9 Application Separable straight plug designed to connect polymeric insulated cable to cable. Mates with the elbow, straight and branch joint connectors. Up to 24 kV - 200 A 151SP INTERFACE A STRAIGHT PLUG 6/10 (12) kV 6.35/11 (12) kV 8.7/15 (17.5) kV 12/20 (24) kV 12.7/22 (24) kV Technical characteristics • The thick conductive EPDM jacket provides a total safe to touch screen which ensures safety for personnel. • Each straight plug is tested for AC withstand and partial discharge prior to leaving the factory. Design Separable connector comprising: 1. Conductive EPDM insert. 2. Conductive EPDM jacket. 3. Insulating EPDM layer moulded between the insert and the jacket. 4. Type A - 250 A interface as described by CENELEC EN 50180 and 50181. 5. Conductor connector. Separable plug type Voltage Um (kV) Current Ir (A) Conductor sizes (mm 2 ) (for information only) min. max. 151SP K151SP 12 24 200 200 16 16 95 95 5 2 223 mm Dia. 54 mm 4 1 3
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
9
ApplicationSeparable straight plugdesigned to connect polymericinsulated cable to cable.Mates with the elbow, straightand branch joint connectors.
Up to 24 kV - 200 A
151SPINTERFACE A
STRAIGHT PLUG
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
Technical characteristics• The thick conductive EPDM
jacket provides a total safe totouch screen which ensuressafety for personnel.
• Each straight plug is testedfor AC withstand and partialdischarge prior to leaving thefactory.
4. Type A - 250 A interfaceas described by CENELECEN 50180 and 50181.
5. Conductor connector.
Separableplugtype
VoltageUm(kV)
CurrentIr
(A)
Conductor sizes (mm2)(for information only)
min. max.151SPK151SP
1224
200200
1616
9595
5
2223 mm
Dia.54 mm
4
1
3
michael ryan
New Logo
10
Kit contentsThe complete (K)151SP straightplug kit comprises the followingcomponents:
The kit also comprises lubricant, wipers,installation instructions and crimp chart.
Straight plug housing(K)151SPH-W
Conductorcontact
151SPC-X
Cableadaptor
11TL
+ + (K)151SP-W-X+11TLstraight plug kit
=
Ordering instructionsSelect the part numberwhich gives the best centringto the cable core insulationdiameter and substitute Xusing table X, according to theconductor size and type.Add a 'K' for use up to 24 kV.