Top Banner
New Methods for Monitoring Neutral Grounding Resistors Rahim Jafari – Western University Mital Kanabar and Ilia Voloh – GE Grid Solutions Tarlochan S. Sidhu – The University of Ontario Institute of Technology Presented by: Matt Proctor – GE Grid Solutions The 71st Annual Conference for Protective Relay Engineers
22

New Methods for Monitoring Neutral Grounding Resistorsprorelay.tamu.edu/.../3/2018/04/...Neutral-Grounding-ResistorsPDF.pdf · Neutral Grounding Resistors (NGR) NGR failure replaces

Jun 19, 2018

Download

Documents

buihanh
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: New Methods for Monitoring Neutral Grounding Resistorsprorelay.tamu.edu/.../3/2018/04/...Neutral-Grounding-ResistorsPDF.pdf · Neutral Grounding Resistors (NGR) NGR failure replaces

New Methods for Monitoring Neutral Grounding Resistors

Rahim Jafari – Western University

Mital Kanabar and Ilia Voloh – GE Grid Solutions

Tarlochan S. Sidhu – The University of Ontario Institute of Technology

Presented by: Matt Proctor – GE Grid Solutions

The 71st Annual Conference for Protective Relay Engineers

Page 2: New Methods for Monitoring Neutral Grounding Resistorsprorelay.tamu.edu/.../3/2018/04/...Neutral-Grounding-ResistorsPDF.pdf · Neutral Grounding Resistors (NGR) NGR failure replaces

Outline

• Neutral Grounding Resistors (NGR)• Importance of NGR Monitoring• Existing NGR Monitoring Methods• Proposed NGR monitoring for configuration 1 • Proposed NGR monitoring for configuration 2 • Conclusions

Page 3: New Methods for Monitoring Neutral Grounding Resistorsprorelay.tamu.edu/.../3/2018/04/...Neutral-Grounding-ResistorsPDF.pdf · Neutral Grounding Resistors (NGR) NGR failure replaces

Neutral Grounding Resistors (NGR)

NGRs are used to control Transient Overvoltages, limit ground overcurrent , and consequent issues.

Page 4: New Methods for Monitoring Neutral Grounding Resistorsprorelay.tamu.edu/.../3/2018/04/...Neutral-Grounding-ResistorsPDF.pdf · Neutral Grounding Resistors (NGR) NGR failure replaces

Neutral Grounding Resistors (NGR)

NGRs Fail due to corrosion, lightning, temperature variation, high frequency local oscilla tions, extended

service life, welding defection, vibration, etc [3].

[4] of the paper

Page 5: New Methods for Monitoring Neutral Grounding Resistorsprorelay.tamu.edu/.../3/2018/04/...Neutral-Grounding-ResistorsPDF.pdf · Neutral Grounding Resistors (NGR) NGR failure replaces

Neutral Grounding Resistors (NGR)

NGR failure replaces advantages of resistance grounding with disadvantages of ungrounded or solidly grounded systems. Without NGR monitoring, there is no indication that whether the system is properly grounded or not .

Importance of NGR Monitoring

Page 6: New Methods for Monitoring Neutral Grounding Resistorsprorelay.tamu.edu/.../3/2018/04/...Neutral-Grounding-ResistorsPDF.pdf · Neutral Grounding Resistors (NGR) NGR failure replaces

Existing NGR Monitoring Methods

Page 7: New Methods for Monitoring Neutral Grounding Resistorsprorelay.tamu.edu/.../3/2018/04/...Neutral-Grounding-ResistorsPDF.pdf · Neutral Grounding Resistors (NGR) NGR failure replaces

Existing NGR Monitoring Methods

Passive Methods:

Monitor R or I of the NGR using the voltage and current of the neutral system that exist due to inherent asymmetry of the system.

Mostly cover faulted condition

Page 8: New Methods for Monitoring Neutral Grounding Resistorsprorelay.tamu.edu/.../3/2018/04/...Neutral-Grounding-ResistorsPDF.pdf · Neutral Grounding Resistors (NGR) NGR failure replaces

Existing NGR Monitoring Methods

Active Methods:

Monitor Ror I of NGR using signal injectionto neutral.

Only cover unfaulted condition

Page 9: New Methods for Monitoring Neutral Grounding Resistorsprorelay.tamu.edu/.../3/2018/04/...Neutral-Grounding-ResistorsPDF.pdf · Neutral Grounding Resistors (NGR) NGR failure replaces

Existing NGR Monitoring Methods

Passive-Active Methods:

Effective Combination of passive and active methods.

Cover both faulted and unfaulted conditions(Continuous Monitoring)

Page 10: New Methods for Monitoring Neutral Grounding Resistorsprorelay.tamu.edu/.../3/2018/04/...Neutral-Grounding-ResistorsPDF.pdf · Neutral Grounding Resistors (NGR) NGR failure replaces

Proposed method for Configuration 1

Configuration 1 – A new passive monitoring method based on V0, VN, and IN.

