Top Banner
UST Compliance Handbook and Documenta/on Toolkit Underground Storage Tank Owners and Operators State of Nevada
13

Nevada UST manual · UST Compliance Handbook and Documentaon Toolkit Underground Storage Tank Owners and Operators State of Nevada

Apr 04, 2018

Download

Documents

phamdan
Welcome message from author
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Page 1: Nevada UST manual · UST Compliance Handbook and Documentaon Toolkit Underground Storage Tank Owners and Operators State of Nevada

UST Compliance HandbookandDocumenta/onToolkitUndergroundStorageTankOwnersandOperatorsStateofNevada

Page 2: Nevada UST manual · UST Compliance Handbook and Documentaon Toolkit Underground Storage Tank Owners and Operators State of Nevada

www.arcnevada.com

801‐597‐6873

Edi/on1.0

NicoleHaynesMcCoy,PhD

COPYRIGHT2012

AllRightsReserved

ARC Nevada

Page 3: Nevada UST manual · UST Compliance Handbook and Documentaon Toolkit Underground Storage Tank Owners and Operators State of Nevada

CONTENTSChapter1:Introduc1ontoUnderground

‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐StorageTankCompliance 1ChapterOverview 1EnvironmentalandRegulatoryContext 1

RegulatedSubstances 2PetroleumProducts 2HazardousSubstances 3

PurposeofThisHandbook 3Organiza1on 4

Chapter2:USTProgramRulesand‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐Regula1ons 5

ChapterOverview 5USTRegulatoryStatus 5ProvisionsoftheEnergyActof2005 5Regula/onsforCompliance 6

OwningorOpera1ngaUSTinNevada 7PermitsandFees 7FinancialResponsibility 7DeliveryProhibi/on 8SecondaryContainment 9No/fica/on 11Record‐keeping 11

RequirementsforTankClosure 12TemporaryClosure 12PermanentClosure 13

‐‐‐Chapter3:ABCOperatorRequirements 15ChapterOverview 15OperatorRequirements 15ClassAOperator 15ClassBOperator 15ClassCOperator 16UnmannedFacili/es 16

TrainingandRegistra1on 17ClassAandBOperators 17ClassCOperators 17RetrainingforNon‐Compliance 17

‐‐‐‐‐‐‐Chapter4:USTSystemComponents 19ChapterOverview 19

USTSystem 19USTSystemComponents 19USTSystemFunc1on 21

‐‐‐Chapter5:SpillandOverfillPreven1on 23ChapterOverview 23Introduc1on 23Table5.1Spillandoverfillpreven3on:Equipmentrequirements 23

SpillPreven1on 24SpillBuckets 24

OverfillPreven1on 25OverfillPreven/onEquipment 26

Table5.2.Overfillpreven3ondevices:Func3onalrequirements 30

Owner/OperatorResponsibili1esinPreven1ngOverfills 30

Table5.3Spillandoverfillpreven3ondevices:Operatorinspec3on 31

‐‐‐‐Chapter6:ReleaseDetec1onforTanks 33ChapterOverview 33Introduc1on 33LeakDetec/onFramework 34

Table6.1.Leakdetec3onfortanks:Requirementoverview 34

In‐TankMonitoring(Automa1cTankGauging) 35ATGPeriodic(Sta/c)Tes/ng 36ATGCon/nuousTes/ng 37TankTestLimita/onsforATGs37

Table6.2.In‐TankMonitoring(Automa3cTankGauging) 38

SecondaryContainmentwithInters11alMonitoring 39ManualInters//alMonitoring 39Con/nuousInters//alMonitoring 40

Table6.3.SecondaryContainmentwithInters33alMonitoring 41

Sta1s1calInventoryReconcilia1on 42SIRProcess 42

Table6.4.Sta3s3calInventoryReconcilia3on(SIR) 44

Page 4: Nevada UST manual · UST Compliance Handbook and Documentaon Toolkit Underground Storage Tank Owners and Operators State of Nevada

InventoryControlandTankTightnessTes1ng 45

Table6.5.InventoryControlandTankTightnessTes3ng 46

ManualTankGauging 47Table6.6.ManualTankGaugingwithTankTightnessTes3ng 48

GroundwaterMonitoring 49VaporMonitoring 49Table6.7.Releasedetec3onfortanks:Systemscompared 51Table6.8.Leakdetec3onfortanks:Operatorinspec3on 52

