Page 1
Asset: CLEVELAND AF NO. 2 - QUEENS, 18-08 WILLOUGHBY AVENUE, New York, 11385
Inspection Id Inspection Type Time In Last Edited
SA : Q488 Architectural - Senior 2019-11-20 12:35 PM 2019-12-02 2:12 PM
AA : Q488 Architectural - Associate 2019-11-20 12:11 PM 2020-07-22 4:49 PM
Asset Data
Question Answer
Was the building fully accessible for inspection Yes
Principal(s) Information
Principal Name Marc Pascente
Organization Grover Cleveland High School - Queens
Did you meet with this Principal? Yes
Did this Principal provide feedback? Yes
Summary of Principal's Feedback The Principal had no comments regarding the physical condition of theAthletic Field at this time.
Principal Name Annette Beale
Organization The Riverview School - Queens
Did you meet with this Principal? No
Did this Principal provide feedback? No
Custodian John Sullivan
Fireman Greg Bianchi
Building Square Footage 5,000
Comments on the Area 282,000 SF Site Area; 156,500 SF Playing Surfaces
Comments on the Stories (Floors) plus Basements 1 (No Basement)
Comments on the Number of Classrooms 0
Comments on the Year Built 1967
Student Population 1732
Staff Population 2
Weather Fair
Facade Photo
Field House - West View
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 1 of 29
Page 2
Main Entrance Photo
Facade A - Field House
Roof Photo
Roof 1 - Southeast View
Have any Systems/Major Building Components been upgraded? Yes
Systems: Limited Roofing, Flashing and Roof Drain repairs
Year: 2018
Systems: Tennis Courts resurfaced
Year: 2017
Systems: Limited Roofing and Leader/Gutter repairs
Year: 2016
Systems: New Artificial Turf at Soccer Field; new Running TrackSurface
Year: 2015
Systems: Athletic Field restoration project including concreteRetaining Wall rebuilt, limited Artificial Turf repairs, andField House Roofing and Masonry repairs
Year: 2010
Systems: New Roofing, Windows and Exterior Guards
Year: 1984
Have there been any New Building Additions? No
Tandem Schools? No
Leased Space? No
Priority Condition
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 2 of 29
Page 3
PriorityCondition ExistLast Year?
PriorityCategory
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Structural Engineer Required
StructuralCondition Type
ConditionDescription
ComponentAffected
LocationDescription
Person(s)Notified
Person(s) Title PhotoImage
No condition recorded
Accessibility
Accessibility Status Question Response
Is the primary or secondary entrance on an accessible route? Yes
Is the building a multi-story building? No
Do any of the following spaces exist? Classroom, Art Room, Auditorium, Cafeteria,Computer, Gymnasiums, Library, Multipurpose Room, Science Labs
No
Are ALL occupied spaces on the accessible route? Yes
Are there accessible toilets in the building? Yes
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
FUNCTIONAL ACCESSIBILITY
Exterior Routes
Exterior Entrances & Exits Yes
Exterior H/C Lifts No No
Exterior Ramps and Railings No No
Interior Routes
Corridor and Lobby H/C Lifts No No
Interior Corridor Doors and Hardware Yes Yes
Interior Corridors and Lobbies Yes
Interior Elevators No
Interior Lobby Doors and Hardware Yes
Interior Ramps No
Rooms & Spaces
Art Rooms No
Auditorium No
Cafeteria No
Classrooms No
Computer Rooms No
Gymnasium No
Library No
Main Office No
Multi-purpose Room No
Nurse's Room No
Pool No
Science Lab No
Toilet Rooms (Boys) 1st Floor Yes Yes
Toilet Rooms (Girls) 1st Floor Yes Yes
Toilet Rooms (Staff) 1st Floor Yes Yes
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 3 of 29
Page 4
Physical Breakdown Structure Exists Required Complies Deficiency AudioInductionSystem
FireAlarmStrobe
Building Template
Inspection
Question Response
Architectural
EXTERIOR Inspected
AREAWAY Does not Exist
AWNINGS AND CANOPIES Inspected
Condition 3 - Fair
Deficiency CONCRETE: MAJOR CRACKS/SPALLING
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 4 of 29
Page 5
Question Response
EXTERIOR
AWNINGS AND CANOPIES
Deficiency Photo1
Facade A
Violations No violations recorded.
