Second Revision No. 125-NFPA 13-2014 [ Global Comment ] Revise Chapter 22 in accordance with the attached document. Supplemental Information File Name Description Extract_check_Chapter_22_2nd_Draft_Review_SR_.docx 13_SR_125_Chapter_22_edited.docx 13_SR_125_Chapter_22_annex.docx Submitter Information Verification Submitter Full Name: [ Not Specified ] Organization: [ Not Specified ] Street Address: City: State: Zip: Submittal Date: Fri Jun 27 18:25:58 EDT 2014 Committee Statement Committee Statement: The NFPA 13 Extract Task Group has reviewed all of the other NFPA documents referencing sprinklers and updated the extracts in Chapter 22. Response Message: National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara... 2 of 301 10/9/2014 8:39 AM
305
Embed
National Fire Protection Association Report - nfpa.org · PDF fileSecond Revision No. 125-NFPA 13-2014 [ Global Comment ] Revise Chapter 22 in accordance with the attached document.
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
Second Revision No. 125-NFPA 13-2014 [ Global Comment ]
Revise Chapter 22 in accordance with the attached document.
The NFPA 13 Extract Task Group has reviewed all of the other NFPA documents referencing sprinklers andupdated the extracts in Chapter 22.
ResponseMessage:
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
2 of 301 10/9/2014 8:39 AM
Extracts Chapter Edits
Renumber and reorder the subsections of Chapter 22 as follows:
Current Subsection
New Subsection
22.02 2
22.03 3
22.04 4
22.05 5
22.06 6
22.07 7
22.08 8
22.09 9
22.10 10
22.11 11
22.12 12
22.13 13
22.14 15
22.15 17
22.16 18
22.17 20
22.18 24
22.19 25
22.20 26
22.21 27
22.22 28
22.23 29
22.24 31
22.25 32
22.26 33
22.27 34
22.28 35
22.29 36
22.30 37
22.31 14
22.32 16
22.33 19
22.34 21
22.35 22
22.36 23
22.37 30
Chapter 22.1 No changes
Chapter 22.2 (NFPA 30) No changes
Chapter 22.3 (NFPA 30B) No changes
Chapter 22.4 (NFPA 33) 22.4.1.7 should be subsection (2) of 22.4.1.6:
22.4.1.7 6 (2) A wet pipe sprinkler system shall also be provided throughout the spray booth. This system shall meet all the applicable requirements of this standard for Extra Hazard (Group 2) occupancies. [33:9.8.2(3)]
Chapter 22.5 (NFPA 36) No changes
Chapter 22.6 (NFPA 37) No changes
Chapter 22.7 (NFPA 40) 22.7.1.5 through 22.7.1.11 should be subsections of 22.7.1.4 (as they are designated in NFPA 40) also 22.7.1.12
should be included in the list of criteria that need to be met as its section within NFPA 40 is included in the criteria
22.7.1.4 For extended term storage vaults in accordance with Section 6.5.5 of NFPA40, fire protection shall be provided by a deluge system with directional nozzles installed in accordance with NFPA 15 and meeting the criteria in 22.7.1.5 4.1 through 22.7.1.114.9. [40:6.5.6]
22.7.1.5 4.1 Sprinkler systems in existing extended term storage vaults that were in compliance with the provisions of this standard at the time of installation shall be permitted to be continued in use. [40:6.5.6.1] 22.7.1.6 4.2 High-velocity open head nozzles each capable of providing a discharge rate of 1.26 L/sec (20 gpm) at a gauge
pressure of 345 kPa (50 psi) shall be installed. [40:6.5.6.2] 22.7.1.7 4.3 The design shall be based on a discharge density of 28 mm/min (0.68 gpm/ft2) over each face of storage racks. [40:6.5.6.3] 22.7.1.84.4* The nozzles shall have a combined spray pattern capable of covering the face of the film storage racks. [40:6.5.6.4] 22.7.1.9 4.5 The nozzles shall be installed at the top of the storage shelf array, aimed at the opposite shelf array. [40:6.5.6.5] 22.7.1.104.6* Nozzles shall be installed on opposite faces of the storage shelf array in a staggered pattern such that no nozzles are directly opposite one another. [40: 6.5.6.6] 22.7.1.11 4.7 The water supply duration shall be a minimum of 20 minutes. [40:6.5.6.7] 22.7.1.12 4.8 The deluge system shall be activated by a signal from one of the following: [40:6.5.6.8] (1) An air sampling–type smoke detection system (2) A fixed temperature heat sensitive cable
Add new Section 22.7.1.13 4.9 Full water flow shall be discharged from the water spray nozzles within 10 seconds
of reaching the set point actuation of the detection system [40:6.5.6.9.6]
21.8.1 Design Requirements. An automatic sprinkler system protection shall be required for all new laboratories in accordance with the following: (1) Automatic sprinkler system protection for Class A and Class B laboratories shall be in accordance with ordinary hazard (Group 2) occupancies. (2) Automatic sprinkler system protection for Class C and Class D laboratories shall be in accordance with ordinary hazard (Group 1) occupancies. [45:6.2.1.1 6.1.1.1] 21.8.2 Fire sprinklers in laboratory units shall be the quick response (QR) sprinkler type installed in accordance with this standard. [45:6.2.1.2 6.1.1.2]
Chapter 22.9 (NFPA 51) – Delete 22.9.1.1 and renumber section
21.9.1.1 The total gas capacity of nonliquefied flammable gas (e.g., acetylene) shall be permitted to be increased to 56.6 m3 (2000 ft3) per control area under one of the following conditions: (1) In cylinder storage areas that are protected by an automatic sprinkler system and water supply designed in accordance with NFPA 13, furnishing a sprinkler discharge density of at least (10 L/min)/m2 [(0.25 gal/min)/ft2] over a minimum operating area of at least 279 m2 (3000 ft2) with sprinklers located not more than 6.1 m (20 ft) above the floor where the cylinders are stored. (2) In cylinder storage areas that are protected by an automatic
water spray fixed system of equal density, designed in accordance with NFPA 15, Standard for Water Spray Fixed Systems for Fire Protection. [51:4.3.2]
22.9.1.2 split into two sections and changed to read: Make sure reference citing is added
22.9.1.2 Oxygen cylinders connected to one manifold shall be limited to a total gas capacity of 6500 ft2 (184 m2)
[51:5.2.5]
22.9.1.2.1 Two such manifolds with connected cylinders shall be permitted to be located in the same room,
provided the building is protected throughout with an approved automatic sprinkler system designed in
accordance with this standard, furnishing a sprinkler discharge density of at least 0.25 gpm/ft2 (10.2 mm/min) over
a minimum operating area of at least 3000 ft2 (279 m2) with sprinklers located not more than 20 ft (6.1 m) above
the floor where the manifolds are located [51:5.2.5.1]
Add new 22.9.1.3 through 22.9.1.4
22.9.1.3 For Mobile Acetylene Trailer Systems, a deluge sprinkler system shall be provided for MATS fire areas used as indoor and outdoor discharging stations. [51:10.5.8.1.1]
22.9.1.4 Deluge sprinkler systems shall provide a minimum density of 0.3 gpm/ft2 (12.2 mm/min) over the MATS fire area being protected. [51:10.5.8.1.2]
22.9.1.5 The deluge system shall be identified and marked with a sign and shall be activated automatically by a fast-acting fire detection system and also by a manual actuator. [51:10.5.8.1.3]
22.9.1.6 The requirements of 22.9.1.3 shall not apply to existing indoor or outdoor facilities, equipment, structures, or installations where MATS are discharged that existed or were approved for construction or installation prior to the effective date of this standard, provided the MATS are protected with an automatic sprinkler system with a minimum design density of not less than 0.25 gm/ft2 (10.2 mm/min). [51:10.5.8.1.4.1]
22.9.2.1 split into two section and changed to read:
22.9.2.1 In buildings protected by an automatic sprinkler system and water supply designed in accordance with this
standard for an Ordinary Hazard Group 2 or more hazardous occupancy, where the occupancy other than the
cylinder storage is not more hazardous than Ordinary Hazard as defined in this standard, the distance between
designated storage areas shall be permitted to be reduced 50 ft (15.2m). [51:4.3.4.1]
22.9.2.2 If the occupancy in such protected buildings between the designated storage areas is free of combustible
materials, the distance shall be permitted to be reduced to 25 ft (7.6m). [51:4.3.4.2]
Chapter 22.10 (NFPA 51A) Add a new Section
22.10.1.2 Mobile Acetylene Trailer Systems (MATS) at mobile acetylene charging plants, a fire sprinkler system in
accordance with this standard. Extra Hazard Group I shall be installed in the areas occupied by trailers in charging
or discharging stations. [51A:11.2.1.3]
Chapter 22.11 (NFPA 55) Items in the Public Comment of NFPA 55 (same cycle as 13). See excel sheet.
Chapter 22.12 (NFPA 59) No changes
Chapter 22.13 (NFPA 59A) No changes
Chapter 22.14 (NFPA 75) Update reference cite:
22.14.2.1* Information technology equipment rooms and information technology equipment areas located in a sprinklered building shall be provided with an automatic sprinkler system. [75:8.1.1 9.1.1] 22.14.2.2 Sprinkler systems protecting information technology equipment areas shall be valved separately from other sprinkler systems. [75:8.1.3 9.1.3] 22.14.2.3* An automatic sprinkler system or a gaseous fire extinguishing system shall be provided for the protection of the area below a raised floor in an information technology equipment room or information technology equipment area where one or more of the following exist:
1) There is a critical need to protect data in the process, reduce equipment damage, and facilitate return to service.
2) The area below the raised floor contains combustible material.
[75:8.1.1.2 9.1.1.2] Proposed changes in the first draft
22.15 (NFPA 82)
22.15.2 Installation Requirements. 22.15.2.1 Automatic sprinklers shall be provided in incinerator Rooms in accordance with this standard. [82:4.2.7.3 5.2.7.3] 22.15.2.2* Waste and Linen Chutes and Transport Systems. [82:5 6] 22.15.2.2.1 Gravity Waste or Linen Chutes. [82:5.2 6.2] 22.15.2.2.1.1 Lined metal chutes shall be protected internally by automatic sprinklers unless they are lined in accordance with 6.2.2.6.1 in NFPA 82. [82:6.2.2.6.2] 22.15.2.2.1.2 This protection requires that a sprinkler be installed at or above the top service opening of the chute. [82:56.2.6.1.2] 22.15.2.2.1.3 Chute Sprinkler Protection. Automatic sprinklers installed in gravity chute service openings shall be recessed out of the chute area through which the material travels. [82:56.2.6.1.3] 22.15.2.2.1.4 In addition, a sprinkler shall be installed within the chute at alternate floor levels in buildings over two stories in height, with a mandatory sprinkler located at the lowest service level. [82:56.2.6.1.4] 22.15.2.2.1.5 Gravity chutes shall be protected internally by automatic sprinklers unless they are lined in accordance with 6.2.2.6.1 in NFPA 82. [; 82:6.2.6.1.1] 22.15.2.2.1.5 6 Chute Room Automatic Sprinklers. Automatic sprinklers shall be installed in chute discharge rooms. [82:56.2.6.2.1] 22.15.2.2.2 Full Pneumatic Waste and Linen Conveying Systems. [82:56.3] 22.15.2.2.2.1 Full pneumatic-type risers shall be protected internally by automatic sprinklers. [82:56.3.4.1] 22.15.2.2.2.2 A sprinkler shall be required at or above the top loading station and at alternate floor levels in buildings over two stories in height, with a mandatory sprinkler located at the lowest loading station. [82:56.3.4.2] 22.15.2.2.2.3 Sprinklers shall be recessed out of the station area through which the material travels. [82:56.3.4.3] 22.15.2.2.3 Gravity Pneumatic Trash or Linen Conveying Systems. [82:56.4] 22.15.2.2.3.1 Chute Automatic Sprinklers. Where material is to be stored at the bottom of the chute and above the riser discharge damper (above the transport tee), automatic sprinklers shall be installed below the last service door on the chute. [82:56.4.2.3] 22.15.2.2.3.2 Automatic sprinklers shall be installed in chute discharge rooms. [82:56.4.2.4.3] 22.15.2.3 Other Waste Handling Systems. [82:7.4] 22.15.2.3.1 Automatic sprinklers shall be installed in rooms where waste handling systems and equipment are used to transport waste from interim storage areas to waste processing equipment, such as incinerators. [82:67.4.1] 22.15.2.3.2 In locations or rooms where waste handling systems and equipment are used for interim storage of waste only, the rooms shall be sprinklered in accordance with requirements
specified in 22.15.2.4. [82:67.4.2] 22.15.2.4 Waste Compactors. [82:78] 22.15.2.4.1 All chute-fed compactors shall have an automatic sprinkler with a minimum 13 mm (1⁄2 in.) orifice installed in the hopper of the compactor.. [82:78.2.1] 22.15.2.4.2 Sprinklers shall be ordinary temperature-rated sprinklers. [82:78.2.1.1] 22.15.2.4.3 Sprinklers shall be supplied by a minimum 25.4 mm(1 in.) ferrous piping or 19 mm (3⁄4 in.) copper tubing line from the domestic cold water supply or by the building fire protection system. [82:78.2.1.2] 22.15.2.4.4 Sprinkler water pipe shall be protected from freezing in outdoor installations. [82:78.2.1.3] 22.15.2.4.5 Hand-fed compactors located within a building and not operated in conjunction with a chute shall not require installation of an automatic sprinkler in the hopper. [82:87.2.2] 22.15.2.5 Waste and recyclables storage rooms shall be provided with automatic Sprinklers in accordance with this standard. [82:89.3] 22.15.2.6 Rooms in which waste processing equipment is located shall be installed with automatic sprinklers. [82:910.4.1]
22.16 (NFPA 86) No changes
22.17 (NFPA 99) Section 22.17 should be changed to reflect applicability to Class A Hyperbaric Chambers only.
22.17 Health Care Facilities Code, Class A Hyperbaric Chambers
This clarification is necessary since the remainder of section 22.17 applies only to Class A chambers, not Class B or
C chambers.
22.18 (NFPA 130) No changes
22.19 (NFPA 140) Editorial change to include extracted material in the X.2 Installation Requirements format
22.19.1 Design Requirements (Reserved)
22.19.2 Installation Requirements
22.19.2.1 The requirements of NFPA 13 prohibiting obstructions to sprinkler discharge shall not be applicable if approved mitigation is employed. [140:4.11.1.3.1] 22.19.2.2 The requirements of NFPA 13 prohibiting obstructions to sprinkler discharge shall not be applicable if the building sprinkler system meets the design criteria for Extra Hazard,
Group 2. [140:4.11.1.3.2] 22.19.2.3 In any production location building protected by an existing automatic sprinkler system, where solid- or hardceiling sets or platforms are introduced and create an obstruction to sprinkler discharge, the provisions of 22.19.4 or 22.19.5 shall be met. [140:5.11.3] 22.19.2.4* The requirements of NFPA 13 prohibiting obstructions to sprinkler discharge shall not be applicable if approved mitigation is employed. [140:5.11.4] 22.19.2.5* The requirements of NFPA 13 prohibiting obstructions to sprinkler discharge shall not be applicable if the building sprinkler system meets the design criteria for Extra Hazard, Group 2. [140:5.11.5]
22.20 (NFPA 150) Editorial change to:
Section 22.20.1 Design Requirements (Reserved)
Section 22.20.1.1 (Reserved)
22.20.2 Installation Requirements. (Reserved)
21.20.2.1 Quick-response sprinklers shall be utilized in animal housing facilities. [150:9.2.3]
22.21 (NFPA 214) Delete sections 22.21.2.4 and 22.21.2.5.1 as they are duplicates of 22.21.1.4 and 22.21.1.5.1.
22.21.2.4 Combustible Fan Decks. For deluge systems using directional spray nozzles in the pendant position,
provisions shall be made to protect the underside of a combustible fan deck at a minimum rate of 0.15 gpm/ft2
(6.11 mm/min), which shall be included as part of the application rate specified in 22.21.1.2. [214:5.2.4.4]
22.21.2.5.1 These discharge outlets shall be open directional spray nozzles or other approved devices arranged to
discharge 0.50 gpm/ft2 (20.4 mm/min) into the distribution basin horizontally, with some of the spray splashing up
and on the underside of the water basin covers. [214:5.2.4.5.1]
Chapter 22.22 (NFPA 307) No changes
Chapter 22.23 (NFPA 318) Editorial changes
22.23.1.1* Automatic sprinklers for cleanrooms or clean zones shall be installed in accordance with NFPA 13 this
standard and shall…..
22.23.1.2 Automatic sprinkler protection shall be designed and installed in the plenum and interstitial space
above cleanrooms in accordance with NFPA‐13, this standard for a density….
Chapter 22.24 (NFPA 409) Add all material
Edit – check on this
Chapter 22.25 (NFPA 415) 22.25.1.3* Other areas of the airport terminal shall be classified based on the occupancy of the area in
accordance with Chapter 5 of this standard. [415:4.5.1.5]
Add new sections:
22.25.1.4 Water Supply. Water supply from public and private sources shall be adequate to supply maximum
calculated sprinkler demand plus a minimum of 500 gpm (1893 L/min) for hose streams. The supply shall be
available at the rate specified for a period of at least 1 hour. [415:4.5.5]
22.25.1.4.1 Main sizes shall be hydraulically calculated based on the total domestic and fire protection
requirements. Mains shall not be less than 8 in. (203 mm) in diameter except that laterals shall be permitted to be
6 in. (152 mm) in diameter if not over 200 ft. (61 m) long. [415:4.5.5.1]
Chapter 22.26 (NFPA 423) No change
Chapter 22.27 (NFPA 804) Editorial changes
For order consistency, renumber: 22.27.1.4 22.27.1.3 ; 22.27.1.3 22.27.1.4 ; 22.27.1.3.1 22.27.1.4.1 ; 22.27.1.3.2 22.27.1.4.2
22.27.2.2 Cable Concentrations Tunnels
22.27.2.3 Turbine Building Deluge…
Add new section:
22.27.2.4 Cable tunnels over 50 ft (15.2 m) long shall be provided with hose stations and portable fire
extinguishers installed outside the tunnel.[804:10.4.2.4(3)]
Chapter 22.28 (NFPA 805) Editorial changes
For order consistency, renumber: 22.28.2.1 22.28.2.2 ; 22.28.2.2 22.28.2.1
Chapter 22.29 (NFPA 851) No changes
Chapter 22.30 (NFPA 909) Update reference numbers
22.30.1.1* Standard-response sprinklers shall be permitted for use in light-hazard areas. [909:12.4.4.29.12.13.1] 22.30.1.2* Preaction and dry pipe systems shall be designed to minimize the risk of corrosion in accordance with the requirements of 9.12.12.322.30.2.1 through 9.12.12.322.30.2.5 of NFPA 909. [909:9.12.1213.35] 22.30.2.1* Branch lines shall be pitched at least 1⁄2 in. per 10 ft (4 mm/m), and mains shall be pitched at least 1⁄4 in. per 10 ft (2 mm/m). [909:9.12.1213.3.1] 22.30.2.2* Auxiliary drains shall be provided at all low points in accordance with NFPA13 requirements for dry pipe systems and preaction systems subject to freezing. [909:9.12.1213.3.2.1] Edit 22.30.2.3* Where steel pipe is used in dry pipe and preaction systems, the provisions of NFPA 13this standard shall be applied assuming water supplies and environmental conditions that contribute to unusual corrosive properties, and a plan shall be developed to treat the system using one of the following methodsto address piping corrosion.: (1) Install a water pipe that is corrosion resistant (2) Treat all water that enters the system using an approved corrosion inhibitor (3) Implement an approved plan for monitoring the interior conditions of the pipe at established intervals and locations. [909:9.12.1213.3.3]
Chapter 22.31 (NFPA 70 NEC) 2014 No changes
Chapter 22.32 (NFPA 76) 2012 No public inputs
Chapter 22.33 (NFPA 91) 2010 Add section and renumber
22.33.1.1 Any portion of an exhaust system utilizing combustible components or having the potential for combustible residue buildup on the inside, where the duct cross-sectional area is greater than or equal to 75 in.2 (480 cm2), shall be provided with an automatic extinguishing system within the duct and at the duct intake, hood, enclosure, or canopy, or shall be constructed of material listed for use without sprinkler protection. [91:9.1] 22.33.1.2 When a sprinkler system is installed, means shall be provided to prevent water accumulation in the duct or flow of water back to a process subject that could be damaged by water. [91:9.2]
Chapter 22.34 (NFPA 99B) 2015 No changes
Chapter 22.35 (NFPA 120) 2015 Coal Mines – 2nd Draft – Sprinkler Task group revised and reorganized the requirements
Requesting report from the task group to help edit this extract section.
22.37.1 – References NFPA 400 in general – instead of extracting all the material
6.2.1.1.1 ‐ : extract from NFPA 5000. Are we extracting an extract?
Appendix A
Add new:
A22.3.1.1 Dry-pipe or preaction systems are not allowed. Tests have shown that control of a fire involving aerosol products requires immediate application of water when the first sprinkler operates. Fire growth is rapid and, once thoroughly established, cannot be controlled by conventional or ESFR systems.
Any significant delay in sprinkler discharge will allow the fire to overtax the system. Increasing the design area for a dry-pipe or preaction system is not feasible because the delay will allow too many sprinklers to operate, thus overtaxing any practically
designed water supply. Paragraph 5.8.1 should not be interpreted as discouraging the use of a foam-water sprinkler system. As long as the ceiling density is not reduced, the use of a foam-water system does not introduce any known negative effects and could offer some additional benefits in combatting any spill fire that might result. [30B:A.5.8.1]
A22.3.2.1 ESFR ceiling sprinklers are permitted to be used in conjunction with the in-rack sprinkler protection criteria in Table 6.3.2.7(e) through Table 6.3.2.7(l) where the following conditions are met: (1) Roof height does not exceed 9.14 m (30 ft). (2) Storage height does not exceed 7.62 m (25 ft). (3) Clearance between top of storage and sprinkler deflectors is at least 0.91 m (3 ft). (4) Ceiling sprinkler design criterion is 12 sprinklers operating at a gauge pressure of 517 kPa (75 psi). (5) All in-rack sprinklers are quick-response type. [30B:A.6.3.2.9]
A22.4.2 Where does this come from in 33? Delete?
A.22.4.2 The area of sprinkler operation includes all sprinklers within the individual spray area as defined by NFPA 33, 3.3.2.3
Editorial fix:
A.21.4.1.1 Spray application operations should be located only in buildings that are completely protected by an approved system of automatic sprinklers. If located in unsprinklered buildings, sprinklers should be installed to protect spray application processes where practical. Because of the rapidity and intensity of fires that involve spray operations, the available water should be ample to simultaneously supply all sprinkler heads likely to open in one fire without depleting the available water for use by hose streams. Noncombustible draft curtains can be used to limit the number of sprinklers that will open. Even when areas adjacent to coating operations are considered under reasonably positive fire control by adequate automatic sprinkler protection, damage is possible if operations are conducted on floors above those containing contents that are highly susceptible to water damage. Waterproofing and drainage of spray room floors can assist in reducing water damage on floors below. The proper drainage of the large volume of water frequently necessary to extinguish spray finishing room fires often presents considerable difficulty. Automatic sprinklers in spray areas, including the interior of spray booths and exhaust ducts, should be wet pipe, preaction, or deluge system so that water can be placed on the fire in the shortest possible time. Automatic sprinklers in spray booths and exhaust ducts should be of the lowest practical temperature rating. The delay in application of water with ordinary dry pipe sprinklers can permit a fire to spread so rapidly that final extinguishment is difficult without large resulting damage.
The location of the sprinkler heads inside spray booths should be selected with care in order to avoid heads being placed in the direct path of spray and yet afford protection for the entire booth interior. When sprinkler heads are in the direct path of spray, even one day’s operation can result in deposits on the sprinkler heads that insulate the fusible link or choke open head orifices to the extent that sprinklers cannot operate efficiently. Automatic sprinklers should also be located so that areas subject to substantial accumulations of overspray residue are protected. Generally, sprinklers are located no more than 4 ft (1.2 m) from side walls of booths and rooms and from dry overspray collectors (where applicable). Sprinklers in booths or rooms should be on extra hazard occupancy spacing of 90 ft2 (8.4 m2). All sprinklers in spray areas should be controlled by an accessible control valve, preferably an OS&Y valve. [33: A.9.4] A.21.4.2.1 Subsection 21.4.1.1 lists four types of automatic sprinkler systems and requires that the one “most appropriate for the portion of the spray area being protected” be used. Generally, an open-head deluge system provides the highest level of protection, given that all sprinklers in the protected area flow simultaneously. This type of system is most appropriate for large, down-draft, water-wash spray booths when protecting automatic electrostatic spray application zones. Wet pipe automatic sprinkler systems are appropriate for protecting spray booths that utilize nonelectrostatic application processes or operations using listed electrostatic application processes. Wet pipe systems are also generally used to protect exhaust plenums (eliminator or scrubber sections), exhaust ducts, and air recirculation filter houses. Dry pipe systems have been included because some exhaust duct designs include sections that are subject to freezing. Preaction systems have been included because some spray application processes and equipment can be damaged by unwanted water discharge. This damage can be disruptive and costly. Powder spray booths and solvent concentrator (air pollution abatement) systems are examples of systems where it is appropriate to use a preaction system. [33: A.9.4.1] A.21.4.2.1 Automatic sprinklers in spray areas, including the interior of spray booths and exhaust ducts, should be wet pipe, preaction, or deluge system so that water can be placed on the fire in the shortest possible time. Automatic sprinklers in spray booths and exhaust ducts should be of the lowest practical temperature rating. The delay in application of water with ordinary dry pipe sprinklers can permit a fire to spread so rapidly that final extinguishment is difficult without large resulting damage. The location of the sprinkler heads inside spray booths should be selected with care in order to avoid heads being placed in the direct path of spray and yet afford protection for the entire booth interior. When sprinkler heads are in the direct path of spray, even one day’s operation can result in deposits on the sprinkler heads that insulate the fusible link or choke open head orifices to the extent that sprinklers cannot operate efficiently. Automatic sprinklers should also be located so that areas
subject to substantial accumulations of overspray residue are protected. Generally, sprinklers are located no more than 4 ft (1.2 m) from side walls of booths and rooms and from dry overspray collectors (where applicable). Sprinklers in booths or rooms should be on extra hazard occupancy spacing of 90 ft2 (8.4 m2). All sprinklers in spray areas should be controlled by an accessible control valve, preferably an OS&Y valve. [33: A.9.4]
Correct number
A.22.7.1.3 See Figure A.22.7.1.3. The illustration shows the location of sprinkler heads and the decomposition vent. [40: A.6.3]
Fix excessive routing
A.22.19.4 See A.4.11.1.3.1 of NFPA 140. [140: A.5.11.4] Paragraphs 4.11.1.3.1 and 4.11.1.3.2 recognize motion picture and television industry practices that require sets to change constantly and that sets are “temporary” construction not subject to building codes or standards. Solid ceilings that obstruct the stage sprinklers are “flown” (moved) in or out to permit special shooting angles or lighting requirements, often on a scene-by-scene basis. With temporary walls and ceilings, it would be impractical to install a sprinkler system in a constantly changing structure. Therefore, one or more of the following mitigation techniques should be used to compensate for the areas shielded from sprinkler spray by solid or hard ceilings or platforms: (1) Approved and listed heat detectors or smoke detectors can be installed beneath such solid or hard ceilings in excess of 600 ft2 (55.7 m2) in area and platforms in excess of 600 ft2
(55.7 m2) in area and 3 ft (0.9 m) in height. Detectors should be connected to an approved and listed central, proprietary, or remote station service or to a local alarm that will provide an audible signal (i.e., a bell or horn) at a constantly attended location. The detector system, including the alarm panel, is defined as a portable system because it is intended to be reinstalled when platforms or sets are changed. The detectors that are secured to standard outlet boxes and the listed fire alarm panels can be temporarily supported by sets, platforms, or pedestals. Spacing of detectors should be per manufacturers’ requirements. (2) The ceiling can be positioned to allow for the operation of the building’s automatic fire sprinkler system after videotaping, filming, or broadcasting of programs has been completed for the day. (3) Afire watch should be provided when the set is not in use. (4) No combustible materials should be stored under any platforms. Consideration should be given to secure such covered areas with screen wire or other materials that will permit visual inspection and emergency access. (5) Approved/listed fire retardants can be applied beneath combustible platforms. (6) Approved/listed fire retardants can be applied to scenery,
props, framework and deck of combustible platforms, and the hard ceilings of combustible sets. [40:A4.11.1.3.1] A.22.19.5 See A.4.11.1.3.1 of NFPA 14022.19.4. [140: A.5.11.5]
Delete duplicate to A.21.25.1.2
A.21.25.1.3 The exposure to the airport terminal building from the airport ramp is significant. The number of building sprinklers operating from the exposure fire could be greater than the number of building sprinklers operating from an internal ignition source.
Editorial correction
A.22.31.2.3 The intent of the NFPA 70 is to allow sprinkler piping in the room protecting the space covering the floor area that includes the electrical equipment as long as the sprinklers and piping are not located in the zone described by 22.31.2.1. The sprinkler and the piping can be above the zone described by 22.31.2.1, but a shield needs to be installed in this case to protect the electrical equipment from potential leakage. [70:A110.26(E)(1)(c)]
A.22.34.1.11 The quantities and pressure of water for fire extinguishing indicated in 22.34.1.11 are based on limited testing and should be considered subject to change as additional data become available. It is recommended that spray coverage tests be carried out at maximum altitude for manned operations. [99B:A4.5.2.5.1]
Chapter 22 Special Occupancy Requirements
22.1 General.
22.1.1 Application.
22.1.1.1
In addition to the requirements of Chapter 8, Chapters 11 through 22, and Chapter 23, the following special occupancy requirements shall apply.
22.1.1.1.1
All provisions of design criteria in this standard, including design area increases and reductions, shall also apply to these special occupancy requirements.
22.1.1.2
Where the requirements of the reference standard differ from the requirements of this standard, the reference standard shall take precedence.
22.1.2 Definitions.
For terms not defined in Chapter 3, the definitions of the reference standard shall apply.
22.2 Flammable and Combustible Liquids.
22.2.1 Design Requirements.
Sprinkler system discharge criteria for the protection of flammable and combustible liquids shall comply with NFPA 30.
22.2.2 Installation Requirements. (Reserved)
22.3 Aerosol Products.
22.3.1 Design Requirements.
Sprinkler system discharge criteria for the protection of aerosol products shall comply with NFPA 30B.
22.3.2 Installation Requirements.
(Reserved)
22.4 Spray Application Using Flammable or Combustible Materials.
22.4.1 Design Requirements.
22.4.1.1*
The automatic sprinkler system shall be a wet pipe system, a dry pipe system, a preaction system, or an open-head deluge system, whichever is most appropriate for the portion of the spray operation being protected. [33:9.4.1]
22.4.1.2
The automatic sprinkler system shall be designed for Extra Hazard (Group 2) occupancies as defined in NFPA 13.
Exception No. 1: For spray application of styrene cross-link thermoset resins, Section 17.3 of NFPA 33 shall apply.
Exception No. 2: Automatic sprinkler systems for powder coating operations shall be designed for Ordinary Hazard (Group 2), as defined in NFPA 13. [33:9.4.2]
22.4.1.3
The water supply shall be sufficient to supply all sprinklers likely to open in any one fire incident without depleting the available water for use in hose streams. [33:9.4.3]
22.4.1.4
Where sprinklers are installed to protect spray areas and mixing rooms only, water shall be permitted to be supplied from domestic water systems, provided the domestic supply can meet the design criteria of 22.4.1.2. [33:9.4.4]
22.4.1.5
The sprinkler system shall be controlled by a separate, listed indicating valve(s), operable from floor level. [33:9.4.5]
22.4.1.6
Automated liquid electrostatic spray application equipment that is unlisted shall be protected further by the following:
(1) In addition to meeting the requirements in 9.8.1 of NFPA 33, the optical flame detection system shall also activate one of the following over each zone in which fire has been detected:
(a) An open head deluge system designed to discharge a minimum density of 24.4 mm/min (0.6 gpm/ft2)
(b) A carbon dioxide extinguishing system
(c) A dry chemical extinguishing system
(d) A gaseous agent extinguishing system
[33:9.8.2(1)]
22.4.1.7 (2) A wet pipe sprinkler system shall also be provided throughout the spray booth. This system shall meet all the applicable requirements of NFPA 13this standard for Extra Hazard (Group 2) occupancies. [33:9.8.2(3)]
22.4.2* Installation Requirements.
22.4.2.1*
Sprinkler systems protecting stacks or ducts shall meet all of the following requirements:
(1) Sprinklers shall be spaced no more than 3.7 m (12 ft) apart.
(2) If exhaust ducts are manifolded, a sprinkler shall be located in the manifold at the junction of each exhaust duct with the manifold.
(3) Sprinklers shall provide a minimum flow of 114 L/min (30 gpm) per head at a minimum of 1 bar (15 psi) pressure.
(4) Sprinklers shall be ordinary temperature rated, unless required to be higher due to operating temperatures measured in the ducts, in which case the operating temperature shall be at least 28°C (50°F) above the inside temperature of the duct.
[33:9.4.6]
22.4.2.1.1
Stacks and exhaust ducts shall be provided with access openings for inspection and cleaning of sprinklers. [33:9.4.6.1]
22.4.2.1.2
Sprinkler systems protecting stacks and ducts that are subject to freezing shall be of a nonfreezing type or be a manually controlled open-head system. [33:9.4.6.2]
22.4.2.2
Sprinklers shall be protected against overspray residue, either by location or covering, so that they will operate quickly in event of fire. [33:9.4.7]
22.4.2.2.1
Sprinklers shall be permitted to be covered only by cellophane bags having a thickness of 0.08 mm (0.003 in.) or less or by thin paper bags. These coverings shall be replaced frequently so that heavy deposits of residue do not accumulate. [33:9.4.7.1]
22.4.2.2.2
Sprinklers that have been painted or coated by overspray or residues shall be replaced with new sprinklers. [33:9.4.7.2]
22.5 Solvent Extraction Plants. [NFPA 36]
22.5.1* Design Requirements.
22.5.2 Installation Requirements. (Reserved)
22.6 Installation and Use of Stationary Combustion Engines and Gas Turbines.
22.6.1* Design Requirements.
Automatic sprinkler systems shall be designed to provide for a density of 0.3 gpm/ft2 (12.2 mm/min) over the most remote 2500 ft2 (230 m2). [37:11.4.5.1]
22.6.2 Installation Requirements.
22.6.2.1
Sprinklers and spray nozzles shall be spaced at a 100 ft2 (9 m2) maximum area of coverage per sprinker or spray nozzle. [37:11.4.5.1.1]
22.6.2.2
Sprinkler and water spray system coverage shall be provided to all areas within the enclosure located within 20 ft (6 m) of the following:
(1) The engine
(2) The lubricating oil system
(3) The fuel system
[37:11.4.5.1.2]
22.6.2.3
Sprinklers and water spray nozzles shall not be directed at engine components that are susceptible to thermal shock or deformation. [37:11.4.5.2]
22.7 Nitrate Film.
22.7.1 Design Requirements.
22.7.1.1
Every room, except projection booths and rewinding rooms, where nitrate film is stored or handled in quantities greater than 51 lb (23 kg), or 10 standard rolls, shall be protected by an automatic sprinkler system that is installed in accordance with the requirements for Group II extra hazard occupancies. [40:5.1.2]
22.7.1.2
Water supplies for automatic sprinklers shall be based on 20 gpm (1.26 L/sec) per sprinkler for 20 minutes for the total number of sprinklers in one vault plus 25 percent of the sprinklers in the communicating fire area. [40:5.2.2]
22.7.1.3* Vaults Other Than Extended Term Storage Vaults.