‐‐‐‐Chapter7:ReleaseDetec1onforLines 53ChapterOverview 53Introduc1on 53Table7.1.LeakDetec3onforPiping:Requirementoverview 53

TypesofSuc/onPiping 54PressurizedPipingSystems 56CatastrophicReleaseDetec/on 57SecondaryLeakDetec/on 59

Table7.2.Lineleakdetec3on:Methodandtes3ngrequirements 63

Table7.3.LeakDetec3onforPiping:Operatorinspec3on 64

ContainmentSumps 64SumpComponents 65

Table7.4.SumpsandDispensers:Operatorinspec3on 66

‐‐‐‐‐‐‐‐‐‐‐‐‐Chapter8:CorrosionProtec1on 67ChapterOverview 67Table8.1.CorrosionProtec3on:Requirementoverview 67

Introduc1ontoCorrosion 68CathodicProtec1on 68CorrosionProtec1onRequirementsbyUSTSystemMaterial 70TankMaterials 70PipingMaterials 71

Table8.2.Corrosionprotec3onsummarybymaterial 72

Tes1ngCPSystems 72Table8.3.Cathodicprotec3on:Operatorinspec3on73

‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐Chapter9:Compa1bility 75ChapterOverview 75Compa1bility 75Table9.1.Compa3bilityoverview 75

Alterna1veFuels 76Ethanol 77Biodiesel 78

‐‐‐‐‐‐‐‐‐‐Chapter10:EmergencyResponse 79ChapterOverview 79Introduc1on 79Table10.1.Emergencyresponse:Requirementoverview 79

AlarmsorUnusualCondi1ons 80AlarmResponse 80UnusualCondi/ons 80

SuspectedReleaseInves1ga1on 81Inves/ga/onSteps 81

Release/SpillResponse 82EmergencyPlanning 82

‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐Chapter11:MarinaUSTs 83ChapterOverview 83Introduc1on 83Table11.1.Marinas:RequirementOverview 83

OwningorOpera1ngaMarinaUSTinNevada 84

TankRequirements 85SecondaryContainment 85Tankfillingequipment 86Monitoring 86

PipingandValveRequirements 86EmergencyShutoff 86SecondaryContainment(forpiping) 86PipingatFloa/ngMarinas 87

DispensingEquipment 87RequiredDailyInspec/on 87RequiredMonthlyInspec/on87

CorrosionProtec1on 88‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐‐Defini1ons 89

Page 5: Nevada UST manual · UST Compliance Handbook and Documentaon Toolkit Underground Storage Tank Owners and Operators State of Nevada

Chapter 5: Spill and Overfill Prevention

Chapter OverviewThischapterfocusesonspillandoverfillpreventionduringdeliveries.Topicscoveredinclude:‣ Spillandoverfillprotectionequipment

suchasspillbuckets,automaticshutoffdevices,ballfloatvalves,andoverfillalarms;

‣ Owner/operatorresponsibilitiesinpreventingoverfills;

‣ Operatorinspectionofspillandoverfillpreventionequipment.

IntroductionRecallthatpreventionofspillsandoverfillsisacriticalcomponentofthepreventionanddetectionrequirementsforUSTownersandoperators.TheU.S.Environmental

ProtectionAgency(EPA)designedpartofthetechnicalregulationsforundergroundstoragetank(UST)systemstoprevent

releasesfromUSTs.TheregulationsrequireUSTstobeprotectedfromspills,overfills,andcorrosion.

Spilloroverfillmeansanyreleaseofaregulatedsubstancethatoccurs:(a) Abovethesurfaceofthegroundata

facilitywhereastoragetankislocated;(b) Fromadispenserformotorfuelabovethe

sheervalveforthedispenser;orc) Fromanyancillaryequipmentforthetanksystemthat:

(1) Isnotincludedinanysystemforthedetectionofaleak;and

(2) Isaccessibletovisualinspection (fromNAC459.996)

TABLE5.1SPILLANDOVERFILLPREVENTION:EQUIPMENTREQUIREMENTS

SPILLANDOVERFILLPREVENTIONEQUIPMENTREQUIREMENTSSPILLANDOVERFILLPREVENTIONEQUIPMENTREQUIREMENTS

What EnsureyourUSTisproperlyequippedwithspillandoverfillpreventionequipment.

