Top Banner
Effect of generation loss and Frequency Response Characteristics (FRC) on tie-line flow to Southern Region under various scenarios and Target setting for FRC and introduction of secondary control in Indian power system
22

NEW Grid

Feb 24, 2016

Download

Documents

zena

Effect of generation loss and Frequency Response Characteristics (FRC) on tie-line flow to Southern Region under various scenarios and Target setting for FRC and introduction of secondary control in Indian power system. Assumptions: Initial frequency: 50.00 Hz - PowerPoint PPT Presentation
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: NEW Grid

Effect of generation loss and Frequency Response Characteristics (FRC)

on tie-line flow to Southern Region under various scenarios

and

Target setting for FRC and introduction of secondary control in Indian power system

Page 2: NEW Grid

NEW Grid

SR Grid

Generation: 93500 MW

Load: 90000 MW

Export to SR: 3500 MW

Generation: 26500 MW

Load: 30000 MW

Import from NEW: 3500 MW

Assumptions:

• Initial frequency: 50.00 Hz

• Capacity on bar in NEW Grid

93500/0.85 = say 110000 MW

• Capacity on bar in SR grid

26500/0.85 = 31200 MW say

• Frequency Response of load3% of load per Hz change uniform

• Governor droop 5% wherever primary response is

there viz. 40% load per Hz

• Losses ignored for simplicity

3500 MW

Page 3: NEW Grid

Effect of 1000 MW generation loss on tie-line flow to SR and frequency under various scenarios

S no Incident No primary response in the entire

system(A)

50% primary

response in the entire

grid(B)

50% primary

response in NEW grid

only(C )

50% primary response in SR grid only

(D)

---------------Frequency and tie-line flow change--------1 1000 MW

generation loss in NEW grid

49.7222 Hz250 MW reduction in flow to South

49.9684 Hz225 MW reduction in flow to South

49.9606 Hz35 MW reduction in flow to South

49.8984 Hz725 MW reduction in flow to South

2 1000 MW generation loss in SR grid

49.7222 Hz750 MW increase in flow to South

49.9684 Hz780 MW increase in flow to South

49.9609 Hz965 MW increase in flow to South

49.8963 Hz280 MW increase in flow to South

Page 4: NEW Grid

Observations to note• Primary response is important on account of– Frequency stabilization post disturbance (case A1 & A2 vs others)– Minimize Under Frequency Relay (UFR) operations– Frequency stabilization in case of islanding of systems

• Primary response cannot and does not– Influence tie-line loading under contingencies (A1/B1, A2/ B2); – hourly boundary flow change problem will remain; load-

shedding will gradually get replaced by economy interchange over certain hours of the day as prevailing in systems worldwide.

• Automatic Generation Control (AGC), if available, would bring down the tie-line loading to schedule in 8-10 minutes.

• Skewed primary response can deteriorate tie-line loading– Case C2 and D1

Page 5: NEW Grid

Frequency Bias, B• Area Control Error (ACE) equationACE = (NIA- NIS) – 10B (FA - FS) - IME

– Where NIA is Actual Net Interchange

– NIS is Scheduled Net Interchange – B is Control Area Bias – FA is Actual Frequency

– FS is Scheduled Frequency

– IME is Interchange (tie line) Metering Error B should ideally be greater than or equal to ß, the control area

frequency response (better to have slight over-correction).traditionally 1% of peak load/generation per 0.1 Hz

Page 6: NEW Grid

What does 1% of peak load/generation per 0.1 Hz translate to?• Governor droop setting is typically 5% which

translates to 100% load change over 2.5 Hz frequency variation viz. 40% per Hz or 4% per 0.1 Hz.

• Bias B of 1% per 0.1 Hz translates to 25% of ideal response of 4% per 0.1 Hz.

Page 7: NEW Grid

Even for the ENTSOE system with mean generation of the order of 306 GW,the overall FRC is of the order of 26000 MW/Hz or 20-25 % of ideal response.

So ideal response appears to be a myth!!