CHIMNEY Inspected
Material Type(s) Masonry
Condition 2 - Between Good and Fair
Deficiency BRICK: OPEN JOINTS
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPOINT
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 - CH
Violations No violations recorded.
Deficiency BRICK: MINOR CRACKS AND SPALLING
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 5 of 29
Page 6
Question Response
EXTERIOR
CHIMNEY
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action RESTITCH
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Roof 1 - CH
Violations No violations recorded.
COPING Does not Exist
CORNICE Does not Exist
DOORS Inspected
DOORS AND FRAMES Inspected
Condition 5 - Poor
Deficiency METAL: DETERIORATED DOOR AND FRAME - MAJORDETERIORATION
Roof Plan reference
Deficiency Quantity 6
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 6 of 29
Page 7
Question Response
EXTERIOR
DOORS
DOORS AND FRAMES
Deficiency Photo1
Facade C - Exit 6
Violations No violations recorded.
DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
TRANSOM/SIDE LIGHT Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
EXTERIOR WALLS Inspected
Material Type(s) Masonry
Replacement Quantity 4,000
Replacement Uom S.F.
InspectedInstance on All Facades
Instance Condition 3 - Fair
Instance Quantity 4,000
Instance Quantity Uom S.F.
Deficiency BRICK: CRACKS/DISPLACED/SPALLED BRICK AT BUILDINGCORNERS
Roof Plan reference
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 7 of 29
Page 8
Question Response
EXTERIOR
EXTERIOR WALLS
Elevation
Deficiency Quantity 30
Quantity Uom S.F.
Potential Action REMOVE AND REBUILD
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Corner of Facades A and D
Violations No violations recorded.
Deficiency BRICK: MINOR CRACKS AND SPALLING
Roof Plan reference
Elevation
Deficiency Quantity 80
Quantity Uom S.F.
Potential Action RESTITCH
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 8 of 29
Page 9
Question Response
EXTERIOR
EXTERIOR WALLS
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Facade A
Violations No violations recorded.
EXTERIOR SOFFITS Inspected
Condition 3 - Fair
Deficiency STUCCO/PLASTER: MAJOR CRACKS/SPALLING
Roof Plan reference
Elevation
Deficiency Quantity 60
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 9 of 29
Page 10
Question Response
EXTERIOR
EXTERIOR SOFFITS Inspected
Deficiency Photo1
Facade A
Violations No violations recorded.
LOUVER Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
PARAPETS Does not Exist
PLAZA DECK Does not Exist
ROOF Inspected
Roofing Inspected
Replacement Quantity 5,000
Replacement Uom S.F.
ROOF HATCH/SMOKE HATCH Does not Exist
LEADERS, GUTTERS, DOWNSPOUTS, SCUPPERS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOFING Inspected
InspectedInstance on Modified Bitumen: Roof 1
Instance Condition 4 - Between Fair and Poor
Instance Quantity 5,000
Instance Quantity Uom S.F.
Does the roof have major mechanical equipment sitting onDunnage Steel less than 18" above the Roofing?
No
Installation Year 1984
Source of Installation Custodial Staff
Deficiency MODIFIED BITUMEN: ROOFING: DELAMINATION
Roof Plan reference
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE ROOFING WITHOUT MAJOR EQUIPMENTREMOVAL
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 10 of 29
Page 11
Question Response
EXTERIOR
ROOF
Roofing
ROOFING
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Center of Roof
Violations No violations recorded.
Deficiency MODIFIED BITUMEN: ROOFING: BEYOND USEFUL LIFE
Deficiency Location/Instance Modified Bitumen: Roof 1
Deficiency Quantity 5,000
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 1
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
ROOFING DRAINS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Specialties Inspected
DUNNAGE STEEL Does not Exist
SKYLIGHT/ROOF VENT Inspected
Material Type(s) Plastic
Condition 2 - Between Good and Fair
Deficiency DAMAGED FLASHING
Roof Plan reference
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 11 of 29
Page 12
Question Response
EXTERIOR
ROOF
Specialties
SKYLIGHT/ROOF VENT
Deficiency Photo1
Roof 1
Violations No violations recorded.
STAIRS/RAMPS: EXTERIOR Inspected
BUILDING CHEEK/FLANK WALLS Does not Exist
RAILINGS Does not Exist
STAIRS/RAMPS Inspected
Condition 3 - Fair
Deficiency STONE: CRACKS, SPALLING
Roof Plan reference
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 4
Purpose of Action LEVEL 2
Deficiency Photo1
Facade B - Exit 3
Violations No violations recorded.