How Spillprevention:spillbuckets‐properlyinstalled,sized,keptclean,dryandingoodconditionOverfillprevention:automaticshutoffdevices,ballfloatvalves,oroverfillalarms.

When Devicesinstalledatinstalla/on;ongoingmaintenanceitem.

Why Federal40CFR280.20PerformancestandardsfornewUSTsystems.(c)Spillandoverfillpreventionequipment.40CFR280.21UpgradingofexistingUSTsystems.(d)Spillandoverfillpreventionequipment.40CFR280.30Spillandoverfillcontrol.

Who Owner/Operatorresponsibleforhavingproper,functionalequipment.

NOTE IfanUSTneverreceivesmorethan25gallonsata3me,theUSTdoesnothavetomeetthespillprotec3onrequirements.Manysmallusedoiltanksfallintothiscategory.

23

SAMPLE

Copyrighted Material ARC Nevada, LLC www.arcnevada.com

Page 6: Nevada UST manual · UST Compliance Handbook and Documentaon Toolkit Underground Storage Tank Owners and Operators State of Nevada

Spill Prevention ManyreleasesatUSTsitescomefromspills.Spillsoftenoccuratthefillpipewhenthedeliverytruck’shoseisdisconnected.Althoughthesespillsareusuallysmall,repeatedsmallreleasescancausesignificantenvironmentalproblems.Humanerrorcausesmostspills.Thesemistakescanbeavoidedbyfollowingindustrystandardpracticesfortankfilling.Ifyouandthedeliverydriverfollowstandardpractices,nearlyallspillscanbeprevented.Forthisreason,federalUSTregulationsrequirethatyoufollowindustrystandardpracticesfortankfilling.

SpillBucketsEPArequiresthatallfillpipeshaveaspillpreventiondeviceinstalledaroundthem.OnlyUSTsystemsthatarefilledby25gallonsorlessareexemptedfromthisrequirement.

Spillbuckets,alsocalledcatchmentbasins,arecontainedsumpsatthefilland/orvaporrecoveryconnectionpoints.

Thespillbucketshouldbelargeenoughtocontainwhatmayspillwhenthedeliveryhoseisuncoupledfromthefillpipe.Atypicaldeliveryhosecanholdabout14gallonsoffuel.

Spillbucketsarenormallylocatedontopofthetankandarepositionedbelowgrade.Thetopofawell‐constructedspillbucketisslightlyabovegradetohelpdrainrainandsurfacewaterawayfromthespillbucketopening.Thatpreventsunwantedliquid

fromgettingintothespillbucketonitswaytoyourtank.

Thereisnocapacityrequirementforspillbucketsandmostrangeinsizefrom5to

25gallons,withlids1‐2feetindiameter.Some/messpillbucketlidswillbecolor‐

codedtohelpthedriverputtherightproductintotherighttank.

Spillbucketsmustbeliquid/ghtinorderforthemtofunc/onasintended(andasrequiredbyEPA)—tokeepsmallspillsattheendofadeliveryfromgefngintothe

soil.Asshowninthediagramsthatfollow,spillbucketsmaycomeequippedwitheitherapumpordraintoremovefuel.Drainvalvesallowexcessfueltobedraineddirectlybackintothetank.Aslongasthedrainvalveis/ght,thisdeviceshouldn’tposeaproblemtoopera/ons.Inaddi/ontospilledfuel(andperhapsevenmorefrequently),waterandsedimentcangetintospillbuckets.Ifyourspillbucket

Federalregulations(40CFR280.20(c))requireUSTsystemstobeequippedwithbothspillpreventionandoverfillpreventionequipment.

Federalregulation40CFR280.20(c)(i)requiresspillpreventionequipmentthatpreventsareleaseofproducttotheenvironmentwhenthetransferhoseisdetachedfromthefillpipe(forexample,aspillcatchmentbasin).