Page 8: NEW Grid

Reasons for decline in frequency response• Steam turbine generators operating on “sliding pressure” or “boiler-

follower” control and/or with “valves wide-open” (VWO) operation. • Blocked governors on nuclear units for licensing reasons. • Less heavy manufacturing in North America (proportionally fewer

large motor loads and a reduction in “load rejection”). • Variable-speed drives on motors that do not provide the traditional

“load rejection”. • A larger proportion of combined cycle units on the system• In the past, many Control Areas carried full reserves for their

individual largest contingency and some for multiple contingencies. De-regulation and competitive pressures have ended both of these practices.

NERC: Frequency Response white paper

Page 9: NEW Grid

Setting Target Frequency Response Obligations

NERC Reliability Standard Attachment A of BAL-003-1: Frequency Response and BiasSetting Standard

Page 10: NEW Grid

Setting Target Frequency Response Obligations

NERC Reliability Standard Attachment A of BAL-003-1: Frequency Response and BiasSetting Standard

Each control area target Frequency Response Obligation is worked out as

Page 11: NEW Grid

FRC Target in the Indian context• Minimum frequency: 49.8 Hz• First Stage of Under Frequency: 49.2 Hz• Largest contingency: 4000 MW UMPP • FRC > 4000 MW/0.6 Hz or 6666 MW/Hz if UFRs are not to

operate• Assuming 25% margin this works out to

– 8333 MW/Hz• Load response would be adequate only if All India load would

reach 280 GW• Target would double if minimum frequency touches 49.5 Hz in

normal course• 8333 MW/Hz might be only 16-17% of ideal response of the

order of 50,000 MW/Hz.

Page 12: NEW Grid

Secondary Control

• Secondary control– Tight control on deviations…….CERC is moving in this

direction through pricing deviations and zero crossing– Area Control Error (ACE) could be introduced once FRC

computations are on a sound footing and publicized so that Bias B can be fixed for each control area

– Automatic Generation Control (AGC) could be introduced in phases• Outer loop operating from RLDCs to ISGS for frequency control and

inter-regional tie line control• Inner loop operating from SLDCs to intra state generating stations

for reducing control area ACE.

Page 13: NEW Grid

Thank you

Page 14: NEW Grid

Computations for tie-line flows under various scenarios indicated above

Page 15: NEW Grid

Case A1: 1000 MW generation loss in NEW Grid and no primary response in the entire grid; only 3% per Hz load response

• Load response of NEW Grid: 0.03*90000 MW= 2700 MW/Hz; Load response of SR Grid= 0.03*30000 MW = 900 MW/Hz; Combined load response= 3600 MW/Hz

• Primary response NEW grid = NIL; SR grid primary response = NIL; Combined primary response = NIL

• Stabilized frequency = 50 Hz-(1000/3600) Hz = 49.7222 Hz• Post disturbance

– Gen in NEW Grid = 93500-1000 = 92500 MW– Load in NEW Grid = 90000 MW-(0.2778 x 2700) MW = 89250 MW– Export to SR Grid = 92500 MW -89250 MW = 3250 MW

– Gen in SR Grid = 26500 MW (no change)– Load in SR Grid = 30000-(0.2778 x 900) = 29750 MW– Import from NEW Grid = 29750 MW-26500 MW = 3250 MW

• Thus tie-line flow reduces from 3500 MW to 3250 MW. Viz. 250 MW

Page 16: NEW Grid

Case A2: 1000 MW generation loss in SR Grid and no primary response in the entire grid; only 3% per Hz load response

• Load response of NEW Grid: 0.03*90000 MW= 2700 MW/Hz; Load response of SR Grid= 0.03*30000 MW = 900 MW/Hz; Combined load response= 3600 MW/Hz

• Primary response NEW grid = NIL; SR grid primary response = NIL; Combined primary response = NIL

• Stabilized frequency = 50 Hz-(1000/3600) Hz = 49.7222 Hz• Post disturbance

– Gen in NEW Grid = 93500 (no change)– Load in NEW Grid = 90000 MW-(0.2778 x 2700) MW = 89250 MW– Export to SR Grid = 93500 MW -89250 MW = 4250 MW

