NEW EFFICIENCY STANDARD

PRESENTATION BY

Bhalchandra BansodRegional Manager-Industrial

[email protected]

+919766342489

Page 2: NEW EFFICIENCY STANDARD PRESENTATION BY Bhalchandra Bansod Regional Manager-Industrial bbansod@baldor.com +919766342489.

INDIAN STANDARS SCENARIO

INDIAN STANDARS SCENARIO

IS8789(1978, REVISED 1998) IS SUPERCEDED BY IS12615(1996, REVISED 2004)

IS8789 MOTORS ARE NOT MANUFACTURED BY REPUTED MANUFACTURERS

IS12615 PRESENTLY USES IEC60034-2 EFFICIENCY MEASUREMENT METHOD.

IS12615 IS JUST REVISED EFFECTIVE JUNE 2011

REVISED STANDARD USES IEC60034-2-1 METHOD OF EFFICIENCY MEASUREMENT.

Page 3: NEW EFFICIENCY STANDARD PRESENTATION BY Bhalchandra Bansod Regional Manager-Industrial bbansod@baldor.com +919766342489.

TOMMORROWS EFFICIENCIES TOMMORROWS EFFICIENCIES

IS12615 -2011 IS12615-2004

IE1 Eff2

IE2 Eff1

IE3 Premium Eff

IE4 Super Premium

Page 4: NEW EFFICIENCY STANDARD PRESENTATION BY Bhalchandra Bansod Regional Manager-Industrial bbansod@baldor.com +919766342489.

75

80

85

90

95

100

1.1

2.2

5.5

11

18.5 30 45 75

110

187

250

340

Eff

icie

nc

y

Power kW

IEC / NEMA Comparison

EPAct

NEMA Premium

EFF2

EFF1

EFF3

Efficiency Comparison across the GlobeEfficiency Comparison across the Globe

Page 5: NEW EFFICIENCY STANDARD PRESENTATION BY Bhalchandra Bansod Regional Manager-Industrial bbansod@baldor.com +919766342489.

EFFICIENCY MEASUREMENT IS APPROXIMATE

EFFICIENCY MEASUREMENT IS APPROXIMATE

Page 6: NEW EFFICIENCY STANDARD PRESENTATION BY Bhalchandra Bansod Regional Manager-Industrial bbansod@baldor.com +919766342489.

EFFICIENCY MEASUREMENT METHODEFFICIENCY MEASUREMENT METHOD

Motor Loaded by Generator Input given equal to output by Name

plate efficiency Stator resistance is measured to calculate

Stator copper loss Slip is measured to calculate rotor copper

loss Friction and windage loss assumed as 1%

of output Stray Loss assumed as 0.5% of Output. Input-losses=Output and

Output/Input=Efficiency

Page 7: NEW EFFICIENCY STANDARD PRESENTATION BY Bhalchandra Bansod Regional Manager-Industrial bbansod@baldor.com +919766342489.

Motor Power

kW IEC 60034-2 IEC 619720.75 0.50 3.001.1 0.50 2.991.5 0.50 2.992.2 0.50 2.983.7 0.50 2.975.5 0.50 2.967.5 0.50 2.9411 0.50 2.9215 0.50 2.89

18.5 0.50 2.8622 0.50 2.8430 0.50 2.7837 0.50 2.7245 0.50 2.6655 0.50 2.5875 0.50 2.4495 0.50 2.30110 0.50 2.16150 0.50 1.88

Assumed stray load losses (% of full-load power)

NEW STANDARD ASSUMES MUCH HIGHER STRAY LOSSES

NEW STANDARD ASSUMES MUCH HIGHER STRAY LOSSES

Stray load losses are due to Magnetic transfer loss in the air gap between the stator and rotor

Page 8: NEW EFFICIENCY STANDARD PRESENTATION BY Bhalchandra Bansod Regional Manager-Industrial bbansod@baldor.com +919766342489.

IS12615 REVISIONIS12615 REVISION IN LINE WITH HARMONISED

GLOBAL STADARD IEC60030-30.

LARGE RANGE FROM 0.37KW TO 375KW.

INCLUSION OF 6 POLE MOTORS

REVISED PUBLICATION IN JUNE 2011

PROPOSED WITHDRAWL OF IE1- JAN 2012

PROPOSED WITHDRAWL OF IE2- JAN 2014

INTRODUCTION OF IE3- JAN 2014

INTRODUCTION OF IE4- TO BE DECIDED

Page 9: NEW EFFICIENCY STANDARD PRESENTATION BY Bhalchandra Bansod Regional Manager-Industrial bbansod@baldor.com +919766342489.

Super E Gives Better Part Load Efficiencies.

Nema Super E compared with Eff2

Super E Gives Better Part Load Efficiencies.

Nema Super E compared with Eff2

50 HP, 4 POLE MOTOR

05

101520253035404550556065707580859095

100105110

0 25 50 75 100 125

% Load

% E

ffici

ency

NEMA PREMIUM

EFF2(IEC)

Page 10: NEW EFFICIENCY STANDARD PRESENTATION BY Bhalchandra Bansod Regional Manager-Industrial bbansod@baldor.com +919766342489.

Upgrading even one, 1 kW motor to a Premium Efficient motor gives double benefit

of Energy Savings and Carbon credits..IN PAT..

Upgrading even one, 1 kW motor to a Premium Efficient motor gives double benefit

of Energy Savings and Carbon credits..IN PAT..