WINDOWS Inspected
Replacement Quantity 800
Replacement Uom S.F.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 12 of 29
Page 13
Question Response
EXTERIOR
WINDOWS
EXTERIOR GUARDS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
LINTELS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
WINDOWS Inspected
Material Type(s) Aluminum
InspectedInstance on Aluminum - Other: All Facades
Instance Condition 4 - Between Fair and Poor
Instance Quantity 800
Instance Quantity Uom S.F.
Installation Year 1984
Source of Installation Custodial Staff
Deficiency ALUMINUM - OTHER: BROKEN PANE
Roof Plan reference
Elevation
Deficiency Quantity 90
Quantity Uom S.F.
Potential Action MAINTENANCE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 2
Deficiency Photo1
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 13 of 29
Page 14
Question Response
EXTERIOR
WINDOWS
WINDOWS
Facade B
Violations No violations recorded.
Deficiency ALUMINUM - OTHER: BEYOND USEFUL LIFE
Deficiency Location/Instance Aluminum - Other: All Facades
Deficiency Quantity 800
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 1
Purpose of Action LEVEL 2
Deficiency Photo1 No photo recorded
Violations No violations recorded.
INTERIOR Inspected
STRUCTURAL Inspected
COLUMNS/BEAMS/BEARING WALLS Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
FLOOR STRUCTURE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
FOUNDATION WALLS Inspected
Material Type(s) Concrete
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ROOF STRUCTURE Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
VAULTS-BUNKERS Does not Exist
CLASSROOMS/CORRIDORS/ADMIN SPACES Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency TERRAZZO: CRACKS
Deficiency Location/Instance Near Exits 5,6
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 14 of 29
Page 15
Question Response
INTERIOR
CLASSROOMS/CORRIDORS/ADMIN SPACES
Floor Finish
Deficiency Photo1
Near Exit 6
Violations No violations recorded.
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency GLAZED BLOCK: CRACKS/SPALLING
Deficiency Location/Instance Near Exit 6
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Exit 6
Violations No violations recorded.
INTERIOR DOOR HARDWARE Inspected
Condition 3 - Fair
Deficiency No deficiencies recorded
LOCKER ROOM Inspected
InspectedInstance on 1st Floor - Boys (217 Lockers)
Alternative use No
InspectedInstance on 1st Floor - Girls (68 Lockers)
Alternative use No
Ceiling
InspectedInstance on 1st Floor - Boys (217 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 1st Floor - Girls (68 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s)
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 15 of 29
Page 16
Question Response
INTERIOR
LOCKER ROOM
Door(s)
InspectedInstance on 1st Floor - Boys (217 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 1st Floor - Girls (68 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish
InspectedInstance on 1st Floor - Boys (217 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
InspectedInstance on 1st Floor - Girls (68 Lockers)
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Locker Room Lockers
InspectedInstance on 1st Floor - Boys (217 Lockers)
Condition 2 - Between Good and Fair
Deficiency DAMAGED UNITS
Deficiency Location/Instance Locker 17
Deficiency Quantity 1
Quantity Uom EACH
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Locker 17
Violations No violations recorded.
Walls
InspectedInstance on 1st Floor - Girls (68 Lockers)
Condition 2 - Between Good and Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Near the window
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 16 of 29
Page 17
Question Response
INTERIOR
LOCKER ROOM
Walls
Deficiency Photo1
Near the window
Violations No violations recorded.
SHOWER ROOM Inspected
InspectedInstance on 1st Floor - Boys
Alternative use No
InspectedInstance on 1st Floor - Girls
Alternative use No
Ceiling
InspectedInstance on 1st Floor - Boys
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Not RequiredInstance on 1st Floor - Girls
Door(s)
Does not ExistInstance on 1st Floor - Boys
Does not ExistInstance on 1st Floor - Girls
Floor Finish
InspectedInstance on 1st Floor - Boys
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Not RequiredInstance on 1st Floor - Girls
Walls
InspectedInstance on 1st Floor - Boys
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Not RequiredInstance on 1st Floor - Girls
STAIRS/RAMPS: INTERIOR Does not Exist
TOILET ROOMS - STAFF Inspected
Ceiling Inspected
Condition 3 - Fair
Deficiency PLASTER: CRACKS/SPALLING
Deficiency Location/Instance Visitors Women
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 17 of 29
Page 18
Question Response
INTERIOR
TOILET ROOMS - STAFF
Ceiling
Deficiency Photo1
Visitors Women
Violations No violations recorded.
