1 NITIN CORPORATION 402, 4 th Floor, Bezzola Commercial Complex, Sion – Trombay Road, Chembur, Mumbai – 400071, India. WEB :www.corponit.com E – MAIL : [email protected][email protected]FAX : +91 - 22 - 25235386 PH (O) : +91 - 22 - 25234478/67973677 THE FOLLOWING GAS FIRED POWER BARGE IS AVAILABLE FOR SALE WITH US WITH IMMEDIATE DELIVERY: 2
18
Embed
NITIN CORPORATION th - corponit.com€¦ · Black start facility for plant start up is available. ... 40 Stage Dual Pressure Condensing type Steam Turbine ... Curves Note: • These
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
1. The Barge mounted Combined Cycle power plant having net power output of 220 MW.
2. Fuel used will be Natural Gas. Required amount of Natural gas is 1 mmscmd approximately.
3. The total fresh water requirement is approx. 1000 cu. m per day.
4. The gas turbines, OTSG’s, steam turbine and their auxiliaries are all mounted on a single floating
barge.
5. Compact Barge of size 106 M x 55 M x 6 M having a total draft of 6 M with minimum onshore
facilities required. Minimum draft 3 M is required.
6. The barge mounted combined cycle power plant (CCPP) has:
4 nos. 50.8 MW- LM6000 PC Sprint aero derivative gas turbines
4 nos. Once Through Steam Generators.
1 no 53 MW rated output steam turbine and generator. 7. Minimum onshore facilities with following major systems:
Switchyard for Power Evacuation, 415V MCC for DM Plant etc.
Fuel treatment and forwarding
Water Treatment Plant and DM plant
Fire Fighting System.
4
Advantages o
Minimum land requirement of about 20 acres for offshore facilities. Foundation is not required for main plant hence reduced construction time.
Black start facility for plant start up is available.
Main plant systems supplied by reputed OEM’s like GE and ABB.
OTSG has dry running capability up to 560 Deg C which is suitable to operate in a simple-cycle mode.
Once Through Steam Generator is quick to adjust during sudden fluctuation in load.
5
GAS TURBINE
Make – GE
Model: LM 6000 PC Sprint
Capacity: 50.8 MW
Installed on Barge
Gas turbine Generator is open air-cooled, synchronous type and totally enclosed
5 Stage Low Pressure Compressor – Compression ratio is 2.4:1, 14 Stage High Pressure
Compressor – Compression ratio is 12.5:1
STEAM TURBINE
Make-ABB
Installed on Barge
Capacity: 53.58 MW
40 Stage Dual Pressure Condensing type Steam Turbine
2 Pole Generator with air cooling for Stator & Rotor winding
6
ONCE THROUGH STEAM GENERATOR
Make – IST, Canada
Dual Pressure OTSG installed at the exhaust of the Gas Turbine
Steam parameters : Pressure/Temperature
HP Steam : 56 Bar / 419oC
LP Steam : 4.7 Bar / 240oC
Dry Running Capability as the tubes are made of Inco alloy
CHILLERS
Used for Cooling the Gas turbine intake air for increasing the Gas turbine output
Chiller Capacity : 1210 TR
Refrigerant used is HFC134a
COMPRESSED AIR SYSTEM
3 X100% Screw Type Air Compressors with 2 x100% desiccant type dryers
Capacity : 12.7 Nm3/min and 8.64 bar g discharge pressure
7
Plant Electrical system (Barge Mounted) Power is generated at 11 KV and Evacuated at 220 KV
2 Nos. of Step-up transformer 11KV /220KV ( 1 each for 2 Gas turbines) and 1 Step-up transformer for Steam turbine
2 Nos. of Unit Auxiliary transformers for stepping down from 11KV to 6.6 KV for running Plant auxiliaries
4 Nos. of Step-down transformers called Auxiliary Transformers for stepping down the 6.6KV to 415V
Other Plant Facilities Demineralization Plant: Demineralization plant (DM plant) produces de-mineralized water for
generating steam in OTSG.
Cooling Water System: Cooling Water System suitable for river/sea water which can be connected to Closed Circuit Cooling Water system onshore if required.
Fire Protection and Fire Detection System The plant fire protection system will consist of the following:
Water Hydrant system (Consisting of six fire water pumps out of which 2 are diesel engine driven
and 1 Barge mounted emergency Fire pump (diesel driven)) - High Velocity Water Spray System (HVWS) System - Carbon Dioxide Flooding System - Portable Fire extinguishers (Water type, Foam type, CO2 gas type, Dry Chemical Powder type
extinguishers). - Fire detection and alarm system.
8
Barge Mounted Power Plant
Curves
Note:
• These are typical curves for Barge Mounted Power Plant before conversion to sprint version. • These Curves are for liquid fuel firing.
9
Correction Parameter for Ambient Pressure
10
GT Heat Rate Correction Factor vs. Ambient Temperature, Humidity
11
GT Power Correction Factor vs. Ambient Temperature, Humidity