[40:6.3] (See Figure A.22.7.1.3.) Fire protection in vaults shall be provided by a deluge system with directional nozzles meeting the criteria in 22.7.1.4. [40:6.3.7]
22.7.1.4
For extended term storage vaults in accordance with Section 6.5.5 of NFPA 40, fire protection shall be provided by a deluge system with directional nozzles installed in accordance with NFPA 15 and meeting the criteria in 22.7.1.4.15 through 22.7.1.4.911. [40:6.5.6]
22.7.1.4.15
Sprinkler systems in existing extended term storage vaults that were in compliance with the provisions of this standard at the time of installation shall be permitted to be continued in use. [40:6.5.6.1]
22.7.1.4.26
High-velocity open head nozzles each capable of providing a discharge rate of 1.26 L/sec (20 gpm) at a gauge pressure of 345 kPa (50 psi) shall be installed. [40:6.5.6.2]
22.7.1.4.37
The design shall be based on a discharge density of 28 mm/min (0.68 gpm/ft2) over each face of storage racks. [40:6.5.6.3]
22.7.1.4.48*
The nozzles shall have a combined spray pattern capable of covering the face of the film storage racks. [40:6.5.6.4]
22.7.1.4.59
The nozzles shall be installed at the top of the storage shelf array, aimed at the opposite shelf array. [40:6.5.6.5]
22.7.1.4.610*
Nozzles shall be installed on opposite faces of the storage shelf array in a staggered pattern such that no nozzles are directly opposite one another. [40: 6.5.6.6]
22.7.1.4.711
The water supply duration shall be a minimum of 20 minutes. [40:6.5.6.7]
22.7.1.4.812
The deluge system shall be activated by a signal from one of the following: [40:6.5.6.8]
(1) An air sampling–type smoke detection system
(2) A fixed temperature heat sensitive cable
22.7.1.13 4.9 Full water flow shall be discharged from the water spray nozzles within 10 seconds of reaching the set point actuation of the detection system [40:6.5.6.9.6]
22.7.2 Installation Requirements.
22.7.2.1
In areas or rooms where nitrate film is handled, the area that is protected per sprinkler head shall not exceed 64 ft2 (6 m2) with sprinklers not being more than 8 ft (2.4 m) apart. [40:5.1.4]
Formatted: Font: Bold
22.7.2.2 Cabinet Protection.
[40:6.2.5]
22.7.2.2.1
Cabinets having a capacity of more than 34 kg (75 lb), or 15 standard rolls, of film shall be provided with at least one automatic sprinkler head. [40:6.2.5.1]
22.7.2.2.2
Where cans are stored on more than one shelf, as shown in Figure 22.7.2.2.2 and as described in 6.2.6.2 or 6.2.6.3 of NFPA 40, one sprinkler shall be provided for each shelf. [40:6.2.5.2]
Figure 22.7.2.2.2 Standard Film Cabinet for Other Than Extended Term Storage Film. [40:Figure 6.2.1]
22.7.2.3 Motion Picture Film Laboratories.
In all cases, sprinklers shall be arranged so that not more than two machines are protected by any one sprinkler head. [40:9.2.5.2]
22.8 Laboratories Using Chemicals.
22.8.1 Design Requirements.
Automatic sprinkler system protection shall be required for all new laboratories in accordance with the following:
(1) Automatic sprinkler system protection for Class A and Class B laboratories shall be in accordance with NFPA 13 for ordinary hazard (Group 2) occupancies.
(2) Automatic sprinkler system protection for Class C and Class D laboratories shall be in accordance with NFPA 13 for ordinary hazard (Group 1) occupancies.
[45:6.12.1.1]
22.8.2 Installation Requirements.
Fire sprinklers in laboratory units shall be the quick response (QR) sprinkler type installed in accordance with NFPA 13. [45:6.12.1.2]
22.9 Oxygen-Fuel Gas Systems for Welding, Cutting, and Allied Processes.
22.9.1 Design Requirements.
22.9.1.1
The total gas capacity of nonliquefied flammable gas (e.g., acetylene) shall be permitted to be increased to 56.6 m3 (2000 ft3) per control area under one of the following conditions:
(1) In cylinder storage areas that are protected by an automatic sprinkler system and water supply designed in accordance with NFPA 13, furnishing a sprinkler discharge density of at least (10 L/min)/m2 [(0.25 gal/min)/ft2] over a minimum operating area of at least 279 m2 (3000 ft2) with sprinklers located not more than 6.1 m (20 ft) above the floor where the cylinders are stored.
(2) In cylinder storage areas that are protected by an automatic water spray fixed system of equal density, designed in accordance with NFPA 15
22.9.1.12
Oxygen cylinders connected to one manifold shall be limited to a total gas capacity of 6500 ft2 (184 m2).42.5 m3 (1500 ft3). [51:5.2.5] 22.9.1.1.1 Two such manifolds with connected cylinders shall be permitted to be located in the same room, provided the building is protected throughout with an approved automatic sprinkler system designed in accordance with NFPA 13this standard, furnishing a sprinkler discharge density of at least (10 L/min)/m2 [(0.25 gpmal/min)/ft2 (10.2 mm/min)] over a minimum operating area of at least 279 m2 (3000 ft2) (279 m2) with sprinklers located not more than 6.1 m (20 ft) (6.1 m) above the floor where the manifolds are located. [51:5.2.5.1]
22.9.1.2 For Mobile acetylene trailer systems, a deluge sprinkler system shall be provided for
MATS fire areas used as indoor and outdoor discharging stations. [51:10.5.8.1.1]
22.9.1.3 Deluge sprinkler systems shall provide a minimum density of 0.3 gpm/ft2 (12.2 mm/min) over the MATS fire area being protected. [51:10.5.8.1.2]
22.9.1.4 The deluge system shall be identified and marked with a sign and shall be activated automatically by a fast-acting fire detection system and also by a manual actuator. [51:10.5.8.1.3]
22.9.1.5 The requirements of 22.9.1.2 shall not apply to existing indoor or outdoor facilities, equipment, structures, or installations where MATS are discharged that existed or were approved for construction or installation prior to the effective date of this standard, provided the MATS are protected with an automatic
Formatted: Superscript
Formatted: Superscript
Formatted: Font: Bold
Formatted: Font: Bold
Formatted: Not Superscript/ Subscript
Formatted: Font: Bold
Formatted: Font: Bold
Formatted: Font: Bold
Formatted: Superscript
Formatted: Font: Bold
Formatted: Font: Bold
sprinkler system with a minimum design density of not less than 0.25 gm/ft2 (10.2 mm/min). [51:10.5.8.1.4.1]
22.9.2 Installation Requirements.
22.9.2.1
In buildings protected by an automatic sprinkler system and water supply designed in accordance with NFPA 13this standard for an Oordinary Hhazard Group 2 or more hazardous occupancy, where the occupancy other than the cylinder storage is not more hazardous than ordinary hazard as defined in NFPA 13this standard, the distance between designated storage areas shall be permitted to be reduced to 15.2 m (50 ft (15.2 m)). [51:4.3.4.1] 22.9.2.2 If the occupancy in such protected buildings between the designated storage areas is free of combustible material, the distance shall be permitted to be reduced to 7.6 m (25 ft (7.6 m)). [51:4.3.4.2]
22.10 Acetylene Cylinder Charging Plants.
22.10.1 Design Requirements.
22.10.1.1
When sprinkler protection is provided, the area in which flammable compressed gases are stored or used shall be protected with a sprinkler system designed to be not less than that required by NFPA 13 for Extra Hazard Group 1 with a minimum design area of 2500 ft2 (232.26 m2). [51A:11.2.1.2]
22.10.1.2 At mobile acetylene trailer systems (MATS) at mobile acetylene charging plants, a fire sprinkler system in accordance with this standard, Extra Hazard Group I shall be installed in the areas occupied by trailers in charging or discharging stations. [51A:11.2.1.3]
22.10.2 Installation Requirements. (Reserved)
22.11 Compressed Gases and Cryogenic Fluids Code.
22.11.1 Design Criteria.
22.11.1.1
When sprinkler protection is required, the area in which compressed gases or cryogenic fluids are stored or used shall be protected with a sprinkler system designed to be not less than that required by NFPA 13 for Ordinary Hazard Group 2. [55:6.10.2.1]
22.11.1.2
When sprinkler protection is required, the area in which the flammable or pyrophoric compressed gases or cryogenic fluids are stored or used shall be protected with a sprinkler system designed to be not less than that required by NFPA 13 for Extra Hazard Group 1. [55:6.10.2.2]
22.11.2 Installation Requirements. (Reserved)
22.12 Utility LP-Gas Plants.
22.12.1 Design Requirements.
22.12.1.1
The design of fire water supply and distribution systems, where used, shall provide for the simultaneous supply of those fixed fire protection systems involved in the maximum single incident expected in the plant, including monitor nozzles, at their design flow and pressure. [59:13.4.2]
Formatted: Font: Bold
Formatted: Font: Bold
Formatted: Font: Bold
Formatted: Font: Bold
Formatted: Space Before: Auto, After: Auto
Formatted: Font: Bold
Formatted: Font: (Default) Times New Roman, Fontcolor: Auto
22.12.1.2
An additional supply of 1000 gal/min (63 L/sec) shall be available for hand hose streams for a period of not less than 2 hours. [59:13.4.2.1]
22.12.1.3
Manually actuated monitors shall be permitted to be used to augment hand hose streams. [59:13.4.2.2]
22.12.2 Installation Requirements. (Reserved)
22.13 Production, Storage, and Handling of Liquefied Natural Gas (LNG).
22.13.1 Design Requirements.
The fire water supply and distribution systems, if provided, shall simultaneously supply water to fixed fire protection systems, including monitor nozzles, at their design flow and pressure, involved in the maximum single incident expected in the plant plus an allowance of 1000 gpm (63 L/sec) for hand hose streams for not less than 2 hours. [59A:12.5.2]
22.13.2 Installation Requirements. (Reserved)
22.14 Protection of Information Technology Equipment.
22.14.1 Design Requirements. (Reserved)
22.14.2 Installation Requirements.
22.14.2.1*
Information technology equipment rooms and information technology equipment areas located in a sprinklered building shall be provided with an automatic sprinkler system. [75:98.1.1]
22.14.2.2
Sprinkler systems protecting information technology equipment areas shall be valved separately from other sprinkler systems. [75:98.1.3]
22.14.2.3*
An automatic sprinkler system or a gaseous fire extinguishing system shall be provided for the protection of the area below a raised floor in an information technology equipment room or information technology equipment area when one or more of the following exist:
(1) There is a critical need to protect data in the process, reduce equipment damage, and facilitate return to service.
(2) The area below the raised floor contains combustible material.
[75:98.1.1.2]
22.15 Standard on Incinerators, and Waste and Linen Handling Systems and Equipment.
22.15.1 Design Requirements. (Reserved)
22.15.2 Installation Requirements.
22.15.2.1
Automatic sprinklers shall be provided in incinerator rooms in accordance with this standard. [82:54.2.7.3]
22.15.2.2* Waste and Linen Chutes and Transport Systems.
[82:65]
22.15.2.2.1 Gravity Waste or Linen Chutes.
[82:65.2]
22.15.2.2.1.1
Gravity Lined metal chutes shall be protected internally by automatic sprinklers unless they are lined in accordance with 65.2.2.6.1 in NFPA 82. [82:65.2.2.6.2; 82:5.2.6.1.1]
22.15.2.2.1.2
This protection requires that a sprinkler be installed at or above the top service opening of the chute. [82:65.2.6.1.2]
22.15.2.2.1.3 Chute Sprinkler Protection.
Automatic sprinklers installed in gravity chute service openings shall be recessed out of the chute area through which the material travels. [82:65.2.6.1.3]
22.15.2.2.1.4
In addition, a sprinkler shall be installed within the chute at alternate floor levels in buildings over two stories in height, with a mandatory sprinkler located at the lowest service level. [82:65.2.6.1.4]
22.15.2.2.1.5 Gravity chutes shall be protected internally by
automatic sprinklers unless they are lined in accordance with
6.2.2.6.1 in NFPA 82. [; 82:6.2.6.1.1]
22.15.2.2.1.65 Chute Room Automatic Sprinklers.
Automatic sprinklers shall be installed in chute terminal rooms. [82:65.2.6.2.1]
22.15.2.2.2 Full Pneumatic Waste and Linen Conveying Systems.
[82:65.3]
22.15.2.2.2.1
Full pneumatic-type risers shall be protected internally by automatic sprinklers. [82:65.3.4.1]
22.15.2.2.2.2
A sprinkler shall be required at or above the top loading station and at alternate floor levels in buildings over two stories in height, with a mandatory sprinkler located at the lowest loading station. [82:65.3.4.2]
22.15.2.2.2.3
Sprinklers shall be recessed out of the station area through which the material travels. [82:65.3.4.3]
22.15.2.2.3 Gravity Pneumatic Trash or Linen Conveying Systems.
[82:65.4]
22.15.2.2.3.1 Chute Automatic Sprinklers.
Where material is to be stored at the bottom of the chute and above the riser discharge damper (above the transport tee), automatic sprinklers shall be installed below the last service door on the chute. [82:65.4.2.3]
22.15.2.2.3.2
Automatic sprinklers shall be installed in chute discharge rooms. [82:65.4.2.4.3]
22.15.2.3 Other Waste Handling Systems. [82:7.4]
22.15.2.3.1
Automatic sprinklers shall be installed in rooms where waste handling systems and equipment are used to transport waste from interim storage areas to waste processing equipment, such as incinerators. [82:76.4.1]
22.15.2.3.2
In locations or rooms where waste handling systems and equipment are used for interim storage of waste only, the rooms shall be sprinklered in accordance with requirements specified in 22.15.2.4. [82:76.4.2]
22.15.2.4 Waste Compactors. [82:8]
[82:7]
22.15.2.4.1
All chute-fed compactors shall have an automatic sprinkler with a minimum 13 mm (1⁄2 in.) orifice installed in the hopper of the compactor. [82:87.2.1]
22.15.2.4.2
Sprinklers shall be ordinary temperature-rated sprinklers. [82:87.2.1.1]
22.15.2.4.3
Sprinklers shall be supplied by a minimum of 1 in. (25.4 mm) ferrous piping or 3⁄4 in. (19 mm) copper tubing line from the domestic cold water supply or by the building fire sprinkler system. [82:87.2.1.2]
22.15.2.4.4
Sprinkler water pipe shall be protected from freezing in outdoor installations. [82:87.2.1.3]
22.15.2.4.5
Hand-fed compactors located within a building and not operated in conjunction with a chute shall not require installation of an automatic sprinkler in the hopper. [82:87.2.2]
22.15.2.5
Waste and recyclables storage rooms shall be provided with automatic sprinklers in accordance with this standard. [82:98.3]
22.15.2.6
Rooms in which waste processing equipment is located shall be installed with automatic sprinklers. [82:109.4.1]
22.16 Standard for Ovens and Furnaces.
22.16.1 Design Requirements. (Reserved)
22.16.2 Installation Requirements.
22.16.2.1*
Where automatic sprinklers are provided, they shall be installed in accordance with NFPA 13, unless otherwise permitted by 22.16.2.2. [86:9.2.1]
22.16.2.2
Where sprinklers that protect only ovens are installed and connection to a reliable fire protection water supply is not feasible, a domestic water supply connection shall be permitted to supply these sprinklers subject to the approval of the authority having jurisdiction. [86:9.2.2]
Formatted: Font: Bold
Formatted: Font: Not Bold
Formatted: Font: Not Bold
Formatted: Font: Not Bold
Formatted: Font: Not Bold
22.16.2.3
Where sprinklers are selected for the protection of ovens, furnaces, or related equipment, the use of closed-head sprinkler systems shall be prohibited and only deluge sprinkler systems shall be used where the following conditions exist:
(1) In equipment where temperatures can exceed 625°F (329°C)
(2) Where flash fire conditions can occur
[86:9.3.3]
22.16.2.4
Furnaces shall be located so as to minimize exposure to power equipment, process equipment, and sprinkler risers. [86:5.1.3.1]
22.16.2.5
Where water from a fixed protection system could come in contact with molten materials, such as molten salt or molten metal, shielding shall be provided to prevent water from contacting the molten material. [86:9.3.1]
22.16.2.6*
Galvanized pipe shall not be used in sprinkler or water spray systems in ovens, furnaces, or related equipment. [86:9.3.2]
22.17 Health Care Facilities Code, Class A Hyperbaric Chambers.
22.17.1 Design Requirements.
22.17.1.1
A fixed water deluge extinguishing system shall be installed in all chamber compartments that are designed for manned operations. [99:14.2.5.2]
22.17.1.2
In chambers that consist of more than one chamber compartment (lock), the design of the deluge system shall meet the requirements of 22.17.1.1 when the chamber compartments are at different depths (pressures). [99:14.2.5.2.1]
22.17.1.3
The deluge system in different compartments (locks) shall operate independently or simultaneously. [99:14.2.5.2.2]
22.17.1.4
Fixed deluge systems shall not be required in chamber compartments that are used strictly as personnel transfer compartments (locks) and for no other purposes. [99:14.2.5.2.3]
22.17.1.5*
Manual activation and deactivation deluge controls shall be located at the operator's console and in each chamber compartment (lock) containing a deluge system. [99:14.2.5.2.4]
22.17.1.6
Controls shall be designed to prevent unintended activation. [99:14.2.5.2.4.1]
22.17.1.7
Water shall be delivered from the fixed discharge nozzles as specified in 22.17.1.9 within 3 seconds of activation of any affiliated deluge control. [99:14.2.5.2.5]
22.17.1.8*
Average spray density at floor level shall be not less than 2 gpm/ft2 (81.5 L/min/m2), with no floor area larger than 10.76 ft2 (1 m2) receiving less than 1 gpm/ft2 (40.75 L/min/m2). [99:14.2.5.2.6]
22.17.1.9
Water shall be available in the deluge system to maintain the flow specified in 22.17.1.8 simultaneously in each chamber compartment (lock) containing the deluge system for 1 minute. [99:14.2.5.2.7]
22.17.1.10
The limit on maximum extinguishment duration shall be governed by the chamber capacity (bilge capacity also, if so equipped) or its drainage system, or both. [99:14.2.5.2.7.1]
22.17.1.11
The deluge system shall have stored pressure to operate for at least 15 seconds without electrical branch power. [99:14.2.5.2.8]
22.17.2 Installation Requirements. (Reserved)
22.18 Fixed Guideway Transit and Passenger Rail Systems.
22.18.1 Design Requirements.
22.18.1.1
Other fire suppression systems, if approved, shall be permitted to be substituted for automatic sprinkler systems in the areas listed in 22.18.2.1. [130:5.7.3.4]
22.18.2 Installation Requirements.
22.18.2.1
An automatic sprinkler protection system shall be provided in areas of stations used for concessions, in storage areas, in trash rooms, and in the steel truss area of all escalators and other similar areas with combustible loadings, except trainways. [130:5.7.3.1]
22.18.2.2
Sprinkler protection shall be permitted to be omitted in areas of open stations remotely located from public spaces. [130:5.7.3.1.1]
22.18.2.3
Installation of sprinkler systems shall comply with NFPA 13 or applicable local codes as required. [130:5.7.3.2]
22.18.2.4
A sprinkler system waterflow alarm and supervisory signal service shall be installed. [130:5.7.3.3]
22.19 Motion Picture and Television Production Studio Soundstages, Approved Production Facilities, and Production Locations. 22.19.1 Design Requirements. (Reserved) 22.19.2 Installation Requirements.
22.19.2.1
The requirements of NFPA 13 prohibiting obstructions to sprinkler discharge shall not be applicable if approved mitigation is employed. [140:4.11.1.3.1]
22.19.2.2
The requirements of NFPA 13 prohibiting obstructions to sprinkler discharge shall not be applicable if the building sprinkler system meets the design criteria for Extra Hazard, Group 2. [140:4.11.1.3.2]
22.19.2.3
In any production location building protected by an existing automatic sprinkler system, where solid- or hard-ceiling sets or platforms are introduced and create an obstruction to sprinkler discharge, the provisions of 22.19.4 or 22.19.5 shall be met. [140:5.11.3]
22.19.2.4*
The requirements of NFPA 13 prohibiting obstructions to sprinkler discharge shall not be applicable if approved mitigation is employed. [140:5.11.4]
22.19.2.5*
The requirements of NFPA 13 prohibiting obstructions to sprinkler discharge shall not be applicable if the building sprinkler system meets the design criteria for Extra Hazard, Group 2. [140:5.11.5]
22.20 Animal Housing Facilities.
22.20.1 Design Requirements. (Reserved)
22.20.1.1 (Reserved)
22.20.2 Installation Requirements. (Reserved)
22.20.2.1
Quick-response sprinklers shall be utilized in animal housing facilities. [150:9.2.3]
22.21 Water Cooling Towers.
22.21.1 Design Requirements.
22.21.1.1 Types of Systems.
22.21.1.1.1*
Because the counterflow tower design lends itself to either closed- or open-head systems, the following systems shall be permitted to be used:
(1) Wet-pipe
(2) Dry-pipe
(3) Preaction
(4) Deluge
[214:5.2.2.1]
22.21.1.1.2*
The open-head deluge system shall be used in crossflow towers to maximize the water distribution and heat detection activation. [214:5.2.2.2]
22.21.1.2 Minimum Rate of Application.
[214:5.2.3]
22.21.1.2.1
Under the fan decks of counterflow towers, the rate of application of water shall be 0.5 gpm/ft2 (20.4 mm/min), including fan opening. [214:5.2.3.1]
22.21.1.2.2
Under the fan decks of crossflow towers, the rate of application of water shall be 0.33 gpm/ft2 (13.45 mm/min), including fan opening. [214:5.2.3.2]
22.21.1.2.3
Over the fill areas of crossflow towers, the rate of application of water shall be 0.5 gpm/ft2 (20.4 mm/min). [214:5.2.3.3]
22.21.1.3 Extended Fan Decks.
On towers having extended fan decks that completely enclose the distribution basin, the discharge outlets protecting the fill area shall be located over the basin, under the extension of the fan deck. [214:5.2.4.3]
22.21.1.3.1
These discharge outlets shall be open directional spray nozzles or other approved spray devices arranged to discharge 0.35 gpm/ft2 (14.26 mm/min) directly on the distribution basin and 0.15 gpm/ft2 (6.11 mm/min) on the underside of the fan deck extension. [214:5.2.4.3.1]
22.21.1.3.2
On towers having extended fan decks that do not completely enclose the hot-water basin, outlets protecting the fill shall be located under the distribution basin in accordance with 5.2.4.2.2 of NFPA 214. [214:5.2.4.3.2]
22.21.1.4 Combustible Fan Decks.
For deluge systems using directional spray nozzles in the pendant position, provisions shall be made to protect the underside of a combustible fan deck at a minimum of 0.15 gpm/ft2 (6.11 mm/min), which shall be included as part of the application rate specified in 5.2.3 of NFPA 214. [214:5.2.4.4]
22.21.1.5* Water Basin Covers.
On film-filled towers that have solid, hot-water basin covers over the complete basin, the discharge outlets protecting the fill area shall be permitted to be located under the basin covers. [214:5.2.4.5]
22.21.1.5.1
These discharge outlets shall be open directional spray nozzles or other approved devices arranged to discharge 0.50 gpm/ft2 (20.4 mm/min) into the distribution basin horizontally, with some of the spray splashing up and on the underside of the water basin covers. [214:5.2.4.5.1]
22.21.1.6 Exterior Protection.
[214:5.2.10]
22.21.1.6.1
Where any combustible exterior surfaces of a tower, including the fan deck and distribution basins, are less than 100 ft (30.5 m) from significant concentrations of combustibles such as structures or piled material, the combustible exposed surfaces of the tower shall be protected by an automatic water spray system. [214:5.2.10.1]
22.21.1.6.2
Systems for exterior protection shall be designed with the same attention and care as interior systems. [214:5.2.10.2]
22.21.1.6.2.1
Pipe sizing shall be based on hydraulic calculations. [214:5.2.10.2.1]
22.21.1.6.2.2
Water supply and discharge rate shall be based on a minimum 0.15 gpm/ft2 (6.11 mm/min) for all protected surfaces. [214:5.2.10.2.2]
22.21.1.7 Sprinkler System Water Supply.
22.21.1.7.1 Deluge Systems.
22.21.1.7.1.1*
Where all cells of a cooling tower are protected by a single deluge system, the water supply shall be adequate to supply all discharge outlets on that system. [214:5.6.1.1]
22.21.1.7.1.2
Where two or more deluge systems are used to protect a cooling tower and fire-resistant partitions are not provided between the deluge systems, the water supply shall be adequate to supply all discharge outlets in the two most hydraulically demanding adjacent systems. [214:5.6.1.2]
22.21.1.7.1.3*
Where two or more deluge systems are separated by fire-resistant partitions, the water supply shall be adequate to supply all discharge outlets in the single most hydraulically demanding system. [214:5.6.1.3]
22.21.1.7.2 Wet, Dry, and Preaction Systems.
22.21.1.7.2.1*
Where each cell of the cooling tower is separated by a fire-resistant partition, the water supply shall be adequate to supply all discharge outlets in the hydraulically most demanding single cell. [214:5.6.2.1]
22.21.1.7.2.2*
Where fire-resistant partitions are not provided between each cell of a cooling tower, the water supply shall be adequate to supply all discharge outlets in the two most hydraulically demanding adjoining cells. [214:5.6.2.2]
22.21.1.7.3 Hose Streams.
Water supplies shall be sufficient to include a minimum of 500 gpm (1892.5 L/min) for hose streams in addition to the sprinkler requirements. [214:5.6.3]
22.21.1.7.4 Duration.
A water supply adequate for at least a 2-hour duration shall be provided for the combination of the water supply specified in 5.6.1 or 5.6.2 of NFPA 214, plus the hose stream demand specified in 22.21.1.7.3. [214:5.6.4]
22.21.2 Installation Requirements.
22.21.2.1* Counterflow Towers.
[214:5.2.4.1]
22.21.2.1.1
The discharge outlets shall be located under the fan deck and fan opening. [214:5.2.4.1.1]
22.21.2.1.2
Except under the fan opening, all discharge outlets shall have deflector distances installed in accordance with Section 8.5 of NFPA 13. [214:5.2.4.1.2]
22.21.2.1.3
Closed-head discharge outlets for dry-pipe and preaction systems shall be installed in the upright position only. [214:5.2.4.1.3]
22.21.2.2* Crossflow Towers.
[214:5.2.4.2]
22.21.2.2.1
The discharge outlets protecting the plenum area shall be located under the fan deck and in the fan opening. [214:5.2.4.2.1]
22.21.2.2.2
Discharge outlets protecting the fill shall be located under the distribution basin on either the louver or drift eliminator side, discharging horizontally through the joist channels. [214:5.2.4.2.2]
22.21.2.2.3
Towers with an air travel dimension longer than the maximum allowable for the discharge device being used shall have discharge devices placed on both sides of the fill area in each joist channel. [214:5.2.4.2.3.1]
22.21.2.2.4
The pressure at each discharge device shall be adequate to provide protection for half of the length of the fill measured along the air travel. [214:5.2.4.2.3.2]
22.21.2.2.5
Where joist channels are wider than 2 ft (0.6 m), more than one discharge device shall be required per joist channel. [214:5.2.4.2.4.1]
22.21.2.2.6
If the discharge device being used is listed for the width of the joist channel being protected, one discharge device per joist channel shall be permitted to be used. [214:5.2.4.2.4.2]
22.21.2.3* Extended Fan Decks.
On towers having extended fan decks that completely enclose the distribution basin, the discharge outlets protecting the fill area shall be located over the basin, under the extension of the fan deck. [214:5.2.4.3]
22.21.2.4 Combustible Fan Decks.
For deluge systems using directional spray nozzles in the pendant position, provisions shall be made to protect the underside of a combustible fan deck at a minimum rate of 0.15 gpm/ft2 (6.11 mm/min), which shall be included as part of the application rate specified in 22.21.1.2. [214:5.2.4.4]
22.21.2.45* Water Basin Covers.
On film-filled towers that have solid, hot-water basin covers over the complete basin, the discharge outlets protecting the fill area shall be permitted to be located under the basin covers. [214:5.2.4.5]
22.21.2.5.1
These discharge outlets shall be open directional spray nozzles or other approved devices arranged to discharge 0.50 gpm/ft2 (20.4 mm/min) into the distribution basin horizontally, with some of the spray splashing up and on the underside of the water basin covers. [214:5.2.4.5.1]
22.21.2.56 Valves.
[214:5.2.6]
22.21.2.56.1
Shutoff valves and automatically operated water control valves, if provided, shall be located as follows:
(1) Outside the fire-exposed area
(2) As close to the cooling tower as possible to minimize the amount of pipe to the discharge device
(3) Where they will be accessible during a fire emergency
[214:5.2.6.1.2]
22.21.52.6.2 Manual Release Valve.
[214:5.2.6.2]
22.21.2.56.2.1
Remote manual release valves, where required, shall be conspicuously located and accessible during a fire emergency. [214:5.2.6.2.1]
22.21.2.56.2.2
Where remote manual release valves are not required, an inspector's test valve shall be provided for each pilot-head-operated system. [214:5.2.6.2.2]
22.21.2.67 Strainers.
Strainers shall be required for systems utilizing discharge devices with waterways of less than 3⁄8 in. (9.5 mm) diameter. [214:5.2.7]
22.21.2.78 Heat Detectors.
Where deluge or preaction systems are used, heat detectors shall be installed and shall be selected from either of the types in 5.2.8.1 or 5.2.8.2 of NFPA 214. [214:5.2.8]
22.21.2.78.1
In mechanical-draft towers, pilot line detectors shall be located under the fan deck at the circumference of the fan opening and under the fan opening where necessary to comply with the spacing requirements in 22.21.2.8.1.1. (For extended fan decks, see 5.2.8.2.3 in NFPA 214.) [214:5.2.8.1.2.1(A)]
22.21.2.78.1.1
Pilot line detectors shall be spaced not more than 8 ft (2.4 m) apart in any direction including the fan opening. Temperature ratings shall be selected in accordance with operating conditions, but shall be no less than intermediate. [214:5.2.8.1.2.1(B)]
22.21.2.78.2
On towers having extended fan decks that completely enclose the distribution basin, electrical heat detectors shall be located under the fan deck extension in accordance with standard, indoor-spacing rules for the type detectors used in accordance with NFPA 72. [214:5.2.8.2.3]
22.21.2.78.2.1
Where the fan deck extension is 16 ft (4.9 m) or less and this dimension is the length of the joist channel, then only one row of detectors centered on and at right angles to the joist channels shall be required. Spacing between detectors shall be in accordance with NFPA 72. [214:5.2.8.2.3.1]
22.21.2.78.2.2
On towers having extended fan decks that do not completely enclose the hot-water basin, electrical heat detectors shall not be required under the fan deck extension. [214:5.2.8.2.3.2]
22.21.2.78.3
Where electrical heat detectors are inaccessible during tower operation, an accessible test detector shall be provided for each detection zone. [214:5.2.8.3]
22.21.2.78.4
Electrical heat detector components exposed to corrosive vapors or liquids shall be protected by materials of construction or by protective coatings applied by the equipment manufacturer. [214:5.2.8.4]
22.21.2.89 Protection for Fan Drive Motor.
[214:5.2.9]
22.21.2.89.1
A sprinkler or spray nozzle shall be provided over each fan drive motor where the motor is located so that it is not within the protected area of the tower. [214:5.2.9.1]
22.21.2.89.2
Where a preaction or deluge system is used, the detection system shall be extended to cover the motor. [214:5.2.9.2]
22.21.2.89.3
Provision shall be made to interlock the fan motors with the fire protection system so that the cooling tower fan motors are stopped in the cell(s) for which the system is actuated. [214:5.2.9.3]
22.21.2.89.4
Where the continued operation of the fans is vital to the process, a manual override switch shall be permitted to be provided to reactivate the fan when it is determined that there is no fire. [214:5.2.9.4]
22.21.2.910 Corrosion Protection.
[214:5.3]
22.21.2.910.1
Piping, fittings, hangers, braces, and attachment hardware including fasteners shall be hot-dipped galvanized steel in accordance with ASTM A 153A/153M, Standard Specification for Zinc Coating (Hot Dip) on Iron and Steel Hardware, or other materials having a superior corrosion resistance. [214:5.3.1]
22.21.2.910.1.1
Exposed pipe threads and bolts on fittings shall be protected against corrosion. [214:5.3.1.1]
22.21.2.910.1.2
All other components shall be corrosion resistant or protected against corrosion by a coating. [214:5.3.1.2]
22.21.2.910.2*
Wax-type coatings shall not be used on devices without fusible elements. [214:5.3.2]
22.21.2.910.3*
Special care shall be taken in the handling and installation of wax-coated or similar sprinklers to avoid damaging the coating. [214:5.3.3]
22.21.2.910.3.1
Corrosion-resistant coatings shall not be applied to the sprinklers by anyone other than the manufacturer of the sprinklers. [214:5.3.3.1]
22.21.2.910.3.2
In all cases, any damage to the protective coating occurring at the time of installation shall be repaired at once using only the coating of the manufacturer of the sprinkler in an approved
manner, so that no part of the sprinkler will be exposed after the installation has been completed. [214:5.3.3.2]
22.22 Standard for the Construction and Fire Protection of Marine Terminals, Piers, and Wharves.
22.22.1 Design Requirements.
22.22.1.1*
Unless the requirements of 22.22.1.2 apply, automatic sprinkler systems shall be designed based upon the design criteria for the protection of Group A plastics. [307:5.4.2.1]
22.22.1.2
With the approval of the authority having jurisdiction, the requirements of 22.22.1.1 shall not apply to buildings used exclusively for the handling or storage of specific cargoes and commodities that are defined as commodity classes less than Group A plastics by this standard. [307:5.4.2.2]
22.22.1.3
Buildings consistent with 22.22.1.2 shall be protected in accordance with the design criteria for the applicable commodity as required by this standard. [307:5.4.2.3]
22.22.1.4
Buildings used for the storage of hazardous materials shall be protected in accordance with this standard and the applicable codes and standards for the type of hazardous material being stored. [307:5.4.2.4]
22.22.2 Installation Requirements.
22.22.2.1 Piers and Wharves with Combustible Substructure.
22.22.2.1.1
Where there is danger of damage to sprinkler equipment by floating objects, physical barriers shall be provided to exclude such objects. [307:4.3.3.1.2.2]
22.22.2.1.2
The installation requirements in 22.22.2.1.2.1, 22.22.2.1.2.1(A), and 22.22.2.1.2.1(B) are also required.
22.22.2.1.2.1* Upward Projecting Sprinklers.
Where narrow horizontal channels or spaces are caused by caps, stringers, ties, and other structural members and where the standard upright sprinkler does not project sufficient water upward to extinguish or control fires on the underside of the pier or wharf deck, a sprinkler that projects water upward to wet the overhead shall be used. [307:4.3.3.1.3.1]
(A)
Location, spacing, and deflector position shall be governed by the discharge pattern of the sprinkler and the structure being protected. [307:4.3.3.1.3.1(A)]
(B)
The following design and installation guides shall apply where pendent sprinklers in the upright position or old-style sprinklers are to be utilized:
(1) The maximum coverage per sprinkler head shall be limited to 80 ft2 (7.5 m2).
(2) Where spacing or arrangement of stringers constitutes typical open-joist construction directly supporting the deck, sprinkler branch lines shall be installed between the bents at right angles to the stringers and shall meet the following requirements:
(a) Spacing between branch lines shall not exceed 10 ft (3 m).
(b) Sprinklers on branch lines shall be staggered and spaced not to exceed 8 ft (2.5 m) on center.
(3) *Where crisscross construction is involved, closer spacing of sprinklers shall be permitted as necessary to provide wetting of the entire structure.
(4) The deflectors of sprinklers on lines under stringers shall be located not less than 4 in. (100 mm) nor more than 10 in. (250 mm) below the bottom plane of the stringer, and not more than 18 in. (450 mm) below the underside of the pier or wharf deck.
