7/27/2019 NY_Sem_85_2008 http://slidepdf.com/reader/full/nysem852008 1/17 1 Stanley A. Mumma, Ph.D., P.E. Professor Emeritus Penn State University, @ Univ. Park, PA [email protected]Web: http://doas-radiant.psu.edu DOAS Supply Air Conditions: Dew Point & Dry Bulb ASHRAE Annual Meeting New York, NY. Sem. 85 January, 2008 2 DOAS Objective Meet the ventilation requirements of ASHRAE Std. 62.1. Decouple the sensible and latent loads: – By reducing the OA DPT to that of the design space DPT, i.e. 55F, thus eliminating the entire OA latent load. – By reducing the OA DPT even lower so that the DOAS air can also handle all of the space latent load. This would result in all terminal cooling equipment operating with dry surfaces.
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
DOAS Objective Meet the ventilation requirements of
ASHRAE Std. 62.1.
Decouple the sensible and latent loads:– By reducing the OA DPT to that of the
design space DPT, i.e. 55F, thus eliminatingthe entire OA latent load.
– By reducing the OA DPT even lower so
that the DOAS air can also handle all of thespace latent load. This would result in allterminal cooling equipment operating withdry surfaces.
7/27/2019 NY_Sem_85_2008
http://slidepdf.com/reader/full/nysem852008 2/17
3
DOAS Defined for this
presentation20-70%
less OA,
than VAVDOAS Unit
W/ Energy
Recovery
Cool/Dry
Supply
Parallel
Sensible
Cooling System
High
Induction
Diffuser
Building
With
Sensible
and Latentcooling
decoupled
4
Key DOAS points:1. 100% OA delivered to each zone via its
own ductwork.
2. Flow rate generally as spec. by Std. 62.1-2007 or greater (LEED, Lat. Ctl)
3. Employ TER, per Std. 90.1-2004.
4. Generally CV.
5. Use to decouple space S/L loads—Dry.
6. Rarely supply at a neutral temperature.
7. Use HID, particularly where parallel sysdoes not use air.
7/27/2019 NY_Sem_85_2008
http://slidepdf.com/reader/full/nysem852008 3/17
5
Fan Coil UnitsFan Coil Units
Air Handling Units
CV or VAV
Air Handling Units
CV or VAV
Unitary ACs
i.e. WSHP’s
Unitary ACs
i.e. WSHP’s
Parallel Terminal Systems
Radiant Cooling PanelsRadiant Cooling Panels
Chilled Beams
DOAS air
Induction Nozzle
Sen Cooling Coil
Room air
VRV
Multi-Splits
VRV
Multi-Splits
6
DPT requirements for parallel equipment:a condensation and septic issue
For equipment with condensate pans, such asfan coil units, the SA DPT is not critical forcondensation control, and can be around 55F,thus eliminating most humidity problems.However there is still the likelyhood thatseptic amplifier problems will occur.
For equipment without condensate pans,such as chilled ceilings, the DPT conditionsare very important to avoid condensationformation and related issues.
7/27/2019 NY_Sem_85_2008
http://slidepdf.com/reader/full/nysem852008 4/17
7
The Simple Latent Load Equation for selecting the required SA DPT
QL=0.68*scfm*(WRoom-Wsupply).
QL. Btu/hr. The latent load is afunction of the envelope transfer,occupant generation, and internalgeneration—plants, coffee pots etc.
Scfm, the DOAS SA flow rate in stand.ft3/min. per ASHRAE Std. 62.1.
– Can be increased by 30% for a LEED point– No need to apply the 62.1 multiple spaces
complications, and always less than for all-air systems—often up to 70% less.
8
The Simple Latent Load Equation for selecting the required SA DPT
QL=0.68*scfm*(WRoom-Wsupply).
WRoom, the room humidity ratio ingr/lbmDA. If the room is at 75F and 50%RH, the room humidity ratio is 64.9gr/lbmDA.
Wsupply, the required supply air DPT,gr/lbmDA, or the unknown in this effortto determine the required SA DPT.
7/27/2019 NY_Sem_85_2008
http://slidepdf.com/reader/full/nysem852008 5/17
9
A simple example: for a single space
Assumptions:– Room occupancy, 20 people
– Occupant latent generation, 205 Btu/hr
– Additional latent transfer and generation, 400Btu/hr. Need to keep the buildingpressurized to minimize the transfercomponent.