– Gen in SR Grid = 26500 MW-1000 MW = 25500 MW– Load in SR Grid = 30000-(0.2778 x 900) = 29750 MW– Import from NEW Grid = 29750 MW-25500 MW = 4250 MW

• Thus tie-line flow increases from 3500 MW to 4250 MW viz. 750 MW

Page 17: NEW Grid

Case B1: 1000 MW generation loss in NEW Grid and 50% primary response in the entire grid; 3% per Hz load response

• Load response of NEW Grid: 0.03*90000 MW= 2700 MW/Hz; Load response of SR Grid= 0.03*30000 MW = 900 MW/Hz; Combined load response= 3600 MW/Hz

• Primary response NEW grid = 109000 MW capacity on bar after tripping of 1000 MW x 0.40 x 0.50 = 21800 MW/Hz ; SR grid primary response = 31200 MW capacity on bar x 0.40 x 0.50= 6240 MW/Hz; Combined primary response = 28040 MW/Hz

• Stabilized frequency = 50 Hz-(1000/(3600 + 28040) Hz = 49.9684 Hz• Post disturbance

– Gen in NEW Grid = 93500-1000 + (0.0316 x 21800) = 93190 MW– Load in NEW Grid = 90000 MW-(0.0316 x 2700) MW = 89915 MW– Export to SR Grid = 93190 MW -89915 MW = 3275 MW

– Gen in SR Grid = 26500 MW + (0.0316 x 6240) = 26697 MW– Load in SR Grid = 30000-(0.0316 x 900) = 29972 MW– Import from NEW Grid = 29972 MW-26697 MW = 3275 MW

• Thus tie-line flow reduces from 3500 MW to 3275 MW. Viz. 250 MW

Page 18: NEW Grid

Case B2: 1000 MW generation loss in SR Grid and 50% primary response in the entire grid; 3% per Hz load response

• Load response of NEW Grid: 0.03*90000 MW= 2700 MW/Hz; Load response of SR Grid= 0.03*30000 MW = 900 MW/Hz; Combined load response= 3600 MW/Hz

• Primary response NEW grid = 110000 MW capacity on bar x 0.40 x 0.50 = 22000 MW/Hz ; SR grid primary response = 30200 MW capacity on bar after tripping of 1000 MW x 0.40 x 0.50= 6040 MW/Hz; Combined primary response = 28040 MW/Hz

• Stabilized frequency = 50 Hz-(1000/(3600 + 28040) Hz = 49.9684 Hz• Post disturbance

– Gen in NEW Grid = 93500 + (0.0316 x 22000) = 94195 MW– Load in NEW Grid = 90000 MW-(0.0316 x 2700) MW = 89915 MW– Export to SR Grid = 94195 MW -89915 MW = 4280 MW

– Gen in SR Grid = 26500 MW-1000 + (0.0316 x 6040) = 25691 MW– Load in SR Grid = 30000-(0.0316 x 900) = 29972 MW– Import from NEW Grid = 29972 MW-25691 MW = 4281 MW

• Thus tie-line flow increases from 3500 MW to 4280 MW. Viz. 780 MW

Page 19: NEW Grid

Case C1: 1000 MW generation loss in NEW Grid and 50% primary response in NEW Grid only; 3% per Hz load response

• Load response of NEW Grid: 0.03*90000 MW= 2700 MW/Hz; Load response of SR Grid= 0.03*30000 MW = 900 MW/Hz; Combined load response= 3600 MW/Hz

• Primary response NEW grid = 109000 MW capacity on bar after tripping of 1000 MW x 0.40 x 0.50 = 21800 MW/Hz ; SR grid primary response = 0 MW/Hz; Combined primary response = 21800 MW/Hz

• Stabilized frequency = 50 Hz-(1000/(3600 + 21800) Hz = 49.9606 Hz• Post disturbance

– Gen in NEW Grid = 93500-1000 + (0.0394 x 21800) = 93359 MW– Load in NEW Grid = 90000 MW-(0.0394 x 2700) MW = 89894 MW– Export to SR Grid = 93359 MW -89894 MW = 3465 MW