24

Spillbuckets,alsocalledcatchmentbasins,comeinmanydifferentdesignsandsizes.BesuretoselectonethatisappropriateforyourUST.

SAMPLE

Copyrighted Material ARC Nevada, LLC www.arcnevada.com

Page 7: Nevada UST manual · UST Compliance Handbook and Documentaon Toolkit Underground Storage Tank Owners and Operators State of Nevada

comeswithadrainthatflowsdirectlyintothetank,youdon’twanttodrainwaterintoyourtank.Waterinthetankisa fuelqualityissue,butanevengreaterconcernisthatwatercanruststeeltanksfromtheinside out,and,inexcess,canimpactyourabilitytodetectleaks.

Ifyourspillbucketdidn’tcomeequippedwithapump,youcanpurchaseasparkfreehandpumptodrawthewaterandsedimentoutofthespillbucket.Note:Ifthismixturecontainsfuelorchemicals,makesureyoudisposeofitproperly,asitmaybeconsideredhazardouswaste.

Spillbucketstakealotofabusefromweather,spilledfuel,drivers,snowplowsandotherfactors.TheyagequicklycomparedtootherpartsoftheUST.Checkthemregularlyandbepreparedtoreplacethemperiodically.

Spillbucketsdon’tkeepthefueloutofthegroundiftheyarenotliquidtight.Monitorthemforcracksorholesinthebottom,keepaneyeonthesealaroundthefillpipe,

Spillbucketcontainingspilledfuel.

andlookforcracksinthebellows.Don’tleavefuelinthem;itdegradestheplasticandcanseepoutthesealorthreadsovertime.Keepthemcleansoyoucandrainexcessfuelintothetankwithoutcontaminatingyourfuel.

Ifaspillbucketisfullofwateritcannotcontainaspill.

Whatshouldyoulookfor?Anyoneofthefollowing:

‣ waterorfuelinthebottom–removeit;‣ debrisofanykindthatdoesn’tbelong

there–removeit;‣ brokenordamageddrainvalve–repairit;

and‣ anyholesorcracksinside‐wallsor

bottom–replacethespillbucket.

Overfill PreventionIfdeliverydriversorUSTownersmakefueldeliverymistakes,atankcanbeoverfilledquicklyandlargevolumescanbereleasedatthefillpipeandthroughloosefittingsonthetopofthetankoralooseventpipe.

Overfillsusuallyresultfromhumanerrorandcanbeavoidedifeveryoneinvolvedinthefueldeliveryfollowsindustrystandardpracticesfortankfilling.

25

Spillbucketequippedwithdrain(A)andaspillbucketequippedwithapump(B).

A B

SAMPLE

Copyrighted Material ARC Nevada, LLC www.arcnevada.com

Page 8: Nevada UST manual · UST Compliance Handbook and Documentaon Toolkit Underground Storage Tank Owners and Operators State of Nevada

Overfillsusuallyreleasemuchlargervolumesthanspills.Whenatankisoverfilled,largevolumescanbereleasedatthefillpipeandthroughloosefittingsonthetopofthetankoralooseventpipe.Note:Thetightnessofthesefittingsnormallyisnotaproblemifthetankisnotfilledbeyonditscapacity.

Accidentallyoverfillinganundergroundstoragetankcanhappenveryquicklyiftheproperoverfillprotectionmeasuresarenotfollowed.

Thinkaboutthefillingprocess:Ahosefroma10,000‐gallontankertruckisconnectedtoafillpipe.Ifthefillprocessisgravity‐driven(andmostare),thedriverturnsavalvetoopenahoseandthefuelflowsin–atabout300gallonsaminute.

Nowimagineifthere’snotenoughroominthetank—someonedidn’tmeasurethecorrectliquidlevel,orthewrongtankisbeingfilled:ineithersituation,anoverfillwilloccur–atabout300gallonsaminute!

Ownersandoperatorscanpreventthepotentialforoverfillproblemsby:

‣ ensuringthereisenoughroominthetankforthedeliverybeforethedeliveryismade;

‣ watchingtheentiredeliverytopreventoverfillingorspilling;and

‣ usingoverfillprotectiondevices.

OverfillPreventionEquipmentYourUSTmusthaveoverfillprotection.