Every year will eliminate:

1 Drum of Oil from being burned

250 Kg of coal from being burned

Up to 800 gms. of carbon emissions from being released into the atmosphere

and....

or....

Page 11: NEW EFFICIENCY STANDARD PRESENTATION BY Bhalchandra Bansod Regional Manager-Industrial bbansod@baldor.com +919766342489.

PREMIUM EFFICIENCY INSIDEPREMIUM EFFICIENCY INSIDE

High Quality Ball Bearing, reduce friction and vibration

Patented Lube-Lok retainer grease seal on both end

Locked bearing reduces endplay and minimizes energy loss in axial movement

How to improve motor Efficiency and provide longer life?

FRICTION LOSS REDUCTION

Page 12: NEW EFFICIENCY STANDARD PRESENTATION BY Bhalchandra Bansod Regional Manager-Industrial bbansod@baldor.com +919766342489.

PREMIUM EFFICIENCY INSIDEPREMIUM EFFICIENCY INSIDE

Fan & Fan cover designed for optimum cooling and quieter operation

Smaller fan generate less losses

Smaller fan can be used due to cooler operation

How to improve motor Efficiency and provide longer life?

WINDAGE LOSS REDUCTION

Page 13: NEW EFFICIENCY STANDARD PRESENTATION BY Bhalchandra Bansod Regional Manager-Industrial bbansod@baldor.com +919766342489.

PREMIUM EFFICIENCY INSIDEPREMIUM EFFICIENCY INSIDE

More Wire volume

Improved slot design

ISR (Inverter Spike Resistant) magnet wire is up to 100 times more resistant to voltage spikes

End turns laced both end

Low temp. raise (< 80°C)

Class F insulation systems

Each 10°C below max allowed temperature double insulation life

How to improve motor Efficiency and provide longer life?

STATOR COPPER LOSS REDUCTION

Page 14: NEW EFFICIENCY STANDARD PRESENTATION BY Bhalchandra Bansod Regional Manager-Industrial bbansod@baldor.com +919766342489.

PREMIUM EFFICIENCY INSIDEPREMIUM EFFICIENCY INSIDE

Improved Rotor insulation

High-pressure die cast aluminum Rotor

Rotor dynamically balanced to IEEE 841 vibration limits as standard (0.08 in/sec). This reduces energy losses in vibrations.

How to improve motor Efficiency and provide longer life?

ROTOR LOSS REDUCTION

Page 15: NEW EFFICIENCY STANDARD PRESENTATION BY Bhalchandra Bansod Regional Manager-Industrial bbansod@baldor.com +919766342489.

PREMIUM EFFICIENCY INSIDEPREMIUM EFFICIENCY INSIDE

Thinner lamination

Improved steel properties for lower losses and also allow same performance after rewind

Optimized air gap. (Hardened and thicker inside shaft)

More steel - Longer stack

How to improve motor Efficiency and provide longer life?

IRON AND STRAY LOSS REDUCTION

Page 16: NEW EFFICIENCY STANDARD PRESENTATION BY Bhalchandra Bansod Regional Manager-Industrial bbansod@baldor.com +919766342489.

What Motors To ReplaceWhat Motors To Replace

Non Branded

Old motors having no efficiency written on name plate(IS8789)

New motors having lower efficiecy on name plate

Motors which are rewound more than once.

Page 17: NEW EFFICIENCY STANDARD PRESENTATION BY Bhalchandra Bansod Regional Manager-Industrial bbansod@baldor.com +919766342489.

WHY BALDOR MOTORSWHY BALDOR MOTORS

Online Greasing facility even for 1 HP motor.

All motors are Inverter ready by Default.

Highest levels of efficiencies IN THE WORLD, Ex stock at Pune/Mumbai/Ahmedabad warehouse.

Customised Compact Motors

Motors and Drives Packages like Cooling Towers to replace the Gearbox with Direct Drives.

Motors with IEC Dimensions for exact replacement.

Distributor in Major Cities.

Service Centers in Major Cities.

Page 18: NEW EFFICIENCY STANDARD PRESENTATION BY Bhalchandra Bansod Regional Manager-Industrial bbansod@baldor.com +919766342489.

High Mechanical Maintenance

More components to fail over time:– Gearbox failures– Oil leaks & contamination– Failed & misaligned drive shafts– Excessive vibration– Additional replacement time due

to large mounting frame

Conventional Cooling Tower Control– Lightly loaded majority

of the time– Peak load for short

durations– Started across the line

• High inrush currents• Mechanical stresses

Conventional Cooling Tower Drives

Page 19: NEW EFFICIENCY STANDARD PRESENTATION BY Bhalchandra Bansod Regional Manager-Industrial bbansod@baldor.com +919766342489.

• IP56 Protection with Enpro Sealing+ Flinger• Permanent Magnet Laminated Yoke Sync

Motor• Encapsulated winding.• Online Greasing once in a year• Unity power factor• 13% Guaranteed Savings at Full Speed.• Upto 50% Energy savings at Low rpm• Installation at Ruchi Infra Kakinada.

New Direct Drive Technology

Page 20: NEW EFFICIENCY STANDARD PRESENTATION BY Bhalchandra Bansod Regional Manager-Industrial bbansod@baldor.com +919766342489.

Affinity Laws for Centrifugal LoadsAffinity Laws for Centrifugal Loads

100%90%80%70%60%50%40%30%

100%73%51%34%22%13%

6%3%

Speed VolumeHorsepower

Required Pressure/

Head

100%81%64%49%36%25%16%

9%

100%90%80%70%60%50%40%30%