(5) *The sprinkler system shall be hydraulically designed in accordance with the requirements of this standard and shall meet the following requirements:
(a) Sprinkler orifice shall be 1⁄2 in. (12.7 mm) and shall discharge at a minimum pressure of 12.5 psi (85 kPa).
(b) Design area shall be based upon the largest area between firestops plus an additional area embracing at least two branch lines on opposite sides of the firestop.
(c) Minimum design area shall be not less than 5000 ft2 (465 m2).
(6) The temperature rating of the sprinkler shall not exceed 165°F (74°C).
(7) The maximum area to be protected by any one system shall be limited to 25,000 ft2 (2325 m2).
[307:4.3.3.1.3.1(B)]
22.23 Semiconductor Fabrication Facilities.
22.23.1 Design Requirements.
22.23.1.1*
Automatic sprinklers for cleanrooms or clean zones shall be installed in accordance with NFPA 13this standard and shall be hydraulically designed for a density of 0.20 gpm/ft2 (8.15 L/min·m2) over a design area of 3000 ft2 (278.8 m2). [318:4.1.2.1]
22.23.1.2
Automatic sprinkler protection shall be designed and installed in the plenum and interstitial space above cleanrooms in accordance with NFPA 13this standard, for a density of 0.20 gpm/ft2 (8.15 L/min·m2) over a design area of 3000 ft2 (278.8 m2). [318:4.1.2.5]
22.23.1.2.1*
Automatic sprinklers shall be permitted to be omitted if the construction and occupancy of these spaces are noncombustible. [318:4.1.2.5.1]
22.23.1.3*
Sprinklers installed in duct systems shall be hydraulically designed to provide 0.5 gpm (1.9 L/min) over an area derived by multiplying the distance between the sprinklers in a horizontal duct by the width of the duct. [318:4.1.2.6.2]
22.23.1.3.1*
Minimum discharge shall be 20 gpm (76 L/min) per sprinkler from the five hydraulically most remote sprinklers. [318:4.1.2.6.2.1]
22.23.2 Installation Requirements.
22.23.2.1*
Wet pipe automatic sprinkler protection shall be provided throughout facilities containing cleanrooms and clean zones. [318:4.1.1]
22.23.2.2*
Approved quick-response sprinklers shall be utilized for sprinkler installations within down-flow airstreams in cleanrooms and clean zones. [318:4.1.2.2]
22.23.2.3*
Sprinklers shall be spaced a maximum of 20 ft (6.1 m) apart horizontally and 12 ft (3.7 m) apart vertically. [318:4.1.2.6.2.2]
22.23.2.4
A separate indicating control valve shall be provided for sprinklers installed in ductwork. [318:4.1.2.6.3]
22.23.2.5
The sprinklers shall be accessible for periodic inspection and maintenance. [318:4.1.2.6.6]
22.24 Aircraft Hangars.
22.24.1 Design Requirements.
Sprinkler systems installed in aircraft hangars shall comply with NFPA 409.
22.24.2 Installation Requirements.
Sprinkler systems installed in aircraft hangars shall comply with NFPA 409.
22.25 Airport Terminal Buildings, Fueling Ramp Drainage, and Loading Walkways.
22.25.1 Design Requirements.
22.25.1.1
Passenger-handling areas shall be classified as Ordinary Hazard Group 1 Occupancy for the purpose of sprinkler system design. [415:4.5.1.3]
22.25.1.2*
Baggage, package, and mail-handling areas shall be classified as Ordinary Hazard Group 2 Occupancy for the purpose of sprinkler system design. [415:4.5.1.4]
22.25.1.3*
Other areas of the airport terminal building shall be classified in accordance with Chapter 5 of this standard based on the occupancy of the area. [415:4.5.1.5]
22.25.1.4 Water Supply. Water supply from public and private sources shall be adequate to supply maximum calculated sprinkler demand plus a minimum of 500 gpm (1893 L/min) for hose streams. The supply shall be available at the rate specified for a period of at least 1 hour. [415:4.5.5]
22.25.1.4.1 Main sizes shall be hydraulically calculated based on the total domestic and fire protection requirements. Mains shall not be less than 8 in. (203 mm) in diameter except that laterals shall be permitted to be 6 in. (152 mm) in diameter if not over 200 ft. (61 m) long. [415:4.5.5.1]
22.25.2 Installation Requirements. (Reserved)
22.26 Aircraft Engine Test Facilities.
22.26.1 Design Requirements.
22.26.1.1*
In engine test cells, the minimum design discharge density shall be 0.50 gpm/ft2 (0.34 L/sec/m2) of protected area. [423:7.6.3]
Formatted: Font: Bold
Formatted: Font: Bold
Formatted: Space Before: Auto, After: Auto
Formatted: Font: (Default) Times New Roman, Fontcolor: Auto
22.26.1.2
In engine test cells, water supplies shall be capable of meeting the largest demand at the design rate plus hose stream demand for a period of 30 minutes. [423:7.6.4]
22.26.1.2.1
Hose stream demand shall be a minimum of 250 gpm (16 L/sec). [423:7.6.4.1]
22.26.1.2.2
The hydraulic calculation and the water supply shall be based on the assumption that all sprinklers in the test cell are operating simultaneously. [423:7.6.4.2]
22.26.2 Installation Requirements. (Reserved)
22.27 Advanced Light Water Reactor Electric Generating Plants.
22.27.1 Design Requirements.
22.27.1.1* Sprinkler System Water Supply.
The fire water supply shall be calculated on the basis of the largest expected flow rate for a period of 2 hours but shall not be less than 300,000 gal (1,135,500 L), and the following criteria also shall apply:
(1) The flow rate shall be based on 500 gpm (1892.5 L/min) for manual hose streams plus the largest design demand of any sprinkler or fixed water spray system as determined in accordance with this standard, with NFPA 15, or with NFPA 804.
(2) The fire water supply shall be capable of delivering the design demand specified in 22.27.1.1(1) with the hydraulically least demanding portion of fire main loop out of service.
[804:9.2.1]
22.27.1.2 Yard Mains.
The underground yard fire main loop shall be installed to furnish anticipated water requirements, and the following criteria also shall be met:
(1) The type of pipe and water treatment shall be design considerations, with tuberculation as one of the parameters.
(2) Means for inspecting and flushing the systems shall be provided.
[804:9.4.1] 22.27.1.34 Cable Spreading Room. The cable spreading room shall have an automatic fixed water-based suppression system, and the following criteria also shall be met:
(1) The location of sprinklers or spray nozzles shall protect cable tray arrangements to ensure water coverage for areas that could present exposure fire hazards to the cable raceways.
(2) Automatic sprinkler systems shall be designed for a density of 0.30 gpm/ft2 (12.2 L/min·m2) over the most remote 2500 ft2 (232.2 m2).
[804:10.4.1.1]
22.27.1.43 Cable Tunnels.
[804:10.4.2]
22.27.1.43.1
Automatic sprinkler systems shall be designed for a density of 0.30 gpm/ft2 (12.2 L/min·m2) for the most remote 100 linear ft (30.5 m) of cable tunnel up to the most remote 2500 ft2 (232.2 m2). [804:10.4.2.2.2]
22.27.1.43.2
Deluge sprinkler systems or deluge spray systems shall meet the following criteria:
(1) They shall be zoned to limit the area of protection to that which the drainage system can handle with any two adjacent systems actuated.
(2) They shall be hydraulically designed with each zone calculated with the largest adjacent zone flowing.
[804:10.4.2.2.4]
22.27.1.4 Cable Spreading Room.
The cable spreading room shall have an automatic fixed water-based suppression system, and the following criteria also shall be met:
(1) The location of sprinklers or spray nozzles shall protect cable tray arrangements to ensure water coverage for areas that could present exposure fire hazards to the cable raceways.
(2) Automatic sprinkler systems shall be designed for a density of 0.30 gpm/ft2 (12.2 L/min·m2) over the most remote 2500 ft2 (232.2 m2).
All areas beneath the turbine generator operating floor shall be protected by an automatic sprinkler or foam-water sprinkler system meeting the following criteria:
(1) The sprinkler system beneath the turbine generator shall be designed around obstructions from structural members and piping.
(2) The sprinkler system shall be designed to a minimum density of 0.30 gpm/ft2 (12.2 L/min·m2) over a minimum application of 5000 ft2 (464.5 m2).
[804:10.8.2.1]
22.27.1.6* Turbine Generator Bearings.
[804:10.8.3]
22.27.1.6.1
Lubricating oil lines above the turbine operating floor shall be protected with an automatic sprinkler system to a minimum density of 0.30 gpm/ft2 (12.2 L/min·m2) that covers those areas subject to oil accumulation, including the area within the turbine lagging (skirt). [804:10.8.4]
22.27.1.6.2
Where shaft-driven ventilation systems are used, an automatic preaction sprinkler system providing a density of 0.30 gpm/ft2 (12.2 L/min·m2) over the entire area shall be provided. [804:10.8.7(2)]
22.27.1.7 Standby Emergency Diesel Generators and Combustion Turbines.
The sprinkler and water spray protection systems shall be designed for a 0.25 gpm/ft2 (10.19 L/min·m2) density over the entire area. [804:10.9.3(2)]
22.27.1.8 Fire Pump Room/House.
If sprinkler and water spray systems are provided for fire pump houses, they shall be designed for a minimum density of 0.25 gpm/ft2 (10.19 L/min·m2) over the entire fire area. [804:10.22.2]
22.27.1.9 Auxiliary Boilers.
Sprinkler and water spray systems shall be designed for a minimum density of 0.25 gpm/ft2 (10.19 L/min·m2) over the entire area. [804:10.24.3]
22.27.2 Installation Requirements.
22.27.2.1 Yard Mains, Hydrants, and Building Standpipes.
[804:9.4]
22.27.2.1.1
Approved visually indicating sectional control valves such as postindicator valves shall be provided to isolate portions of the main for maintenance or repair without simultaneously shutting off the supply to both primary and backup fire suppression systems. [804:9.4.2]
22.27.2.1.2*
Sectional control valves shall allow maintaining independence of the individual loop around each unit, and the following also shall apply:
(1) For such installations, common water supplies shall also be permitted to be utilized.
(2) For multiple-reactor sites with widely separated plants [approaching 1 mi (1.6 km) or more], separate yard fire main loops shall be used.
[804:9.4.4]
22.27.2.1.3
Sprinkler systems and manual hose station standpipes shall have connections to the plant underground water main so that a single active failure or a crack in a moderate-energy line can be isolated so as not to impair both the primary and the backup fire suppression systems unless otherwise permitted by the following:
(1) Alternatively, headers fed from each end shall be permitted inside buildings to supply both sprinkler and standpipe systems, provided steel piping and fittings meeting the requirements of ASME B31.1, Code for Power Piping, are used for the headers (up to and including the first valve) supplying the sprinkler systems where such headers are part of the seismically analyzed hose standpipe system.
(2) Where provided, such headers shall be considered an extension of the yard main system.
(3) Each sprinkler and standpipe system shall be equipped with an outside screw and yoke (OS&Y) gate valve or other approved shutoff valve.
[804:9.4.7]
22.27.2.2 Cable ConcentrationsTunnels.
The location of sprinklers or spray nozzles shall protect cable tray arrangements and possible transient combustibles to ensure water coverage for areas that could present exposure fire hazards to the cable raceways. [804:10.4.2.2.3]
22.27.2.3 Turbine BuildingDeluge.
Deluge sprinkler systems or deluge spray systems shall meet the following criteria:
(1) They shall be zoned to limit the area of protection to that which the drainage system can handle with any two adjacent systems actuated.
(2) They shall be hydraulically designed with each zone calculated with the largest adjacent zone flowing.
[804:10.4.2.2.4]
22.27.2.4 Cable tunnels over 50 ft (15.2 m) long shall be provided with hose stations and portable fire extinguishers installed outside the tunnel. [804:10.4.2.4(3)]
22.28 Light Water Nuclear Power Plants.
22.28.1 Design Requirements.
A fire protection water supply of reliability, quantity, and duration shall be provided by one of the two following methods:
(1) A fire protection water supply of not less than two separate 300,000 gal (1,135,500 L) supplies shall be provided.
(2) The 2-hour fire flow rate for 2 hours shall be calculated, and the following criteria shall be met:
(a) The flow rate shall be based on 500 gpm (1892.5 L/min) for manual hose streams plus the largest design demand of any sprinkler or fixed water spray system(s) in the power block as determined in accordance with NFPA 13 or NFPA 15.
(b) The fire water supply shall be capable of delivering this design demand with the hydraulically least demanding portion of fire main loop out of service.
[805:5.5.1]
22.28.2 Installation Requirements. 22.28.2.12 Sprinkler systems and manual hose station standpipes shall be connected to the plant fire protection water main so that a single active failure or a crack to the water supply piping to these systems can be isolated so as not to impair both the primary and backup fire suppression systems. [805:5.5.12]
22.28.2.21
Each sprinkler and standpipe system shall be equipped with an outside screw and yoke (OS&Y) gate valve or other approved shutoff valve. [805:5.5.17]
22.28.2.2
Sprinkler systems and manual hose station standpipes shall be connected to the plant fire protection water main so that a single active failure or a crack to the water supply piping to these systems can be isolated so as not to impair both the primary and backup fire suppression systems. [805:5.5.12]
22.29 Hydroelectric Generating Plants. [NFPA 851]
22.29.1 Design Requirements.
22.29.1.1 Hydraulic Control Systems.
Fixed fire protection for this equipment, where provided, should be as follows:
(1) Automatic wet pipe sprinkler systems utilizing a design density of 0.25 gpm/ft2 (10.2 mm/min) for the entire hazard area.
(2) Automatic foam-water sprinkler systems providing a density of 0.16 gpm/ft2 (6.5 mm/min).
Formatted: Font: Bold
Formatted: Space Before: Auto, After: Auto
Formatted: Font: Not Bold
Formatted: Font: Not Bold
Formatted: Font: (Default) Times New Roman,Underline, Font color: Auto
[851:7.2.4]
22.29.1.2 Cable Concentrations.
Sprinkler or water spray systems should be designed for a density of 0.30 gpm/ft2 (12.2 mm/min) over 2500 ft2 (232 m2). This coverage is for area protection. Individual cable tray tier coverage could be required based on the fire risk evaluation. [851:7.5.3]
22.29.1.3 Cable Tunnels.
Where protection is required by the fire risk evaluation, cable tunnels should be protected by automatic water spray, automatic wet pipe sprinkler, or foam-water spray systems. Automatic sprinkler systems should be designed for a density of 0.30 gpm/ft2 (12.2 mm/min) over 2500 ft2 (232 m2) or the most remote 100 linear ft (30.5 m) of cable tunnel up to 2500 ft2 (232 m2). [851:7.6.1]
22.29.1.4 Emergency Generators.
Emergency generators located within main plant structures should be protected by automatic sprinkler, water spray, foam-water sprinkler, compressed air foam, or gaseous-type extinguishing systems. Sprinkler and water spray protection systems should be designed for a 0.25 gpm/ft2 (10.2 mm/ min) density over the fire area. [851:7.11.2]
22.29.1.5 Air Compressors.
Automatic sprinkler protection designed for a density of 0.25 gpm/ft2 (10.2 mm/min) over the postulated oil spill or compressed air foam should be considered for air compressors containing a large quantity of oil. [851:7.12]
22.29.1.6 Hydraulic Systems for Gate and Valve Operators.
Hydraulic control systems should use a listed fire-resistant fluid. Automatic sprinkler protection designed for a density of 0.25 gpm/ ft2 (10.2 mm/min) over the fire area or compressed air foam systems should be considered for hydraulic systems not using a listed fire-resistant fluid. [851:7.13]
22.29.1.7 Fire Pumps.
Rooms housing diesel-driven fire pumps should be protected by automatic sprinkler, water spray, foamwater sprinkler, or compressed air foam systems. If sprinkler and water spray protection systems are provided, they should be designed for a density of 0.25 gpm/ft2 (10.2 mm/min) over the fire area. For automatic foam-water sprinkler systems, a density of 0.16 gpm/ft2 (6.5 mm/min) should be provided. [851:7.14]
22.29.2 Installation Requirements.
22.29.2.1 Hydraulic Control Systems.
Fire extinguishing systems, where installed for lube oil systems employing combustible-type oil, should include protection for the reservoirs, pumps, and all oil lines, especially where unions exist on piping and beneath any shielded area where flowing oil can collect. Facilities not provided with curbs or drains should extend coverage for a distance of 20 ft (6 m) from the oil lines, when measured from the outermost oil line. [851:7.2.7]
22.30 Code for the Protection of Cultural Resource Properties — Museums, Libraries, and Places of Worship. [NFPA 909]
22.30.1 Design Requirements.
22.30.1.1*
Standard-response sprinklers shall be permitted for use in light-hazard areas. [909:9.12.13.112.4.4.2]
22.30.1.2*
Preaction and dry pipe systems shall be designed to minimize the risk of corrosion in accordance with the requirements of 22.30.2.19.12.12.3.1 through 22.30.2.59.12.12.3.5 of NFPA 909. [909:9.12.13.52.3]
22.30.1.3 System Design for Museums, Libraries, and Their Collections in Compact Storage.
22.30.1.3.1*
The design shall recognize the nature of the potential threat of a fire that originates in a compact mobile storage unit, where fuel loads are invariably large and fire growth is significantly different from that in other kinds of storage. [909:9.12.23.4.1.3]
22.30.1.3.2*
The automatic fire suppression system, the compact storage system, and the storage compartmentalization features shall be designed to limit fire damage in accordance with the facility’s fire safety objectives. [909:9.12.23.4.1.4(A)]
22.30.1.3.3
Design calculations shall include the number and size of the storage modules, the separation provided between the modules end-to-end and back-to-back, and the type of material being stored. [909:9.12.23.4.1.4(B)]
22.30.1.3.4
Where the automatic fire suppression is provided by automatic fire sprinkler systems, the systems shall be wet pipe, single interlock pre-action, or single non-interlock pre-action systems. [909:9.12.23.4.1.4(C)]
22.30.1.3.5
Dry pipe or double-interlock pre-action systems shall not be installed in compact storage areas. [909:9.12.23.4.1.4(D)]
22.30.1.3.6
Where compact storage is installed in an existing storage area, the existing automatic fire detection and fire suppression systems shall be modified as required to accommodate the increased fire loading. [909:9.12.23.4.1.4(E)]
22.30.2 Installation Requirements.
22.30.2.1*
Branch lines shall be pitched at least 1⁄2 in. per 10 ft (4 mm/m), and mains shall be pitched at least 1⁄4 in. per 10 ft (2 mm/m). [909:9.12.132.3.1]
22.30.2.2*
Auxiliary drains shall be provided at all low points in accordance with NFPA 13 requirements for dry pipe systems and preaction systems subject to freezing. [909:9.12.1213.3.2.1]
22.30.2.3*
Where steel pipe is used in dry pipe and preaction systems, the provisions of NFPA 13this standard shall be applied assuming water supplies and environmental conditions that contribute to unusual corrosive properties, and a plan shall be developed to address piping corrosion.treat the system using one of the following methods:
(1) Install a water pipe that is corrosion resistant
(2) Treat all water that enters the system using an approved corrosion inhibitor
(3) Implement an approved plan for monitoring the interior conditions of the pipe at established intervals and locations.
The space equal to the width and depth of the equipment and extending from the floor to a height of 6 ft (1.8 m) above the equipment or to the structural ceiling, whichever is lower, shall be dedicated to the electrical installation. No piping, ducts, leak protection apparatus, or other equipment foreign to the electrical installation shall be located in this zone.
Exception: Suspended ceilings with removable panels shall be permitted within the 1.8-m (6-ft) zone. [70:110.26(E)(1)(a)]
22.31.2.2
The area above the dedicated space required by 22.31.2.1 shall be permitted to contain foreign systems, provided protection is installed to avoid damage to the electrical equipment from condensation, leaks, or breaks in such foreign systems. [70:110.26(E)(1)(b)]
22.31.2.3*
Sprinkler protection shall be permitted for the dedicated space where the piping complies with this section. [70:110.26(E)(1)(c)]
22.32 Fire Protection of Telecommunication Facilities.
22.32.1 Design Requirements. (Reserved)
22.32.2 Installation Requirements.
22.32.2.1
All piping for dry pipe and pre-action sprinkler systems shall be installed with a pitch in accordance with NFPA 13 whether or not the piping is subjected to freezing conditions. [76:8.6.2.2.2]
22.33 Exhaust Systems for Air Conveying of Vapors, Gases, Mists, and Noncombustible Particulate Solids.
22.33.1 Design Requirements.
22.33.1.1 Any portion of an exhaust system utilizing combustible
components or having the potential for combustible
residue buildup on the inside, where the duct cross-sectional
area is greater than or equal to 75 in.2 (480 cm2), shall be
provided with an automatic extinguishing system within the
duct and at the duct intake, hood, enclosure, or canopy, or
shall be constructed of material listed for use without sprinkler
protection. [91:9.1]
Formatted: Font: Bold
22.33.1.21
When a sprinkler system is installed, means shall be provided to prevent water accumulation in the duct or flow of water back to a process subject that could be damaged by water. [91:9.2]
22.33.2 Installation Requirements. (Reserved)
22.34 Hypobaric Facilities.
22.34.1 Design Requirements.
22.34.1.1
A fire suppression system consisting of independently supplied and operating handline and fixed deluge-type water spray systems shall be installed. [99B:4.5.1.5]
22.34.1.2
Design of the fire suppression system shall be such that failure of components in either the handline or deluge system will not render the other system inoperative. [99B:4.5.1.6]
22.34.1.3
System design shall be such that activation of either the handline or the deluge system shall automatically cause the following:
(1) Visual and audio alarm indicators shall be activated at the chamber operator's console.
(2) All ungrounded electrical leads for power and lighting circuits contained inside the chamber shall be disconnected.
(3) Emergency lighting and communication, where used, shall be activated.
[99B:4.5.1.7]
22.34.1.4
Intrinsically safe circuits, including sound-powered communications, shall be permitted to remain connected when either the handline or deluge system is activated. [99B:4.5.1.8]
22.34.1.5
Control circuitry and other electrical equipment involved in the fire detection and suppression system shall be powered from the critical branch of the emergency electrical system and connected to the uninterruptible power supply (UPS). [99B:4.5.1.11]
22.34.1.6
In chambers that consist of more than one compartment, the deluge system shall operate independently or simultaneously even if the compartments are at different pressures (altitudes). [99B:4.5.2.2]
22.34.1.7
Fixed deluge systems shall not be required in chamber compartments that are used strictly as personnel transfer compartments and for no other purpose. [99B:4.5.2.3]
22.34.1.8
Manual activation and deactivation deluge controls shall be located at the operator's console and in each chamber compartment containing a deluge system. [99B:4.5.2.4]
22.34.1.9
Controls shall be designed to prevent unintended activation. [99B:4.5.2.4.1]
22.34.1.10
Water shall be delivered from the fixed discharge nozzles of the deluge system within 3 seconds of activation of any affiliated deluge control. [99B:4.5.2.5]
22.34.1.11*
Total water demand shall be determined by multiplying the total chamber floor area by 7.5 gpm/ft2 (305.6 L/min/m2). [99B:4.5.2.5.1]
22.34.1.12
The minimum operating pressure at the nozzle shall be 30 psi (206 kPa). [99B:4.5.2.5.2]
22.34.1.13
The water supply shall be constantly and fully charged. [99B:4.5.2.6]
22.34.1.14
The water supply pressure shall be constantly monitored and an interlock shall prevent chamber operation if water supply pressure has fallen 10 percent below normal operating charge pressure. [99B:4.5.2.7]
22.34.1.15
There shall be water in the deluge system to maintain the flow specified in 22.34.1.11 simultaneously in each chamber containing the deluge system for 1 minute. [99B:4.5.2.8]
22.34.1.16
The limit on maximum extinguishment duration shall be governed by the chamber capacity (bilge capacity also, if so equipped) and/or its drainage system. [99B:4.5.2.9]
22.34.1.17
The deluge system shall have stored pressure to operate for at least 15 seconds without electrical branch power. [99B:4.5.2.10]
22.34.2 Installation Requirements. (Reserved)
22.35 Coal Mines.
22.35.1 Design Requirements.
22.35.1.1 Underground Mining Operations.
22.35.1.1.1*
Fire sprinkler systems for underground mining operations shall be designed and installed in accordance with NFPA 120.
22.35.1.2 Coal Preparation Plants and Crusher Buildings.
22.35.1.2.1
When automatic sprinkler systems are to be supplied through the standpipe system, hydraulic calculations shall be used to ensure that the piping and the water supply meet the hose and automatic sprinkler demands simultaneously. [120:6.3.2.3.2]
22.35.1.3 Underground Conveyors.
22.35.1.3.1
The application rate shall not be less than 10.2 L/min/m2 (0.25 gpm/ft2) of the top surface of the top belt. [120:9.4.6.4]
22.35.1.3.2
The water supply shall be free of excessive sediment and corrosives and provide the required flow for not less than 10 minutes. A strainer with a flush-out connection and manual shutoff valve shall be provided. [120:9.4.6.6]
22.35.1.3.3
The system shall be interlocked to shut down the conveyor and provide an audible and a visual alarm. [120:9.4.6.8]
22.35.1.3.4
Fire suppression systems shall also comply with 22.35.1.1.1. [120:9.4.6.10]
22.35.1.3.5
Sprinkler systems shall meet the following requirements:
(1) The sprinklers shall be installed in accordance with NFPA 13 as far as practical, and shall have components that have been listed.
(2) The water supply shall be capable of supplying a constant flow of water with all heads functioning for a period of 10 minutes.
(3) The sprinkler head activation temperature shall not be less than 65.6°C (150°F) or greater than 148.9°C (300°F).
[120:9.4.6.13]
22.35.2 Installation Requirements.
22.35.2.1 Underground Conveyors.
22.35.2.1.1
Deluge water spray systems, foam systems, closed-head sprinkler systems, or dry-chemical systems automatically actuated by rise in temperature shall be installed at main and secondary belt conveyor drives. [120:9.4.6.1]
22.35.2.1.2
Fire suppression systems shall extend to the drive areas of belt conveyors, including drive motor(s), reducer, head pulley, and belt storage unit (takeup), including any hydraulic power unit; its electrical controls; and the top and bottom of the first 15.2 m (50 ft) of belt from the drive on the downwind side. [120:9.4.6.2]
22.35.2.1.3
Piping for the deluge, foam, or closed-head sprinkler system shall be metal and listed for sprinkler applications. [120:9.4.6.3]
22.35.2.1.4
The discharge shall be directed at both the upper and the bottom surface of the top belt and the upper surface of the bottom belt. [120:9.4.6.5]
22.35.2.1.5
Maximum distance between nozzles on a branch line shall not exceed 2.4 m (8 ft). [120:9.4.6.7]
22.35.2.1.6
The components of the system shall be located so as to minimize the possibility of damage by roof fall or by the moving belt and its load. [120:9.4.6.9]
22.35.2.1.7
Deluge water spray systems shall meet the requirements of 22.35.2.1.7.1 through 22.35.2.1.7.5. [120:9.4.6.11]
22.35.2.1.7.1
The system shall be activated by heat detectors. [120:9.4.6.11.1]
22.35.2.1.7.2
Heat detectors shall be located at the belt drive, hydraulic takeup unit (unless fire-resistive fluid is used), discharge roller, and the roof above the conveyor. [120:9.4.6.11.1.1]
22.35.2.1.7.3
Heat detectors at the roof line should be spaced 2.4 m to 3.0 m (8 ft to 10 ft) apart along the entire length of the protected area of the belt. [120:9.4.6.11.1.2]
22.35.2.1.7.4
The nozzles shall be full cone, corrosion resistant, and provided with blow-off dust covers. [120:9.4.6.11.2]
22.35.2.1.7.5
A closed sprinkler head shall be used over the electrical controls. [120:9.4.6.11.3]
22.35.2.2 Mine Surface Buildings.
22.35.2.2.1
If sprinklers are installed, waterflow, valve tamper, and low building temperature alarms shall be provided. [120:8.6.1.2]
22.36 Metal/Nonmetal Mining and Metal Mineral Processing Facilities.
22.36.1 Design Requirements.
22.36.1.1 Water Supplies.
22.36.1.1.1
When automatic sprinkler systems are supplied through the hand hose line standpipe system, hydraulic calculations shall be used to ensure that the piping and water supply will supply the hose and automatic sprinkler demands simultaneously. [122:6.2.3]
22.36.1.1.2
Where a fire water supply [for a surface mineral processing plant] is required by the risk assessment, capacity and availability shall provide the water demand for fire-fighting purposes, including hose and sprinkler systems, for a minimum duration of 2 hours. [122:13.7.2]
22.36.1.2*
Where provided, automatic sprinkler systems installed for the protection of flammable liquid or diesel fuel storage areas shall be of the foam-water type. [122:11.3.1]
22.36.1.3 New Solvent Extraction (SX) Facilities.
22.36.1.3.1
Fixed fire suppression shall be provided for the following SX facility areas and equipment:
(1) Buildings housing SX processes
(2) Interior of all mixer-settler vessels/cells
(3) Crud tanks that include treatment filters and centrifuges
(4) Coalescers
(5) Along launders and weirs outside of mixer-settler vessels
(10) Over elevated pipe racks carrying organic solvents in plastic pipes
(11) Other areas handling, processing, or exposed to flammable or combustible liquids
[122:13.19.1]
22.36.1.3.2*
Fire suppression for applications in 22.36.1.3.1 shall be water, foam, dry chemical, or water mist. [122:13.19.1.1]
22.36.1.3.3*
Design of fire suppression systems in 22.36.1.3.1 shall be based on criteria set forth in NFPA 11; NFPA 15; NFPA 16; and NFPA 17. [122:13.19.1.2]
22.36.1.3.4*
Actuation of fire suppression systems in 22.36.1.3.1 shall be automatic. [122:13.19.1.3]
22.36.1.3.5
As exposure protection, automatic water-only deluge (open-head) sprinkler systems shall be provided between mixer-settler trains if spaced closer than 15.24 m (50 ft) from each other. [122:13.19.2]
22.36.1.3.6
As exposure protection, automatic water-only deluge sprinkler systems shall be provided around the exterior perimeter of organic solvent tanks if spaced closer than 15.24 m (50 ft) from each other. [122:13.19.3]
22.36.1.3.7
As exposure protection, automatic fire suppression shall be provided over other critical equipment (i.e., transformers) or outside along important building walls [i.e., motor control center (MCC) rooms] that are within 15.24 m (50 ft) of a solvent fire area. [122:13.19.4]
22.36.1.3.8
Hydraulic design of automatic fire suppression systems in 22.36.1.3.1 shall include the simultaneous operation of all fire protection systems associated with a single (multi-cell) train. [122:13.19.5]
22.36.1.3.9
The total flow rate of foam application and water associated with the discharge of automatic fire extinguishing systems, fixed monitors, and hydrants shall determine the total volume of fire water required. [122:13.19.6]
22.36.2 Installation Requirements. (Reserved)
22.37 Hazardous Materials Code.
22.37.1 Design Requirements.
Sprinkler system discharge criteria for the protection of hazardous materials shall comply with NFPA 400.
22.37.1.1 Requirements for Occupancies Storing Quantities of Hazardous Materials Exceeding the Maximum Allowable Quantities per Control Area for High Hazard Contents.
The design of the sprinkler system shall be not less than ordinary hazard Group 2 in accordance with NFPA 13, except as follows:
(1) Where different requirements are specified in Chapters 11 through 21 of NFPA 400
(2) Where the materials or storage arrangement requires a higher level of sprinkler system protection in accordance with nationally recognized standards
(3) Where approved alternative automatic fire extinguishing systems are permitted
[400:6.2.1.1.1]
22.37.1.2 General Requirements for Storage of Ammonium Nitrate Solids and Liquids.
Sprinkler systems shall be of the approved type and designed and installed in accordance with NFPA 13, and the following:
(1) Ammonium nitrate in noncombustible or combustible containers (paper bags or noncombustible containers with removable combustible liners) shall be designated as a Class I commodity.
(2) Where contained in plastic containers, ammonium nitrate shall be designated as a Class II commodity.
(3) Where contained in fiber packs or noncombustible containers in combustible packaging, ammonium nitrate shall be designated as a Class III commodity.
[400:11.2.6.1.3 ]
22.37.1.3 General Requirements for Storage of Organic Peroxide Formulations.
22.37.1.3.1
Where required by other provisions of this code, automatic sprinklers and water spray systems shall be designed and installed according to the requirements of NFPA 13 and NFPA 15 and shall provide the following discharge densities:
(1) Class I — 0.50 gpm/ft2 (20.4 L/min/m2)
(2) Class II — 0.40 gpm/ft2 (16.3 L/min/m2)
(3) Class III — 0.30 gpm/ft2 (12.2 L/min/m2)
(4) Class IV — 0.25 gpm/ft2 (10.2 L/min/m2)
[400:14.2.6.1]
22.37.1.3.2
The system shall be designed as follows:
(1) It shall provide the required density over a 3000 ft2 (280 m2) area for areas protected by a wet pipe sprinkler system or 3900 ft2 (360 m2) for areas protected by a dry pipe sprinkler system.
(2) The entire area of any building of less than 3000 ft2 (280 m2) shall be used as the area of application.
[400:14.2.6.2]
22.37.1.3.3
Where required for detached storage buildings containing Class I organic peroxide formulations in quantities exceeding 2000 lb (907 kg), automatic sprinkler protection shall be open-head deluge-type, designed and installed in accordance with NFPA 13. [400:14.2.6.3]
22.37.1.4 Indoor Storage of Oxidizer Solids and Liquids.
22.37.1.4.1
Sprinkler protection for Class 2 oxidizers shall be designed in accordance with Table 22.37.1.4.1. [400:15.3.2.3.4.1 ]
Table 22.37.1.4.1 Ceiling Sprinkler Protection for Class 2 Oxidizers in Palletized or Bulk and Rack Storage Areas
Type of Storage
Ceiling Sprinklers
In-Rack Sprinklers
Storage Height Density
Area of Application
ft m gpm/ft2 L/min/m2 ft2 m2
Palletized or bulk 8 2.4 0.20 8 3750 348 —
Palletized or bulk 12 3.7 0.35 14 3750 348 —
Rack 12 3.7 0.20 8 3750 348 One line above each level of storage, except the top level
Rack 16 4.9 0.30 12 2000 186 One line above each level of storage, except the top level
[400: Table 15.3.2.3.2.10(B)]
22.37.1.4.2
Ceiling sprinklers shall be high-temperature sprinklers. [400:15.3.2.3.4.2]
22.37.1.4.3 Storage Protection for Class 2 Oxidizers with In-Rack Sprinklers.
(A)
In-rack sprinklers shall be quick-response sprinklers with an ordinary-temperature rating and have a K-factor of not less than K = 8.0. [400:15.3.2.3.4.3(A)]
(B)
In-rack sprinklers shall be designed to provide 25 psi (172 kPa) for the six most hydraulically remote sprinklers on each level. [400:15.3.2.3.4.3(B)]
(C)
The in-rack sprinklers shall be 8 ft to 10 ft (2.4 m to 3.0 m) spacings in the longitudinal flue space at the intersection of the transverse flue spaces. [400:15.3.2.3.4.3(C)]
22.37.1.4.4 Sprinkler Criteria for Class 3 Oxidizers.
22.37.1.4.4.1 Class 3 Oxidizers Less than 2300 lb (1043 kg).
(A)
Sprinkler design criteria for buildings that require sprinkler protection and contain total quantities of Class 3 oxidizers less than 2300 lb (1043 kg) shall be in accordance with the requirements of 22.37.1.4.4.1(B). [400:15.3.2.4.13.1(A)]
(B)
Facilities that require sprinkler protection and contain total quantities of Class 3 oxidizers greater than 200 lb (91 kg), but less than 2300 lb (1043 kg), shall follow the sprinkler design criteria in Table 22.37.1.4.4.1(B). [400:15.3.2.4.13.1(B)]
Table 22.37.1.4.4.1(B) Sprinkler Protection of Class 3 Oxidizers Stored in Total Quantities Greater than 200 lb (91 kg) but Less than 2300 lb (1043 kg)
Storage Parameters Shelf Bulk or Pile Bulk or Pile Rack
Maximum storage height 6 ft (1.8 m) 5 ft (1.5 m) 10 ft (3 m) 10 ft (3 m)
Maximum ceiling height 25 ft (7.6 m) 25 ft (7.6 m) 25 ft (7.6 m) NA
22.37.1.4.4.4 Special In-Rack Sprinkler Protection for Class 3 Oxidizers.
(A)
Where required by Table 22.37.1.4.4.3, special in-rack sprinkler protection shall be as shown in Figure 22.37.1.4.4.4(A). [400:15.3.2.4.13.5(A)]
Figure 22.37.1.4.4.4(A) Arrangement of Barriers and In-Rack Sprinklers for Special Fire Protection Provisions. [400: Figure 15.3.2.4.13.5(A)]
(B)
In-rack automatic sprinklers shall be provided under each horizontal barrier and arranged in accordance with 22.37.1.4.4.4(C) through 22.37.1.4.4.4(I). [400:15.3.2.4.13.5(K)]
(C)
For double-row racks, two lines of in-rack sprinklers shall be provided between the face of the rack and the longitudinal vertical barrier located in the center of the rack. [400:15.3.2.4.13.5(L)]
(D)
For single-row racks, two lines of in-rack sprinklers shall be provided between each rack face. [400:15.3.2.4.13.5(M)]
(E)
Three in-rack sprinklers shall be provided on each in-rack sprinkler line as follows:
(1) Two sprinklers on each line shall be spaced approximately 11⁄2 in. (38.1 mm) from each transverse vertical barrier.