The water tap on

a bathtub flows at approximately 5 gallons per minute. Filling the average American bathtub at

300 gallons per minute would take

less than 10 seconds!

NewUSTsmusthaveoverfillprotectiondeviceswhentheyareinstalled.OlderUSTsshouldhavebeenupgradedby1998withspillandoverfillpreventiondevices.

Overfillpreventiondevicesworkinoneofthreeways:Placedinthefillpipe,theystoptheflowoffuel.Installedintheventpipe,theysloworrestricttheflowoffuel(butdonotstopitentirely).Alarmsneitherstopnorrestrictflowinandofthemselves,butalertthedriver(andpotentiallytheoperator)thatthetankisnearlyfull.

Thethreemaintypesofoverfillprotectiondevicesare:

1. Automaticshutoffdevices(stopstheflowoffuel)

2. Ballfloatvalves(slowstheflowoffuel)3. Overfillalarms(alertsthedriver).

AutomaRcShutoffDevicesOfthethreetypesofoverfillprotectiondevices,theautomaticshutoffdevice(ASD)istheonlyonecapableofcompletelystoppingtheflowoffuel.DependingonthetypeofASDinstalled,itmayslowtheflowoffuelbeforestoppingitorbesettotrip,stoppingtheflowabruptly.

Federalregulation40CFR280.20(c)(ii)requiresoverfillpreventionequipmentthatwill:

‣ Automaticallyshutoffflowintothetankwhenthetankisnomorethan95percentfull;or

‣ Alertthetransferoperatorwhenthetankisnomorethan90percentfullbyrestrictingtheflowintothetankortriggeringahigh‐levelalarm;or

‣ Restrictflow30minutespriortooverfilling,alerttheoperatorwithahigh‐levelalarm1minutebeforeoverfilling,orautomaticallyshutoffflowintothetanksothatnoneofthefittingslocatedontopofthetankareexposedtoproductduetooverfilling.

26

SAMPLE

Copyrighted Material ARC Nevada, LLC www.arcnevada.com

Page 9: Nevada UST manual · UST Compliance Handbook and Documentaon Toolkit Underground Storage Tank Owners and Operators State of Nevada

Builtintothefillpipe,theASDisessentiallyatubeinsideofwhichisavalve(oftencalleda“flapper”valve)connectedtoafloat.Asthefuellevelrises,itliftsthefloatfromaverticaltohorizontalposition.Whenthetankisnearlyfull(inNevada,therequiredsettingisatamaximumof95%capacity),thefloatarmisatfullheight,andtheshutoffvalveiscompletelyclosed.

IfyouhaveanASDinstalledonyourtank,lookdownthefillopeningandseeifyoucanspotthemechanism.

Ifyouhaveatwo‐valvesystem,afterthemainvalvecloses,abypassvalveallowsasmallamountofproducttoflow(5to10

gallonsperminute)sothatthehosecanbedrained.Ifthedeliverycontinuesbeyondacertainlevel,thebypassvalvealsocloses.

Anopenautoma/cshutoffvalve(A),andclosed(B).

A B

Oncethebypassvalvecloses(onatwo‐valvesystem)orthemainvalveshuts(onaone‐valvesystem),fuelistrappedinthehose.

Thispreventsanoverfill,butthebackupoffuelupthehosemeansthereisnoplaceforthefueltogo(recallthatmosttanksaregravityfilledandfuelcan’tbepumpedbackintothetruck).Asaresult,thehosemustremainconnectedtothetankuntilfuellevelsinthetankdropenoughforthefloattorelax,releasingtheshutoffvalveandallowingtheremainderofthefueltoflowintothetank.

Ifanoverfilldoesoccur,solongasthedeliveryhoseistight,thereshouldn’tbeaspillontheground—atleastuntilthehoseisdisconnected.Beawarethatthereisalotmorefuelinthehosethanwillfitinthespillbucket.

HavinganASDdoesn’tguaranteethatanoverfillwon’thappen.Commonsourcesoffailureinclude:

‣ Brokendevice;‣ Devicebypassedbystickorotherobject;

and

Automatic shutoff devices are commonly referred to as

drop-tube devices or “flapper”

valves.