– Std. 62.1 ventilation required, i.e. the DOASSA flow rate, 400 scfm.
– Design room humidity ratio, 64.9 gr/lbmDA
10
Solving for WSupply
20*205+400=0.68*400*(64.9- WSupply).
WSupply=48.4 gr/lbmDA, or a DPT of 47.3F
Psychrometric process of DOAS SA
35 40 45 50 55 60 65 70 75 80
DBT, F
20
30
40
50
60
70
80
90
100
110
120
130
140
W , g r / l b m D A
A simple example: for a single space
Qsen=12,000 Btu/hr Qlat=4,500 Btu/hr
7/27/2019 NY_Sem_85_2008
http://slidepdf.com/reader/full/nysem852008 6/17
11
Solving for WSupply
20*205+400=0.68*400*(64.9- WSupply).
WSupply=48.4 gr/lbmDA, or a DPT of 47.3F
A simple example: for a single space
12
If over ventilated by 30% for a LEED point, i.e. SA = 520 scfm
Solving for WSupply
20*205+400=0.68*520*(64.9- WSupply).
WSupply=52.2 gr/lbmDA, or a DPT of 49.3F
In each case the SA DBT is lower than theconventional 50-55F.
7/27/2019 NY_Sem_85_2008
http://slidepdf.com/reader/full/nysem852008 7/17
13
Cooling capacity vs. room DPT
12
14
16
18
20
22
24
26
28
30
32
52 53 54 55 56 57 58 59 60 61 62
Room DPT, F
F l u x ,
B t u / h r - f t 2
Panel A
Panel B
Impact of DPT selection on a chilled ceiling’s capacity.
14
DOAS equipment on the market today I: Cooling equipment. that adds sensible
energy recovery or hot gas for centralreheat.
II: Cooling equipment that uses totalenergy recovery, with or without reheat.
III: Cooling equipment that uses totalenergy recovery and passive
dehumidification wheels IV: Cooling equipment that uses active
dehumidification wheels, generallywithout energy recovery.
7/27/2019 NY_Sem_85_2008
http://slidepdf.com/reader/full/nysem852008 8/17
15
DOAS equipment on the market
16
40 50 60 70 80 90
DBT, F
20
40
60
80
100
120
140
160
H u m
i d i t y R a t i o , g r / l b m
Conditioning 1000 scfm OA from 85F, 148 gr. CC+HGRH
1, OA
2 3, SA
QCC, Total=9.7 Tons
S/TRatio=0.376
Lost Cooling:
Room
QL. Sp=1.26 T
QL, OA=4.82 T
QS, Reheat=2.79 T QS,OA
=
0.9 T
7/27/2019 NY_Sem_85_2008
http://slidepdf.com/reader/full/nysem852008 9/17
17
DOAS equipment on the market
18
40 50 60 70 80 90
DBT, F
20
40
60
80
100
120
140
160
H u m
i d i t y R a t i o , g r / l b m
Conditioning 1000 scfm OA from 85F, 148 gr. EW+CC+HGRH
1, OA
2 3, SA
QCC, Total=5.6 TonsS/TRatio=0.57
43% reduction in OA
load, and a real
improvement in the
S/TRatio
Room
QL. Sp=1.26 T
QS, Reheat=2.79 T
QL, OA=0.96 T
QS=0.2 T
Leaving
EW
7/27/2019 NY_Sem_85_2008
http://slidepdf.com/reader/full/nysem852008 10/17
19
DOAS equipment on the market today
20
Psychrometrics f or EW+CC+SW
45 50 55 60 65 70 75 80 85 90
DBT, F
40
50
60
70
80
90
100
110
120
130
140
150
H u m i d i t y R a t i o , g r / l b m
1
6
7
43
2
5
Conditioning 1000 scfm OA from 85F, 148 gr w/ EW+CC+SW
QCC, Total=4 Tons
SW further reduces the
CC load, but also causes
the SA to have 2 ton less
sen. Cooling capacity
7/27/2019 NY_Sem_85_2008
http://slidepdf.com/reader/full/nysem852008 11/17
21
DOAS equipment on the market today
Desiccant added for 3 reasons:1. 45F CHWS still works
2. achieve DPT < freezing
3. reduce or eliminate reheat
22
EW+CC+PDHC Psychrometrics
45 50 55 60 65 70 75 80 85 90
DBT, F
40
50
60
70
80
90
100
110
120
130
140
150
H u m i d i t y R a t i o , g r / l b m
1
6
7
4
3
2
5
Conditioning 1000 scfm OA from 85F, 148 gr w/ EW+CC+PDHC
QCC, Total=4 Tons
but the SA has lost
1.8 tons of sen
cooling
7/27/2019 NY_Sem_85_2008