(2) One in-rack sprinkler on each in-rack sprinkler line shall be located approximately equidistant between the transverse vertical barriers.
[400:15.3.2.4.13.5(N)]
(F)
In-rack sprinklers shall be of the upright or pendent type, with the fusible element located no more than 6 in. (152.4 mm) from the horizontal barrier. [400:15.3.2.4.13.5(O)]
(G)
In-rack sprinklers shall be K = 8.0, quick-response, ordinary-temperature-rated sprinklers. [400:15.3.2.4.13.5(Q)]
(H)
The in-rack sprinkler system shall be designed to supply 6 sprinklers on each line, with a total of 12 sprinklers operating at gauge pressure of 25 psi (172 kPa). [400:15.3.2.4.13.5(R)]
(I)
The design of the in-rack sprinkler system shall be independent of, and shall not be required to be balanced with, ceiling sprinkler systems. [400:15.3.2.4.13.5(S)]
22.37.1.4.4.5 Sprinkler Criteria for Class 4 Oxidizers.
(A)
Sprinkler protection for Class 4 oxidizers shall be installed on a deluge sprinkler system to provide water density of 0.35 gpm/ft2 (14.4 L/min/m2) over the entire storage area. [400:15.3.2.5.4.6(A)]
(B)
Sprinkler protection shall be installed in accordance with NFPA 13. [400:15.3.2.5.4.6(B)]
22.37.2 Installation Requirements.
(Reserved)
A.22.4.1.1
Spray application operations should be located only in buildings that are completely protected by an approved system of automatic sprinklers. If the operations are located in unsprinklered buildings, sprinklers should be installed to protect spray application processes where practical. Because of the rapidity and intensity of fires that involve spray operations, the available water should be ample to simultaneously supply all sprinkler heads likely to open in one fire without depleting the available water for use by hose streams. Noncombustible draft curtains can be used to limit the number of sprinklers that will open.
Even when areas adjacent to coating operations are considered under reasonably positive fire control by adequate automatic sprinkler protection, damage is possible if operations are conducted on floors above those containing contents that are highly susceptible to water damage. Waterproofing and drainage of spray room floors can assist in reducing water damage on floors below. Proper drainage of the large volume of water frequently necessary to extinguish spray finishing room fires often presents considerable difficulty.
Automatic sprinklers in spray areas, including the
interior of spray booths and exhaust ducts, should be wet pipe,
preaction, or deluge system so that water can be placed on the
fire in the shortest possible time. Automatic sprinklers in spray
booths and exhaust ducts should be of the lowest practical
temperature rating. The delay in application of water with ordinary
dry pipe sprinklers can permit a fire to spread so rapidly
that final extinguishment is difficult without large resulting
damage.
The location of the sprinkler heads inside spray booths
should be selected with care in order to avoid heads being
placed in the direct path of spray and yet afford protection for
the entire booth interior. When sprinkler heads are in the
direct path of spray, even one day’s operation can result in
deposits on the sprinkler heads that insulate the fusible link or
choke open head orifices to the extent that sprinklers cannot
operate efficiently.
Automatic sprinklers should also be located so that areas
subject to substantial accumulations of overspray residue are
protected. Generally, sprinklers are located no more than 4 ft
(1.2 m) from side walls of booths and rooms and from dry
overspray collectors (where applicable). Sprinklers in booths
or rooms should be on extra hazard occupancy spacing of
90 ft2 (8.4 m2).
All sprinklers in spray areas should be controlled by an
accessible control valve, preferably an OS&Y valve. [33: A.9.4]
Subsection 22.4.1.1 lists four types of automatic sprinkler systems and requires that the one “most appropriate for the portion of the spray area being protected” be used. Generally, an open-head deluge system provides the highest level of protection, given that all sprinklers in the protected area flow simultaneously. This type of system is most appropriate for large, downdraft, water-wash spray booths when protecting automatic electrostatic spray application zones.
Wet pipe automatic sprinkler systems are appropriate for protecting spray booths that utilize nonelectrostatic application processes or operations using listed electrostatic application processes. Wet pipe systems are also generally used to protect exhaust plenums (eliminator or scrubber sections), exhaust ducts, and air recirculation filter houses.
Dry pipe systems have been included because some exhaust duct designs include sections that are subject to freezing.
Preaction systems have been included because some spray application processes and equipment can be damaged by unwanted water discharge. This damage can be disruptive and costly. Powder spray booths and solvent concentrator (air pollution abatement) systems are examples of systems where it is appropriate to use a preaction system. [33: A.9.4.1]
Water supply requirements for most industrial paint spray operations should be adequate to supply all automatic sprinklers in the spray area. Loss experience has shown that fires starting in the exhaust duct can spread to the spray booth and that fires starting in the booth can spread to the exhaust duct.
Sprinklers or sprinkler systems protecting stacks or ducts should be of a type not subject to freezing. Automatic systems are preferred, but manual systems are also acceptable. For some industries, such as the automotive industry, manually operated open-head systems have proved to be effective protection for ducts and stacks. [33: A.9.4.6]
A.22.5.1
Water spray or deluge systems that are used to protect solvent extraction process equipment or structures should be designed to provide a density of not less than 0.25 gpm/ft2 (10.3 mm/min) of protected surface area. (See NFPA 13 and NFPA 15, for additional information.) Foam-water sprinkler or deluge systems that are used for the same purposes should be designed to provide a density of not less than 0.16 gpm/ft2 (6.5 mm/min) of protected surface area. (See NFPA 13 and NFPA 16 for additional information.)
Preparation buildings should be protected with automatic sprinkler systems designed for ordinary hazard (Group 2), in accordance with NFPA 13. [36: A.4.8]
A.22.6.1
Automatic sprinkler systems are considered to be effective in controlling lubricating oil fires. Sprinkler densities provided in this standard are based on Extra Hazard, Group 1 occupancy as defined in NFPA 13. Automatic sprinkler protection designed as local protection for the engine in many cases provides better protection than sprinkler protection installed only at the ceiling level, particularly in the case of pressurized lubricating oil fires.
Consideration should be given to providing local protection when the protected engine equipment is located in a high bay area. Delayed activation time or lack of water penetration could delay fire suppression from a ceiling system.
Local protection for engines can be accomplished using either a wet system or a single interlock pre-action deluge system with heat detection. Detectors for actuation of a pre-action system should be located above the engine and around the system piping.
For diesel engine installations, the system piping should loop the engine at the height of the cylinder heads.
Because of the tight radial clearances on combustion gas turbines and the potential for rubbing of rotating parts and increased damage, it is advisable to use great care if using a sprinkler or water spray suppression system. Water from a ceiling or spot protection system could effectively control a fire; however, gaseous suppression agents could be just as effective without the potential for equipment damage when the system activates. [37: A.11.4.5.1]
A.22.7.1.3
See Figure A.22.7.1.3. The illustration shows the location of sprinkler heads and the decomposition vent. [40: A.6..3]
Figure A.22.7.1.3 Standard Film Vault (for Other Than Extended Term Storage Film). [40:Figure A.6.3]
A.22.7.1.8
One acceptable nozzle spray pattern would be such that at a 2.4 m (8 ft) distance the cone is about 1.5 m (5 ft) in diameter. See Figure A.22.7.1.8. [40: A.6.5.6.4]
Figure A.22.7.1.10(a) shows an example of a nozzle layout consistent with the recommended arrangement for a vault design as shown in Figure A.22.7.1.10(b). [40: A.6.5.6.6]
Figure A.22.7.1.10(a) Nozzle Layout for Typical Vault. [40:Figure A.6.5.6.6(a)]
In facilities that are under the supervision of an operator or other person familiar with the equipment, during all periods that equipment is energized, the normal delay between the initial outbreak of a fire and the operation of a sprinkler system will provide adequate time for operators to shut down the power by use of the electrical disconnecting means as prescribed in Section 10.4 of NFPA 75. In other instances where a fire can operate sprinkler heads before discovery by personnel, a method of automatic detection should be provided to automatically de-energize the electronic equipment as quickly as possible.
To minimize damage to electronic computer equipment located in sprinkler-protected areas, it is important that power be off prior to the application of water on the fire. [75: A.8.1.2]
A.22.14.2.3
The use of carbon dioxide systems for the protection of spaces beneath raised floors is discussed in Section B.5 of NFPA 12, wherein it is pointed out that the design of such systems requires compensation for leakage and provision for a soft discharge to minimize turbulence and agent loss through perforated tiles. These same concerns exist for other inert gas clean agent systems installed in accordance with NFPA 2001. Since these spaces are usually of a very limited height, this type of fire suppression system may be easier to design and install than sprinklers. [75: A.8.1.1.2]
A.22.15.2.2
See Figure A.22.15.2.2(a) through Figure A.22.15.2.2(h).
Automatic sprinkler protection should be considered for ovens, furnaces, or related equipment if any of the following conditions exists:
(1) The material being processed is combustible.
(2) Racks, trays, spacers, or containers are combustible.
(3) There are areas where appreciable accumulations of combustible drippings or deposits are present on the inside of the oven surface or on racks, trays, and so forth.
The type of sprinklers and arrangement should be appropriate to the oven arrangement, interior ductwork, and the material passing through the oven. [86: A.9.2.1]
A.22.16.2.6
At elevated temperatures, galvanizing can flake off of pipe surfaces, and the flakes can collect at and obstruct the discharge of the fire suppression system. [86: A.9.3.2]
A.22.17.1.5
More than one control station could be required in a compartment (lock) depending on its size. [99: A.14.2.5.2.4]
A.22.17.1.8
Experience has shown that, when water is discharged through conventional sprinkler heads into a hyperbaric atmosphere, the spray angle is reduced because of increased resistance to water droplet movement in the denser atmosphere. This is so, even though the water pressure differential is maintained above chamber pressure. Therefore, it is necessary to compensate by increasing the number of sprinkler heads. It is recommended that spray coverage tests be conducted at maximum chamber pressure.
Some chamber configurations, such as small-diameter horizontal cylinders, could have a very tiny floor, or even no floor at all. For horizontal cylinder chambers and spherical chambers, floor level should be taken to mean the level at 1⁄4 diameter below the chamber centerline or actual floor level, whichever yields the larger floor area. [99: A.14.2.5.2.6]
A.22.19.4
See A.4.11.1.3.1 of NFPA 140. [140: A.5.11.4]
Paragraphs 4.11.1.3.1 and 4.11.1.3.2 recognize
motion picture and television industry practices that require
sets to change constantly and that sets are “temporary” construction
not subject to building codes or standards. Solid ceilings
that obstruct the stage sprinklers are “flown” (moved) in
or out to permit special shooting angles or lighting requirements,
often on a scene-by-scene basis. With temporary walls
and ceilings, it would be impractical to install a sprinkler system
in a constantly changing structure. Therefore, one or
more of the following mitigation techniques should be used to
compensate for the areas shielded from sprinkler spray by
solid or hard ceilings or platforms:
(1) Approved and listed heat detectors or smoke detectors can
be installed beneath such solid or hard ceilings in excess of
600 ft2 (55.7 m2) in area and platforms in excess of 600 ft2
Formatted: Font: (Default) Arial, 10 pt, Font color:Custom Color(RGB(30,41,96))
(55.7 m2) in area and 3 ft (0.9 m) in height. Detectors
should be connected to an approved and listed central, proprietary,
or remote station service or to a local alarm that will
provide an audible signal (i.e., a bell or horn) at a constantly
attended location. The detector system, including the alarm
panel, is defined as a portable system because it is intended
to be reinstalled when platforms or sets are changed. The
detectors that are secured to standard outlet boxes and the
listed fire alarm panels can be temporarily supported by sets,
platforms, or pedestals. Spacing of detectors should be per
manufacturers’ requirements.
(2) The ceiling can be positioned to allow for the operation
of the building’s automatic fire sprinkler system after videotaping,
filming, or broadcasting of programs has been
completed for the day.
(3) Afire watch should be provided when the set is not in use.
(4) No combustible materials should be stored under any
platforms. Consideration should be given to secure such
covered areas with screen wire or other materials that will
permit visual inspection and emergency access.
(5) Approved/listed fire retardants can be applied beneath
combustible platforms.
(6) Approved/listed fire retardants can be applied to scenery,
props, framework and deck of combustible platforms,
and the hard ceilings of combustible sets.
[40:A.4.11.1.3.1]
A.22.19.5
See A.4.11.1.3.1 of NFPA 140A.22.19.4. [140: A.5.11.5]
A.22.21.1.1.1
A deluge system provides a higher degree of protection where water supplies are adequate. In climates that are subject to freezing temperatures, a deluge system minimizes the possibility of failure due to pipes freezing. [214: A.5.2.2.1]
A.22.21.1.1.2
The crossflow design is such that it is difficult to locate sprinklers in the most desirable spots for both water distribution and heat detection. This situation can be solved by separating these two functions and using separate water discharge and detection systems. [214: A.5.2.2.2]
A.22.21.1.5
See Figure A.22.21.2.5
A.22.21.1.7.1.1
Where a single deluge system protects an entire water-cooling tower, regardless of the number of cells, the water supply needs to be based on the entire deluge system coverage. (See Figure A.22.21.1.7.1.1.) [214: A.5.6.1.1]
Figure A.22.21.1.7.1.1 Single Deluge System. [214:Figure A.5.6.1.1]
A.22.21.1.7.1.3
Deluge systems separated by fire-resistant partitions can be treated independently as worst-case water supply situations. (See Figure A.22.21.1.7.1.3.) [214: A.5.6.1.3]
Formatted: Font: (Default) Arial, 10 pt, Font color:Custom Color(RGB(30,41,96))
Formatted: Font: (Default) Arial, 10 pt, Font color:Custom Color(RGB(30,41,96))
Formatted: Font: (Default) Arial, 10 pt, Font color:Custom Color(RGB(30,41,96))
Formatted: Font: (Default) Arial, 10 pt, Font color:Custom Color(RGB(30,41,96))
A.22.21.1.7.2.1
Water-cooling towers with each cell separated by a fire-resistant partition and protected by wet, dry, or preaction system(s) should have the water supply based on the most demanding individual cell. (See Figure A.22.21.1.7.2.1.) [214: A.5.6.2.1]
Figure A.22.21.1.7.2.1 Multiple Wet, Dry, or Preaction Systems with Fire-Resistant Partitions. [214:Figure A.5.6.2.1]
A.22.21.1.7.2.2
Without fire-resistant partitions between cells, the worst-case situation involves the most demanding adjoining cells. (See Figure A.22.21.1.7.2.2.) [214: A.5.6.2.2]
Figure A.22.21.1.7.2.2 Multiple Wet, Dry, or Preaction Systems with No Fire-Resistant Partitions. [214:Figure A.5.6.2.2]
A.22.21.2.1
See Figure A.22.21.2.1(a) through Figure A.22.21.2.1(d).
Figure A.22.21.2.1(a) Plan View, Typical Deluge Fire Protection Arrangement for Counterflow Towers. [214:Figure A.5.2.4.1(a)]
Figure A.22.21.2.1(b) Section View, Typical Deluge Fire Protection Arrangement for Counterflow Towers. [214:Figure A.5.2.4.1(b)]
Figure A.22.21.2.1(c) Plan View, Typical Deluge or Dry Pipe Fire Protection Arrangement for Counterflow Towers. [214:Figure A.5.2.4.1(c)]
Figure A.22.21.2.1(d) Section View, Typical Deluge or Dry Pipe Fire Protection Arrangement for Counterflow Towers. [214:Figure A.5.2.4.1(d)]
A.22.21.2.2
See Figure A.22.21.2.2(a) through Figure A.22.21.2.2(d).
Figure A.22.21.2.2(a) Plan View, Typical Deluge Fire Protection Arrangement for Crossflow Towers. [214:Figure A.5.2.4.2(a)]
Figure A.22.21.2.2(b) Section View, Typical Deluge Fire Protection Arrangement for Crossflow Towers. [214:Figure A.5.2.4.2(b)]
Figure A.22.21.2.2(c) Plan View, Typical Deluge Fire Protection Arrangement for Multicell Crossflow Towers. [214:Figure A.5.2.4.2(c)]
Figure A.22.21.2.2(d) Section View, Typical Deluge Fire Protection Arrangement for Multicell Crossflow Towers. [214:Figure A.5.2.4.2(d)]
A.22.21.2.3
Location of the nozzle relative to surfaces to be protected should be determined by the particular nozzle's discharge characteristics. Care should also be taken in the selection of nozzles to obtain waterways not easily obstructed by debris, sediment, sand, and so forth, in the water. [See Figure A.22.21.2.3(a) and Figure A.22.21.2.3(b).] [214: A.5.2.4.3]
Figure A.22.21.2.3(a) Plan View, Typical Deluge Fire Protection Arrangement for Crossflow Towers with Completely Enclosed Distribution Basins. [214:Figure A.5.2.4.3(a)]
Figure A.22.21.2.3(b) Section View, Typical Deluge Fire Protection Arrangement for Crossflow Towers with Completely Enclosed Distribution Basins. [214:Figure A.5.2.4.3(b)]
A.22.21.2.5
See Figure A.22.21.2.5.
Figure A.22.21.2.5 Typical Deluge Fire Protection Arrangement for Crossflow Towers with Covers Completely Enclosing Distribution Basins. [214:Figure A.5.2.4.5]
A.22.21.2.10.2
Approved discharge devices are made of nonferrous material and are corrosion-resistant to normal atmospheres. Some atmospheres require special coatings on the discharge devices. [214: A.5.3.2]
A.22.21.2.10.3
Corrosion attacks the exposed metal and, in time, creeps under the wax coating. [214: A.5.3.3]
A.22.22.1.1
Group A plastics represent the most challenging commodities that can be protected by a sprinkler system designed in accordance with this standard. Due to the widely varying nature of commodities that pass through transit sheds, container freight stations, transload facilities, and similar buildings used for handling and temporary storage of general cargo, a minimum automatic
sprinkler design based upon the protection of Group A plastic commodity under the provisions of NFPA 13 provides an appropriate level of fire protection. [307: A.5.4.2.1]
A.22.22.2.1.2.1
Examples of sprinklers that project water upward are pendent sprinklers installed in an upright position or old-style sprinklers. [307: A.4.3.3.1.3.1]
A.22.22.2.1.2.1(B)(3)
An example of crisscross construction (ties on stringers) is illustrated in Figure B.1(a) of NFPA 307. [307: A.4.3.3.1.3.1(B)(3)]
A.22.22.2.1.2.1(B)(5)
The use of firestops for draft control (e.g., to bank heat, facilitate the opening of sprinkler heads, and prevent the overtaxing of the sprinkler system) is particularly important in the design of sprinkler protection for combustible substructures. The fire walls and firestops of 4.3.3.4 and 4.3.3.5 of NFPA 307 should be incorporated into the sprinkler system design for draft control to the maximum extent practical; however, due to limitations in the size of the design area for the sprinkler system, additional firestops normally are needed. These additional or supplemental firestops need only have limited fire resistance, but they should be as deep as possible and be of substantial construction, such as double 3 in. (76.2 mm) planking, where exposed to the elements. Where not exposed to the possibility of physical damage, 3⁄4 in. (19.05 mm) treated plywood extending 48 in. (1219.2 mm) below stringers with solid blocking between stringers should provide adequate durability and reasonable effectiveness. [307: A.4.3.3.1.3.1(B)(5)]
A.22.23.1.1
Typical configurations of cleanrooms and their chases and plenums create numerous areas that might be sheltered from sprinkler protection. These areas can include air-mixing boxes, catwalks, hoods, protruding lighting, open waffle slabs, equipment, piping, ducting, and cable trays. Care should be taken to relocate or supplement sprinkler protection to ensure that sprinkler discharge covers all parts of the occupancy. Care should also be taken to ensure that sprinklers are located where heat will be satisfactorily collected for reliable operation of the sprinkler.
Gaseous fire suppression systems are not substitutes for automatic sprinkler protection. The large number of air changes in cleanrooms can cause dilution or stratification of the gaseous agent.
It is recommended that sprinkler systems be inspected at least semiannually by a qualified inspection service. (See NFPA 25.) The length of time between such inspections can be decreased due to ambient atmosphere, water supply, or local requirements of the authority having jurisdiction.
Prior to taking a sprinkler system out of service, one should be certain to receive permission from all authorities having jurisdiction and to notify all personnel who might be affected during system shutdown. A fire watch during maintenance periods is a recommended precaution. Any sprinkler system taken out of service for any reason should be returned to service as promptly as possible.
A sprinkler system that has been activated should be thoroughly inspected for damage and its components replaced or repaired promptly. Sprinklers that did not operate but were subjected to
corrosive elements of combustion or elevated temperatures should be inspected and replaced if necessary, in accordance with the minimum replacement requirements of the authority having jurisdiction. Such sprinklers should be destroyed to prevent their reuse. [318: A.4.1.2.1]
A.22.23.1.2.1
Examples of combustible materials that might be found in these spaces are as follows:
(1) Roof, floor, wall construction materials
(2) Unapproved HEPA or ULPA filter modules
(3) Supply air or exhaust ducts
(4) Air handler unit enclosures or air plenum boxes
(5) Exposed electrical cable or pipe insulation
(6) Plastic piping
(7) Flammable or combustible liquid piping
[318: A.4.1.2.5.1]
A.22.23.1.3
Small-orifice sprinklers, 3⁄8 in. (9.5 mm) or larger, can be used. [318: A.4.1.2.6.2.1]
A.22.23.1.3.1
Small-orifice sprinklers, 3⁄8 in. (9.5 mm) or larger, can be used. [318: A.4.1.2.6.2.1]
A.22.23.2.1
Automatic sprinkler systems and their water supplies should be designed for maximum reliability. In the event of any impairments of the yard main system, sprinkler system lead-in(s) connections should be capable of being isolated and protection promptly restored through valving or interconnection of automatic sprinkler systems, or both, inside the building. [318: A.4.1.1]
A.22.23.2.2
The use of quick-response sprinklers, while still delayed in opening by the downward airflow, would respond to a smaller-size fire more quickly than would conventional sprinklers. (Glass bulb–type quick-response sprinklers might be preferable to other types of quick-response sprinklers.) [318: A.4.1.2.2]
A.22.23.2.3
Small-orifice sprinklers, 3⁄8 in. (9.5 mm) or larger, can be used. [318: A.4.1.2.6.2.1]
A.22.25.1.2
The exposure to the airport terminal building from the airport ramp is significant. The number of building sprinklers operating from the exposure fire can be greater than from an internal ignition source. [415: A.4.5.1.5]
A.22.25.1.3
The exposure to the airport terminal building from the airport ramp is significant. The number of building sprinklers operating from the exposure fire could be greater than the number of building sprinklers operating from an internal ignition source.
A.22.26.1.1
Because of the nature of the test cell fire potential, deluge systems are considered more appropriate than automatic sprinklers due to their speed of operation and simultaneous discharge of all nozzles; however, automatic sprinklers can be used as follows:
(1) In small cells [600 ft2 (56 m2) or less] where it is likely that all sprinklers would fuse at the same time
(2) As a backup to a manual water spray or other manual system
[423: A.7.6.3]
A.22.27.1.1
The water supply for the permanent fire protection water system should be based on providing a 2-hour water supply for both items (1) and (2), as follows:
(1) Either item (a) or (b), whichever is larger:
(a) The largest fixed fire suppression system demand
(b) Any fixed fire suppression system demand that could be reasonably expected to operate simultaneously during a single event (e.g., turbine underfloor protection in conjunction with other fire protection systems in the turbine area)
(2) The hose stream demand of not less than 500 gpm (1892.5 L/min)
[804: A.9.2.1]
A.22.27.1.5
To avoid water application to hot parts or other water-sensitive areas and to provide adequate coverage, designs that incorporate items such as fusible element operated spray nozzles might be necessary. [804: A.10.8.2.1]
A.22.27.1.6
Additional information concerning turbine generator fire protection can be found in EPRI Research Report 1843-2,“Turbine Generator Fire Protection by Sprinkler System.” [804: A.10.8.3]
A.22.27.2.1.2
A common yard fire main loop can serve multi-unit nuclear power plant sites if it is cross-connected between units. [804: A.9.4.4]
A.22.30.1.1
Standard-response sprinklers employ more robust operating elements than quick-response sprinklers and can be more appropriate for use in areas where concern for inadvertent water discharge outweighs the advantages of thermal sensitivity. [909: A.9.12.12.2]
A.22.30.1.2
Preaction and dry pipe sprinkler systems are more subject to corrosion than standard wet pipe systems, due to the presence of both air and moisture within the pipes. In addition to causing problems which could impair the operation of the sprinkler system and possibly result in system failures, such as preventing valves from opening, restricting water flow and pressure to the sprinklers, and clogging drops and branch lines. The higher rates of corrosion can also result in sprinkler system malfunctions such as leaks that can have a significant adverse impact on sensitive collections and cultural properties. The products of corrosion (black and orange residue made up primarily of ferric and ferrous oxides and hydroxides) that collect in the piping can cause considerable damage to artwork, historic fabric, and collections upon discharge. The corrosion in the systems can also lead to leaks and piping failures, especially at joints, along the bottom of pipes between roll grooves, and other places where moisture accumulates. Based on this, additional precautions are warranted in areas with susceptible collections or historic fabric, or where sprinkler system repairs or replacement of piping would put the building or contents at an unacceptable risk. [909: A.9.12.12.3]
A.22.30.1.3.1
The automatic fire suppression system, the compact storage system, and the storage compartmentation features should be designed to limit fire damage in accordance with the facility’s fire safety objectives (e.g., confine fire growth to the compact storage module of origin). Significant factors to consider include the number and size of the storage modules, the separation provided between the modules (end-to-end and back-to-back), and the type of materials being stored. In general, double-interlock pre-action systems and dry pipe systems are inappropriate for compact storage, because of the additional delay they introduce, coupled with the delays in activation resulting from the compact storage units themselves.
Other protection features should be considered to limit the extent of potential fire damage, including the following:
(1) Very high density sprinkler systems
(2) Quick-response sprinklers
(3) Early-warning smoke detection
(4) Spacers between carriages or, for automated systems, automatic park mode to increase flue spaces between carriages upon activation of a fire alarm or during idle periods
(5) Metal vertical barriers in the middle of the shelf
(6) Open-top shelving .
[909: A.9.12.23.4.1.3]
A.22.30.1.3.2
The system should be designed to confine fire growth to the compact storage module of origin or the shelving range of origin. [909: A.9.12.23.4.1.4(A)]
A.22.30.2.1
Although prior to the 2007 edition NFPA 13 permitted the pipe for systems not subject to freezing to be installed without a back pitch, similar to the design of wet pipe systems, this arrangement allows water to accumulate in low points, increasing the rate of corrosion. Proper pitching is an important element in reducing the risk of corrosion. The pitch requirements included in NFPA 13 should be considered the minimum acceptable pitch. Where adequate clearance is provided to permit the system to be installed without causing interferences with structural elements or causing low points, pitches exceeding this minimum requirement such as 4 mm/m (1⁄2 in. per 10 ft) should be considered. [909: A.9.12.12.3.1]
A.22.30.2.2
Additional auxiliary drainage should be provided, in accordance with NFPA 13, regardless of whether the protected area is subject to freezing. [909: A.9.12.12.3.2.1]
A.22.30.2.3
The wording is based on NFPA 13, 24.1.5.2. The special sensitivity of cultural resource properties to water damage that could result from piping corrosion warrants the assumption of water supplies and environmental conditions that contribute to unusual corrosive properties. [909: A.9.12.12.3.3]
A.22.31.2.3
The intent of the NFPA 70 is to allow sprinkler piping in the room protecting the space covering the floor area that includes the electrical equipment as long as the sprinklers and piping are not located in the zone described by 22.31.2.1. The sprinkler and the piping can be above the zone described by 22.31.2.1, but a shield needs to be installed in this case to protect the electrical equipment from potential leakage. [70:110.26(E)(1)(c)
A.22.34.1.11
The quantities and pressure of water for fire extinguishing indicated in 22.34.1.11 are based on limited testing and should be considered subject to change as additional data become available. It is recommended that spray coverage tests be carried out at maximum altitude for manned operations. [99B:A.4.5.2.5.1]
A.22.35.1.1.1
See 4.3.3 of NFPA 120 for unique requirements for protecting this unusual type of occupancy.
A.22.36.1.2
Underground shaft mines that use diesel-powered equipment generally employ underground diesel fuel storage areas to facilitate equipment refueling. Adit-type mines in the western United States can initially locate diesel fuel storage and refueling facilities on the surface; however, as the active mine workings progress further from the adit portal(s), these facilities usually are moved underground.
A common means of fire protection currently found in many underground diesel fuel storage areas is a fixed water sprinkler system. The federal Mine Safety and Health Administration (MSHA) currently approves such systems for this application. The consensus of the committee is that this situation represents a significant safety hazard. According to the NFPA Fire Protection Handbook, water sprinklers can be used on diesel fuel for control but not for extinguishment.
“The Health and Safety Implications of the Use of Diesel- Powered Equipment in Underground Mines,” a report by an interagency task group prepared for MSHA in 1985, concludes that “water spray or fog usually will not extinguish diesel fuel fires.”
In an underground mine, fire control is not sufficient; fire extinguishment is essential for the following reasons:
(1) As long as a fire burns, even if it does not grow in intensity or area and appears to be responsive to fire control, toxic smoke and fire gases are produced that can endanger persons in the mine.
(2) According to the NFPA Fire Protection Handbook, overpressure failure of containers when exposed to fire is considered the principal hazard of closed-container flammable and combustible liquid storage.
Formatted: Font: Bold
Formatted: Font: Bold
(3) Even a “controlled” fire can cause container failure, producing a fire so intense that the sprinkler system is unable to control it, much less extinguish it.
(4) Water sprays are not effective in extinguishing pressure fires, running fuel fires, and obstructed spill fires, all of which can occur in a diesel refueling area.
(5) Water supplies are limited in many underground mines. Fire control, therefore, should be considered temporary, because the fire will grow immediately to maximum intensity when the water supply is depleted.
(6) The vapor pressure of diesel fuel increases with elevation due to reduced barometric pressure. As a result, even fuels without flash point–reducing additives can become flammable, depending on the altitude at which they are used. This reduction in flash point could result in reclassification of the diesel fuel to a Class IC flammable liquid. There is no clear consensus in the literature and industry practice as to the effectiveness of fixed water sprays in controlling and extinguishing fires involving Class IC flammable liquids. Although industry practice strongly favors fixed water sprays for such applications, the literature and available research results clearly indicate the ineffectiveness of fixed sprays on Class IC liquids, especially on pressure fires, running fuel fires, and obstructed spill fires.
Water sprinkler systems installed for the protection of diesel fuel storage areas might not be effective in suppression even though they do provide good control through cooling; foam-water systems can provide suppression. [122: A.11.3.1]
A.22.36.1.3.2
Although water-only deluge, foam-water, and dry chemical systems might be effective in controlling or suppressing SX facility fires, there might be use for more than one application in a given facility. Manual response has been ineffective in recent losses and automatic suppression is advised for both existing and new facilities.
While water spray can be effective, due to potentially high flow requirements a mixer-settler cell might overflow during the suppression process. This might create additional concerns with drainage and fire spread.
Foam has been shown to be an effective suppressant medium for SX fires. However, environmental aspects, potential contamination of process liquids (particularly associated with accidental system initiation), and the difficulty or inability to conduct system flow tests on a periodic basis are negative points in the selection of foam.
High pressure water mist or fog might prove to be a potentially effective suppressant medium and might not create the contamination, environmental, and testing obstacles that accompany foam or the large volumes that accompany conventional high density water deluge systems. Currently, there are no public domain tests conducted on mist systems for pool fires of the size involved in a large SX settler; thus, actual suppressability under all fire conditions has not been demonstrated. [122: A.13.19.1.1]
A.22.36.1.3.3
The following best practices design guidance for automatic fire suppression systems is advised:
For settler tanks or cells, use either Type 1 foam chambers or open head deluge sprinklers with foam discharge. When using foam chambers, provide a 3 percent aqueous filmforming foam (AFFF) foam discharge, in accordance with NFPA 11, with a density of 4.1 L/min/m2 (0.10 gpm/ft2) over the entire settler area. When using open head deluge sprinklers, provide a 3 percent AFFF foam discharge, in accordance with NFPA 16, with a density of 6.5 L/min/m2 (0.16 gpm/ft2). Design for a 20-minute discharge period.
For mixers, launders, drainage sumps, and piping trenches, use open head deluge sprinklers and provide a 3 percent AFFF foam discharge, in accordance with NFPA 16, with a density of 6.5 L/min/m2 (0.16 gpm/ft2) and a 20-minute foam discharge period.
For the interior of tank farm vessels containing combustible or flammable liquids such as loaded organic tanks, coalescers, crud treatment tanks, and diluent tanks use a Type 1 foam chamber and provide a 3 percent automatic AFFF foam discharge, in accordance with NFPA 11, into each of the tanks with a density of 4.1 L/min/m2 (0.10 gpm/ft2) and a 20-minute foam discharge period.
For the exterior surfaces of tank farm equipment containing combustible or flammable liquids such as loaded organic tanks, coalescers, crud treatment tanks, diluent tanks, crud treatment filters, centrifuges, pumps, and pipe racks, provide automatic open head (water only) deluge sprinklers based on a discharge density of 10.2 L/min/m2 (0.25 gpm/ft2). [122: A.13.19.1.2]
A.22.36.1.3.4
Actuation of automatic fire suppression systems can be done using ultraviolet/infrared (UV/IR) dual spectrum detectors, heat detection cable, rate of rise heat detectors, or standard air pilot heads. High speed detection is considered advisable to suppress a solvent fire in its incipient stages. [122: A.13.19.1.3]
Second Revision No. 145-NFPA 13-2014 [ Global Comment ]
See attached global revision....
Supplemental Information
File Name Description
13_SR_145_Chapter_16_edited_rev_MJK_.docx
13_SR_145_Chapter_17_edited_rev_MJK_.docx
Submitter Information Verification
Submitter Full Name: Matthew Klaus
Organization: National Fire Protection Assoc
Street Address:
City:
State:
Zip:
Submittal Date: Tue Jul 01 08:30:05 EDT 2014
Committee Statement
CommitteeStatement:
The suggested wording is based on the suggested format from the redundancy task group on changes to chapters 16 and17.