27

Ballfloatvalve.Overfillalarm. Automa/cshutoffdevices.

SAMPLE

Copyrighted Material ARC Nevada, LLC www.arcnevada.com

Page 10: Nevada UST manual · UST Compliance Handbook and Documentaon Toolkit Underground Storage Tank Owners and Operators State of Nevada

‣ Deviceinstalledwrongoratincorrectheight.

Sometimesattemptsaremadetooverridetheoverfilldevicebyusingastickorotherobjecttoforcethefloatmechanismdownandkeepthevalveopen.Thiscanoccurifthevalvehasactivatedanddeliverypersonnelareforcedtowaituntilthefuelclearsthehose,orifthevalvehasn’tshutofftheflowoffuel,butisslowingdownanormaldelivery.

Abypassedorbrokendeviceincreasesthechancesofanoverfillthatresultsinasignificantspill.Beawarethatowners(notdrivers)areliableforspillsandoverfillsthatoccurduringdelivery.

EPAsproposedregulationsrequirethatyouhavetheautomaticshutoffcheckedforproperproductlevelheightsettingatleastonce,andthenonceayearhaveatechnicianorthirdpartyinspectorvisuallyinspectthedevice.Keepacopyofyourtestresultsandcorrectanyproblems.

EPAalsoproposestorequirethatUSTownersandoperatorsinspectoverfillpreventionequipmentforfunctionandfillpipesforpotentialobstructionsevery30days.

BallFloatValves

Recallthatalltanksareventedandthattheventpipespreventthebuildupofpressureinthetankbyallowingpetroleumvaporstoescape.Duringafueldelivery,thetank“exhales”outtheventasthefuelcomingintothetankdisplacesthepetroleumvaporsandpushesthemout.

Ballfloatsconsistofashortlengthofpipethatextendsdownintothetopofthe

Ball float valves

are also known as float-vent valves.

tankfromtheventopening.Typicallyawirecagecontainingahollowballisfastenedtothelowerendofthepipe.Theballsitsbelowtheendofthepipewithinthewirecage.Aslongastheproductisbelowthatoftheball,thetankventpiperemainsopenandthetankcanbreathe.

Ifthefuellevelistoohigh,theballfloatsupandblockstheventopening(inNevada,theballfloatvalvemustac/vate

whenthetankisnomorethan90%full).

Withthetankbeingunableto“exhale”asitnormallydoes,itbecomesmoredifficulttofillthetank,whichshouldalertthedrivertoclosethetruck’sshutoffvalve.

Whenyourelyonaballfloatventvalve,youwanttowatchoutforthefollowing:

‣ Theballismissing.Thecagecanrustoutorbecomebentoutofshape;

‣ Theballwon’tfloat.Itcanrustontothecageorcorrodethroughandfillwithproduct;

‣ Thevalveisinstalledwrongoratincorrectheight;

‣ Aremotefillopeningorothertank‐topriserisnotliquid/ght.Thisallowsthetanktoexhaleevenauerthefuellevel

Illustra/onofhowaballfloatventvalveoperates.

28

SAMPLE

Copyrighted Material ARC Nevada, LLC www.arcnevada.com

Page 11: Nevada UST manual · UST Compliance Handbook and Documentaon Toolkit Underground Storage Tank Owners and Operators State of Nevada

pushestheballintotheventopening,preven/ngapressurebuildupfromsignalingthatthetankisfull.

Ballfloatsareincompa/blewith:

‣ Suctionpiping–productcanbeforcedouttheaireliminator,

‣ Pressurizeddeliveries–itcouldblowyourtankoutattheseams,

‣ Stage1coaxialdroptube–itcanpushfuelupthevaporreturnintersticeandbackintothetruck.

Ifyourfacilityhastwo‐pointvaporrecoverywithaballfloat,ensurethatthevaporrecoverypoppetremainsfreeofrocksorotherobstructionsasthesedisabletheballfloatdeviceandcanbeanairqualityviolation.

Wesuggestthatyouhavetheballfloatventvalvecheckedforproperproductlevelheightsefngatleastonce,andthenonceayearhaveatechnicianorthirdpartyinspectorvisuallyinspectthedevicetomakesuretheballiss/lldoingwhatit’s supposedtodo.Keepacopyofyourtestresultsandcorrectanyproblems.