Door(s) Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Floor Finish Inspected
Condition 3 - Fair
Deficiency TERRAZZO: CRACKS
Deficiency Location/Instance Visitors Men
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Visitors Men
Violations No violations recorded.
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency GLAZED BLOCK: CRACKS/SPALLING
Deficiency Location/Instance Visitors Men
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 18 of 29
Page 19
Question Response
INTERIOR
TOILET ROOMS - STAFF
Walls
Deficiency Photo1
Visitors Men
Violations No violations recorded.
TOILET ROOMS - STUDENTS Inspected
Ceiling Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Door(s) Does not Exist
Floor Finish Inspected
Condition 2 - Between Good and Fair
Deficiency TERRAZZO: CRACKS
Deficiency Location/Instance Girls
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Girls
Violations No violations recorded.
Stalls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
ATHLETIC FIELDS Inspected
PLAYING SURFACE Inspected
Synthetic Turf Field exists? Year of Installation
Yes 2,015
Replacement Quantity 156,500
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 19 of 29
Page 20
Question Response
ATHLETIC FIELDS
PLAYING SURFACE
Replacement Uom S.F.
InspectedInstance on Handball Courts
Instance Condition 2 - Between Good and Fair
Instance Quantity 6,500
Instance Quantity Uom S.F.
Deficiency No deficiencies recorded
InspectedInstance on Running Track
Instance Condition 1 - Good
Instance Quantity 42,000
Instance Quantity Uom S.F.
Deficiency No deficiencies recorded
InspectedInstance on Soccer Field
Instance Condition 1 - Good
Instance Quantity 79,000
Instance Quantity Uom S.F.
Deficiency No deficiencies recorded
InspectedInstance on Tennis Courts
Instance Condition 3 - Fair
Instance Quantity 29,000
Instance Quantity Uom S.F.
Deficiency ASPHALT: DAMAGED/DETERIORATED
Deficiency Location/Instance Tennis Courts 1 and 2
Roof Plan reference
Deficiency Quantity 600
Quantity Uom S.F.
Potential Action REPAIR
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Tennis Court 1
Violations No violations recorded.
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 20 of 29
Page 21
Question Response
ATHLETIC FIELDS
FIXED EQUIPMENT Inspected
Basketball Backboard Does not Exist
Basketball Hoops Does not Exist
Basketball Posts Does not Exist
Football Goal Posts Does not Exist
Tennis Net Posts Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
SEATING Inspected
Benches Inspected
Concrete Does not Exist
Metal/Wood/Plastic Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Bleachers Inspected
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency CRACKS/SPALLING - MAJOR
Deficiency Location/Instance 5th row Center
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
5th row Center
Violations No violations recorded.
Metal/Wood/Plastic Does not Exist
SITE Inspected
CONTAINERIZATION Does not Exist
Drainage System for Asphalt Inspected
Catch Basins/Manhole - Surrounded by asphalt Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Asphalt Covering Does not Exist
Drainage System for Concrete Inspected
Catch Basins/Manhole - Surrounded by concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Concrete Covering Does not Exist
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 21 of 29
Page 22
Question Response
SITE
Drainage System for Soil Inspected
Catch Basins/Manhole - Surrounded by Soil Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Culverts - Soil Covering Does not Exist
DRINKING FOUNTAINS Inspected
Condition 1 - Good
Deficiency No deficiencies recorded
FENCES Inspected
Condition 4 - Between Fair and Poor
Deficiency CHAIN LINK: DAMAGED/DETERIORATED
Deficiency Location/Instance South side
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
South side
Violations No violations recorded.
Deficiency CHAIN LINK: RUST - MAJOR
Deficiency Location/Instance Near Bleachers north Entrance, Tennis Court 2, near Field House
Deficiency Quantity 700
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Bleachers north Entrance
Violations No violations recorded.
Deficiency WROUGHT IRON: DAMAGED/DETERIORATED
Deficiency Location/Instance Dekalb Avenue
Deficiency Quantity 80
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 22 of 29
Page 23
Question Response
SITE
FENCES
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Dekalb Avenue
Violations No violations recorded.
IRRIGATION SYSTEM Does not Exist
PAVING Inspected
Student Non-Use Inspected
Gravel Exists? No
Asphalt Inspected
Condition 3 - Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Parking Lot, Dekalb Avenue Driveway
Deficiency Quantity 400
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Dekalb Avenue Driveway
Violations No violations recorded.
