PNEUMATIC HOOK UP DIAGRAM FOR SH/RH CONTROL VALVES
-
Limit SwitchesUSED TO INDICATE THE OPEN OR CLOSE POSITION OF THE
CONTROL VALVE
-
LIMIT SWITCH
-
AIR LOCK VALVEUSED TO MAINTAIN THE VALVE IN STAYPUT CONDITION ON
SUPPLY AIR / SIGNAL AIR FAILURE
-
AIR LOCK
-
USED TO MAINTAIN AIR PRESSURE AT INLET OF POSITIONER
-
AIR SET
-
PNEUMATIC POSITIONERA FEEDBACK DEVICE THAT RECEIVES A PNEUMATIC
SIGNAL FROM A CONTROLLER COMPARES THAT SIGNAL TO THE ACTUAL
POSITION OF THE VALVE . THE POSITIONER SENDS OR BLEEDS AIR PRESSURE
TO OR FROM THE ACTUATOR UNTIL THE CORRECT VALVE POSITION IS
ACHIEVED.
-
PNEUMATIC POSITIONER
-
SOLENOID VALVEUSED TO MAINTAIN STAYPUT VALVE POSITION ON SIGNAL
AIR FAILURE
-
VOLUME BOOSTER USED TO ENABLE FASTER OPENING ( IN LARGER VALVES
AND BIGGER ACTUATORS )
-
VOLUME BOOSTER
-
CONTROLLER COMPARES PROCESS PARAMETER WITH SET VALUE AND GIVES
SIGNAL
-
CONTROLLER
-
I /P CONVERTERUSED TO CONVERT ELECTRICAL SIGNAL TO PNEUMATIC
SIGNAL
-
I / P CONVERTER
-
POSITION TRANSMITTERUSED TO INDICATE THE PERCENTAGE OPENING OF
THE VALVE
-
TYPICAL CONTROL VALVES IN BOILERSUPERHEATER SPRAY CONTROL
VALVEREHEATER SPRAY CONTROL VALVESOOT BLOWER PRESSURE REDUCING
VALVEFULL LOAD FEED WATER CONTROL VALVELOW LOAD FEED WATER CONTROL
VALVEDEARATOR LEVEL CONTROL VALVE
-
SPRAY STATION ARRANGEMENT
-
FLASHING
DOWNSTREAM PRESSURE IS
-
FLASHING & CAVITATION PHENOMENON
-
HOW TO CONTROL FLASHING REDESIGN SYSTEM TO AVOID
FLASHINGDISCHARGE INTO LARGE VESSEL AND AWAY FROM ANY CRITICAL
SURFACES.HARD FACING OF TRIM & DOWNSTREAM PASSAGE
-
CAVITATION- PR IN THE VENA CONTRACTA BELOW VAPOUR PR AND PR
RECOVERY ABOVE THE VAPOUR PR .
- VAPOUR BUBBLES FORM WHICH THEN COLLAPSE AS PR RECOVERS
IMPLOSION OF VAPOUR BUBBLES CAN ERODE METAL SURFACES IN BOTH THE
VALVE BODY AND DOWNSTREAM PIPING , AS WELL AS CAUSE NOISE.
-
HOW TO ELIMINATE CAVITATIONBY USING ANTI CAVITATION CAGEWITH
MULTIPLE CAGESUSING RETAINER OR CAGE WITH A TORTUOUS PATHBY USING
MULTI-STAGE PRESSURE DROP VALVE
-
LINEAR CHARACTERISTIC USED WHEN MAX. P IS TAKEN ACROSS THE
VALVE.
WHEN UPSTREAM PRESSURE IS CONSTANT
USED RARELY
-
EQUAL PERCENTAGE CHARACTERISTICUSED WHEN MAX. P IS TAKEN IN
PIPING & SYSTEM
HIGH P LOW Q , LOW P HIGH Q
WHEN VALVE IS OVERSIZED BECAUSE OF LIMITED DATA , =% IS BEST
MOST COMMONLY USED
-
LEVEL CONTROL VALVESCONSTANT P ACROSS VALVE - LINEAR
CHARACTERISTIC USED
P AT MAX. LOAD > 0.2 P AT MIN LOAD - LINEAR CHARACTERISTIC
USED
P AT MAX. LOAD < 0.2 P AT MIN. LOAD - =% CHARACTERISTIC
USED
-
PRESSURE CONTROL VALVES LIQUID SERVICE - =% CHARACTERISTIC
GAS SERVICE , SMALL VOLUME FLOW - =% CHARACTERISTIC
GAS SERVICE , LARGE VOLUME FLOW- LINEAR CHARACTERISTIC
GAS , P AT MAX. LOAD > 0.2 P AT MIN . LOAD - LINEAR
CHARACTERISTIC
GAS , P AT MAX. LOAD < 0.2 P AT MIN. LOAD - =%
CHARACTERISTIC
-
FLOW CONTROL VALVES WIDE RANGE OF FLOW SET POINTS - LINEAR
CHARACTERISTIC USED
SMALL RANGE OF FLOW SET POINTS - =% CHARACTERISTIC USED
-
TYPES OF CONTROL VALVES USED BY BHEL -TRICHYSUPERHEATER SPRAY
CONTROL VALVEREHEATER SPRAY CONTROL VALVESOOT BLOWER PRESSURE
REDUCING VALVEFULL LOAD FEED WATER CONTROL VALVELOW LOAD FEED WATER
CONTROL VALVEDEARATOR LEVEL CONTROL VALVE
-
SUPERHEATER SPRAY CONTROL VALVE The moderation of temperature of
superheated steam is achieved by spraying water into the steam .