Page 11: New Methods for Monitoring Neutral Grounding Resistorsprorelay.tamu.edu/.../3/2018/04/...Neutral-Grounding-ResistorsPDF.pdf · Neutral Grounding Resistors (NGR) NGR failure replaces

Monitoring Logics in unfaulted condition:

1- Opposite variation of VN3rd and V03rdand

2- Faster acceleration of V03rd than the VN3rd

OR

Slowly activated 0-15% generator sta tor ground protection functions.

Proposed method for Configuration 1

Page 12: New Methods for Monitoring Neutral Grounding Resistorsprorelay.tamu.edu/.../3/2018/04/...Neutral-Grounding-ResistorsPDF.pdf · Neutral Grounding Resistors (NGR) NGR failure replaces

Monitoring Logic in faulted condition:

Proposed method for Configuration 1

Page 13: New Methods for Monitoring Neutral Grounding Resistorsprorelay.tamu.edu/.../3/2018/04/...Neutral-Grounding-ResistorsPDF.pdf · Neutral Grounding Resistors (NGR) NGR failure replaces

Failed-Short NGR in unfaulted condition. Failed-open NGR in unfaulted condition.

Proposed method for Configuration 1

Page 14: New Methods for Monitoring Neutral Grounding Resistorsprorelay.tamu.edu/.../3/2018/04/...Neutral-Grounding-ResistorsPDF.pdf · Neutral Grounding Resistors (NGR) NGR failure replaces

Low injection hardware test setup (Playback)

Proposed method for Configuration 1

Monitoring method incorporated into an availablegenerator protection relay and tested

Page 15: New Methods for Monitoring Neutral Grounding Resistorsprorelay.tamu.edu/.../3/2018/04/...Neutral-Grounding-ResistorsPDF.pdf · Neutral Grounding Resistors (NGR) NGR failure replaces

Catastrophically activated 0-15% generator sta tor ground protection functions:Result: Ground fault a t 5% of the generator sta tor winding (4.17ms < 5ms)

Proposed method for Configuration 1

Page 16: New Methods for Monitoring Neutral Grounding Resistorsprorelay.tamu.edu/.../3/2018/04/...Neutral-Grounding-ResistorsPDF.pdf · Neutral Grounding Resistors (NGR) NGR failure replaces

Slowly activated 0-15% generator sta tor ground protection functions:Result: Failed-short NGR Alarm (9.9ms > 5ms)

Proposed method for Configuration 1

Page 17: New Methods for Monitoring Neutral Grounding Resistorsprorelay.tamu.edu/.../3/2018/04/...Neutral-Grounding-ResistorsPDF.pdf · Neutral Grounding Resistors (NGR) NGR failure replaces

A new passive-Active monitoring method based on V0, Vinj, IN, and Iinj.

Proposed method for Configuration 2

Needed Current Sensor

Page 18: New Methods for Monitoring Neutral Grounding Resistorsprorelay.tamu.edu/.../3/2018/04/...Neutral-Grounding-ResistorsPDF.pdf · Neutral Grounding Resistors (NGR) NGR failure replaces

Proposed method for Configuration 2

Monitoring Logics:

1- Unfaulted condition: R=real(Z20Hz)

70% < R < 130%

2- Faulted condition: R=real(Z60Hz)

70% < R < 130%

Page 19: New Methods for Monitoring Neutral Grounding Resistorsprorelay.tamu.edu/.../3/2018/04/...Neutral-Grounding-ResistorsPDF.pdf · Neutral Grounding Resistors (NGR) NGR failure replaces

Failed-Short NGR in unfaulted condition.

Proposed method for Configuration 2

Page 20: New Methods for Monitoring Neutral Grounding Resistorsprorelay.tamu.edu/.../3/2018/04/...Neutral-Grounding-ResistorsPDF.pdf · Neutral Grounding Resistors (NGR) NGR failure replaces

Failed-open NGR in unfaulted condition.

Proposed method for Configuration 2

Page 21: New Methods for Monitoring Neutral Grounding Resistorsprorelay.tamu.edu/.../3/2018/04/...Neutral-Grounding-ResistorsPDF.pdf · Neutral Grounding Resistors (NGR) NGR failure replaces

Conclusions

1- NGRs fail and need to be monitored.2- Integrity of NGR can be monitored with zero cost If

3rd harmonic voltage exists in neutral of unit-connected generators.

3- If unit-connected generators are equipped with sub-harmonic signal injection based generator sta tor ground protection, NGR monitoring can be provided by only an additional current sensor.

4- Both of the proposed NGR monitoring methods can be incorporated into digita l protective relays.

Page 22: New Methods for Monitoring Neutral Grounding Resistorsprorelay.tamu.edu/.../3/2018/04/...Neutral-Grounding-ResistorsPDF.pdf · Neutral Grounding Resistors (NGR) NGR failure replaces

Thank You

Questions?