OverfillAlarmsOverfillalarmsdon’tstopfuelfromflowing,buttheydoalertthedriverthatanoverfillincidentisabouttooccur.Ofthethreeoverfillpreventiontechnologies,theyarethemostversatileinthattheycanbeusedwitheithergravityorpumpeddeliveriesandwithtightorlooseconnections.

Overfillalarmsuseprobesinstalledinthetank(seeillustration)toactivateanalarmwhenthetankiseither90percentfullorwithin1minuteofbeingoverfilled.Typicallyoverfillalarmsaretiedintoanautomatictankgaugingsystem(ATG).Thealarmmaybeeitherablinkingredlight,a

siren(mostcommon),orboth.Makesurethealarmislocatedwherethedrivercanseeorheariteasily.

Althoughnotrequired,someoverfillalarms aresettoactivateatmultiplelevels:

‣ 90%full:Highproductalarm(requiredminimumsetting–youhaveaboutaminute);

‣ 95%full:High‐highproductalarm(youhavelessthan1minute);and

‣ 100%full:Maxproductalarm(it’stoolate).

Overfillalarmsworkonlyiftheyalertthedriverattherighttimeandthedriverrespondsquickly.Problemswithoverfillalarmscaninclude:

‣ Overfillsettingincorrectlyprogrammedsothealarmgoesofftoolate.

‣ Communicationtothetankgaugeisn’tworking.

‣ Alarmboxmalfunctioningorbroken.Driverisn’tnearbytohear/seealarmandrespond.

‣ Overfillalarmactivatesbutnooneresponds.

‣ Overfillalarmconnectedtoanelectricalcircuitthatcanbeturned“off”orthatdoesnotalertifacircuitbreakeristripped.

Wesuggestthatyouhavetheoverfillalarmcheckedforproperproductlevelheightsettingatleastonce,andthenonceayearhaveatechnicianorthirdpartyinspectorfunction‐testthealarmbox,thewiring,andthefloat.Keepacopyofyourtestresultsandcorrectanyproblems.

29

SAMPLE

Copyrighted Material ARC Nevada, LLC www.arcnevada.com

Page 12: Nevada UST manual · UST Compliance Handbook and Documentaon Toolkit Underground Storage Tank Owners and Operators State of Nevada

TABLE5.2.OVERFILLPREVENTIONDEVICES:FUNCTIONALREQUIREMENTS

OVERFILLPREVENTIONDEVICES:FUNCTIONALREQUIREMENTSOVERFILLPREVENTIONDEVICES:FUNCTIONALREQUIREMENTS

What USTmusthaveatleastonedevicefromthelistbelow:‣ automaticallyshutoffflowintothetankwhenthetankisnomorethan95

percentfull;or‣ restricttheflowintothetankortriggeringahigh‐levelalarmwhenthetank

isnomorethan90percentfull;or‣ restrictflow30minutespriortooverfilling,alerttheoperatorwithahigh‐

levelalarm1minutebeforeoverfilling,orautomaticallyshutoffflowintothetank.

How ‣ Automaticshutoffdevices(mustshutoffflowwhentankis≤95%full)‣ Ballfloat(vent)valves(mustrestrictflowwhentankis≤90%full)‣ Overfillalarms(mustalarmwhentankis≤90%full)

When Requiredattankinstalla/onfortanksinstalledauer1986;Requiredupgradetoexis/ngtankssince1998

Why Federal40CFR280.20(c)(ii)‐ Spillandoverfillpreven/onequipment40CFR280.30‐SpillandOverfillControl(Owner’sResponsibili3es)

Who Ownerresponsibleforhavingproperdevice.

NOTE Manufacturersdonotrecommendusingballfloatvalveswithsuc3onpiping,pressurizeddelivery,orcoaxialStageIvaporrecovery.