Quantity of spray is controlled by the spray control valve . Feed
water at about 182 kg/sq.cm pressure and 240 C temperature is
regulated and supplied to the system at a pressure of 170 kg/sq.cm
. It can be noticed that the pressure drop across the control valve
is only moderate . However , selection of control valve for this
application should be done taking the following factors into
consideration . Valve will be operating at minimum condition most
of the time .As such the valve plug will be close to the seat for a
long period of time causing erosion of the seat and plug .So the
resultant valve offered should ensure around 15% opening at the
minimum operating conditions . Equal Percentage characteristic is
needed for this service .A cage design valve enables maximum
pressure drop to take place in the cage rather than in the seat and
thus protects the seat ring . This ensures continuous trouble free
operation .TYPICAL OPERATING PARAMETERS OF SH SPRAY CONTROL
VALVEInlet pressure : 182 kg/ sq.cmOutlet pressure : 170 kg/
sq.cmOperating temperature : 240 Deg. CFlow rate : 34.5 Tons /
Hr.
-
REHEATER SPRAY CONTROL VALVEIt handles a higher pressure drop
when compared to the superheater spray control valve.In order to
avoid cavitation , erosion , vibration and noise associated with
this service , a multi stage pressure reducing valve is needed for
this service .Typical operating parameters are given below .Inlet
Pressure : 170 kg/ sq.cmOutlet Pressure : 100 kg / sq.cm Operating
Temperature : 240 Deg CFlow rate : 15 tons / hr
-
SOOT BLOWER PRESSURE REDUCING VALVEThis control valve design
requires high pressure- temperature class design due to the very
critical nature of the application.Soot blowers are operated
occassionally during the day . This leads to temperature cycling of
the valve . In addition to the temperature cycles , high pressure
drops create high noise levels and can cause excesive wear and
vibration to occur in the trim .Hence a special low noise /
anti-vibration trim with better noise attentuation features is
required for this application.Typical operating parameters for this
applicationInlet Presure : 175 kg / sq.cmOutlet Pressure : 30 kg /
sq.cmOperating Temperature : 420 Deg. CFlow rate : 8 tons/ hr
-
FULL LOAD FEED WATER CONTROL VALVEIt handles a relatively large
volume of flow . When the boiler is in full load operation or near
it , this valve will be in continuous operation . Since this valve
takes over from low load feed control valve after having achieved a
steady operation : the pressure drop across this valve is less .A
cage guided valve , 12 x 8 size , for this application ( for 210
MW/ 250 MW) and 16 x 12 size for 500 MW plant is used.A Balanced
trim construction enables to meet the high shut off requirements
with conventional actuators . The valve design should handle large
volume of flow ( higher Cv for given body size) keeping flow
velocities very much within limits.Typical operating parameters for
this valve are Inlet Pressure : 233 kg / sq. cm Outlet Pressure :
228 kg / sq. cm Operating Temperature : 240 Deg . C Flow quantity :
720 Tons / hr
-
LOW LOAD FEED WATER CONTROL VALVEAt boiler start up , the feed
water is to be fed at low pressure and consequently the low load
feed control valve handles very high pressure drops . Because of
this high pressure drops ,there are chances for the feed water to
flash / cavitate . The internals of the valves are to be carefully
selected to meet these severe service conditions . The trim is made
of hardened stainless steel / SS316 with Stellite overlay .A cage
guided 6 x 4 size ( for 210 / 250 MW units ) and 8 cage guided
valve for 500 MW plant is used . Typical operating parameters of
this control valve are given below .Inlet Pressure ; 233 kg / sq.
cmOutlet pressure : 100 kg / sq.cmOperating Temperature : 240 Deg.
CFlow quantity : 200 tons / hr
-
DEARATOR LEVEL CONTROL VALVEThe purpose of this valve , as the
name implies , is to maintain a correct level in the deaerator .