The concern for the in-rack sprinkler to be able to develop a pattern is focused on two separated components – one is thepallet load and the other is the horizontal frame members. We are explicit regarding the placement in regard to the palletload but inconsistent regarding the structural members. In section 16.2.1.4.2.5 on CMDA sprinklers for storage up to 25 ft itis clear that where a vertical separation form the pallet load is required, separation from the frame members is also required.For CMSA and ESFR for storage up to 25 ft, a vertical separation is required but there is no mention on the horizontal framemembers. Both requirements are explicated required for >25 ft storage but the vertical separation is all in-rack sprinklerswhereas the horizontal members are addressed just on in-racks only in the longitudinal flues. This allows sprinklers inmultiple row racks to completed obstructed by the horizontal rack member for storage heights over 25 ft for al sprinklertypes, for CMSA and ESFR in all racks for storage less than 25 ft but for CMDA for storage between 20 ft and 25 ft thehorizontal frame members can not obstruct the in-rack sprinklers. Chapter 17 addresses this issue in a similar fashion andrequires the horizontal member to be accounted for only for double row racks with storage greater than 25 ft. Having aconsistent requirement for both components impacting in-rack sprinkler discharge makes sense.
ResponseMessage:
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
3 of 301 10/9/2014 8:39 AM
COMP: These section titles are wrong…. They should be unchanged from 2013… MJK . The submitter was just putting them in as a frame of reference. (Note: I pasted in the correct titles from the 2013 edition so you can more easily identify the sections. The titles themselves do not have to be changed in Terra/Arbortext. --Kim) 16.1.11.2 In single-row, double-row, or multiple-row racks, a minimum 6 in. (152.4 mm) vertical clear space shall be maintained between the in-rack sprinkler deflectors and the top of a tier of storage. 16.1.11.2.1 Face sprinklers in such racks shall be located within the rack a minimum of 3 in. (76 mm) from rack uprights and no more than 18 in. (460 mm) from the aisle face of storage. 16.1.11.2.2 Longitudinal flue in-rack sprinklers shall be located at the intersection with the transverse flue space and with the deflector located at or below the bottom of horizontal load beams or above or below other adjacent horizontal rack members. 16.1.11.2.3 Such in-rack sprinklers shall be a minimum of 3 in. (76 mm) radially from the side of the rack uprights.
16.2.1.4.2.3* The elevation of in-rack sprinkler deflectors with respect to storage shall not be a consideration in single- or double-row rack storage up to and including 20 ft (6.1 m) high. (See Section C.16.) 16.2.1.4.2.4* In single- or double-row racks without solid shelves with storage over 20 ft (6.1 m) high, or in multiple-row racks, or in single- or double-row racks with solid shelves and storage height up to and including 25 ft (7.6 m), a minimum of 6 in. (152 mm)
vertical clear space shall be maintained between the in-rack sprinkler deflectors and the top of a tier of storage. (A) Sprinkler discharge shall not be obstructed by horizontal rack members. 16.2.1.4.2.5 For multiple-row racks, a minimum of 6 in. (152 mm) shall be maintained between the in-rack sprinkler deflector and the top of a tier of storage. (A) Sprinkler discharge shall not be obstructed by horizontal rack members. 16.2.2 CMSA Sprinklers for Rack Storage of Class I Through Class IV Commodities Stored Up to and Including 25 ft (7.6 m) in Height. 16.2.2.7.2 The minimum of 6 in. (152.4 mm) vertical clear space shall be maintained between the sprinkler deflectors and the top of a tier of storage. (A) Sprinkler discharge shall not be obstructed by horizontal rack members. 16.2.3 Early Suppression Fast-Response (ESFR) Sprinklers for Rack Storage of Class I Through Class IV Commodities Stored Up to and Including 25 ft (7.6 m) in Height. 6.2.3.6.3 The minimum of 6 in. (152.4 mm) vertical clear space shall be maintained between the sprinkler deflectors and the top of a tier of storage. (A) Sprinkler discharge shall not be obstructed by horizontal rack members. 16.3 Protection Criteria for Rack Storage of Class I Through Class IV Commodities Stored Over 25 ft (7.6 m) in Height. 6.3.1.3.2.5 The minimum of 6 in. (152.4 mm) vertical clear space shall be maintained between the sprinkler deflectors and the top of a tier of storage.
(A) Sprinkler discharge shall not be obstructed by horizontal rack members. 16.3.1.3.2.6 In-rack sprinklers shall be a minimum of 3 in. (76 mm) radially from the side of the rack uprights. 16.3.1.3.2.7 Face sprinklers in such racks shall be located within the rack a minimum of 3 in. (76 mm) from rack uprights and no more than 18 in. (460 mm) from the aisle face of storage.
16.3.2 CMSA Sprinklers for Rack Storage of Class I Through Class IV Commodities Stored Over 25 ft (7.6 m) in Height.
16.3.2.7.2 The minimum of 6 in. (152 mm) vertical clear space shall be maintained between the sprinkler deflectors and the top of a tier of storage.
(A) Sprinkler discharge shall not be obstructed by horizontal rack members.
16.3.2.7.3 In-rack sprinklers shall be a minimum of 3 in. (76 mm) radially from the side of the rack uprights. 16.3.2.7.4 Face sprinklers in such racks shall be located within the rack a minimum of 3 in. (76 mm) from rack uprights and no more than 18 in. (460 mm) from the aisle face of storage. COMP: Renumber current 16.3.2.7.3 onward starting with 16.3.2.7.5
16.3.3 Early Suppression Fast-Response (ESFR) Sprinklers for Rack Storage of Class I Through Class IV Commodities Stored Over 25 ft (7.6 m) in Height.
16.3.3.5.4 The minimum of 6 in. (152 mm) vertical clear space shall be maintained between the sprinkler deflectors and the top of a tier of storage.
(A) Sprinkler discharge shall not be obstructed by horizontal rack members.
16.3.3.5.8 In-rack sprinklers shall be a minimum of 3 in. (76 mm) radially from the side of the rack uprights. 16.3.3.5.9 Face sprinklers in such racks shall be located within the rack a minimum of 3 in. (76 mm) from rack uprights and no more than 18 in. (460 mm) from the aisle face of storage.
COMP: These section titles are wrong…. They should be unchanged from 2013… MJK . The submitter was just putting them in as a frame of reference. (Note: I pasted in the correct titles from the 2013 edition so you can more easily identify the sections. The titles themselves do not have to be changed in Terra/Arbortext. --Kim) 17.1.10 Flue Space Requirements for Storage Over 25 ft (7.6 m).
17.1.10.2 In single-, double-, or multiple-row racks, a minimum 6 in. (152 mm) vertical clear space shall be maintained between the in-rack sprinkler deflectors and the top of a tier of storage. 17.1.10.2.1 Face sprinklers in such racks shall be located within the rack a minimum of 3 in. (76 mm) from rack uprights and no more than 18 in. (460 mm) from the aisle face of storage. 17.1.10.2.2 Such in-rack sprinklers shall be a minimum of 3 in. (76 mm) radially from the side of the rack uprights.
17.2.1.5.1 In-Rack Sprinkler Clearance. The minimum of 6 in. (152 mm) vertical clear space shall be maintained between the sprinkler deflectors and the top of a tier of storage. (A) Sprinkler discharge shall not be obstructed by horizontal rack members.
17.2.2.6.2 The minimum of 6 in. (152 mm) vertical clear space shall be maintained between the sprinkler deflectors and the top of a tier of storage. (A) Sprinkler discharge shall not be obstructed by horizontal rack members.
17.2.3.4.3 The minimum of 6 in. (152.4 mm) vertical clear space shall be maintained between the sprinkler deflectors and the top of a tier of storage. (A) Sprinkler discharge shall not be obstructed by horizontal rack members.
17.3.1.9 The minimum of 6 in. (152 mm) vertical clear space shall be maintained between the in-rack sprinkler deflectors and the top of a tier of storage. (A) Sprinkler discharge shall not be obstructed by horizontal rack members.
17.3.1.13 In-rack sprinklers shall be a minimum of 3 in. (76 mm) radially from the side of the rack uprights. 17.3.1.14 Face sprinklers in such racks shall be located within the rack a minimum of 3 in. (76 mm) from rack uprights and no more than 18 in. (460 mm) from the aisle face of storage. COMP: Renumber current 17.3.1.13 onward starting with 17.3.1.15 17.3.2 CMSA Sprinklers for Rack Storage of Plastics Commodities Stored Over 25 ft (7.6 m) in Height.
17.3.3.4.4 The minimum of 6 in. (152 mm) vertical clear space shall be maintained between the sprinkler deflectors and the top of a tier of storage. (A) Sprinkler discharge shall not be obstructed by horizontal rack members.
17.3.3.4.8 In-rack sprinklers shall be a minimum of 3 in. (76 mm) radially from the side of the rack uprights. 17.3.3.4.9 Face sprinklers in such racks shall be located within the rack a minimum of 3 in. (76 mm) from rack uprights and no more than 18 in. (460 mm) from the aisle face of storage.
Second Revision No. 147-NFPA 13-2014 [ Global Comment ]
Reinsert the K 14 and K 16.8 lines into table 17.2.3.1 (see attached)
Supplemental Information
File Name Description
Table_17.2.3.1_SR.pdf
Submitter Information Verification
Submitter Full Name: Matthew Klaus
Organization: National Fire Protection Assoc
Street Address:
City:
State:
Zip:
Submittal Date: Tue Jul 01 09:37:47 EDT 2014
Committee Statement
CommitteeStatement:
The K14 and K 16.8 rows for the 25 ft ceiling height were inadvertently deleted during the first draft. This is aneditorial correction to reinsert them.
ResponseMessage:
Public Comment No. 196-NFPA 13-2014 [Section No. 17.2.3]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
4 of 301 10/9/2014 8:39 AM
Second Revision No. 65-NFPA 13-2014 [ Global Comment ]
Remove the word “open” from the heading of 16.2, 16.3, 17.2 and 17.3.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Wed Jun 25 14:04:30 EDT 2014
Committee Statement
CommitteeStatement:
The design criteria provided for ceiling sprinklers is based upon the assumption that the racks are open. Rather thanadding the word open to several section headers, adding a statement that clarifies the intent of the standard is a moredirect way of establishing the way the standard has been written.
ResponseMessage:
Public Comment No. 187-NFPA 13-2014 [Global Input]
Public Comment No. 294-NFPA 13-2014 [Section No. 16.2]
Public Comment No. 295-NFPA 13-2014 [Section No. 16.3]
Public Comment No. 362-NFPA 13-2014 [Section No. 16.2.1.4.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
7 of 301 10/9/2014 8:39 AM
Second Revision No. 71-NFPA 13-2014 [ Global Comment ]
Revise 17.1.5 to read as follows:
17.1.5 Solid Shelving
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Wed Jun 25 15:10:16 EDT 2014
Committee Statement
CommitteeStatement:
The term solid shelf rack in the heading for 17.1.5 is being replaced with solid shelving which is the terminologyused in the subsequent section.
ResponseMessage:
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
8 of 301 10/9/2014 8:39 AM
Second Revision No. 78-NFPA 13-2014 [ Global Comment ]
Revise all of the metric values in chapter 5 and 12-24 based on the soft conversions provided by the metric task group.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 10:37:36 EDT 2014
Committee Statement
CommitteeStatement:
The conversions proposed for the 2016 edition will be based on a soft conversion scheme as opposed to thetraditional hard conversion. The attached spreadsheet provides the proposed conversion.
ResponseMessage:
Public Comment No. 172-NFPA 13-2014 [Section No. 17.3.3.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
9 of 301 10/9/2014 8:39 AM
Second Revision No. 144-NFPA 13-2014 [ Global Input ]
See attached revisions
Supplemental Information
File Name Description
PC-275_UPDATED_SR_Language_.docx
Submitter Information Verification
Submitter Full Name: Matthew Klaus
Organization: National Fire Protection Assoc
Street Address:
City:
State:
Zip:
Submittal Date: Tue Jul 01 08:26:29 EDT 2014
Committee Statement
CommitteeStatement:
The suggested wording is based on the suggested format from the redundancy task group on changes to chapters 16 and17.
The concern for the in-rack sprinkler to be able to develop a pattern is focused on two separated components – one is thepallet load and the other is the horizontal frame members. We are explicit regarding the placement in regard to the palletload but inconsistent regarding the structural members. In section 16.2.1.4.2.5 on CMDA sprinklers for storage up to 25 ft itis clear that where a vertical separation form the pallet load is required, separation from the frame members is alsorequired. For CMSA and ESFR for storage up to 25 ft, a vertical separation is required but there is no mention on thehorizontal frame members. Both requirements are explicated required for >25 ft storage but the vertical separation is allin-rack sprinklers whereas the horizontal members are addressed just on in-racks only in the longitudinal flues. This allowssprinklers in multiple row racks to completed obstructed by the horizontal rack member for storage heights over 25 ft for alsprinkler types, for CMSA and ESFR in all racks for storage less than 25 ft but for CMDA for storage between 20 ft and 25 ftthe horizontal frame members can not obstruct the in-rack sprinklers.
Chapter 17 addresses this issue in a similar fashion and requires the horizontal member to be accounted for only for doublerow racks with storage greater than 25 ft.
Having a consistent requirement for both components impacting in-rack sprinkler discharge makes sense.
ResponseMessage:
Public Comment No. 275-NFPA 13-2014 [Global Input]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
10 of 301 10/9/2014 8:39 AM
16.1.11.2 In single-row, double-row, or multiple-row racks, a minimum 6 in. (152.4 mm) vertical clear space shall be maintained between the in-rack sprinkler deflectors and the top of a tier of storage. 16.1.11.2.1 Face sprinklers in such racks shall be located within the rack a minimum of 3 in. (76 mm) from rack uprights and no more than 18 in. (460 mm) from the aisle face of storage. 16.1.11.2.2 Longitudinal flue in-rack sprinklers shall be located at the intersection with the transverse flue space and with the deflector located at or below the bottom of horizontal load beams or above or below other adjacent horizontal rack members. 16.1.11.2.3 Such in-rack sprinklers shall be a minimum of 3 in. (76 mm) radially from the side of the rack uprights.
16.2.1.4.2.3* The elevation of in-rack sprinkler deflectors with respect to storage shall not be a consideration in single- or double-row rack storage up to and including 20 ft (6.1 m) high. (See Section C.16.) 16.2.1.4.2.4* In single- or double-row racks without solid shelves with storage over 20 ft (6.1 m) high, or in multiple-row racks, or in single- or double-row racks with solid shelves and storage height up to and including 25 ft (7.6 m), a minimum of 6 in. (152 mm) vertical clear space shall be maintained between the in-rack sprinkler deflectors and the top of a tier of storage. (A) Sprinkler discharge shall not be obstructed by horizontal rack members.
16.2.1.4.2.5 For multiple-row racks, a minimum of 6 in. (152 mm) shall be maintained between the in-rack sprinkler deflector and the top of a tier of storage. (A) Sprinkler discharge shall not be obstructed by horizontal rack members. 16.2.2 CMSA 16.2.2.7.2 The minimum of 6 in. (152.4 mm) vertical clear space shall be maintained between the sprinkler deflectors and the top of a tier of storage. (A) Sprinkler discharge shall not be obstructed by horizontal rack members.
16.2.3 ESFR 6.2.3.6.3 The minimum of 6 in. (152.4 mm) vertical clear space shall be maintained between the sprinkler deflectors and the top of a tier of storage. (A) Sprinkler discharge shall not be obstructed by horizontal rack members. 16.3 >25 ft 6.3.1.3.2.5 The minimum of 6 in. (152.4 mm) vertical clear space shall be maintained between the sprinkler deflectors and the top of a tier of storage. (A) Sprinkler discharge shall not be obstructed by horizontal rack members. 16. 3.1.3.2.6 In-rack sprinklers shall be a minimum of 3 in. (76 mm) radially from the side of the rack uprights. 16.3.1.3.2.7 Face sprinklers in such racks shall be located within the rack a minimum of 3 in. (76 mm) from rack uprights and no more than 18 in. (460 mm) from the aisle face of storage.
16.3.2 CMSA
16.3.2.7.2 The minimum of 6 in. (152 mm) vertical clear space shall be maintained between the sprinkler deflectors and the top of a tier of storage.
(A) Sprinkler discharge shall not be obstructed by horizontal rack members.
16.3.2.7.3 In-rack sprinklers shall be a minimum of 3 in. (76 mm) radially from the side of the rack uprights. 16.3.2.7.4 Face sprinklers in such racks shall be located within the rack a minimum of 3 in. (76 mm) from rack uprights and no more than 18 in. (460 mm) from the aisle face of storage. Renumber current 16.3.2.7.3 onward starting with 16.3.2.7.5
16.3.3 ESFR
16.3.3.5.4 The minimum of 6 in. (152 mm) vertical clear space shall be maintained between the sprinkler deflectors and the top of a tier of storage.
(A) Sprinkler discharge shall not be obstructed by horizontal rack members.
16.3.3.5.8 In-rack sprinklers shall be a minimum of 3 in. (76 mm) radially from the side of the rack uprights. 16.3.3.5.9 Face sprinklers in such racks shall be located within the rack a minimum of 3 in. (76 mm) from rack uprights and no more than 18 in. (460 mm) from the aisle face of storage.
17.1.10 >25ft
17.1.10.2 In single-, double-, or multiple-row racks, a minimum 6 in. (152 mm) vertical clear space shall be maintained between the in-rack sprinkler deflectors and the top of a tier of storage. 17.1.10.2.1 Face sprinklers in such racks shall be located within the rack a minimum of 3 in. (76 mm) from rack uprights and no more than 18 in. (460 mm) from the aisle face of storage. 17.1.10.2.2 Such in-rack sprinklers shall be a minimum of 3 in. (76 mm) radially from the side of the rack uprights.
17.2.1.5.1 In-Rack Sprinkler Clearance. The minimum of 6 in. (152 mm) vertical clear space shall be maintained between the sprinkler deflectors and the top of a tier of storage. (A) Sprinkler discharge shall not be obstructed by horizontal rack members.
17.2.2.6.2 The minimum of 6 in. (152 mm) vertical clear space shall be maintained between the sprinkler deflectors and the top of a tier of storage. (A) Sprinkler discharge shall not be obstructed by horizontal rack members.
17.2.3.4.3 The minimum of 6 in. (152.4 mm) vertical clear space shall be maintained between the sprinkler deflectors and the top of a tier of storage. (A) Sprinkler discharge shall not be obstructed by horizontal rack members.
17.3.1.9 The minimum of 6 in. (152 mm) vertical clear space shall be maintained between the in-rack sprinkler deflectors and the top of a tier of storage. (A) Sprinkler discharge shall not be obstructed by horizontal rack members.
17.3.1.13 In-rack sprinklers shall be a minimum of 3 in. (76 mm) radially from the side of the rack uprights. 17.3.1.14 Face sprinklers in such racks shall be located within the rack a minimum of 3 in. (76 mm) from rack uprights and no more than 18 in. (460 mm) from the aisle face of storage. Renumber current 17.3.1.13 onward starting with 17.3.1.15 17.3.2 N/A 17.3.3.4.4 The minimum of 6 in. (152 mm) vertical clear space shall be maintained between the sprinkler deflectors and the top of a tier of storage. (A) Sprinkler discharge shall not be obstructed by horizontal rack members.
17.3.3.4.8 In-rack sprinklers shall be a minimum of 3 in. (76 mm) radially from the side of the rack uprights. 17.3.3.4.9 Face sprinklers in such racks shall be located within the rack a minimum of 3 in. (76 mm) from rack uprights and no more than 18 in. (460 mm) from the aisle face of storage.
Second Revision No. 111-NFPA 13-2014 [ Section No. 3.9.1.17 ]
3.9.1.17* Low-Piled Storage.
Solid-piled, palletized, rack storage, bin box, and shelf storage up to 12 ft (3.7 m) in height.
Supplemental Information
File Name Description
13_SR_111_A.3.9.1.17_edited.docx
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 20:04:38 EDT 2014
Committee Statement
CommitteeStatement:
In response to CC 6, this revision clarifies that the definition is not providing direction on allowable protocol, butrather simply making a distinction between high and low piled storage.
ResponseMessage:
Public Comment No. 189-NFPA 13-2014 [Section No. 3.9.1.17]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
31 of 301 10/9/2014 8:39 AM
A.3.9.1.17 This definition is not intended to address allowable design approaches and protection schemes.
Second Revision No. 131-NFPA 13-2014 [ Section No. 5.6.3.3 ]
5.6.3.3* Class III.
5.6.3.3.1
A Class III commodity shall be defined as a product fashioned from wood, paper, natural fibers, or Group C plastics with orwithout cartons, boxes, or crates and with or without pallets.
5.6.3.3.2
A Class III commodity shall be permitted to contain a limited amount (5 percent or less by weight of unexpanded plastic orvolume 5 percent or less by volume of expanded plastic ) of Group A or Group B plastics.
5.6.3.3.3
Commodities containing a mix of both Group A expanded and unexpanded plastics shall comply with Figure 5.6.3.4.2 .
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Mon Jun 30 07:04:34 EDT 2014
Committee Statement
CommitteeStatement:
The commodity classification definitions for Class III (Section 5.6.3.3.2) and Class IV (Section 5.6.3.4.1) definitions havebeen clarified to identify the permissible amount of unexpanded vs. expanded plastics. The standard Class IV testcommodity contains approximately 15% by weight unexpanded plastic and additional expanded plastic in the commoditywould be beyond the protection scheme required for Class IV commodities in this standard.
ResponseMessage:
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
33 of 301 10/9/2014 8:39 AM
Second Revision No. 132-NFPA 13-2014 [ Section No. 5.6.3.4 ]
5.6.3.4* Class IV.
5.6.3.4.1
A Class IV commodity shall be defined as a product, with or without pallets, that meets one of the following criteria:
(1) Constructed partially or totally of Group B plastics
(2) Consists of free-flowing Group A plastic materials
(3) Contains within itself or its packaging an appreciable amount of Group A plastics as indicated in Figure 5.6.3.4.1 (greaterthan 5 to 15 percent by weight of Group A unexpanded plastic or greater than 5 percent to 25 percent by volume ofexpanded Group A plastic) of Group A plastics.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
34 of 301 10/9/2014 8:39 AM
5.6.3.4.2
Commodities containing a mix of both Group A expanded and unexpanded plastics shall comply with Figure 5.6.3.4.2 .
Figure 5.6.3.4.2 Classification of Commodities Containing Group A or B Plastics Commodities Containing a Mixtureof Expanded and Unexpanded Group A Plastics .
5.6.3.4.3
The remaining materials shall be permitted to be metal, wood, paper, natural or synthetic fibers, or Group B or Group Cplastics.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
35 of 301 10/9/2014 8:39 AM
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Mon Jun 30 07:08:47 EDT 2014
Committee Statement
CommitteeStatement:
The commodity classification definitions for Class III (Section 5.6.3.3.2) and Class IV (Section 5.6.3.4.1) definitionshave been clarified to identify the permissible amount of unexpanded vs. expanded plastics.
The standard Class IV test commodity contains approximately 15% by weight unexpanded plastic and additionalexpanded plastic in the commodity would be beyond the protection scheme required for Class IV commodities in thisstandard.
ResponseMessage:
Public Comment No. 10-NFPA 13-2014 [Section No. 5.6.3.4.1]
Public Comment No. 135-NFPA 13-2014 [Section No. 5.6.3.4.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
36 of 301 10/9/2014 8:39 AM
IV
III
III
IV
Class III commodities shall be permitted to contain a limited
amount (5 percent by weight of unexpanded plastic or 5 percent by
volume of expanded plastic or less) of Group A. Refer to 5.6.2 if a
plastic pallet is used.
Class IV commodities shall be permitted to contain within itself or
its packaging an appreciable amount (5 percent to 15 percent by
weight of Group A unexpanded plastic or 5 percent to 25 percent
by volume of expanded Group A plastic) of Group A plastics as
indicated in Figure 5.6.3.5. Refer to 5.6.2 if a plastic pallet is used.
Group AClass I, II, III or IV commodities shall be protected as one of the
following Group A plastic commodities depending upon the
packaging and plastic material characteristics:
1. Cartoned commodities containing greater than 25 percent and
up to 40 percent by volume of expanded Group A plastic shall be
protected as cartoned unexpanded Group A plastic.
2.Cartoned commodities containing more than 40 percent by
volume of expanded Group A plastic shall be protected as cartoned
expanded Group A plastic.
3. Exposed commodities containing greater than 5% and up to 25
percent by volume of expanded Group A plastic shall be protected
as exposed unexpanded Group A plastic.
Percentage by Volume of Group A Expanded Plastic
5 10 15 20 25 30
Figure 5.6.3.4 Commodities Containing a Mixture of
Expanded and Unexpanded Group A Plastics
Pe
rce
nta
ge b
y W
eig
ht
of
Gro
up
A
Un
exp
and
ed
Pla
stic
25
20
Group A
15
10
5
035 40
4. Exposed commodities containing greater than 25% by volume of
expanded Group A plastic should be protected as exposed
expanded Group A plastic commodity.
Second Revision No. 133-NFPA 13-2014 [ Section No. 5.6.4 ]
5.6.4* Classification of Plastics, Elastomers, and Rubber.
Plastics, elastomers, and rubber shall be classified as Group A, Group B, or Group C.
5.6.4.1* Group A.
The following materials shall be classified as Group A:
(4) PVC (polyvinyl chloride — flexible — PVCs with plasticizer content up to 20 percent)
(5) PVDC (polyvinylidene chloride)
(6) PVDF (polyvinylidene fluoride)
PVF (polyvinyl fluoride)
(7) Urea (urea formaldehyde)
5.6.4.4
Cartoned Group A plastics shall be further subdivided as either expanded or unexpanded.
5.6.4.4.1
If the commodity is more than 40 percent (by volume) cartoned expanded plastic, it shall be protected as a cartonedexpanded Group A plastic.
Supplemental Information
File Name Description
13_SR_133_A.5.6.4.1.1_edited.docx
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Mon Jun 30 07:16:32 EDT 2014
Committee Statement
CommitteeStatement:
The commodity classification definitions for Class III (Section 5.6.3.3.2) and Class IV (Section 5.6.3.4.1) definitionshave been clarified to identify the permissible amount of unexpanded vs. expanded plastics.
The standard Class IV test commodity contains approximately 15% by weight unexpanded plastic and additionalexpanded plastic in the commodity would be beyond the protection scheme required for Class IV commodities in thisstandard.
ResponseMessage:
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
38 of 301 10/9/2014 8:39 AM
A.5.6.4.1.1 Generally, expanded plastics are low-density materials and commonly referred to as “foam plastics.”
Second Revision No. 121-NFPA 13-2014 [ New Section after 11.1.6.3 ]
11.1.6.3.1
Where the system is a combined sprinkler/standpipe system (Class I or Class III) and the building is fully sprinklered inaccordance with NFPA 13, no inside hose demand shall be required at any of the standpipe outlets.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Jun 27 16:10:36 EDT 2014
Committee Statement
CommitteeStatement:
In one edition of NFPA 13 (2007) the requirement for 50 gpm to be added at the two most remote standpipe outlets forcombined sprinkler/standpipe systems was added to the annex (A.11.1.5.6). This caused problems for two reasons. Thefirst problem is that it violated section 11.1.5.6 in the body of the standard, which stated that the standpipe and sprinklerdemands were not required to be added together. The second problem was that the rule was in the annex, where it wasnot enforceable.
The committee reviewed the subject again in while writing the 2010 edition of the standard and agreed that the 50 gpminside hose demand is not required at the standpipe outlets, so they took this annex note out of the standard. But noclarification was added to the standard and the question continues to come up. The situation needs to be clarified for theuser that the flow for the standpipe system is calculated separately and is not required to be added, in whole or in part, tothe sprinkler flow demand.
ResponseMessage:
Public Comment No. 333-NFPA 13-2014 [New Section after 11.1.6.3]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
130 of 301 10/9/2014 8:39 AM
Second Revision No. 120-NFPA 13-2014 [ Section No. 11.2.3.1.4 ]
11.2.3.1.4 Restrictions.
When either the density/area method or room design method is used, the following shall apply:
(1)
(2) For areas of sprinkler operation less than 2500 ft2 (232 m2) for extra hazard occupancies, the density for 2500 ft2 (232
m2) shall be used.
Unless the requirements of 11.2.3.1.4 (4) are met for buildings having unsprinklered combustible concealed spaces, asdescribed in 8.15.1.2 and 8.15.6 , the minimum area of sprinkler operation for that portion of the building shall be
When using the density/area or room design method, unless the requirements of 11.2.3.1.5.2 are met for buildings havingunsprinklered combustible concealed spaces, as described in 8.15.1.2 and 8.15.6, the minimum area of sprinkler operation for
that portion of the building shall be 3000 ft2 (279 m2).
(A)
The design area of 3000 ft2 (279 m2) shall be applied only to the sprinkler system or portions of the sprinkler system that areadjacent to the qualifying combustible concealed space.
(B)
The term adjacent shall apply to any sprinkler system protecting a space above, below, or next to the qualifying concealedspace except where a barrier with a fire resistance rating at least equivalent to the water supply duration completely separatesthe concealed space from the sprinklered area.
11.2.3.1.5.2
The following unsprinklered concealed spaces shall not require a minimum area of sprinkler operation of 3000 ft2 (279 m2):
(1) Noncombustible and limited-combustible concealed spaces with minimal combustible loading having no access. Thespace shall be considered a concealed space even with small openings such as those used as return air for a plenum.
(2) Noncombustible and limited-combustible concealed spaces with limited access and not permitting occupancy or storageof combustibles. The space shall be considered a concealed space even with small openings such as those used asreturn air for a plenum.
(3) Combustible concealed spaces filled entirely with noncombustible insulation.
(4)
(5) Concealed spaces where rigid materials are used and the exposed surfaces have a flame spread index of 25 or less andthe materials have been demonstrated to not propagate fire more than 10.5 ft (3.2 m) when tested in accordance withASTM E84, Standard Test Method of for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standardfor Test for Surface Burning Characteristics of Building Materials, extended for an additional 20 minutes in the form inwhich they are installed in the space.
(6) Concealed spaces in which the exposed materials are constructed entirely of fire-retardant treated fire-retardant-treatedwood as defined by NFPA 703.
(7) Concealed spaces over isolated small compartments rooms not exceeding 55 ft2 (5.1 m2) in area.
(8) Vertical pipe chases under 10 ft2 (0.93 m2), provided that in multifloor buildings the chases are firestopped at each floorusing materials equivalent to the floor construction, and where such pipe chases shall contain no sources of ignition,piping shall be noncombustible, and pipe penetrations at each floor shall be properly sealed.
(9) Exterior columns under 10 ft2 (0.93 m2) in area formed by studs or wood joists, supporting exterior canopies that are fullyprotected with a sprinkler system.
(10)
* For areas of sprinkler operation less than 1500 ft2 (139 m2) used for light and ordinary hazard occupancies, the density
for 1500 ft2 (139 m2) shall be used.
* Light or ordinary hazard occupancies where noncombustible or limited-combustible ceilings are directly attached to thebottom of solid wood joists or solid limited-combustible construction or noncombustible construction so as to create
enclosed joist spaces 160 ft3 (4.5 m3) or less in volume, including space below insulation that is laid directly on top orwithin the ceiling joists in an otherwise sprinklered concealed space.
* Light or ordinary hazard occupancies where noncombustible or limited-combustible ceilings are attached to the bottom ofcomposite wood joists either directly or on to metal channels not exceeding 1 in. (25.4 mm) in depth, provided the
adjacent joist channels are firestopped into volumes not exceeding 160 ft3 (4.5 m3) using materials equivalent to 1⁄2 in.(12.7 mm) gypsum board, and at least 31⁄2 in. (90 mm) of batt insulation is installed at the bottom of the joist channelswhen the ceiling is attached utilizing metal channels.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
131 of 301 10/9/2014 8:39 AM
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Jun 27 14:45:28 EDT 2014
Committee Statement
CommitteeStatement:
This revision corrects having multiple requirements in a single paragraph and employs the same structure as 12.9.The issue of combustible concealed spaces is very common and having it's own title is much more user friendly versesthe vague use of restrictions.
ResponseMessage:
Public Comment No. 92-NFPA 13-2014 [Global Input]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
132 of 301 10/9/2014 8:39 AM
Second Revision No. 128-NFPA 13-2014 [ Section No. 11.2.3.2.3.1 ]
11.2.3.2.3.1
Where listed quick-response sprinklers, including extended coverage quick-response sprinklers, are used throughout a systemor portion of a system having the same hydraulic design basis, the system area of operation shall be permitted to be reducedwithout revising the density as indicated in Figure 11.2.3.2.3.1 when all of the following conditions are satisfied:
(1) Wet pipe system
(2) Light hazard or ordinary hazard occupancy
(3) 20 ft (6.1 m) maximum ceiling height
(4) There are no No unprotected ceiling pockets as allowed by 8.6.7 and 8.8.7 exceeding 32 ft2 (3 m2)
(5) No unprotected areas above cloud ceilings as allowed by 8.15.24
Figure 11.2.3.2.3.1 Design Area Reduction for Quick-Response Sprinklers.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Jun 27 19:11:10 EDT 2014
Committee Statement
CommitteeStatement:
The Technical Committee on Installation Criteria added language for eliminating sprinklers above cloud ceilings. It isnot appropriate to utilize this exception for an area where sprinklers were omitted.
ResponseMessage:
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
133 of 301 10/9/2014 8:39 AM
Second Revision No. 122-NFPA 13-2014 [ Section No. 11.3.1.4 ]
11.3.1.4
For modifications or additions to existing systems equipped with residential sprinklers, the listed discharge criteria less than 0.1
gpm/ft2 (4.1 mm/min) shall be permitted to be used.
11.3.1.4.1
Where replacing residential sprinklers manufactured prior to 2003 that are no longer available from the manufacturer and that
are installed using a design density less than 0.05 gpm/ft 2 (2.04 mm/min), a residential sprinkler with an equivalent K-factor(± 5 percent) shall be permitted to be used provided the currently listed coverage area for the replacement sprinkler is notexceeded.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Jun 27 16:34:08 EDT 2014
Committee Statement
Committee Statement: This language was added in response to CC Note No. 20 appeared in the First Draft Report.
Response Message:
Public Comment No. 228-NFPA 13-2014 [Section No. 11.3.1.4]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
134 of 301 10/9/2014 8:39 AM
Second Revision No. 123-NFPA 13-2014 [ New Section after 11.3.4.3 ]
11.3.5 Sprinkler-Protected Glazing.
Where the sprinkler-protected glazing is required to comply with 8.15.26 , the water supply duration for the design area thatincludes the window sprinklers shall be not less than the required rating of the assembly.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Jun 27 16:40:27 EDT 2014
Committee Statement
Committee Statement: This language is intended to correlate with the new sprinkler protected glazing section in 8.15.23.
Response Message:
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
135 of 301 10/9/2014 8:39 AM
Second Revision No. 79-NFPA 13-2014 [ New Section after 12.1.3.1.3.2 ]
12.1.3.1.4*
Where the building height changes within a compartment, the sprinklers directly over the storage shall be capable ofprotecting storage directly beneath.
12.1.3.1.4.1
Where a barrier to heat and smoke in accordance with 12.3(2) or 12.3(3) is not present, the sprinkler criteria 15 ft (4.6 m)into the perimeter of the lower ceiling area shall be the same as the sprinkler protection for the high ceiling area.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 12:48:19 EDT 2014
Committee Statement
CommitteeStatement:
This revision clarifies the proper design height requirements for sprinklers under a roof with a pitch of 2:12 orless.
Response Message:
Public Comment No. 326-NFPA 13-2014 [New Section after 12.1.3.1.3.2]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
136 of 301 10/9/2014 8:39 AM
Second Revision No. 73-NFPA 13-2014 [ Section No. 12.3 ]
12.3* Adjacent Hazards or Design Methods.