Owner/OperatorResponsibilitiesinPreventingOverfillsAsthepersonwhoislegallyresponsibleforensuringthatoverfillsdonothappenduringfueldeliveriesatyourUSTfacility,developawridendeliveryprocedurethatallpersonnelinvolvedinthedeliveryprocessfollow.Thisprocedureshouldincludethefollowingmeasures:

Ensurethereisenoughroominthetankbeforeeachdelivery.Measurethefuellevelinyourtank(s)beforeeachdelivery.Knowtheworkingcapacityofyourtank(s).(Theworkingcapacityistheamountoffuelthetankwillholdwithouttriggering

theoverfillpreven/ondevice).Ifyouhaveatankgauge,orderyourfuelbasedonthe90%ullagereadingfromthetankgauge.

Monitorallfueldeliveriesfrombeginningtoend.Deliverydriversmaybemorecarefulifsomeoneiswatching.Usesecuritycamerastomonitorthedeliveryprocessandletthedriversknowthattheyareoncamera.

Inspectyourspillbucketsrou1nely.Ifnecessary,cleanbeforeandaiereachproductdelivery.

Respondtoalloverfillindica1ons.Ifatankgaugeisaler/ngtoanoverfill,makesurebothyourstaffandthedriverrespondappropriately.Neverignoreanalarm.Anoverfillmeansyouhaveordered

30

SAMPLE

Copyrighted Material ARC Nevada, LLC www.arcnevada.com

Page 13: Nevada UST manual · UST Compliance Handbook and Documentaon Toolkit Underground Storage Tank Owners and Operators State of Nevada

toomuchfuel;re‐evaluatethemethodsusedtocalculatehowmuchfueltoordertopreventafutureoverfill(orpoten/alspill).

Prepareforspillsthatcanoccurdespiteawell‐func1oningoverfillpreven1onsystem.Hosescanbreak,adrivercandisconnectahosewithoutrealizingthetankisover‐filled,oralooseriser

somewhereonatankcanpreventaballfloatvalvefromfunc/oning.Makesureyouhaveanemergencyplaninplaceforwhattodoifanoverfilloccursandthatdeliverydrivers,operators,andotherpersonnelareawareoftheproceduresandtheirresponsibili/esincaseofanoverfillemergency.

TABLE5.3SPILLANDOVERFILLPREVENTIONDEVICES:OPERATORINSPECTION

SPILLANDOVERFILLPREVENTIONDEVICES:OPERATORINSPECTIONSPILLANDOVERFILLPREVENTIONDEVICES:OPERATORINSPECTIONSPILLANDOVERFILLPREVENTIONDEVICES:OPERATORINSPECTION

What Checkspillandoverfillpreven/onequipmentforfunc/onandobstruc/ons.Checkspillandoverfillpreven/onequipmentforfunc/onandobstruc/ons.

How SpillBuckets‣ Lidsareingoodcondition,fittightly‣ Shouldn’thaveanyvisibleholes,cracks,or

damagedareas‣ Shouldn’tbedeformedorwarped‣ Basinshouldbeclean,dry,andfreefromdebris

OverfillPreventionEquipment‣ Allfillsareunobstructed‣ Automaticshutoffvalvesorballfloats

arepresentandfunctional‣ Overfillalarmisproperlylocatedand

clearlyidentified

When ‣ Required:Atinstallation(ifrequiredbymanufacturer)‣ Proposed:Atinstallation(regardlessofmanufacturer’srequirements)‣ Proposed:Every30days‣ Proposed:Testspillpreventionequipmentatleastonceevery12months

‣ Required:Atinstallation(ifrequiredbymanufacturer)‣ Proposed:Atinstallation(regardlessofmanufacturer’srequirements)‣ Proposed:Every30days‣ Proposed:Testspillpreventionequipmentatleastonceevery12months

Why Federal:40CFR280.37(proposed)40CFR280.35(proposed)

Federal:40CFR280.37(proposed)40CFR280.35(proposed)

Who ClassBOperatorortheirdesignee.ClassBOperatorortheirdesignee.

NOTE Proposedfederalregula3onswillrequireoperator“walkthrough”inspec3onsofspillandoverfillpreven3onequipmentevery30daysandhavespillpreven3onequipmenttestedatleastonceevery12months.

Proposedfederalregula3onswillrequireoperator“walkthrough”inspec3onsofspillandoverfillpreven3onequipmentevery30daysandhavespillpreven3onequipmenttestedatleastonceevery12months.