This valve performs its function by varying condensate flow into
the deaerating vessel in response to load and a level signal . The
service conditions confronting these valves vary directly with the
plant load .The service conditions faced are mild when compared to
spray control valves and low load feed water control valve .A cage
guided valve is recommended for this application .Typical operating
parameters for this valve are Inlet Pressure : 19.6 kg /
sq.cmOutlet Pressure : 13.8 kg/ sq.cmOperating Temperature : 49.2
Deg. CFlow rate : 523.3 Tons/ hr
-
TYPES OF CONTROL VALVES USED BY BHEL -TRICHYSUPERHEATER SPRAY
CONTROL VALVEREHEATER SPRAY CONTROL VALVESOOT BLOWER PRESSURE
REDUCING VALVEFULL LOAD FEED WATER CONTROL VALVELOW LOAD FEED WATER
CONTROL VALVEDEARATOR LEVEL CONTROL VALVE
-
SUPERHEATER SPRAY CONTROL VALVE The moderation of temperature of
superheated steam is achieved by spraying water into the steam .
Quantity of spray is controlled by the spray control valve . Feed
water at about 182 kg/sq.cm pressure and 240 C temperature is
regulated and supplied to the system at a pressure of 170 kg/sq.cm
. It can be noticed that the pressure drop across the control valve
is only moderate . However , selection of control valve for this
application should be done taking the following factors into
consideration . Valve will be operating at minimum condition most
of the time .As such the valve plug will be close to the seat for a
long period of time causing erosion of the seat and plug .So the
resultant valve offered should ensure around 15% opening at the
minimum operating conditions . Equal Percentage characteristic is
needed for this service .A cage design valve enables maximum
pressure drop to take place in the cage rather than in the seat and
thus protects the seat ring . This ensures continuous trouble free
operation .TYPICAL OPERATING PARAMETERS OF SH SPRAY CONTROL
VALVEInlet pressure : 182 kg/ sq.cmOutlet pressure : 170 kg/
sq.cmOperating temperature : 240 Deg. CFlow rate : 34.5 Tons /
Hr.
-
REHEATER SPRAY CONTROL VALVEIt handles a higher pressure drop
when compared to the superheater spray control valve.In order to
avoid cavitation , erosion , vibration and noise associated with
this service , a multi stage pressure reducing valve is needed for
this service .Typical operating parameters are given below .Inlet
Pressure : 170 kg/ sq.cmOutlet Pressure : 100 kg / sq.cm Operating
Temperature : 240 Deg CFlow rate : 15 tons / hr
-
SOOT BLOWER PRESSURE REDUCING VALVEThis control valve design
requires high pressure- temperature class design due to the very
critical nature of the application.Soot blowers are operated
occassionally during the day . This leads to temperature cycling of
the valve . In addition to the temperature cycles , high pressure
drops create high noise levels and can cause excesive wear and
vibration to occur in the trim .Hence a special low noise /
anti-vibration trim with better noise attentuation features is
required for this application.Typical operating parameters for this
applicationInlet Presure : 175 kg / sq.cmOutlet Pressure : 30 kg /
sq.cmOperating Temperature : 420 Deg. CFlow rate : 8 tons/ hr
-
FULL LOAD FEED WATER CONTROL VALVEIt handles a relatively large
volume of flow . When the boiler is in full load operation or near
it , this valve will be in continuous operation . Since this valve
takes over from low load feed control valve after having achieved a
steady operation : the pressure drop across this valve is less .A
cage guided valve , 12 x 8 size , for this application ( for 210
MW/ 250 MW) and 16 x 12 size for 500 MW plant is used.A Balanced
trim construction enables to meet the high shut off requirements
with conventional actuators . The valve design should handle large
volume of flow ( higher Cv for given body size) keeping flow
velocities very much within limits.Typical operating parameters for
this valve are Inlet Pressure : 233 kg / sq. cm Outlet Pressure :
228 kg / sq. cm Operating Temperature : 240 Deg . C Flow quantity :
720 Tons / hr
-
LOW LOAD FEED WATER CONTROL VALVEAt boiler start up , the feed
water is to be fed at low pressure and consequently the low load
feed control valve handles very high pressure drops . Because of
this high pressure drops ,there are chances for the feed water to
flash / cavitate . The internals of the valves are to be carefully
selected to meet these severe service conditions . The trim is made
of hardened stainless steel / SS316 with Stellite overlay .A cage
guided 6 x 4 size ( for 210 / 250 MW units ) and 8 cage guided
valve for 500 MW plant is used . Typical operating parameters of
this control valve are given below .Inlet Pressure ; 233 kg / sq.
cmOutlet pressure : 100 kg / sq.cmOperating Temperature : 240 Deg.
CFlow quantity : 200 tons / hr
-
DEARATOR LEVEL CONTROL VALVEThe purpose of this valve , as the
name implies , is to maintain a correct level in the deaerator .
This valve performs its function by varying condensate flow into
the deaerating vessel in response to load and a level signal . The
service conditions confronting these valves vary directly with the
plant load .The service conditions faced are mild when compared to
spray control valves and low load feed water control valve .A cage
guided valve is recommended for this application .Typical operating
parameters for this valve are Inlet Pressure : 19.6 kg /
sq.cmOutlet Pressure : 13.8 kg/ sq.cmOperating Temperature : 49.2
Deg. CFlow rate : 523.3 Tons/ hr