For buildings with two or more adjacent hazards or design methods, the following shall apply:
(1) Where areas are not physically separated by a barrier or partition capable of delaying heat from a fire in one area fromfusing sprinklers in the adjacent area, the required sprinkler protection for the more demanding design basis shall extend15 ft (4.6 m) beyond its perimeter.
(2) The requirements of 12.3(1) shall not apply where the areas are separated by a draft curtain, or barrier,or located abovean aisle, where the aisle has a minimum 2 ft (0.6 m) horizontal separation from an adjacent hazard, or a partition that iscapable of delaying heat from a fire in one area from fusing sprinklers in the adjacent area.
(3) The requirements of 12.3(1) shall not apply to the extension of more demanding criteria from an upper ceiling level tobeneath a lower ceiling level where the difference in height between the ceiling levels is at least 2 ft (0.6 m), locatedabove an aisle, where the aisle has a minimum 2 ft (0.6 m) horizontal separation from an adjacent hazard .
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Wed Jun 25 18:40:39 EDT 2014
Committee Statement
CommitteeStatement:
The concept of a partition, barrier and draft curtain were all considered to provide the same level of protection in the firstdraft language. Rather than deleting the allowance for a draft curtain as a means of separating adjacent hazards, therevised second draft language requires a clear aisle to be created beneath the draft curtain or barrier. This provides anadditional level of protection from sprinklers on the “wrong side” of the barrier from opening first.
ResponseMessage:
Public Comment No. 158-NFPA 13-2014 [Section No. 12.3]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
137 of 301 10/9/2014 8:39 AM
Second Revision No. 81-NFPA 13-2014 [ Section No. 12.6.7.1 ]
12.6.7.1
ESFR sprinklers designed to meet any criteria in Chapter 12 or Chapter 14 through Chapter 20 shall be permitted to protectany of the following:
(1) Light hazard occupancies
(2) Ordinary hazard occupancies
(3) Any storage arrangement in Chapter 13 referencing OH1, OH2, EH1, and EH2 design criteria
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 13:22:32 EDT 2014
Committee Statement
CommitteeStatement:
Chapter 12 contains ESFR criteria for protecting idle pallet storage, so that chapter should be referenced in thisprovision as well.
Response Message:
Public Comment No. 159-NFPA 13-2014 [Section No. 12.6.7.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
138 of 301 10/9/2014 8:39 AM
Second Revision No. 82-NFPA 13-2014 [ Section No. 12.6.7.2 ]
12.6.7.2
Quick-response CMSA sprinklers designed to meet any criteria in Chapter 12 or Chapter 14 through Chapter 20 shall bepermitted to protect any of the following:
(1) Light hazard occupancies
(2) Ordinary hazard occupancies
(3) Any storage arrangement in Chapter 13 referencing OH1, OH2, EH1, and EH2 design criteria
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 13:22:45 EDT 2014
Committee Statement
CommitteeStatement:
Chapter 12 contains CMSA criteria for protecting idle pallet storage, so that chapter should be referenced in thisprovision as well.
Response Message:
Public Comment No. 160-NFPA 13-2014 [Section No. 12.6.7.2]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
139 of 301 10/9/2014 8:39 AM
Second Revision No. 83-NFPA 13-2014 [ Section No. 12.6.7.3 ]
12.6.7.3
Standard-response CMSA sprinklers designed to meet any criteria in Chapter 12 or Chapter 14 through Chapter 20 shall bepermitted to protect any of the following:
(1) Ordinary hazard occupancies
(2) Any storage arrangement in Chapter 13 referencing OH1, OH2, EH1, and EH2 design criteria
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 13:23:16 EDT 2014
Committee Statement
CommitteeStatement:
Chapter 12 contains CMSA criteria for protecting idle pallet storage, so that chapter should be referenced in thisprovision as well.
Response Message:
Public Comment No. 161-NFPA 13-2014 [Section No. 12.6.7.3]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
140 of 301 10/9/2014 8:39 AM
Second Revision No. 143-NFPA 13-2014 [ Section No. 12.8.6 [Excluding any Sub-Sections] ]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
141 of 301 10/9/2014 8:39 AM
Unless indicated otherwise, the minimum water supply requirements for a hydraulically designed sprinkler system shall bedetermined by adding the hose stream allowance from Table 12.8.6 to the water demand for sprinklers.
Table 12.8.6 Hose Stream Allowance and Water Supply Duration
Commodity Sprinkler TypeSprinklerSpacing
Type
Number of *Ceiling
Sprinklers inDesign Area*
Size of DesignArea at Ceiling
Hose StreamAllowance
WaterSupply
Duration(minutes)gpm L/min
Class I-IV Commodities,Group A plastics, idle
wood pallets, idle plasticpallets and miscellaneous
storage
Control modedensity/area
(CMDA)
Standard andextended-coverage
NA
Up to 1200 ft2
(111 m2) 250 950 60
Over 1200 ft2 (111
m2) up to 1500 ft2
(139 m2) 500 1900 90
Over 1500 ft2
(139 m2) up to
2600 ft2 (240 m2) 500 1900 120
Over 2600 ft2
(240 m2) 500 1900 150
Control ModeSpecific
Application( CMSA)
Standard
Up to 12 NA 250 950 60
Over 12 to 15 NA 500 1900 90
Over 15 to 25 NA 500 1900 120
Over 25 NA 500 1900 150
Extended-coverage
Up to 6 NA 250 950 60
Up to 8†
144 ft 2 (13.4
m 2 )maximum NA 250 950 60
Over 6 to 8 NA 500 1900 90
Over 8 to 12 NA 500 1900 120
Over 12 NA 500 1900 150
EarlySuppression
Fast Response( ESFR)
Standard
Up to 12 NA 250 950 60
Over 12 to 15 NA 500 1900 90
Over 15 to 25 NA 500 1900 120
Over 25 NA 500 1900 150
On-floor rubber tirestorage up to 5 ft (1.5 m)
in heightCMOA & CMSA
Standardand
extended-coverage Any Any 250 950 120
Rubber tire storage
CMDA
Standardand
extended-coverage NA
Up to 5000 ft 2
(372 m 2 750 2850 180
CMSA Standard Up to 15 NA 500 1900 180
ESFR StandardUp to 12 NA 250 950 180
Over 12 to20 NA 500 1900 180
Roll paper
CMDA StandardNA
Up to 4000 ft 2
(372 m 2 500 1900 120
CMSA Standard Up to 25 NA 500 1900 120
ESFR Standard Up to 12 NA 250 950 60
NA: Not applicable.
*For CSMA and ESFR sprinklers, the additional sprinklers included in the design area for obstructions do not need to beconsidered in determining the total number of sprinklers in this column.
†Limited to a maximum of 144 ft 2 (13.4 m 2 ) per sprinkler.
Supplemental Information
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
These additions to Table 12.8.6 and related sections consolidate water supply information from chapters 18 and 19into a single source in the general requirements for storage chapter for clarity.
ResponseMessage:
Public Comment No. 311-NFPA 13-2014 [Section No. 12.8.6 [Excluding any Sub-Sections]]
Public Comment No. 251-NFPA 13-2014 [Section No. 21.2.1]
Public Comment No. 252-NFPA 13-2014 [Section No. 21.3.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
or .SP~r.V~LI>'Rr~ Z<J n\fS (O~Uh.IV IJUI"' fl,tf: II,
/4 Lr! l'r"'... s?Jt:tfl/ /(, e t 15 /?.:"/(,
*'"*' L X:M.tTe'tJ 'tD l't 1'1Al'>M"-"'
bingalls
Line
bingalls
Line
bingalls
Line
bingalls
Line
bingalls
Line
bingalls
Line
bingalls
Line
bingalls
Line
bingalls
Text Box
insert space before "m2"
bingalls
Line
bingalls
Text Box
change double asterisk to dagger (no super)
bingalls
Line
bingalls
Line
bingalls
Line
bingalls
Line
bingalls
Line
bingalls
Line
bingalls
Line
bingalls
Line
bingalls
Text Box
insert space before "m"
bingalls
Line
bingalls
Line
bingalls
Line
bingalls
Line
bingalls
Text Box
insert hyphen after "extended" (extended-coverage)
bingalls
Text Box
[for clarification] NA: Not applicable. *For CMSA and ESFR sprinklers, the additional sprinklers included in the design area for obstructions do not need to be considered in determining the total number of sprinklers in this column. †Limited to a maximum of 144 ft2 (13.4 m2) per sprinkler.
bingalls
Line
bingalls
Line
bingalls
Line
bingalls
Line
bingalls
Line
bingalls
Line
bingalls
Text Box
lowercase where marked
Second Revision No. 84-NFPA 13-2014 [ Section No. 12.9 ]
When using the density/area method or room design method, unless the requirements of 12.9.2 are met for buildings havingunsprinklered combustible concealed spaces as described in 8.15.1.2 and 8.15.6, the minimum area of sprinkler operation for
that portion of the building shall be 3000 ft2 (279 m2).
12.9.1.1
The design area of 3000 ft2 (279 m2) shall be applied only to the sprinkler system or portions of the sprinkler system that areadjacent to the qualifying combustible concealed space.
12.9.1.2
The term adjacent shall apply to any sprinkler system protecting a space above, below, or next to the qualifying concealedspace except where a barrier with a fire resistance rating at least equivalent to the water supply duration completely separatesthe concealed space from the sprinklered area.
12.9.2
The following unsprinklered combustible concealed spaces shall not require a minimum design area of sprinkler operation of
3000 ft2 (279 m2):
(1) Noncombustible and limited-combustible concealed spaces with minimal combustible loading having no access. Thespace shall be considered a concealed space even with small openings such as those used as return air for a plenum.
(2) Noncombustible and limited-combustible concealed spaces with limited access and not permitting occupancy or storageof combustibles. The space shall be considered a concealed space even with small openings such as those used asreturn air for a plenum.
(3) Combustible concealed spaces filled entirely with noncombustible insulation.
(4) Concealed spaces where rigid materials are used and the exposed surfaces have a flame spread index of 25 or less andthe materials have been demonstrated to not propagate fire more than 10.5 ft (3.2 m) when tested in accordance withASTM E 84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standardfor Test for Surface Burning Characteristics of Building Materials, extended for an additional 20 minutes in the form inwhich they are installed in the space.
(5) Concealed spaces in which the exposed materials are constructed entirely of fire retardant–treated wood as defined byNFPA 703.
(6) Concealed spaces over isolated small compartments not exceeding 55 ft2 (5.1 m2) in area.
(7) Vertical pipe chases under 10 ft2 (0.93 m2), provided that in multifloor buildings the chases are firestopped at each floorusing materials equivalent to the floor construction. Such pipe chases shall contain no sources of ignition, piping shall benoncombustible, and pipe penetrations at each floor shall be properly sealed.
(8) Exterior columns under 10 ft2 (0.93 m2) in area formed by studs or wood joists, supporting exterior canopies that are fullyprotected with a sprinkler system.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 13:48:35 EDT 2014
Committee Statement
CommitteeStatement:
The only topic addressed by this section is combustible concealed spaces and restriction is a rather ambiguoustitle.
Response Message:
Public Comment No. 88-NFPA 13-2014 [Section No. 12.9]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
Committee Statement: This revision correlates with the chapter titles for 14, 15, 16, 17, 18, & 19
Response Message:
Public Comment No. 90-NFPA 13-2014 [Chapter 13]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
145 of 301 10/9/2014 8:39 AM
Second Revision No. 74-NFPA 13-2014 [ Section No. 13.3.4.2 ]
13.3.4.2
Maximum horizontal Horizontal spacing of in-rack sprinklers in single- or double-row racks with Class Ithrough IV commodities,Group A plastics, tires, and rolled paper shall be in accordance with Table 13.3.4.2 . shall not exceed 8 ft (2.4 m).
Table 13.3.4.2 In-Rack Sprinkler Spacing for Class I, II, III, and IV Commodities Stored in Single- or Double-Row Racks Up to12 ft (3.7 m) in Height
Commodity Class
Aisle Widths I and II III IV Group A Plastics, Tires and Rolled Paper
Encapsulated ft m ft m ft m ft m ft m
No 8 2.4 12 3.7 12 3.7 10 3.0 8 2.4
No 4 1.2 12 3.7 10 3.0 10 3.0 8 2.4
Yes — — 8 2.4 8 2.4 8 2.4 8 2.4
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Wed Jun 25 18:46:03 EDT 2014
Committee Statement
CommitteeStatement:
The inclusion of criteria for the installation of in-rack sprinklers for protection of Class I, II, III, and IV Commodities andRolled Paper is confusing to the user of hte standard when there is no requirement under Table 13.2.1 for in-racksprinklers with these products. The installation of in-rack sprinklers with miscellaneous storage is only required for certainGroup A plastic and tire arrangements.
ResponseMessage:
Public Comment No. 249-NFPA 13-2014 [Section No. 13.3.4.2]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
146 of 301 10/9/2014 8:39 AM
Second Revision No. 86-NFPA 13-2014 [ New Section after 14.1.2 ]
14.1.3
Protection criteria for Group A plastics shall be permitted to be used for Class I, II, III, and IV commodities with the samestorage and height configuration.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 13:52:58 EDT 2014
Committee Statement
CommitteeStatement:
Contary to the Committee Statement for resolution of PI No. 94 the inclusion of the proposed section is needed sinceunder the provisions of 14.2.5 for encapsualted storage can exceed that requried for Group A plastics storage asallowed in Chapter 16.
ResponseMessage:
Public Comment No. 246-NFPA 13-2014 [New Section after 14.1.2]
Public Comment No. 247-NFPA 13-2014 [New Section after 15.1.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
147 of 301 10/9/2014 8:39 AM
Second Revision No. 87-NFPA 13-2014 [ Section No. 14.4.1 ]
14.4.1
Protection of palletized and solid-piled storage of Class I through Class IV commodities shall be in accordance with Table14.4.1.
Table 14.4.1 ESFR Protection of Palletized and Solid-Piled Storage of Class I Through Class IV Commodities
Commodity
MaximumStorageHeight
MaximumCeiling/Roof
HeightNominalK-Factor
Orientation
MinimumOperatingPressure
ft m ft m psi bar
Class I, II, III, or IV, encapsulatedand nonencapsulated (noopen-top containers)
20 6.1 25 7.6
14.0
(200)
Upright/
pendent50 3.4
16.8
(240)
Upright/
pendent35 2.4
22.4
(320)Pendent 25 1.7
25.2
(360)Pendent 15 1.0
25 7.6
30 9.1
14.0
(200)
Upright/
pendent50 3.4
16.8
(240)
Upright/
pendent35 2.4
22.4
(320)Upright/pendent Pendent 25 1.7
25.2
(360)Upright/pendent Pendent 15 1.0
32 9.8
14.0
(200)
Upright/
pendent60 4.1
16.8
(240)
Upright/
pendent42 2.9
30 9.1 35 10.7
14.0
(200)
Upright/
pendent75 5.2
16.8
(240)
Upright/
pendent52 3.6
22.4
(320)Pendent 35 2.4
25.2
(360)Pendent 20 1.4
35 10.7 40 12.2
16.8
(240)Pendent 52 3.6
22.4
(320)Pendent 40 2.8
25.2
(360)Pendent 25 1.7
35 10.7 45 13.7
22.4
(320)Pendent 40 2.8
25.2
(360)Pendent 40 2.8
40 12.2 45 13.7
22.4
(320)Pendent 40 2.8
25.2
(360)Pendent 40 2.8
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
148 of 301 10/9/2014 8:39 AM
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 13:53:58 EDT 2014
Committee Statement
CommitteeStatement:
As directed by the Correlating Committee, the TC reviewed the modifications to the table for the “upright orientation”for K 25.2, K22.4 and K 16.8 sprinklers at 32 ft ceiling height.
ResponseMessage:
Public Comment No. 194-NFPA 13-2014 [Section No. 14.4.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
149 of 301 10/9/2014 8:39 AM
Second Revision No. 75-NFPA 13-2014 [ Section No. 15.2 ]
15.2* Control Mode Density/Area Sprinkler Protection Criteria for Palletized, Solid-Piled, Bin Box, Shelf, or Back-to-Back ShelfStorage of Plastic and Rubber Commodities.
15.2.1 Storage 5 ft (1.5 m) or Less in Height.
For the storage of Group A plastics stored 5 ft (1.5 m) or less in height, the sprinkler design criteria for miscellaneous storagespecified in Chapter 13 shall be used. The protection criteria in Chapter 13 shall be acceptable for storage of Group A plasticcommodities up to and including 5 ft (1.5 m) in height. (See Table 13.2.1 for specific Group A plastic storage height protectioncriteria.)
15.2.2* Storage Over 5 ft (1.5 m) in Height.
15.2.2.1
Protection for plastic and rubber commodities shall be in accordance with Section 15.2. The decision tree shown in Figure15.2.2.1 shall be used to determine the protection in each specific situation, subject to the following limitations:
(1) Commodities that are stored palletized, solid piled, or in bin boxes up to 25 ft (7.6 m) in height.
(2) Commodities that are stored in shelf storage up to 15 ft (4.6 m) in height.
(3) Commodities that are stored using back-to-back shelf storage up to 15 ft (4.6 m) in height. The minimum aisle width shallbe 60 in. (1524 mm). The design criteria shall be in accordance with Table 15.2.2.1. The back-to-back shelf shall have afull height solid vertical transverse barrier of 3⁄8 in. (9.5 mm) plywood or particleboard, 22 gauge sheet metal, or equivalent,from face of aisle to face of aisle, spaced at a maximum 45 ft (13.7 m) interval. The transverse barrier shall be permittedto terminate at the longitudinal barrier.
Table 15.2.2.1 Back-to-Back Shelf Storage of Cartoned Unexpanded Group A Plastics
Storage Height Ceiling HeightProtection
ft m ft m
Over 5 up to 8 1.5/2.4 Up to 14 4.3 Ordinary Hazard Group 2
Up to 12 3.7 Up to 15 4.6 0.45 gpm/ft2 over 2500 ft2 18.3 mm/min/232 m2
Up to 12 3.7 Up to 30 9.1 0.6 gpm/ft2 over 2500 ft2 24.5 mm/min/232 m2
Up to 15 4.6 Up to 30 9.1 0.7 gpm/ft2 over 2500 ft2 28.5 mm/min/232 m2
Figure 15.2.2.1 Decision Tree.
15.2.2.2*
Factors affecting protection requirements such as closed/open array, clearance to ceiling, and stable/unstable piles shall beapplicable only to storage of Group A plastics. This decision tree also shall be used to determine protection for commoditiesthat are not wholly Group A plastics but contain such quantities and arrangements of the same that they are deemed morehazardous than Class IV commodities.
15.2.2.3
Group B plastics and free-flowing Group A plastics shall be protected in the same manner as a Class IV commodity. (SeeChapter 14 for protection of these storage commodities with spray sprinklers.)
15.2.2.4
Group C plastics shall be protected in the same manner as a Class III commodity. (See Chapter 14 for protection of thesestorage commodities with spray sprinklers.)
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
150 of 301 10/9/2014 8:39 AM
15.2.2.5*
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
151 of 301 10/9/2014 8:39 AM
Design areas and densities for the appropriate storage configuration shall be selected from Table 15.2.2.5(a) or Table15.2.2.5(b) as appropriate.
Table 15.2.2.5(a) Design Densities for Palletized, Solid-Piled, Bin Box, or Shelf Storage of Group A Plastic Commodities (U.S.Customary Units)
Maximum Storage Height
(ft)Roof/Ceiling Height (ft)
Density (gpm/ft2)
A B C D E
>5 to ≤12
Up to 15 0.2 EH2 0.3 EH1 EH2
>15 to 20 0.3 0.6 0.5 EH2 EH2
>20 to 32 0.4 0.8 0.6 0.45 0.7
15
Up to 20 0.3 0.6 0.5 0.4 0.45
>20 to 25 0.4 0.8 0.6 0.45 0.7
>25 to 35 0.45 0.9 0.7 0.55 0.85
20
Up to 25 0.4 0.8 0.6 0.45 0.7
>25 to 30 0.45 0.9 0.7 0.55 0.85
>30 to 35 0.6 1.2 0.85 0.7 1.1
25Up to 30 0.45 0.9 0.7 0.55 0.85
>30 to 35 0.6 1.2 0.85 0.7 1.1
Notes:
(1) Minimum clearance between sprinkler deflector and top of storage shall be maintained as required.
(2) Column designations correspond to the configuration of plastics storage as follows:
A: (1) Nonexpanded, unstable
(2) Nonexpanded, stable, solid unit load
B: Expanded, exposed, stable
C: (1) Expanded, exposed, unstable
(2) Nonexpanded, stable, cartoned
D: Expanded, cartoned, unstable
E: (1) Expanded, cartoned, stable
(2) Nonexpanded, stable, exposed
(3) EH1 = Density required by Figure 13.2.1 for Curve EH1
EH2 = Density required by Figure 13.2.1 for Curve EH2
(4) Roof/ceiling height >35 ft is not permitted.
Table 15.2.2.5(b) Design Densities for Palletized, Solid-Piled, Bin Box, or Shelf Storage of Group A Plastic Commodities (S.I.Units)
Maximum Storage Height
(m)
Roof/Ceiling Height
(m)
Density
(mm/min)
A B C D E
Up to 4.6 8.2 EH2 12.2 EH1 EH2
>1.5 to ≤3.6 >4.6 to 6.1 12.2 24.4 20.4 EH2 EH2
>6.1 to 9.8 16.3 32.6 24.4 18.3 28.5
Up to 6.1 12.2 24.4 20.4 16.3 18.3
4.6 >6.1 to 7.6 16.3 32.6 24.4 18.3 28.5
>7.6 to 10.7 18.3 36.7 28.5 22.4 34.6
Up to 7.6 16.3 32.6 24.4 18.3 28.5
6.1 >7.6 to 9.1 18.3 36.7 28.5 22.4 34.6
>9.1 to 10.7 24.4 49.0 34.6 28.5 44.8
7.6Up to 9.1 18.3 36.7 28.5 22.4 34.6
>9.1 to 10.7 24.4 49.0 34.6 28.5 44.8
Notes:
(1) Minimum clearance between sprinkler deflector and top of storage shall be maintained as required.
(2) Column designations correspond to the configuration of plastics storage as follows:
A: (1) Nonexpanded, unstable
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
152 of 301 10/9/2014 8:39 AM
(2) Nonexpanded, stable, solid unit load
B: Expanded, exposed, stable
C: (1) Expanded, exposed, unstable
(2) Nonexpanded, stable, cartoned
D: Expanded, cartoned, unstable
E: (1) Expanded, cartoned, stable
(2) Nonexpanded, stable, exposed
(3) EH1 = Density required by Figure 13.2.1 for Curve EH1
EH2 = Density required by Figure 13.2.1 for Curve EH2
(4) Roof/ceiling height >35 ft is not permitted.
15.2.2.6
The ceiling-only protection criteria specified in Chapter 17 for rack storage of Group A plastic commodities shall be permitted tobe used for solid-piled and palletized storage of the same commodity at the same height and clearance to ceiling.
15.2.2.7*
For Table 15.2.2.5(a) and Table 15.2.2.5(b), the design areas shall be as follows:
(1) The area shall be a minimum of 2500 ft2 (232 m2).
(2) Where Table 15.2.2.5(a) and Table 15.2.2.5(b) allow densities and areas to be selected in accordance with Curve EH1and Curve EH2 of Figure 13.2.1, any density/area from the curves in Figure 13.2.1 shall be permitted. When selecting apoint from the EH1 or EH2 density/area curves of Figure 13.2.1, the following area reductions shall be permitted:
(a) For K-8.0 (115) sprinklers used with Curve EH1, the design area shall be permitted to be reduced by 25 percent, but
not below 2000 ft2 (186 m2), where high temperature sprinklers are used.
(b) For K-11.2 (160) or larger sprinklers, the design area shall be permitted to be reduced by 25 percent, but not below
2000 ft2 (186 m2), regardless of temperature rating.
(3) For closed arrays, the area shall be permitted to be reduced to 2000 ft2 (186 m2).
15.2.2.8*
Interpolation of densities between storage heights shall be permitted.
15.2.2.8.1
Densities shall be based on the 2500 ft2 (232 m2) design area.
15.2.2.8.2
Interpolation of ceiling/roof heights shall not be permitted.
15.2.2.9
For storage of Group A plastics between 5 ft (1.5 m) and 12 ft (3.7 m) in height, the installation requirements for extra hazardsystems shall apply.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Wed Jun 25 18:48:56 EDT 2014
Committee Statement
CommitteeStatement:
The terminology “5 ft or less” is used throughout the standard, therefore the revision was made to the proposed languagefor consistency with the rest of the storage chapters. There is value in emphasizing impact of the 5 ft storage height. As forthe renumbering, each digit has meaning and shows the grouping of the criteria. Everything from the old 15.2.3 through15.2.10 applies to storage over 5 ft. This attention to the numbers correlates with that of ch 14 and 16 (section 14.2.4 is agood example). The smaller amount of criteria in ch 15 as allowed us to be casual about the numbering process withoutsignificant confusion but is not a reason to continue the practice. This is especially true with the current focus on thestructure/redundancy and format of multiple chapters.
ResponseMessage:
Public Comment No. 100-NFPA 13-2014 [Section No. 15.2]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
153 of 301 10/9/2014 8:39 AM
Second Revision No. 63-NFPA 13-2014 [ New Section after 16.1.2.2 ]
16.1.2.3*
The ceiling design criteria for single-, double-, and multiple-row racks in Chapter 16 shall be based on open rackconfigurations as defined in 3.9.3.7.4.
16.1.2.3.1
Solid shelf racks as defined in 3.9.3.7.9 or obstructions resulting in solid shelf requirements may require additional in-racksprinklers that may affect the ceiling design requirements.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Wed Jun 25 13:53:10 EDT 2014
Committee Statement
CommitteeStatement:
The design criteria provided for ceiling sprinklers is based upon the assumption that the racks are open. Rather thanadding the word open to several section headers, adding a statement that clarifies the intent of the standard is a moredirect way of establishing the way the standard has been written.
ResponseMessage:
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
154 of 301 10/9/2014 8:39 AM
Second Revision No. 88-NFPA 13-2014 [ New Section after 16.1.2.2 ]
16.1.2.4 Alternative Protection.
Class I, II, III, IV commodities requiring a greater level of protection than is available from the overhead sprinkler system shallbe permitted to be protected in accordance with 16.1.2.4.1 through 16.1.2.4.9 .
16.1.2.4.1
Where the storage rack will not be solely dedicated to the storage of commodities requiring a greater level of protection thanis available from the overhead sprinkler system, either of the following shall apply:
(1) Extend the protection prescribed by 16.1.2.4 horizontally one pallet load in all directions beyond the commoditystorage area requiring the higher level of protection.
(2) Install a vertical barrier to segregate the commodities requiring the higher level of protection from any adjacentcommodities.
16.1.2.4.2
Commodities that can be protected by the ceiling-level sprinkler system shall be permitted to be stored vertically above andhorizontally adjacent to the portions of the storage rack equipped as prescribed by 16.1.2.4 .
16.1.2.4.3 Horizontal Barriers.
Horizontal barriers shall be installed at every tier level of the dedicated storage rack where the rack is equipped with solidshelves.
16.1.2.4.3.1
Where the dedicated storage rack is open-frame, horizontal barriers shall be installed at vertical increments not exceeding 12ft (3.6 m).
16.1.2.4.3.2
The barriers shall span horizontally so that all flue spaces within the rack bay are covered.
16.1.2.4.3.3
A maximum 3 in. (75 mm) wide gap shall be permitted at rack uprights.
16.1.2.4.3.4
The solid barrier shall be installed on a horizontal plane within a rack, beneath which in-rack sprinklers shall be installed, asfollows:
(1) The barrier shall be constructed of minimum 22 gauge (0.7 mm) sheet metal or of minimum 3 ⁄3 in. (10 mm) plywood.
(2) The barrier shall extend to both aisle faces of the racks, covering up both the longitudinal and the transverse fluespaces of the rack bays in which they are installed.
(3) The barrier shall be fitted to within 3 in. (75 mm) of any vertical rack member or other equipment that would create anopening, such as vertical in-rack sprinkler pipe drops.
16.1.2.4.4 In-Rack Sprinklers.
Minimum K-8.0 (K-115) quick-response sprinklers (ceiling-level or in-rack) shall be installed beneath each horizontal barrier.The deflector of the sprinkler shall be located as close to the underside of the horizontal barrier as possible.
16.1.2.4.4.1 Single-Row Racks.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
155 of 301 10/9/2014 8:39 AM
(A)
For single-row racks, sprinklers shall be installed at each rack upright and at each rack mid-bay as shown in Figure16.1.2.4.4.1(A) .
Figure 16.1.2.4.4.1(A) Alternative Protection for Single-Row Racks.
(B)
The maximum linear spacing between sprinklers shall not exceed 5 ft (1.5 m).
16.1.2.4.4.2 Double-Row Racks.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
156 of 301 10/9/2014 8:39 AM
(A)
For double-row racks, sprinklers shall be installed at each rack upright within the longitudinal flue space and at the face of therack and at the mid-bay face of each rack bay as shown in Figure 16.1.2.4.4.2(A) .
Figure 16.1.2.4.4.2(A) Alternative Protection for Double-Row Racks.
(B)
The maximum linear spacing between sprinklers shall not exceed 5 ft (1.5 m) at the rack face and 10 ft (3.0 m) within thelongitudinal flue space.
16.1.2.4.4.3 Multiple-Row Racks.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
157 of 301 10/9/2014 8:39 AM
(A)
For multiple-row racks, an alternating sprinkler arrangement shall be installed within adjacent transverse flue spaces asshown in Figure 16.1.2.4.4.3(A) , with sprinklers at the face of each flue space.
Figure 16.1.2.4.4.3(A) Alternative Protection for Multiple-Row Racks.
(B)
The maximum linear spacing between sprinklers at the face and at each alternating bay shall not exceed 5 ft (1.5 m) andshall not exceed 10 ft (3.0 m) between sprinklers at every other bay.
16.1.2.4.5
The design of an in-rack sprinkler system shall be based on a minimum flow of 60 gpm (230 L/min) from the most remote sixsprinklers for single-row racks or the most remote eight sprinklers for both double-row and multiple-row racks.
16.1.2.4.6
A hose demand allowance of 500 gpm (1,900 L/min) shall be included in the hydraulic design.
16.1.2.4.7
The demand duration shall provide for a minimum of 2 hours.
16.1.2.4.8
The in-rack sprinkler demand shall not be required to be hydraulically balanced with the ceiling-level sprinkler system.
16.1.2.4.9 Ceiling Sprinkler System.
The ceiling-level sprinkler system shall be designed based on the highest commodity hazard not protected by the criteriaprescribed by 16.1.2.4 .
Supplemental Information
File Name Description
Scheme_A_Drawings_Single_Row.pdf Fig 16.1.2.3.4.1
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
158 of 301 10/9/2014 8:39 AM
Scheme_A_Drawings_Double_Row.pdf Fig 16.1.2.3.4.2
Scheme_A_Drawings_Multi_Row.pdf Fig 16.1.2.3.4.3
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 14:13:02 EDT 2014
Committee Statement
CommitteeStatement:
This protection criteria was introduced during last cycle for certain solid shelf arrangements. This protection Scheme wasoriginally developed and tested for protection of Class IIIB combustible liquids in plastic containers for NFPA 30 so as toallow of protection of pockets of such stored materials with the use of solid barriers and enhanced in-rack sprinkler arraysthat provided a direct application of water within the storage array. Test references to support such criteria for Class IIIBliquids is provided by NFPA 30, Table D.2(e) 1 as P-21 to P-31 from the Directory of Fire Tests Involving Storage ofFlammable and Combustible Liquids in Containers, 3rd edition. The adequacy of such protection for the higher hazardClass IIIB combustible liquids provides justification for protection of Class I, II, III, IV Commodities or Group A plastics.
ResponseMessage:
Public Comment No. 248-NFPA 13-2014 [New Section after 16.1.2.2]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
159 of 301 10/9/2014 8:39 AM
Second Revision No. 69-NFPA 13-2014 [ Section No. 16.1.6 ]
16.1.6 Solid Shelf Rack Shelving .
16.1.6.1
Where solid shelving in single-, double-, and multiple-row racks exceeds 20 ft2 (1.86 m2) in area but does not exceed 64 ft2
(5.95 m2) in area, sprinklers shall not be required below every shelf, but shall be installed at the ceiling and below shelves atintermediate levels not more than 6 ft (2 m) apart vertically. (See Section C.11.)
16.1.6.2
Where solid shelving in single-, double-, and multiple-row racks exceeds 64 ft2 (5.95 m2) in area or where the levels of storageexceed 6 ft (2 m), sprinklers shall be installed at the ceiling and below each level of shelving.
16.1.6.3
Where multiple-row racks of any height have no longitudinal flue or where double-row racks with storage up 25 ft (7.6 m) inheight have no longitudinal flue, the situation shall not be considered solid shelves where transverse flues exist at maximum 5ft (1.5 m) intervals, and additional in-rack sprinklers shall not be required in accordance with 16.1.6.1 and 16.1.6.2.
16.1.6.4
The maximum horizontal spacing between in-rack sprinklers shall be 10 ft (3.1 m).
16.1.6.5
Where the criteria in 16.1.6.6 are not met, the water demand for the in-rack sprinklers shall be based on a minimum flow of 30gpm (114 L/min) discharging from the following number of sprinklers balanced to the ceiling sprinkler demand in accordancewith Section 23.8 23.4.5 :
(1) Six sprinklers where only one level of in-rack sprinklers is installed to protect Class I, Class II, or Class III commodity
(2) Eight sprinklers where only one level of in-rack sprinklers is installed to protect Class IV commodity
(3) Ten sprinklers (five on each of the top two levels) where more than one level of in-rack sprinklers is installed to protectClass I, Class II, or Class III commodity
(4) Fourteen sprinklers (seven on each of the top two levels) when where more than one level of in-rack sprinklers is installedto protect Class IV commodity
16.1.6.6
The water demand for in-rack sprinklers shall not be required to be balanced to the ceiling sprinkler demand where additionalface sprinklers are installed under each solid shelf at rack uprights, and the in-rack sprinklers are calculated to discharge atleast 60 gpm (227 L/min) from eight sprinklers.
16.1.6.7*
Where solid shelves obstruct only a portion of the rack, in-rack sprinklers shall be installed horizontally, one flue beyond theend of the solid shelf, and vertically, all tiers beneath the solid shelves.
16.1.6.8
Ceiling design criteria for CMDA, CMSA, and ESFR sprinklers shall be an applicable option for open racks combined within-rack sprinklers installed in accordance with 16.1.6.1 or 16.1.6.2 .
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Wed Jun 25 14:48:54 EDT 2014
Committee Statement
CommitteeStatement:
The term solid shelf rack is being replaced with solid shelving as that is the type of arrangement being described inthe subsequent sections.
ResponseMessage:
Public Comment No. 86-NFPA 13-2014 [Global Input]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
160 of 301 10/9/2014 8:39 AM
Second Revision No. 66-NFPA 13-2014 [ New Section after 16.1.6.6 ]
16.1.6.7*
Where solid shelves obstruct only a portion of the rack, in-rack sprinklers shall be installed horizontally, one flue beyond theend of the solid shelf, and vertically, all tiers beneath the solid shelves.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Wed Jun 25 14:27:12 EDT 2014
Committee Statement
CommitteeStatement:
There is no guidance on where to stop the horizontal placement of in-rack sprinklers for racks with only portions of theassembly having solid shelving. There is guidance in 16.1.8.2 on racks with just a portion containing a higher hazardcommodity. This criteria requires extending the in-racks a full bay or 8 ft. whereas this PC extends it only one flue. Thisseems sufficient to halt the horizontal fire extension caused by the solid shelf.