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Dekalb Avenue Driveway
Deficiency Quantity 25
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 23 of 29
Page 24
Question Response
SITE
PAVING
Student Non-Use
Concrete
Deficiency Photo1
Dekalb Avenue Driveway
Violations No violations recorded.
Pavers Does not Exist
Student Use Inspected
Gravel Exists? No
Asphalt Does not Exist
Concrete Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Pavers Inspected
Condition 2 - Between Good and Fair
Deficiency HEAVING
Deficiency Location/Instance Near the flagpole
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near the flagpole
Violations No violations recorded.
Site Sidewalks & Walkways Inspected
Asphalt Inspected
Condition 3 - Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance East of track
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 24 of 29
Page 25
Question Response
SITE
PAVING
Site Sidewalks & Walkways
Asphalt
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
East of track
Violations No violations recorded.
Concrete Inspected
Condition 3 - Fair
Deficiency CRACKS - MAJOR
Deficiency Location/Instance Near Field House
Deficiency Quantity 200
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Field House
Violations No violations recorded.
Pavers Does not Exist
DOT Sidewalk Inspected
Asphalt Does not Exist
Concrete Inspected
Condition 4 - Between Fair and Poor
Deficiency HEAVING
Deficiency Location/Instance Willoughby Avenue
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 25 of 29
Page 26
Question Response
SITE
PAVING
DOT Sidewalk
Concrete
Deficiency Photo1
Willoughby Avenue
Violations No violations recorded.
Deficiency DAMAGED CURBS
Deficiency Location/Instance Dekalb Avenue, Willoughby Avenue
Deficiency Quantity 50
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Dekalb Avenue
Violations No violations recorded.
Deficiency DAMAGED/DETERIORATED/MISSING SECTIONS
Deficiency Location/Instance Dekalb Avenue, Willoughby Avenue
Deficiency Quantity 800
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Dekalb Avenue
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 26 of 29
Page 27
Question Response
SITE
PAVING Inspected
DOT Sidewalk
Concrete Inspected
Violations No violations recorded.
Pavers Does not Exist
PLAYGROUNDS Does not Exist
RETAINING WALLS Inspected
Are there any Retaining Walls 6' OR higher facing publicstreet/sidewalk?
Yes
Condition 3 - Fair
Deficiency CAST IN PLACE CONCRETE: DETERIORATED EXPANSIONJOINT
Deficiency Location/Instance Handball Court
Deficiency Quantity 10
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Handball Court
Violations No violations recorded.
Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance Near Tennis Courts, Handball Court, near Field House Exit 4, Southside
Deficiency Quantity 100
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Near Tennis Courts
Violations No violations recorded.
SEATING Inspected
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 27 of 29
Page 28
Question Response
SITE
SEATING
Benches Inspected
Concrete Does not Exist
Metal/Wood/Plastic Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
SITE WALLS (NOT RETAINING WALLS) Inspected
Condition 3 - Fair
Deficiency BRICK: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance Dekalb Avenue
Deficiency Quantity 10
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Dekalb Avenue
Violations No violations recorded.
Deficiency CAST IN PLACE CONCRETE: CRACKS/SPALLING - MAJOR
Deficiency Location/Instance Handball Court
Deficiency Quantity 20
Quantity Uom S.F.
Potential Action REPLACE
Urgency of Action PRIORITY 3
Purpose of Action LEVEL 2
Deficiency Photo1
Handball Court
Violations No violations recorded.
STAIRS/RAMPS: EXTERIOR Inspected
Railings Inspected
Condition 4 - Between Fair and Poor
Deficiency MISSING
Deficiency Location/Instance East,west of Bleachers
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 28 of 29
Page 29
Question Response
SITE
STAIRS/RAMPS: EXTERIOR
Railings
Deficiency Quantity 20
Quantity Uom L.F.
Potential Action REPLACE
Urgency of Action PRIORITY 5
Purpose of Action LEVEL 6
Deficiency Photo1
East of Bleachers
Violations No violations recorded.
Site Cheek/flank Walls Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
Stairs/ramps Inspected
Condition 2 - Between Good and Fair
Deficiency No deficiencies recorded
NYC Department of Education
Architectural Inspection
Building Condition Assessment Survey 2019 - 2020
Q488
PB/A&W Print Date: 9/14/2020Page 29 of 29