http://slidepdf.com/reader/full/nysem852008 12/17
23
DOAS equipment on the market today
24
EW+PDHC+CC Psychrometrics
45 50 55 60 65 70 75 80 85 90
DBT, F
40
50
60
70
80
90
100
110
120
130
140
150
H u m i d i t y R a t i o , g r / l b m
1
6
7
4
3
2
5
Conditioning 1000 scfm OA from 85F, 148 gr w/ EW+PDHC+CC
QCC, Total=5.2 Tons
and a 0.8 ton loss in
sensible cooling
7/27/2019 NY_Sem_85_2008
http://slidepdf.com/reader/full/nysem852008 13/17
25
DOAS equipment on the market today
26
30 40 50 60 70 80 90 100 110
DBT, F
20
30
40
50
60
70
80
90
100
110
120
130
140
150
H u m i d i t y R a t i o , g r / l b m
2
1
3
4
Conditioning 1000 scfm OA from 85F, 148 gr w/ CC+ADesW
QCC, Total=6.8 Tons
and 47 MBtu reactivation heat
input
And add 1.2 ton sensible load
to the terminal equipment
7/27/2019 NY_Sem_85_2008
http://slidepdf.com/reader/full/nysem852008 14/17
27
Selecting the appropriate SA DBT
Based upon the DOAS equipment available,each of which is capable of delivering therequired DPT, there are many options forSAT.
Given that the required DPTs for the simpleexample discussed above were below theordinary SAT of 50-55F, it is often thoughtthat the SA must be warmed, even to aneutral temperature.
It was noted that as the SAT was increased, it
lost some of its ability to do sensible cooling,throwing more load onto the terminalequipment.
28
Things to consider when selecting the SA DBT
The advantages of using SAtemperature equal to the required DPT,i.e. no reheat– It can offset a part of the terminal
equipment’s sensible cooling duty
– First and operating costs associated with
central reheat equipment is eliminated.– Simplifies controls.
– Reduces the total load on the cooling plant
7/27/2019 NY_Sem_85_2008
http://slidepdf.com/reader/full/nysem852008 15/17
29
Things to consider when selecting the SA DBT
The disadvantages of using SAtemperature equal to the required DPT,i.e. no reheat.
– Terminal reheat may be needed at times. It isallowed by Std 90.1 when the flow rate doesnot exceed that required for ventilation. Notall code jurisdictions allow terminal reheat.
» Terminal reheat can be minimized with either
DCV or Critical zone SAT reset. Next speaker willaddress these two options.
30
Things to consider when selecting the SA DBT – Diffuser selection is more critical: dumping
and condensation formation must be avoided.
– UFAD can not be used, since the SAT can’t bebelow about 68F
– If terminal equipment is placed in series(never recommended) the low temperaturescause the terminal equipment to be derated.
Series also requires the fan in the terminalequipment to handle all the air moving in thespace. The next speaker will discuss this indetail.
7/27/2019 NY_Sem_85_2008
http://slidepdf.com/reader/full/nysem852008 16/17
31
Conclusions
Computing the required DOAS SA DPThas been shown to be easy.
The industry has many fine pieces ofequipment to meet the required DPT.
– Some operating at low CC temperatures,which can derate the cooling equipment.
– Some with passive dehumidificationequipment that facilitate low DPT’s with
ordinary CC temperatures.– Some with active desiccant wheels.
– In most cases an EW is highly advised.
32
Conclusions Selecting the SA DBT is a trade off
involving first cost, operating cost, andcomplexity.
Reheat avoidance is most commonconcern when selecting the SA DBT.
– Reheat can be minimized in many ways asdiscussed.