ResponseMessage:
Public Comment No. 78-NFPA 13-2014 [Global Input]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
161 of 301 10/9/2014 8:39 AM
Second Revision No. 67-NFPA 13-2014 [ New Section after 16.1.6.6 ]
16.1.6.8
Ceiling design criteria for CMDA, CMSA, and ESFR sprinklers shall be an applicable option for open racks combined within-rack sprinklers installed in accordance with 16.1.6.1 or 16.1.6.2 .
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Wed Jun 25 14:29:23 EDT 2014
Committee Statement
CommitteeStatement:
There is a need for guidance on what system criteria to use when there are solid shelves. The addition of the wordceiling provides clarity that the sprinkler technology being described is at the ceiling, and not the in-rack sprinklers.
Due to the historical perspective that the General section on solid shelf racks applies only to spray sprinkler, identifyingall sprinkler types corrects that misunderstanding. It also emphasizes that this section is indeed applicable to ESFR andCMSA system as already identified in 8.4.6.1.1.
ResponseMessage:
Public Comment No. 82-NFPA 13-2014 [New Section after 16.1.6.6]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
162 of 301 10/9/2014 8:39 AM
Second Revision No. 77-NFPA 13-2014 [ Section No. 16.2.1.3.4.3 ]
16.2.1.3.4.3
For storage height over 12 ft (3.7 m) up to and including 20 ft (6.1 m) protected with ceiling sprinklers and with more than onelevel of in-rack sprinklers, but not in every tier, densities obtained from design curves and adjusted in accordance with Figure16.2.1.3.4.1 shall be permitted to be reduced an additional 20 percent, as indicated in Table 16.2.1.3.4.3.
Table 16.2.1.3.4.3 Adjustment to Ceiling Sprinkler Density for Storage Height and In-Rack Sprinklers
Permitted Ceiling Sprinklers DensityAdjustments Where In-Rack Sprinklers Are
Installed
Over 12 ft (3.7 m)through 25 ft (7.6 m)
None Yes None
Over 12 ft (3.7 m)through 20 ft (6.1 m)
Minimum required Yes None
More than minimum,but not in every tier
YesReduce density 20% from that of minimumin-rack sprinklers
In every tier exceptabove the top tier
YesReduce density 40% from that of minimumin-rack sprinklers
Over 20 ft (6.1 m)through 25 ft (7.5 m)
Minimum required No None
More than minimum,but not in every tier
NoReduce density 20% from that of minimumin-rack sprinklers
In every tier exceptabove the top tier
NoReduce density 40% from that of minimumin-rack sprinklers
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Wed Jun 25 19:12:19 EDT 2014
Committee Statement
CommitteeStatement:
The revisions to 16.1.2.1.3.4.6 and Table 16.2.1.3.4.3 clarify that sprinklers are not required above the top tier ofstorage in a rack.
Response Message:
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
163 of 301 10/9/2014 8:39 AM
Second Revision No. 76-NFPA 13-2014 [ Section No. 16.2.1.3.4.6 ]
16.2.1.3.4.6*
For storage height over 20 ft (6.1 m) up to and including 25 ft (7.6 m) protected with ceiling sprinklers and in-rack sprinklers ateach tier except above the top tier , densities obtained from design curves shall be permitted to be reduced 40 percent, asindicated in Table 16.2.1.3.4.3. Densities shall not be adjusted in accordance with Figure 16.2.1.3.4.1 for storage height.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Wed Jun 25 19:09:45 EDT 2014
Committee Statement
CommitteeStatement:
The annex note makes clear that the intent of the committee to require in rack sprinklers in every tier does not includean in-rack sprinkler above the top tier of storage, which is protected by the ceiling sprinklers. As an annex note cannotoverride the body of the standard, this wording should be in the body of the standard.
ResponseMessage:
Public Comment No. 336-NFPA 13-2014 [New Section after 16.2.1.3.4.6]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
164 of 301 10/9/2014 8:39 AM
Second Revision No. 91-NFPA 13-2014 [ Section No. 16.2.1.3.5 ]
16.2.1.3.5
For solid shelf rack storage, Table 16.2.1.3.2 shall be used to establish the density/area criteria and in-rack sprinklers shallbe installed in accordance with 16.1.6 .
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 16:09:50 EDT 2014
Committee Statement
CommitteeStatement:
The modification makes the standard more user friendly by having the criteria located in section on solidshelves.
Response Message:
Public Comment No. 258-NFPA 13-2014 [Section No. 16.2.1.3.5]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
165 of 301 10/9/2014 8:39 AM
Second Revision No. 110-NFPA 13-2014 [ Section No. 16.2.1.4.3.2 ]
16.2.1.4.3.2
Where a storage rack, due to its length, requires less than the number of in-rack sprinklers specified in 16.2.1.4.3.1 (1)through 16.2.1.4.3.1 (4), only those in-rack sprinklers in a single rack shall be included in the calculation.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 19:08:35 EDT 2014
Committee Statement
CommitteeStatement:
The committee statement is that this section provides clarity. Since this requirement is clearly stated in 16.1.8.3 and itis only repeated in 16.2, it should either be repeated in 16.3, 17.2, and 17.3 or deleted.
The redundancy task group agreed with this PC without any changes.
ResponseMessage:
Public Comment No. 79-NFPA 13-2014 [Section No. 16.2.1.4.3.2]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
166 of 301 10/9/2014 8:39 AM
Second Revision No. 68-NFPA 13-2014 [ Section No. 16.2.2.1.1 ]
16.2.2.1.1
Protection of solid shelf racks with CMSA sprinklers at the ceiling shall be permitted where in-rack shall not be permittedsprinklers are installed in accordance with 16.1.6 . to protect storage on solid shelf racks unless the solid shelf racks areprotected with In-rack in-rack sprinklers shall be installed in every level below the highest solid shelf in accordance with16.1.6 .
16.2.2.1.1.1
Where solid shelves are used, in-rack sprinklers shall be installed in every level below the highest solid shelf.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Wed Jun 25 14:34:07 EDT 2014
Committee Statement
CommitteeStatement:
Section 16.2.2.1.1 in the First Draft is being replaced by the two sections created in this Second Revision. There is notechnical change, the original section is being broken into two requirements since it included 2 “shall” statements.
ResponseMessage:
Public Comment No. 164-NFPA 13-2014 [New Section after 16.2.2.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
167 of 301 10/9/2014 8:39 AM
Second Revision No. 92-NFPA 13-2014 [ Section No. 16.3.2.1.1 ]
16.3.2.1.1
Protection of solid shelf racks with CMSA sprinklers at the ceiling shall be permitted where in-rack sprinklers are installed inaccordance with 16.1.6 . In-rack shall not be permitted to protect storage on solid shelf racks unless the solid shelf racks areprotected with in-rack sprinklers shall be installed in every level below the highest solid shelf in accordance with 16.1.6 .
16.3.2.1.1.1
Where solid shelves are used, in-rack sprinklers shall be installed in every level below the highest solid shelf
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 16:18:42 EDT 2014
Committee Statement
CommitteeStatement:
Editorial – to co-ordinate the text with the similar requirement of 16.2.3.2 (FR-210). Similar requirements should beworded similarly, for clarity and consistency.
ResponseMessage:
Public Comment No. 165-NFPA 13-2014 [New Section after 16.3.2.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
168 of 301 10/9/2014 8:39 AM
Second Revision No. 93-NFPA 13-2014 [ Section No. 16.3.3.2.1 ]
16.3.3.2.1
Protection of solid shelf racks with ESFR sprinklers at the ceiling shall be permitted where in-rack sprinklers are installed shallnot be permitted to protect storage on solid shelf racks unless the solid shelf racks are protected with in-rack sprinklers inaccordance with 16.1.6.
16.3.3.2.1.1
Where solid shelves are used, in-rack sprinklers shall be installed in every level below the highest solid shelf.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 16:20:30 EDT 2014
Committee Statement
CommitteeStatement:
Editorial revision intended to co-ordinate the text with the similar requirement of 16.2.3.2 (FR-210). Similarrequirements should be worded similarly, for clarity and consistency.
ResponseMessage:
Public Comment No. 94-NFPA 13-2014 [Section No. 16.3.3.2 [Excluding any Sub-Sections]]
Public Comment No. 166-NFPA 13-2014 [New Section after 16.3.3.2]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
169 of 301 10/9/2014 8:39 AM
Second Revision No. 64-NFPA 13-2014 [ New Section after 17.1.2.7 ]
17.1.2.8*
The ceiling design criteria for single-, double-, and multiple-row racks in Chapter 17 shall be based on open rack configurationsas defined in 3.9.3.7.4.
17.1.2.8.1
Solid shelf racks as defined in 3.9.3.7.9 or obstructions resulting in solid shelf requirements may require additional in-racksprinklers that may affect the ceiling design requirements.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Wed Jun 25 14:01:25 EDT 2014
Committee Statement
CommitteeStatement:
The design criteria provided for ceiling sprinklers is based upon the assumption that the racks are open. Rather thanadding the word open to several section headers, adding a statement that clarifies the intent of the standard is a moredirect way of establishing the way the standard has been written.
ResponseMessage:
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
170 of 301 10/9/2014 8:39 AM
Second Revision No. 89-NFPA 13-2014 [ New Section after 17.1.2.7 ]
17.1.2.9 Alternative Protection.
The protection of Group A plastic commodities requiring a greater level of protection than is available from the overheadsprinkler system shall be permitted to be protected in accordance with 17.1.2.9.1 through 17.1.2.9.9 .
17.1.2.9.1
Where the storage rack will not be solely dedicated to the storage of commodities requiring a greater level of protection thanis available from the overhead sprinkler system, either of the following shall apply:
(1) Extend the protection prescribed by 17.1.2.9 horizontally one pallet load in all directions beyond the commoditystorage area requiring the higher level of protection.
(2) Install a vertical barrier to segregate the commodities requiring the higher level of protection from any adjacentcommodities.
17.1.2.9.2
Commodities that can be protected by the ceiling-level sprinkler system shall be permitted to be stored vertically above andhorizontally adjacent to the portions of the storage rack equipped as prescribed by 17.1.2.9 .
17.1.2.9.3 Horizontal Barriers.
Horizontal barriers shall be installed at every tier level of the dedicated storage rack where the rack is equipped with solidshelves.
17.1.2.9.3.1
Where the dedicated storage rack is open-frame, horizontal barriers shall be installed at vertical increments not exceeding 12ft (3.6 m).
17.1.2.9.3.2
The barriers shall span horizontally so that all flue spaces within the rack bay are covered.
17.1.2.9.3.3
A maximum 3 in. (75 mm) wide gap shall be permitted at rack uprights.
17.1.2.9.3.4
The solid barrier shall be installed on a horizontal plane within a rack, beneath which in-rack sprinklers shall be installed, asfollows:
(A)
The barrier shall be constructed of minimum 22 gauge (0.7 mm) sheet metal or of minimum 3 ⁄8 in. (10 mm) plywood.
(B)
The barrier shall extend to both ends and both aisle faces of the racks covering up both the longitudinal and transverse fluespaces of the rack bays in which they are installed.
(C)
The barrier shall be fitted to within 3 in. (75 mm) of any vertical rack member or other equipment that would create anopening, such as vertical in-rack sprinkler pipe drops.
17.1.2.9.4 In-Rack Sprinklers.
Minimum K-8.0 (K-115) quick-response sprinklers (ceiling-level or in-rack) shall be installed beneath each horizontal barrier.The deflector of the sprinkler shall be located as close to the underside of the horizontal barrier as possible.
17.1.2.9.4.1 Single-Row Racks.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
171 of 301 10/9/2014 8:39 AM
(A)
For single-row racks, sprinklers shall be installed at each rack upright and at each rack mid-bay as shown in Figure17.1.2.9.4.1(A) .
Figure 17.1.2.9.4.1(A) Alternative Protection Single-Row Racks.
(B)
The maximum linear spacing between sprinklers shall not exceed 5 ft (1.5 m).
17.1.2.9.4.2 Double-Row Racks.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
172 of 301 10/9/2014 8:39 AM
(A)
For double-row racks, sprinklers shall be installed at each rack upright within the longitudinal flue space and at the face of therack and at the mid-bay face of each rack bay as shown in Figure 17.1.2.9.4.2(A) .
Figure 17.1.2.9.4.2(A) Alternative Protection Double-Row Racks.
(B)
The maximum linear spacing between sprinklers shall not exceed 5 ft (1.5 m) at the rack face and 10 ft (3.0 m) within thelongitudinal flue space.
17.1.2.9.4.3 Multiple-Row Racks.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
173 of 301 10/9/2014 8:39 AM
(A)
For multiple-row racks, an alternating sprinkler arrangement shall be installed within adjacent transverse flue spaces, asshown in Figure 17.1.2.9.4.3(A) , with sprinklers at the face of each flue space.
Figure 17.1.2.9.4.3(A) Alternative Protection Multiple-Row Racks.
(B)
The maximum linear spacing between sprinklers at the face and each alternating bay shall not exceed 5 ft (1.5 m) and shallnot exceed 10 ft (3.0 m) between sprinklers at every other bay.
17.1.2.9.5
The design of an in-rack sprinkler system shall be based on a minimum flow of 60 gpm (230 L/min) from the most remote sixsprinklers for single-row racks or the most remote eight sprinklers for both double-row and multiple-row racks.
17.1.2.9.6
A hose demand allowance of 500 gpm (1,900 L/min) shall be included in the hydraulic design.
17.1.2.9.7
The demand duration shall provide for a minimum of 2 hours.
17.1.2.9.8
The in-rack sprinkler demand shall not be required to be hydraulically balanced with the ceiling-level sprinkler system.
17.1.2.9.9 Ceiling Sprinkler System.
The ceiling-level sprinkler system shall be designed based on the highest commodity hazard not protected by the criteriaprescribed by 17.1.2.9 .
Supplemental Information
File Name Description
Scheme_A_Drawings_Single_Row.pdf Fig 17.1.2.8.4.1
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
174 of 301 10/9/2014 8:39 AM
Scheme_A_Drawings_Double_Row.pdf Fig 17.1.2.8.4.2
Scheme_A_Drawings_Multi_Row.pdf Fig 17.1.2.8.4.3
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 14:19:01 EDT 2014
Committee Statement
CommitteeStatement:
This protection criteria was introduced during last cycle for certain solid shelf arrangements. This protection Scheme wasoriginally developed and tested for protection of Class IIIB combustible liquids in plastic containers for NFPA 30 so as toallow of protection of pockets of such stored materials with the use of solid barriers and enhanced in-rack sprinkler arraysthat provided a direct application of water within the storage array. Test references to support such criteria for Class IIIBliquids is provided by NFPA 30, Table D.2(e) 1 as P-21 to P-31 from the Directory of Fire Tests Involving Storage ofFlammable and Combustible Liquids in Containers, 3rd edition. The adequacy of such protection for the higher hazardClass IIIB combustible liquids provides justification for protection of Class I, II, III, IV Commodities or Group A plastics.
ResponseMessage:
Public Comment No. 250-NFPA 13-2014 [New Section after 17.1.2.7]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
175 of 301 10/9/2014 8:39 AM
Second Revision No. 70-NFPA 13-2014 [ Section No. 17.1.5.5 ]
17.1.5.5
Design criteria for combined ceiling and in-rack Ceiling design criteria for CMDA, CMSA, and ESFR sprinklers shall be usedfor the storage configurations in an applicable option for open racks combined with in-rack sprinklers installed in accordancewith 17.1.5.1 and 17.1.5.2.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Wed Jun 25 15:06:15 EDT 2014
Committee Statement
CommitteeStatement:
Due to the historical perspective that the General section on solid shelf racks applies only to spray sprinkler, identifyingall sprinkler types corrects that misunderstanding. It also emphasizes that this section is indeed applicable to ESFR andCMSA system as already identified in 8.4.6.1.1.
ResponseMessage:
Public Comment No. 84-NFPA 13-2014 [Section No. 17.1.5.5]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
176 of 301 10/9/2014 8:39 AM
Second Revision No. 72-NFPA 13-2014 [ New Section after 17.1.5.7 ]
17.1.5.8
Where solid shelves obstruct only a portion of the rack, in-rack sprinklers shall be installed horizontally, one flue beyond theend of the solid shelf, and vertically, all tiers beneath the solid shelves.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Wed Jun 25 15:17:44 EDT 2014
Committee Statement
CommitteeStatement:
There is currently no guidance on this issue for spray sprinklers. Considering that it applies to all sprinkler types, it shouldgo in only the general section. There is no guidance on where to stop the horizontal placement of in-rack sprinklers forracks with only portions of the assembly having solid shelving. There is guidance in 17.1.7.2 on racks with just a portioncontaining a higher hazard commodity. This criteria requires extending the in-racks a full bay or 8 ft. whereas this PCextends it only one flue. This seems sufficient to halt the horizontal fire extension caused by the solid shelf. Editorial changeto merge items a and b into a single requirement. The language describing where in-racks should be located where solidshelves are used should be retained since it provides guidance to the user within the section providing the ceiling criteriafor ESFR and CMSA above and below 25 feet of storage.
ResponseMessage:
Public Comment No. 93-NFPA 13-2014 [Global Input]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
177 of 301 10/9/2014 8:39 AM
Second Revision No. 94-NFPA 13-2014 [ Section No. 17.2.2.1.1 ]
17.2.2.1.1
Protection of solid shelf racks with CMSA sprinklers at the ceiling shall be permitted where in-rack sprinklers are installedshall not be permitted to protect storage on solid shelf racks unless the solid shelf racks are protected with in-rack sprinklers inaccordance with 17.1.5. In-rack sprinklers shall be installed in every level below the highest solid shelf.
17.2.2.1.1.1
In-rack Where solid shelves are used, in-rack sprinklers shall be installed in every level below the highest solid shelf.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 16:41:22 EDT 2014
Committee Statement
CommitteeStatement:
Editorial revision to co-ordinate the text with the similar requirement of 16.2.3.2 (FR-210). Similar requirementsshould be worded similarly, for clarity and consistency.
ResponseMessage:
Public Comment No. 168-NFPA 13-2014 [New Section after 17.2.2.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
178 of 301 10/9/2014 8:39 AM
Second Revision No. 96-NFPA 13-2014 [ Section No. 17.2.3.1.1 ]
17.2.3.1.1
ESFR protection as defined shall not apply to the following:
(1) Rack storage involving solid shelves, except for the situation as permitted by 17.2.3.1.2
(2) Rack storage involving open-top cartons or containers
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 16:51:39 EDT 2014
Committee Statement
Committee Statement: This revision is an editorial correction to make the language consistent with similar sections.
Response Message:
Public Comment No. 364-NFPA 13-2014 [Section No. 17.2.3.1.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
179 of 301 10/9/2014 8:39 AM
Second Revision No. 95-NFPA 13-2014 [ Section No. 17.2.3.1.2 ]
17.2.3.1.2
Protection of solid shelf racks with ESFR sprinklers at the ceiling shall be permitted where in-rack sprinklers are installed shallnot be permitted to protect storage on solid shelf racks unless the solid shelf racks are protected with in-rack sprinklers inaccordance with 17.1.5. In-rack sprinklers shall be installed in every level below the highest solid shelf.
17.2.3.1.2.1
In-rack Where solid shelves are used, in-rack sprinklers shall be installed in every level below the highest solid shelf.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 16:50:00 EDT 2014
Committee Statement
CommitteeStatement:
Editorial revision to co-ordinate the text with the similar requirement of 16.2.3.2 (FR-210). Similar requirementsshould be worded similarly, for clarity and consistency.
ResponseMessage:
Public Comment No. 169-NFPA 13-2014 [New Section after 17.2.3.1.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
180 of 301 10/9/2014 8:39 AM
Second Revision No. 102-NFPA 13-2014 [ New Section after 17.2.3.4.9 ]
17.2.3.5* Protection of Exposed Expanded Group A Plastics.
17.2.3.5.1
Protection of single-, double-, and multiple-row rack storage of exposed expanded Group A plastics shall be permitted to bein accordance with 17.2.3.5.2 through 17.2.3.5.8 .
17.2.3.5.2
The maximum storage height shall be 25 ft (9.1 m).
17.2.3.5.3
The maximum ceiling height shall be 40 ft (12.2 m).
17.2.3.5.4
Sprinklers shall be intermediate temperature–rated ESFR pendent sprinklers with a nominal K-factor of K-25.2 (360).
17.2.3.5.5
The design area shall consist of the most hydraulically demanding area of 12 sprinklers.
17.2.3.5.6
The minimum operating pressure shall be 60 psi (4.1 bar).
17.2.3.5.7
The minimum aisle width shall be 8 ft (2.4 m).
17.2.3.5.8
The rack shall have a solid vertical barrier of 3 ⁄8 in. (9.5 mm) plywood or particleboard, 22 gauge sheet metal, or equivalent,from face of rack to face of rack, spaced at a maximum of 16.5 ft (5.0 m) intervals.
17.2.3.5.8.1
The vertical barrier shall extend from a maximum of 4 in. (102 mm) above the floor to the maximum storage height.
17.2.3.5.8.2
The plan area of storage between vertical barriers and aisles shall not exceed 124 ft 2 (11.52 m 2 )
17.2.3.5.8.3
The vertical barrier shall extend across the longitudinal flue.
17.2.3.5.8.4
Commodity shall be permitted to extend a nominal 4 in. (102 mm) beyond the vertical barrier at the aisle.
Supplemental Information
File Name Description
13_SR_102_A_17_2_3_5_rev_MJK_.docx
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 17:47:04 EDT 2014
Committee Statement
CommitteeStatement:
The design protocol established in the first draft for storage over 25 feet is appropriate for storage less than 25feet.
Response Message:
Public Comment No. 265-NFPA 13-2014 [Section No. 17.3.3.5]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
181 of 301 10/9/2014 8:39 AM
A.17.2.3.5 The Fire Protection Research Foundation conducted a series of full-scale fire tests at Underwriters Laboratories to develop protection criteria for the rack storage of exposed expanded Group A plastic commodities. The tests are documented in the report, “Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers.” The criteria for exposed expanded plastics are based on Tests 2, 3, and 7 of the series, which investigated a 40 ft (12.2 m) ceiling with a range of storage heights. The tests used K-25.2 intermediate-temperature ESFR sprinklers with vertical barriers attached to the rack uprights at nominal 16 ft (4.9 m) apart. Vertical barriers of sheet metal and 3⁄8 in. plywood were both investigated. In Tests 1 through 6, transverse flue spaces between commodities were blocked. Comparing the results of Test 6, with blocked transverse flue spaces, and Test 7, with no blocking of transverse flue spaces, revealed the number of operated sprinklers decreased from 11 to 7 and improved suppression of the fire. The area limitation between the vertical barriers and aisles indicated in 17.3.3.5.9.2 will limit the depth of a multiple-row rack arrangement. The hose stream allowance and water supply duration requirements considered the burning characteristics of the exposed expanded plastic commodity, which generates a high rate of heat release very quickly. However, the commodity involved in the combustion process is quickly consumed after fire suppression or control is achieved. While the resulting criteria is available to be used for ceiling heights up to 40 ft (12.2 m), more cost-efficient protection criteria could be available from other sources for ceiling heights of 30 ft (9.1 m) and less. The research planning was based on the availability of design criteria from other sources for ceiling heights of 30 ft (9.1 m) and less.
Commented [IB1]: SL: ‘commodity involved’ is the ‘exposed expanded plastic commodity’?
Second Revision No. 97-NFPA 13-2014 [ Section No. 17.3.1.8 ]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
182 of 301 10/9/2014 8:39 AM
17.3.1.8*
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
183 of 301 10/9/2014 8:39 AM
For protection of storage of exposed unexpanded Group A plastics, whether encapsulated or nonencapsulated, or cartonedGroup A plastics, expanded or unexpanded, whether encapsulated or nonencapsulated, on multiple-row racks, in-racksprinklers shall be arranged in accordance with one of the options in Figure 17.3.1.8(a) through Figure 17.3.1.8(f) . The highestlevel of in-rack sprinklers shall be not more than 10 ft (3.1 m) below the top of storage.
Figure 17.3.1.8(a) In-Rack Sprinkler Arrangement, Cartoned Group A Plastic and Exposed Nonexpanded Group APlastic, Multiple-Row Racks, Storage Height Over 25 ft (7.6 m) — Option 1 [10 ft (3.1 m) Maximum Spacing].
Figure 17.3.1.8(b) In-Rack Sprinkler Arrangement, Cartoned Group A Plastic and Exposed Nonexpanded Group APlastic, Multiple-Row Racks, Storage Height Over 25 ft (7.6 m) — Option 2 [10 ft (3.1 m) Maximum Spacing].
Figure 17.3.1.8(c) In-Rack Sprinkler Arrangement, Cartoned Group A Plastic and Exposed Nonexpanded Group APlastic, Multiple-Row Racks, Storage Height Over 25 ft (7.6 m) — Option 1 [5 ft (1.5 m) Maximum Spacing].
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
184 of 301 10/9/2014 8:39 AM
Figure 17.3.1.8(d) In-Rack Sprinkler Arrangement, Cartoned Group A Plastic and Uncartoned Unexpanded Group APlastic, Multiple-Row Racks, Storage Height Over 25 ft (7.6 m) — Option 2 [5 ft (1.5 m) Maximum Spacing].
Figure 17.3.1.8(e) In-Rack Sprinkler Arrangement, Cartoned Group A Plastic and Exposed Nonexpanded Group APlastic, Multiple-Row Racks, Storage Height Over 25 ft (7.6 m) — Option 3 [5 ft (1.5 m) Maximum Spacing].
Figure 17.3.1.8(f) In-Rack Sprinkler Arrangement, Cartoned Group A Plastic and Exposed Nonexpanded Group APlastic, Multiple-Row Racks, Storage Height Over 25 ft (7.6 m) — Option 4 [5 ft (1.5 m) Maximum Spacing].
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
185 of 301 10/9/2014 8:39 AM
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 16:54:04 EDT 2014
Committee Statement
CommitteeStatement:
As per the Committee Statement, the longitudinal flues were to be eliminated to create consistency between thefigures in the section. However, the First Draft Report does not reflect the revision.
ResponseMessage:
Public Comment No. 170-NFPA 13-2014 [Section No. 17.3.1.8]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
186 of 301 10/9/2014 8:39 AM
Second Revision No. 98-NFPA 13-2014 [ Section No. 17.3.2.1.1 ]
17.3.2.1.1
Protection of solid shelf racks with CMSA sprinklers at the ceiling shall be permitted where in-rack sprinklers are installed shallnot be permitted to protect storage on solid shelf racks unless the solid shelf racks are protected with in-rack sprinklers inaccordance with 17.1.5. In-rack sprinklers shall be installed in every level below the highest solid shelf.
17.3.2.1.1.1
In-rack Where solid shelves are used, in-rack sprinklers shall be installed in every level below the highest solid shelf.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 16:55:01 EDT 2014
Committee Statement
CommitteeStatement:
Editorial revision to co-ordinate the text with the similar requirement of 16.2.3.2 (FR-210). Similar requirementsshould be worded similarly, for clarity and consistency.
ResponseMessage:
Public Comment No. 171-NFPA 13-2014 [New Section after 17.3.2.1.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
187 of 301 10/9/2014 8:39 AM
Second Revision No. 99-NFPA 13-2014 [ Section No. 17.3.3.1.1 ]
17.3.3.1.1
ESFR sprinklers shall not be permitted to protect storage on solid shelf racks unless the solid shelf racks are protected within-rack sprinklers in accordance with 17.1.5. Where solid shelves are used, in-rack sprinklers shall be installed in every levelbelow the highest solid shelf.
17.3.3.1.1.1
Where solid shelves are used, in-rack sprinklers shall be installed in every level below the highest solid shelf.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 16:57:09 EDT 2014
Committee Statement
CommitteeStatement:
Editorial revision to co-ordinate the text with the similar requirement of 16.2.3.2 (FR-210). Similar requirementsshould be worded similarly, for clarity and consistency.
ResponseMessage:
Public Comment No. 173-NFPA 13-2014 [New Section after 17.3.3.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
188 of 301 10/9/2014 8:39 AM
Second Revision No. 100-NFPA 13-2014 [ Section No. 17.3.3.5.5 ]
17.3.3.5.5
The design area shall consist of the most hydraulically demanding area of 15 sprinklers consisting of five sprinklers on each ofthree branch lines 12 sprinklers .
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 17:11:43 EDT 2014
Committee Statement
CommitteeStatement:
The FPRF final report for exposed expanded plastic includes a final test that was conducted between the First andSecond Draft Meetings. During this test, 7 sprinklers operated, which, including the 50% safety factor would support theinclusion of the 12 sprinkler design in lieu of the 15 sprinkler design that was accepted at the first draft. Please see theFPRF Report :Protection for Exposed Expanded Group A Plastics for more information.
ResponseMessage:
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
189 of 301 10/9/2014 8:39 AM
Second Revision No. 101-NFPA 13-2014 [ Section No. 17.3.3.5.7 ]
17.3.3.5.7
The hose stream allowance shall be 250 gpm (950) and the water supply duration shall be 60 minutes.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 17:12:55 EDT 2014
Committee Statement
Committee Statement: This section is not required since it is redundant with Table 12.8.6.
Response Message:
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
190 of 301 10/9/2014 8:39 AM
Second Revision No. 106-NFPA 13-2014 [ Section No. 18.3 ]
18.3 Water Supplies.
Total water supplies shall be in accordance with the following options:
A minimum of not less than 750 gpm (2835 L/min) for hose streams in addition to that required for automatic sprinklersand foam systems. Water supplies shall be capable of supplying the demand for sprinkler systems and hose streams fornot less than 3 hours.
For on-floor storage up to and including 5 ft (1.5 m) in height, hose stream requirements shall be permitted to be 250gpm (946 L/min) with a water supply duration of not less than 2 hours.
For ESFR and CMSA sprinkler systems approved for rubber tire storage, duration and hose allowance shall be inaccordance with Table 18.4(c) and Table 18.4(d) .
capable of providing flow for automatic sprinklers, hose streams, and foam systems (if provided) for the duration required inTable 12.8.6 .
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 17:56:31 EDT 2014
Committee Statement
CommitteeStatement:
These additions to Table 12.8.6.1 consolidate water supply information from chapters 18 and 19 into a single sourcein the general requirements for storage chapter for clarity.
ResponseMessage:
Public Comment No. 312-NFPA 13-2014 [Section No. 18.3]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
191 of 301 10/9/2014 8:39 AM
Second Revision No. 146-NFPA 13-2014 [ Section No. 18.4 ]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
192 of 301 10/9/2014 8:39 AM
18.4* Ceiling Systems.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
193 of 301 10/9/2014 8:39 AM
Sprinkler discharge and area of application shall be in accordance with one of the following:
(1) Table 18.4(a) or Table 18.4(b) for standard spray sprinklers
(2) Table 18.4(c) for CMSA sprinklers
(3) Table 18.4(d) for ESFR sprinklers
Table 18.4(a) Protection Criteria for Rubber Tire Storage Using Control Mode Density/Area Sprinklers
Piling Method
PileHeight
(ft)
Sprinkler Discharge Density
(gpm/ft2 over ft2)
(see Note 1)
Areas of Application (ft2)
(see Note 1)
OrdinaryTemperature
HighTemperature
(see Note 1)
(1) On-floor storage Up to 5 0.19 2000 2000
(a) Pyramid piles, on-sideOver 5 to12
0.30 2500 2500
(b) Other arrangements such that nohorizontal channels are formed (see Note 2)
Over 12 to18
0.60 Not allowed 2500
(2) On-floor storage Up to 5 0.19 2000 2000
Tires, on-treadOver 5 to12
0.30 2500 2500
(3) Palletized portable rack storage Up to 5 0.19 2000 2000
On-side or on-tread
Over 5 to20
See Table 18.4(b) — —
Over 20 to30
0.30 plus high-expansion foam 3000 3000
(4) Palletized portable rack storage, on-side
Up to 5 0.19 2000 2000
Over 5 to20
See Table 18.4(b) — —
Over 20 to25
0.60 and Not allowed 5000
0.90 (see Note 3) or Not allowed 3000
0.75 with 1-hour fire-resistiverating of roof and ceilingassembly
Not allowed 4000
(5) Open portable rack storage, on-side oron-tread
Up to 5 0.19 2000 2000
Over 5 to12
0.60 5000 3000
Over 12 to20
0.60 and Not allowed 5000
0.90 (see Note 3) or Not allowed 3000
0.30 plus high-expansion foam 3000 3000
(6) Open portable rack storage, lacedOver 12 to20
0.60 and Not allowed 5000
0.90 (see Notes 3 and 5) Not allowed 3000
(7) Single-, double-, and multiple-row fixedrack storage on pallets, on-side, or on-treadwithout shelves
Up to 5 0.19 2000 2000
Over 5 to20
See Table 18.4(b) or 0.40 plusone level in-rack sprinklers or
3000 3000
0.30 plus high-expansion foam 3000 3000
Over 20 to30
0.30 plus high-expansion foam Not allowed 3000
(8) Single-, double-, and multiple-row fixedrack storage without pallets or shelves,on-side or on-tread
Up to 5 0.19 2000 2000
Over 5 to12
0.60 5000 3000
0.40 plus one level in-racksprinklers
3000 3000
Over 12 to20
0.60 and Not allowed 5000
0.90 (see Note 3) or Not allowed 3000
0.40 plus one level in-racksprinklers or
3000 3000
0.30 plus high-expansion foam 3000 3000
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
194 of 301 10/9/2014 8:39 AM
Piling Method
PileHeight
(ft)
Sprinkler Discharge Density
(gpm/ft2 over ft2)
(see Note 1)
Areas of Application (ft2)
(see Note 1)
OrdinaryTemperature
HighTemperature
(see Note 1)
Over 20 to30
0.30 plus high-expansion foam Not allowed 3000
For SI units, 1 ft = 0.3048 m; 1 ft2 = 0.0929 m2; 1 gpm/ft2 = 40.746 mm/min.
Notes:
(1) Sprinkler discharge densities and areas of application are based on a maximum clearance to ceiling of 10 ft (3.1 m) with themaximum height of storage anticipated.
(2) Laced tires on-floor, vertical stacking on-side (typical truck tires), and off-road tires. Laced tires are not stored to a significantheight by this method due to the damage inflicted on the tire (i.e., bead).
(3) Water supply shall fulfill both requirements.
(4) Shelf storage of rubber tires shall be protected as solid rack shelving.
(5) This protection scheme is for use with K-16.8 (240) or larger control mode sprinklers only. Maximum clearance to ceilingcan be increased to 14 ft (4.25 m) with this scheme.
