    High ‐Rise Fire Protection

    Standpipe and Sprinkler Systems

    By:Douglas Nadeau, PE

    PresidentRAN Fire Protection Engineering, PC

    Tel: 518 ‐275 ‐0791 .

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    2/53

    Wh talk about hi h-rise buildin s?

    Focus on the Buildin Code a lication

    Purpose of the presentation

    My experience

    Question

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    3/53

    sprinkler retrofitStarted on 12 th floor Delayed call to FireDe artmentSprinkler System disabledFire Pum s shut downFire Damage – 12 th-16 th

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    4/53

    Overview of High-Rise Buildings

    Standpipe Systems

    Sprinkler Systems

    Water Supply

    Design Issues

    Key Points

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    5/53

    Overview of High ‐Rise Buildings

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    6/53

    Commercial

    Mixed occupancy

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    7/53

    Building Occupancy Characteristics Continued

    Residential buildin s ma contain senior citizens

    or people with special needs.

    Residential buildings often have similar floor

    plans.

    Commercial building floor plans often differ from

    .

    .

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    8/53

    internal attack.

    A fire fighting team working from a riser areunlikel to control a full involved 100 ft x 200 ftfloor area.

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    9/53

    High ‐Rise Characteristic Features Continued

    in inner city areas.

    High-rises are closed buildings – causing a rapidbuild u of heat and smoke.

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    10/53

    ‐Chapter 4 – Special Detailed Requirements

    Based on Use and Occupancy - . . .

    over 30 feet in height.

    Standpipe Protection - §905.3.1 Buildingheight. Class III standpipe systems shall be

    level of the highest story is located more than30 feet…

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    11/53

    High ‐Rise Building Code provisions applies to

    Buildings having occupied floors located more

    level of fire department vehicle access

    Some exceptions such as air traffic control

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    12/53

    High ‐Rise Building CodeChapter 4

    There is a difference!

    Standby required for fire pumps, fire command…

    mergency s or egress g ng, re a arm…

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    13/53

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    14/53

    Purpose – installed to providea equa e wa er ow or ose s reams

    used to extinguish the fire.

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    15/53

    Building Code and Fire Code

    NFPA 14

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    16/53

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    17/53

    High ‐Rise Standpipe System Continued

    Buildin Code Exce tion!!!

    Class I standpipes are allowed in buildingsequipped throughout with an automaticspr n er system nsta e n accor ance w t§903.3.1.1 or §903.3.1.2.

    Note throughout

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    18/53

    ‐ –

    ry u oma c - areas su ec o reez ng

    Dry Manual - open parking garages

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    19/53

    High ‐Rise Standpipe System NFPA 14 Overview

    ” .

    ” ” –sprinkler protection.

    Determine hose valve locations – max travel.

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    20/53

    High ‐Rise Standpipe SystemNFPA 14 Overview

    remote 2½ in. hose connection

    Generally 500 gpm at hydraulically most

    additional (max 1250 gpm)

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    21/53

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    22/53

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    23/53

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    24/53

    NFPA, June 2007

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    25/53

    Purpose – installed to providea equa e proper y pro ec on o

    control the fire.

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    26/53

    Building Code and Fire Code

    NFPA 13

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    27/53

    High ‐Rise Sprinkler SystemBuilding Code Requirements

    . .

    Buildings shall be equipped throughout

    accordance with NFPA 13.

    A secondary water supply where required.

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    28/53

    High ‐Rise Sprinkler System ““equipped equipped throughout throughout ””

    §903.3.1.1 NFPA 13 sprinkler systems. -

    portion thereof be equipped throughout …

    – Exempt locations – where water is bad

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    29/53

    High ‐Rise Sprinkler System Alternative protection . .

    protection is permitted in lieu of automatic

    1. recognized by the applicable standard

    2. Such installations shall be approved bythe code enforcement official.

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    30/53

    High ‐Rise Sprinkler System Building Code Chapter 9

    point of connection to riser.

    Rubbish chutes need to have sprinkler

    .

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    31/53

    High ‐Rise Sprinkler SystemNFPA 13 Overview

    constantly attended signaling service

    Additional alarm apparatusWaterflow device er floor for the s rinkler s stemsCentral station service is required if a constantsupervision by qualified personnel is not provided

    Distinct trouble signal to indicate impairment of thesprinkler system

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    32/53

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    33/53

    High ‐Rise Water Supply Characteristics

    Secondary Water Supply

    Fire Pump

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    34/53

    On-site water supply

    Equal to the hydraulically calculated sprinkler,

    , ,

    Duration of not less than 30 minutes

    Exception for existing buildings

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    35/53

    Zoning - Pressure

    Break Tanks

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    36/53

    Series and ParallelFire Pumps

    Meant to boost the pressure from a lower

    .The design is dependent on both operating

    Parallel Fire Pumps

    Primary and secondaryMeant to boost flow volume

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    37/53

    es uaPressure

    Height(feet) Zones Remarks

    65 psi 200 1 max 175

    psi rating100 si 120 165 psi 350 1 PRV’s

    re uired

    65 psi 580 2 Design limit

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    38/53

    on or ng o e wa er eve s recommen e

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    39/53

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    40/53

    What is the biggest issue?

    ressure

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    41/53

    Standpipe system pressure limit is 350 psi

    Generally (product specific, safety factor of 8)c e u e maxes at ps

    Schedule 40 minimum at 350 psi

    Reduction to 65 si ma be allowed b the Authority Having Jurisdiction. Generally used forexisting buildings.

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    42/53

    there may be listing problems.

    Sprinkler listing are limited to 175 psiun ess a spec a s ng.

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    43/53

    Make sure that water su l will meet s stemdemand.

    Combined Standpipe/Sprinkler systems requiredadditional coordination between NFPA 13 and 14

    Generally the standpipe will be the most.

    THE CASE.

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    44/53

    out for applying current code sectionsrec y o e u ng.

    Due Diligence is required to identify.

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    45/53

    ng newpreaction systems

    Jocke umsetting

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    46/53

    Existing buildingand systems

    Upgrading to meet

    requirements.

    Listing pressurera ngs

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    47/53

    New Construction

    Water Supply

    Greatest Demand

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    48/53

    ut e a tat on

    Preparing for thefuture tenantrenovation.

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    49/53

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    50/53

    What is the most effective means of fire controlin high-rise buildings?

    What is the pressure requirement for thehydraulically most remote hose connection for a

    high-rise building standpipe systems?

  • 8/16/2019 NY1397 Nadeau High Rise Fire Protection

    51/53

    Anal ze the Code

    Plan earl – communicate with CEO

    Address existing buildings uniquely

    Address exceptions

    PRESSURE!