– Gen in SR Grid = 26500 MW (no change)– Load in SR Grid = 30000-(0.0394 x 900) = 29965 MW– Import from NEW Grid = 29965 MW-26500 MW = 3465 MW

• Thus tie-line flow reduces from 3500 MW to 3465 MW. Viz. 35 MW

Page 20: NEW Grid

Case C2: 1000 MW generation loss in SR Grid and 50% primary response in NEW Grid only; 3% per Hz load response

• Load response of NEW Grid: 0.03*90000 MW= 2700 MW/Hz; Load response of SR Grid= 0.03*30000 MW = 900 MW/Hz; Combined load response= 3600 MW/Hz

• Primary response NEW grid = 110000 MW capacity on bar x 0.40 x 0.50 = 22000 MW/Hz ; SR grid primary response = 0 MW/Hz; Combined primary response = 21800 MW/Hz

• Stabilized frequency = 50 Hz-(1000/(3600 + 22000) Hz = 49.9609 Hz• Post disturbance

– Gen in NEW Grid = 93500 + (0.0391 x 22000) = 94360 MW– Load in NEW Grid = 90000 MW-(0.0391 x 2700) MW = 89895 MW– Export to SR Grid = 94360 MW -89895 MW = 4465 MW

– Gen in SR Grid = 26500 MW-1000 MW = 25500 MW– Load in SR Grid = 30000-(0.0391 x 900) = 29965 MW– Import from NEW Grid = 29965 MW-26500 MW = 4465 MW

• Thus tie-line flow increases from 3500 MW to 4465 MW. Viz. 965 MW

Page 21: NEW Grid

Case D1: 1000 MW generation loss in NEW Grid and 50% primary response in SR Grid only; 3% per Hz load response

• Load response of NEW Grid: 0.03*90000 MW= 2700 MW/Hz; Load response of SR Grid= 0.03*30000 MW = 900 MW/Hz; Combined load response= 3600 MW/Hz

• Primary response NEW grid = 0 MW/Hz ; SR grid primary response = 31200 MW capacity on bar x 0.40 x 0.50 = 6240 MW/Hz; Combined primary response = 6240 MW/Hz

• Stabilized frequency = 50 Hz-(1000/(3600 + 6240) Hz = 49.8984 Hz• Post disturbance

– Gen in NEW Grid = 93500-1000 = 92500 MW– Load in NEW Grid = 90000 MW-(0.1016 x 2700) MW = 89726 MW– Export to SR Grid = 92500 MW -89726 MW = 2774 MW

– Gen in SR Grid = 26500 MW + (0.1016 x 6240) = 27134 MW– Load in SR Grid = 30000-(0.1016 x 900) = 29909 MW– Import from NEW Grid = 29909 MW-27134 MW = 2775 MW

• Thus tie-line flow reduces from 3500 MW to 2775 MW. Viz. 725 MW

Page 22: NEW Grid

Case D2: 1000 MW generation loss in SR Grid and 50% primary response in SR Grid only; 3% per Hz load response

• Load response of NEW Grid: 0.03*90000 MW= 2700 MW/Hz; Load response of SR Grid= 0.03*30000 MW = 900 MW/Hz; Combined load response= 3600 MW/Hz

• Primary response NEW grid = 0 MW/Hz ; SR grid primary response = 30200 MW capacity on bar after tripping of 1000 MW x 0.40 x 0.50 = 6040 MW/Hz; Combined primary response = 6040 MW/Hz

• Stabilized frequency = 50 Hz-(1000/(3600 + 6040) Hz = 49.8963 Hz• Post disturbance

– Gen in NEW Grid = 93500 MW (no change)– Load in NEW Grid = 90000 MW-(0.1037 x 2700) MW = 89720 MW– Export to SR Grid = 93500 MW -89720 MW = 3780 MW

– Gen in SR Grid = 26500 MW -1000 + (0.1037 x 6240) = 26126 MW– Load in SR Grid = 30000-(0.1037 x 900) = 29906 MW– Import from NEW Grid = 29906 MW-26126 MW = 3780 MW

• Thus tie-line flow increases from 3500 MW to 3780 MW. Viz. 280 MW