Other sources of CO, e.g. a generator set used