Table 18.4(b) Control Mode Density/Area Sprinklers System Density (gpm/ft2 over ft2) for Palletized Portable Rack Storageand Fixed Rack Storage of Rubber Tires with Pallets Over 5 ft (1.5 m) to 20 ft (6.1 m) in Height
Storage Height
(ft)
Sprinkler Temperature
High Temperature Ordinary Temperature
>5 to 10 0.32/2000 0.32/2000
>10 to 12 0.39/2000 0.39/2600
>12 to 14 0.45/2000 0.45/3200
>14 to 16 0.5/2300 0.5/3700
>16 to 18 0.55/2600 0.55/4400
>18 to 20 0.6/3000 0.6/5000
Table 18.4(c) Control Mode Specific Application (CMSA) Protection for Rubber Tires
Piling Method
MaximumStorageHeight
MaximumCeiling/Roof
Height K-FactorType ofSystem
Number ofSprinklers
OperatingPressure
HoseStream
Allowance
WaterSupply
Duration(hours)ft m ft m
Rubber tire storage,on-side or on-tread,in palletized portableracks, or openportable racks, orfixed racks withoutsolid shelves
25 7.6 32 9.8 11.2 (160) Wet 15
75 psi
(5.2 bar)
500 gpm
(1900 L/min) 3
25 7.6 32 9.816.8(240) Wet 15
35 psi
(2.4 bar)500 gpm
(1900 L/min) 3
Table 18.4(d) Early Suppression Fast-Response (ESFR) Sprinklers for Protection of Rubber Tires (see Note 1)
Piling MethodPile
Height
MaximumBuildingHeight
NominalK-factor
OrientationNumber ofSprinklers
MinimumOperatingPressure
(see Note 2)
Duration(hours)
HoseAllowance
ft m psi bar gpm L/min
Rubber tire storage,on-side or on-tread, inpalletized portableracks, open portableracks, or fixed rackswithout solid shelves
Up to 25ft
(7.6 m)
30 9.1
14.0
(200)
Upright/
pendent
12
(see Note 2)50 3.5 1 250 946
16.8
(240)
Upright/
pendent
12
(see Note 2)35 2.4 1 250 946
22.4
(320)Pendent
12
(see Note 2)25 1.7 1 250 946
25.2 (360) Pendent12
(see Note 2)15 1.0 1 250 946
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
On-tread, on-side,and laced tires inopen portable steelracks or palletizedportable racks
Up to 25ft (7.6 m)
30 9.1
14.0
(200)Pendent
20
(see Notes 3and 4)
75 5.2 3 500 1900
16.8
(240)Pendent
20
(see Notes 3and 4)
52 3.6
Rubber tire storage,on-side, in palletizedportable racks
Up to 25ft (7.6 m)
40 12.2
1 250 946
16.8
(240)Pendent 12 52 3.6
Rubber tire storage,on-tread, or laced inopen portable steelracks
Up to 25ft (7.6 m)
40 12.225.2
(360)Pendent 12 40 2.8 1 250 946
On-tread, on-side,and laced tires inopen portable steelracks or palletizedportable racks
Up to 30ft (9.1 m)
40 12.225.2
(360)Pendent 12 75 5.2 1 250 946
Notes:
(1) Wet systems only.
(2) The shape of the design area shall be in accordance with 14.4.3 and 14.4.4 .
(3) Where used in this application, ESFR protection is expected to control rather than to suppress the fire.
(4) The design area shall consist of the most hydraulically demanding area of 20 sprinklers, consisting of five sprinklers on
each of four branch lines. The design shall include a minimum operating area of 1600 ft2 (149 m2).
Supplemental Information
File Name Description
Table_18.4_c_and_d_with_edits_SR_146_.pdf Table 18.4(c) and Table 18.4(d) with edits (8/14 BI)
Submitter Information Verification
Submitter Full Name: Matthew Klaus
Organization: National Fire Protection Assoc
Street Address:
City:
State:
Zip:
Submittal Date: Tue Jul 01 09:29:34 EDT 2014
Committee Statement
CommitteeStatement:
These additions to Table 12.8.6.1 consolidate water supply information from chapters 18 and 19 into a single sourcein the general requirements for storage chapter for clarity.
(Last two columns of Table 18.4(c) and last three columns of Table 18.4.(d) deleted -- moved to Table 12.8.6)
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
196 of 301 10/9/2014 8:39 AM
ResponseMessage:
Public Comment No. 313-NFPA 13-2014 [Section No. 18.4]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
197 of 301 10/9/2014 8:39 AM
bingalls
Line
bingalls
Text Box
insert period after "14.4.3" and deleted "14.4.4."
bingalls
Text Box
delete last 2 columns of Table 18.4(c)
bingalls
Text Box
delete last 3 columns of Table 18.4(d)
Second Revision No. 105-NFPA 13-2014 [ Section No. 19.1.1.1 ]
19.1.1.1
The water supply system for automatic fire protection systems shall be designed for a minimum duration of 2 hours.
19.1.1.1.1
For ESFR sprinklers, the water supply duration shall be 1 hour.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 17:55:52 EDT 2014
Committee Statement
CommitteeStatement:
These additions to Table 12.8.6.1 consolidate water supply information from chapters 18 and 19 into a single sourcein the general requirements for storage chapter for clarity.
ResponseMessage:
Public Comment No. 314-NFPA 13-2014 [Section No. 19.1.1.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
198 of 301 10/9/2014 8:39 AM
Second Revision No. 104-NFPA 13-2014 [ Section No. 19.1.1.2 ]
19.1.1.2
At least 500 gpm (1900 L/min) shall be added to the sprinkler demand for large and small hose stream allowance.
19.1.1.2.1
For ESFR sprinklers, the hose stream allowance shall be for 250 gpm (946 L/min).
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 17:55:29 EDT 2014
Committee Statement
CommitteeStatement:
These additions to Table 12.8.6.1 consolidate water supply information from chapters 18 and 19 into a single sourcein the general requirements for storage chapter for clarity.
ResponseMessage:
Public Comment No. 315-NFPA 13-2014 [Section No. 19.1.1.2]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
199 of 301 10/9/2014 8:39 AM
Second Revision No. 103-NFPA 13-2014 [ Section No. 19.1.1.3 ]
19.1.1.1
The water supply design shall include the demand of the automatic sprinkler system plus the hose stream allowance plus,where provided, the high-expansion foam system for the duration specified in Table 12.8.6 .
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 17:55:09 EDT 2014
Committee Statement
CommitteeStatement:
These additions to Table 12.8.6.1 consolidate water supply information from chapters 18 and 19 into a single sourcein the general requirements for storage chapter for clarity.
ResponseMessage:
Public Comment No. 316-NFPA 13-2014 [Section No. 19.1.1.3]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
200 of 301 10/9/2014 8:39 AM
Second Revision No. 129-NFPA 13-2014 [ Section No. 20.5.6.4 ]
20.5.6.4
Sprinklers shall be provided in transverse flue spaces in accordance with 20.5.6.4.1 through 20.5.6.4.3.1 and Figure 20.5.6.4.
Figure 20.5.6.4 Sprinkler Location and Spacing in Transverse Flues.
20.5.6.4.1
For double- and multiple-row racks, in-rack sprinklers shall be installed in the transverse flues at each catwalk level and shallbe staggered vertically. For single-row racks, in-rack sprinklers shall be installed in the transverse flue at each catwalk level.
20.5.6.4.2
For double- and multiple-row racks sprinklers installed in the transverse flues shall be located not less than 18 in. (0.46 m) butnot greater than 24 in. (0.61 m) from the face of the rack on the catwalk side.
20.5.6.4.3
For single-row racks, sprinklers installed in the transverse flues shall be staggered horizontally such that the sprinkler at firstlevel is not less than 18 in. (0.46 m) but not greater than 24 in. (0.61 m) from the face of the rack on the catwalk side.
20.5.6.4.3.1
At the next level the sprinkler in the transverse flue shall be located not less than 6 in. (0.15 m) but not greater than 12 in. (0.30m) from the back face of the rack. This staggering shall be repeated throughout all catwalk levels.
20.5.6.4.4
In-rack sprinklers shall be installed a minimum 6 in. (150 mm) above the top of storage.
20.5.6.4.5
Transverse flue sprinklers shall be quick-response, ordinary temperature, nominal K-5.6 (80), K-8.0 (115), or K-11.2 (160) andinstalled in accordance with Figure A.20.5.6.3.5(a) and Figure A.20.5.6.3.5(b).
Supplemental Information
File Name Description
FR_226_sketch.pdf
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Jun 27 19:24:53 EDT 2014
Committee Statement
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
201 of 301 10/9/2014 8:39 AM
Committee Statement: The lines on the rack drawing shown in the first draft do not show up as shown in FR 226.
Response Message:
Public Comment No. 174-NFPA 13-2014 [Section No. 20.5.6.4]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
202 of 301 10/9/2014 8:39 AM
PLAN VIEW
Sprinkler on odd level
Sprinkler on even level
18-24"
10'-6" Max.
Transverse Flue Sprinkler
6-12"
Second Revision No. 109-NFPA 13-2014 [ Section No. 21.1.2 ]
21.1.2
The requirements of Chapters 12 through 20 shall apply unless modified by this chapter.
21.1.2.1
Sprinklers having standard coverage areas that require up to 20 sprinklers to be included in the hydraulic calculation shall beinstalled in accordance with 8.4.6.2 , 8.4.6.3 , 8.4.6.3.1 and 12.1.1 .
21.1.2.1.1
Quick-response sprinklers shall also be installed in accordance with 8.4.6.4.1 and 8.4.6.4.2 .
21.1.2.2
Sprinklers having extended coverage areas that require up to 10 sprinklers to be included in the hydraulic calculation shall beinstalled in accordance with 8.4.6.2 , 8.4.6.3 , 8.4.6.3.1 and 12.1.1 .
21.1.2.2.1
Quick-response sprinklers shall also be installed in accordance with 8.4.6.4.1 and 8.4.6.4.2 .
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 18:25:36 EDT 2014
Committee Statement
CommitteeStatement:
This revision is in response to the request from the correlating to address th eother design requirements and theirapplicability to the design protocol in Ch 21.
ResponseMessage:
Public Comment No. 229-NFPA 13-2014 [Section No. 21.5.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
203 of 301 10/9/2014 8:39 AM
Second Revision No. 148-NFPA 13-2014 [ New Section after 21.3.1 ]
21.3.2
Protection of Class I through Class IV and cartoned unexpanded plastic commodities stored on single-, double-, ormultiple-row racks without solid shelves or solid-piled, palletized, shelf, or bin-box storage arrangements shall be permitted tobe protected in accordance with Table 21.3.2 .
Table 21.3.2 CMSA K-25.2 Upright Standard Coverage Sprinkler Design Criteria for Single-, Double-, and Multiple-RowRacks Without Solid Shelves and Solid-Piled, Palletized Storage Arrangement of Class I Through IV and CartonedUnexpanded Plastic Commodities
StorageArrangement Commodity
Class
MaximumStorageHeight
MaximumCeiling/Roof
HeightK-Factor
OrientationSystemType
Numberof Design
Sprinklers
MinimumOperatingPressure
SprinklerLinear
Spacing
SprinklerArea Spacing
ft m ft m Min Max Min Max
Solid-piled,palletized, and
single-,double-, andmultiple-rowracks withoutsolid shelves(no open topcontainers)
Class I–IVencapsulated
andnonencapsulated,
and cartonednonexpanded
plastics
25 7.6 30 9.125.2 (360)
UprightWet 12
20 psi (1.4bar)
8 ft(2.4m)
12 ft(3.6m)
80 ft 2
(7.5m 2 )
100
ft 2
(9.0
m 2 )
Supplemental Information
File Name Description
Pages_from_13_PC_353_CREATE_SR_.pdf
SR_148_Table.docx
Submitter Information Verification
Submitter Full Name: Matthew Klaus
Organization: National Fire Protection Assoc
Street Address:
City:
State:
Zip:
Submittal Date: Wed Jul 02 07:05:18 EDT 2014
Committee Statement
CommitteeStatement:
New sprinkler design criteria to be included in the alternative storage design chapter of NFPA 13. This data has beenadded based on the testing conducted and summarized in PC 353.
ResponseMessage:
Public Comment No. 353-NFPA 13-2014 [New Section after 21.3.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
204 of 301 10/9/2014 8:39 AM
Table 21.3.x CMSA K 25.2 Upright Standard Coverage Sprinkler Design Criteria for Single-, double-, and multiple-row racks without solid shelves;
and solid-piled, palletized, shelf, or bin-box storage arrangementof Class I Through Class IV and Cartoned Unexpanded Plastic Commodities
21.3.2 CMSA K‐25.2 Upright Standard Coverage Sprinkler Design Criteria for Single‐, double‐ and multiple‐row racks without solid shelves; and
solid‐piled, palletized storage arrangement of Class I Through IV and Cartoned Unexpanded Plastic Commodities
Storage Arrangement
Commodity Class
Max Storage Height
Max Ceiling/Roof Height
K‐Factor Orientation
System Type
Number of Design Sprinklers
Min Operating Pressure
Sprinkler Linear Spacing
Sprinkler Area Spacing
Solid‐piled, palletized, and Single‐, double‐, and multiple‐row racks without solid shelves(no open top comtainers)
Class I‐IV encapsulated and nonencapsulated, and cartoned nonexpanded plastics
Ft M Ft M 25.2 (360) Upright
Wet 12 20 psi(1.4 bar)
Min Max Min max
25 7.6 30 9.1 8 ft(2.4m)
12 ft(3.6m)
80 ft2(7.5m2
)
100 ft2(9.0m2)
Second Revision No. 149-NFPA 13-2014 [ New Section after 21.3.1 ]
21.3.3
Protection of Class I through Class IV and cartoned unexpanded plastic commodities stored on single-, double-, ormultiple-row racks without solid shelves or solid-piled, palletized, shelf, or bin-box storage arrangements shall be permitted tobe protected in accordance with Table 21.3.3 .
Table 21.3.3 CMSA K-25.2 Pendent Standard Coverage Sprinkler Design Criteria for Single-, Double-, and Multiple-RowRacks Without Solid Shelves and Solid-Piled, Palletized Storage Arrangement of Class I Through IV and CartonedUnexpanded Plastic Commodities
StorageArrangement
CommodityClass
MaximumStorageHeight
MaximumCeiling/Roof
HeightK-Factor
OrientationSystemType
Numberof Design
Sprinklers
MinimumOperatingPressure
SprinklerLinear
Spacing
SprinklerArea Spacing
ft m ft m Min Max Min Max
Solid-piled,palletized, and
single-,double-, andmultiple-rowracks withoutsolid shelves(no open topcontainers)
Class I–IVencapsulated
andnonencapsulated,
and cartonednonexpanded
plastics
25 7.6 30 9.125.2 (360)Pendent
Wet 1215psi (1.0
bar)8 ft
(2.4m)
12 ft(3.6m)
80 ft 2
(7.5m 2 )
100
ft 2
(9.0
m 2 )
Supplemental Information
File Name Description
Storage_TG_13_PC_358_CREATE_SR_.pdf
SR_149_Table.docx
Submitter Information Verification
Submitter Full Name: Matthew Klaus
Organization: National Fire Protection Assoc
Street Address:
City:
State:
Zip:
Submittal Date: Wed Jul 02 07:11:59 EDT 2014
Committee Statement
CommitteeStatement:
New sprinkler design criteria to be included in the alternative storage design chapter of NFPA 13. This data has beenadded based on the testing conducted and summarized in PC 358.
ResponseMessage:
Public Comment No. 358-NFPA 13-2014 [New Section after 21.3.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
205 of 301 10/9/2014 8:39 AM
Table 21.3.x CMSA K 25.2 Upright Standard Coverage Sprinkler Design Criteria for Single-, double-, and multiple-row racks without solid shelves;
and solid-piled, palletized, shelf, or bin-box storage arrangementof Class I Through Class IV and Cartoned Unexpanded Plastic Commodities
21.3.2 CMSA K‐25.2 Upright Standard Coverage Sprinkler Design Criteria for Single‐, double‐ and multiple‐row racks without solid shelves; and
solid‐piled, palletized storage arrangement of Class I Through IV and Cartoned Unexpanded Plastic Commodities
Storage Arrangement
Commodity Class
Max Storage Height
Max Ceiling/Roof Height
K‐Factor Orientation
System Type
Number of Design Sprinklers
Min Operating Pressure
Sprinkler Linear Spacing
Sprinkler Area Spacing
Solid‐piled, palletized, and Single‐, double‐, and multiple‐row racks without solid shelves(no open top comtainers)
Class I‐IV encapsulated and nonencapsulated, and cartoned nonexpanded plastics
Ft M Ft M 25.2 (360) Upright
Wet 12 15psi (1.0 bar)
Min Max Min max
25 7.6 30 9.1 8 ft (2.4m)
12ft(3.6m)
80 ft2(7.5m2)
100 ft2(9.0m2)
Second Revision No. 112-NFPA 13-2014 [ Section No. 23.3.5 ]
23.3.5 Computer-Generated Hydraulic Reports.
23.3.5.1* General.
23.3.5.1.1
Hydraulic calculations shall be prepared on form sheets that include a summary sheet, a graph sheet, a water supply analysis,a node analysis, and detailed worksheets.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
206 of 301 10/9/2014 8:39 AM
23.3.5.1.2
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
207 of 301 10/9/2014 8:39 AM
The data shall be presented in the order shown in Figure 23.3.5.1.2(a) through Figure 23.3.5.1.2(d).
Figure 23.3.5.1.2(a) Summary Sheet.
Figure 23.3.5.1.2(b) Graph Sheet.
Figure 23.3.5.1.2(c) Supply and Node Analysis Sheet.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
208 of 301 10/9/2014 8:39 AM
Figure 23.3.5.1.2(d) Detailed Worksheet.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
209 of 301 10/9/2014 8:39 AM
23.3.5.2 Summary Sheet.
The summary sheet as shown in Figure 23.3.5.1.2(a) shall contain the following information, where applicable:
(1) Project name and date
(2) Location (including street address)
(3) Owner or expected occupant of space being designed
(4) Name, address, and phone number of installing contractor
(5) Name and phone number of designer
(6) Authority having jurisdiction
(7) Standard or document system is being designed to, including the edition of the document
(8) Design area number and location
(9) Drawing or sheet number where design area is located
(10) Occupancy or commodity classification and information
(11) For storage applications (including miscellaneous), additional information including storage height, ceiling height, storageconfiguration, aisle width, orientation of upright or pendent, sprinkler K-factor and sprinkler temperature, and the table andor curve utilized in the design
(12) System type, including the system volume with type of protection system indicated in the notes
(13) Sprinkler type, including coverage and response type.
(14) Slope of roof or ceiling within the design area
(15) System design requirements, as follows:
(a) Design area of application, ft2 (m2)
(b) Minimum rate of water application (density), gpm/ft2 (mm/min)
(c) Area per sprinkler, ft2 (m2)
(d) Number of sprinklers calculated
(16) Total water requirements as calculated, including allowance for inside hose, outside hydrants, water curtain, and exposuresprinklers, and allowance for in-rack sprinklers, gpm (L/min)
(17) Ceiling height if used for quick response sprinkler reduction
(18) Elevation of highest calculated sprinkler
(19) Water supply information, including the following:
(a) Date and time of test
(b) Location of the test and flow hydrant(s)
(c) Source of the water for the flow test
(d) Elevation of the test hydrant relative to the finished floor
(e) Size of fire pump, gpm @ psi
(f) Size of on-site water tank
(20) Notes that include peaking information for calculations performed by a computer program, type of preaction system,limitations (dimension, flow, and pressure) on extended-coverage or other listed special sprinklers, system type, includingthe system volume
23.3.5.3 Graph Sheet.
A graphic representation of the complete hydraulic calculation shall be plotted on semiexponential graph paper (Q1.85) asshown in Figure 23.3.5.1.2(b) and shall include the following:
(1) Water supply curve
(2) Sprinkler system demand
(3) Hose demand (where applicable)
(4) In-rack sprinkler demand (where applicable)
(5) Additional pressures supplied by a fire pump or other source (when applicable)
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
210 of 301 10/9/2014 8:39 AM
23.3.5.4 Supply Analysis.
Information summarized from the graph sheet as shown in Figure 23.3.5.1.2(c) shall include the following:
(1) Node tag at the source
(2) Static pressure [psi (bar)] available at the source
(3) Residual pressure [psi (bar)] available at the source
(4) Total flow [gpm (L/min)] available at the source
(5) Available pressure [psi (bar)] at the source when the total calculated demand is flowing
(6) Total calculated demand [gpm (L/min)] at the source
(7) Required pressure [psi (bar)] when flowing total calculated demand
23.3.5.5 Node Analysis.
Organized information as shown in Figure 23.3.5.1.2(c) regarding the node tags given to each hydraulic reference point on thesystem as indicated on the shop drawings shall include the following information:
(1) Node tag for each specific point on the system used in the hydraulic calculations
(2) Elevation in ft (m) of each node tag
(3) K-factor of flowing nodes (such as sprinklers)
(4) Hose allowance in gpm (L/min) requirements for the node tag
(5) Pressure in psi (bar) at the node
(6) Discharge in gpm (L/min) calculated at the node
(7) Notes that indicate any special requirements for the node
23.3.5.6 Detailed Worksheets.
Detailed worksheets as shown in Figure 23.3.5.1.2(d) or computer printout sheets shall contain the following information:
(1) Sheet number
(2) Hydraulic reference points used in each step
(3) Elevation in ft (m) at each hydraulic reference point
(4) Sprinkler description and discharge constant (K) for the flowing reference point
(5) Flow in gpm (L/min) for the flowing reference point (when applicable)
(6) Total flow in gpm (L/min) through each step
(7) Nominal pipe size in in. (mm)
(8) Actual internal diameter of pipe in in. (mm)
(9) Quantity and length in ft (m) of each type of fitting and device
(10) Pipe lengths in ft (m), center-to-center of fittings
(11) Equivalent pipe lengths in ft (m) of fittings and devices for the step
(12) Total equivalent length in ft (m) of pipes and fitting for the step
(13) C-factor used in each step
(14) Friction loss in psi/ft (bar/m) of pipe
(15) Sum of the pressures from the previous step (starting pressure at beginning)
(16) Elevation head in psi (bar) between reference points
(17) Total friction loss in psi (bar) between reference points
(18) Required pressure in psi (bar) at each reference point
(19) Notes and other information shall include the following:
(a) Velocity pressure and normal pressure if included in calculations
(b) In-rack sprinkler demand balanced to ceiling demand
(c) Notes to indicate starting points or reference to other sheets or to clarify data shown
(d) Diagram to accompany gridded system calculations to indicate flow quantities and directions for lines with sprinklersoperating in the remote area
(e) Combined K-factor calculations for sprinklers on drops, armovers, or sprigs where calculations do not begin at thesprinkler
(f) The pressure [psi/(bar)] loss assigned the backflow device when included on a system
(g) Friction factor and Reynold's number when the Darcy–Weisbach equation is used
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
211 of 301 10/9/2014 8:39 AM
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Jun 27 13:32:46 EDT 2014
Committee Statement
CommitteeStatement:
The standard forms for manual calculations and computer generated forms should be combined. There is no need tohave separate reports for hand calculations versus computer generated calculations.
ResponseMessage:
Public Comment No. 303-NFPA 13-2014 [Section No. 23.3.5]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
212 of 301 10/9/2014 8:39 AM
Second Revision No. 113-NFPA 13-2014 [ Section No. 23.4.1.2 ]
23.4.1.2
Pipe sizes shall be no less than 1 in. (25 mm) nominal for ferrous for black or galvanized steel piping and 3⁄4 in. (20 mm)nominal for copper tubing or brass, stainless steel, or nonmetallic piping listed for fire sprinkler service unless permitted by8.15.20.4 and 8.15.20.5.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Jun 27 13:33:43 EDT 2014
Committee Statement
CommitteeStatement:
As per Section 6.3, brass and stainless steel piping is now recognized in the standard. Therefore, this section shouldbe further modified to indicate the minimum allowable pipe sizes for those materials as well.
ResponseMessage:
Public Comment No. 175-NFPA 13-2014 [Section No. 23.4.1.2]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
213 of 301 10/9/2014 8:39 AM
Second Revision No. 114-NFPA 13-2014 [ Section No. 23.4.1.4 ]
23.4.1.4* Velocity Limitations.
Unless required by other NFPA standards, the velocity of water flow shall not be limited when hydraulic calculations areperformed using the Hazen Williams and/ or Darcy Weisbach formulas.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Jun 27 13:34:38 EDT 2014
Committee Statement
CommitteeStatement:
Editorial deleting the "and/or". Also, a title should not be provided for this paragraph unless it titles are provided forthe other paragraphs at this same level in the numbering system.
ResponseMessage:
Public Comment No. 339-NFPA 13-2014 [Section No. 23.4.1.4]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
214 of 301 10/9/2014 8:39 AM
Second Revision No. 115-NFPA 13-2014 [ Section No. 23.7.2.6 ]
23.7.2.6*
Where the total number of sprinklers above and below a ceiling exceeds the number specified in Table 23.7.2.4 Table23.7.2.2.1 for 21⁄2 in. (64 mm) pipe, the pipe supplying such sprinklers shall be increased to 3 in. (76 mm) and sized thereafteraccording to the schedule shown in Table 23.7.2.2.1 Table 23.7.2.4 for the number of sprinklers above or below a ceiling,whichever is larger.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Jun 27 13:44:45 EDT 2014
Committee Statement
CommitteeStatement:
As noted in the Committee Statement, the existing code section incorrectly references Table 23.5.2.2.1 instead of Table23.5.2.4. However, the agreed to change to the text was not implemented into the First Draft Report. Since Section 23.5was moved to 23.7, the text should now be revised to reference Table 23.7.2.4.
ResponseMessage:
Public Comment No. 176-NFPA 13-2014 [Section No. 23.7.2.6]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
215 of 301 10/9/2014 8:39 AM
Second Revision No. 116-NFPA 13-2014 [ Section No. 24.1.3.3 ]
24.1.3.3
For new systems to be supplied by Where a single main less than 4 in. (100 mm) in diameter , which will serve both domesticand serves both fire systems, the domestic and other uses, the non-fire demand shall be added to the hydraulic calculationsfor the fire system at the point of connection unless provisions have been made to automatically isolate the domesticdemand the non-fire demand during a fire event .
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Jun 27 13:52:10 EDT 2014
Committee Statement
CommitteeStatement:
This language simplifies the distinction between fire system water demand and all other water demands servedby a single main.
Response Message:
Public Comment No. 98-NFPA 13-2014 [Section No. 24.1.3.3]
Public Comment No. 178-NFPA 13-2014 [Section No. 24.1.3.3]
Public Comment No. 296-NFPA 13-2014 [Section No. 24.1.3.3]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
216 of 301 10/9/2014 8:39 AM
Second Revision No. 126-NFPA 13-2014 [ Section No. A.5.3.1 ]
A.5.3.1
Ordinary hazard (Group 1) occupancies include occupancies having uses and conditions similar to the following:
(1) Automobile parking and showrooms
(2) Bakeries
(3) Beverage manufacturing
(4) Canneries
(5) Dairy products manufacturing and processing
(6) Electronic plants
(7) Glass and glass products manufacturing
(8) Laundries
(9) Restaurant service areas
(10) Porte cocheres
(11) Mechanical rooms with stockpiles up to 8 ft (2.4 m)
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Jun 27 18:50:42 EDT 2014
Committee Statement
CommitteeStatement:
As proposed, new Sentence (11) says "Mechanical rooms with stockpiles up to 8 ft (2.4 m)", but as per the NFPA 1 FireCode, Section 10.19.5.1, "Combustible material shall not be stored in boiler rooms, mechanical rooms, or electricalrooms". Therefore, the reference to 8 ft stockpiles must be deleted. NFPA 13 should not be implying that it may be alrightto put storage into any such service rooms.
ResponseMessage:
Public Comment No. 181-NFPA 13-2014 [Section No. A.5.3.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
223 of 301 10/9/2014 8:39 AM
Second Revision No. 127-NFPA 13-2014 [ Section No. A.5.4.2 ]
A.5.4.2
Extra hazard (Group 2) occupancies include occupancies having uses and conditions similar to the following:
(1) Asphalt saturating
(2) Flammable liquids spraying
(3) Flow coating
(4) Manufactured home or modular building assemblies (where finished enclosure is present and has combustible interiors)
(5) Open oil quenching
(6) Plastics manufacturing
(7) Solvent cleaning
(8) Varnish and paint dipping
(9) Car stackers and car lift systems with 2 cars stacked vertically
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Jun 27 19:02:10 EDT 2014
Committee Statement
CommitteeStatement:
The parking garage can be reasonably protected with sprinklers only at the ceiling if the hazard classification is increasedto Extra Hazard Group 2. The definition of Extra Hazard Group 2 includes, “occupancies where shielding of combustibles isextensive” (Section 5.4.2 of the 2013 edition of NFPA 13). The basic concept in this section is that hazards that wouldnormally be classified as Ordinary Hazard can be protected with sprinklers only at the ceiling by increasing the density andarea of coverage, and by decreasing the sprinkler spacing, in accordance with the Extra Hazard rules. Examples of suchsituations include factories where manufactured homes are built. During the process of building a manufactured home,sprinkler protection is not extended down inside the manufactured home, but sprinklers at the roof of the factory areexpected to control any fire, including one starting inside a home being manufactured. By upgrading the design basis of thesprinkler system to Extra Hazard Group 2 (increasing the density by 167% and increasing the area of operation by 67%) thesprinkler system is expected to handle the additional challenge of a shielded fire (see A.5.4.2 of the 2013 edition), andshould be sufficient to handle the fuel load of two cars (one above another), preventing the fire from spreading to theadjacent cars while maintaining acceptable conditions for the structural members within the structure.
ResponseMessage:
Public Comment No. 310-NFPA 13-2014 [Section No. A.5.4.2]
Public Comment No. 201-NFPA 13-2014 [Section No. A.5.4.1]
Public Comment No. 245-NFPA 13-2014 [Section No. A.5.3.2]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
224 of 301 10/9/2014 8:39 AM
Second Revision No. 135-NFPA 13-2014 [ Section No. A.5.6 ]
A.5.6
Specification of the type, amount, and arrangement of combustibles for any commodity classification is essentially an attemptto define the potential fire severity, based on its burning characteristics, so the fire can be successfully controlled by theprescribed sprinkler protection for the commodity class. In actual storage situations, however, many storage arrays do not fitprecisely into one of the fundamental classifications; therefore, the user needs to make judgments after comparing eachclassification to the existing storage conditions. Storage arrays consist of thousands of products, which makes it impossible tospecify all the acceptable variations for any class. As an alternative, a variety of common products are classified in this annexbased on judgment, loss experience, and fire test results.
Table A.5.6 provides examples of commodities not addressed by the classifications in Section 5.6. The commodities listed inTable A.5.6 are outside of the scope of NFPA 13 protection.
Table A.5.6.3 is an alphabetized list of commodities with corresponding classifications.
Table A.5.6.3 through Table A.5.6.3.4 and Table A.5.6.4.1 provide examples of commodities within a specific class.
Table A.5.6 Examples of Commodities Not Addressed by Classifications in Section 5.6
Ammunition components Components
- Bulk Primers primers and powder
Batteries
- Lithium and other similar exotic metals - Lithium-ion and other rechargeable batteries that contain combustibleelectrolyte
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
225 of 301 10/9/2014 8:39 AM
Committee Statement: Table A.5.6 has been updated based on the review by the commodity classification task group.
Response Message:
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
226 of 301 10/9/2014 8:39 AM
Second Revision No. 134-NFPA 13-2014 [ Section No. A.5.6.1.1 ]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
227 of 301 10/9/2014 8:39 AM
A.5.6.1.1
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
228 of 301 10/9/2014 8:39 AM
Commodity classification is governed by the types and amounts of materials (e.g., metal, paper, wood, plastics) that are a partof a product and its primary packaging. Consideration of all characteristics of the individual storage units, not just the product, iscritical to identify the appropriate commodity classification. Refer to Table A.5.6.1.1 for general guidance for classifyingcommodities. For situations where it is difficult to determine the appropriate classification, testing should be considered toappropriately characterize the commodity.
Table A.5.6.1.1 General Guide to Identifying the Commodity Class for Solid Combustibles
Characteristics of Unit Load Commodity Class1
Material Used to Construct Product Packaging Material PalletMaterial
Noncombustible Product
Entirely noncombustibleNone or single layer single-layercorrugated cartons
None, metal,or wood
Class I
Entirely noncombustibleMultiple-layered corrugated cartons,wooden crates, or wood boxes
None, metal,or wood
Class II
Noncombustible with Group A plasticcomponents
None or single layer corrugated cartonsNone, metal,or wood
See Figure 5.6.3.4.1
Entirely noncombustible or noncombustiblewith plastic components
Corrugated cartons, wooden crates, orwood boxes, with plastic packaging
None, metal,or wood
See Figure 5.6.3.4.1
Entirely noncombustible or noncombustiblewith plastic components
Any type PlasticSee 5.6.2 and Figure5.6.3.4.1
Wood, Paper, Natural Fibers or Group CPlastics
Entirely wood, paper, natural fibers, orGroup C plastics
None, corrugated cartons, woodencrates, or wood boxes
None, metal,or wood
Class III
Entirely wood, paper, natural fibers, orGroup C plastics
Corrugated cartons, wooden crates, orwood boxes, with plastic packaging
None, metal,or wood
See Figure 5.6.3.4.1
Wood, paper, natural fibers, or Group Cplastics, with Group A plastic components
None, corrugated cartons, woodencrates, or wood boxes with or withoutplastic packaging
None, metal,or wood
See Figure 5.6.3.4.1
Wood, paper, natural fibers, or Group Cplastics, with or without Group A plasticcomponents
Any type PlasticSee 5.6.2 and Figure5.6.3.4.1
Group B Plastics
Entirely Group B plastics or free- flowingplastic materials
None, corrugated cartons, woodencrates, or wood boxes
None, metal,or wood
Class IV
Entirely Group B plastics or free- flowingplastic materials
Corrugated cartons, wooden crates, orwood boxes, with plastic packaging
None, metal,or wood
See Figure5.6.3.4.1 See Figure5.6.3.4
Group B plastics with Group A plasticcomponents
None, corrugated cartons, woodencrates, or wood boxes, with or withoutplastic packaging
None, metal,or wood
See Figure5.6.3.4.1 See Figure5.6.3.4
Entirely Group B plastics or free flowingplastic materials, or Group B plastics andGroup A plastic components
Any type PlasticSee 5.6.2 and Figure5.6.3.4.1
Group A Plastics
Entirely unexpanded Group A plasticCorrugated cartons, wooden crates, orwood boxes, without expanded Group Aplastic packaging
None, metal,wood, orplastic
Cartoned unexpandedGroup A Plastic plastic
Entirely unexpanded Group A plastic NoneNone, metal,wood, orplastic
Exposed unexpandedGroup A Plastic plastic
Entirely unexpanded Group A plasticCorrugated cartons, wooden crates, orwood boxes, with expanded Group Aplastic packaging
None, metal,wood, orplastic
See Figure 5.6.3.4.1
Unexpanded Group A plastic with expandedGroup A plastic components
Corrugated cartons, wooden crates, orwood boxes, with or without expandedGroup A plastic packaging
None, metal,wood, orplastic
See Figure 5.6.3.4.1
Unexpanded Group A plastic withexpanded Group A plastic components
NoneNone, metal,wood, orplastic
See 5.6.4.4.2
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
229 of 301 10/9/2014 8:39 AM
Characteristics of Unit Load Commodity Class1
Material Used to Construct Product Packaging Material PalletMaterial
Expanded Group A plasticCorrugated cartons, wooden crates, orwood boxes, with or without expandedGroup A plastic packaging
None, metal,wood, orplastic
Cartoned expandedGroup A Plastic plastic
Expanded Group A plastic NoneNone, metal,wood, orplastic
Exposed expandedGroup A Plastic plastic
Note: This table provides guidance for the general characteristics to be considered in classifying a commodity. The additionalcommodity classification information included in this standard as well as any relevant test data that is available should beconsidered in identifying the appropriate classification.
Supplemental Information
File Name Description
Table_A.5.6.1.1_SR_134_edited.1408103761883.xlsx
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Mon Jun 30 07:57:25 EDT 2014
Committee Statement
Committee Statement: Table A.5.6.1.1 has been revised to correlate with the changes made to Table A.5.6.3
Response Message:
Public Comment No. 182-NFPA 13-2014 [Section No. A.5.6.1.1]
Public Comment No. 198-NFPA 13-2014 [Section No. A.5.6]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
230 of 301 10/9/2014 8:39 AM
Material Used to Construct Product Packaging Material Pallet Material
Entirely noncombustible None or single-layer corrugated cartons None, metal, or wood Class I
Entirely noncombustible Multiple-layered corrugated cartons, wooden crates, or
wood boxes
None, metal, or wood Class II
Noncombustible with Group A plastic components None or single-layer corrugated cartons None, metal, or wood See Figure 5.6.3.4
Entirely noncombustible or noncombustible with plastic
components
Corrugated cartons, wooden crates, or wood boxes,
with plastic packing
None, metal, or wood See Figure 5.6.3.4
Entirely noncombustible or noncombustible with plastic
components
Any type Plastic See Figure 5.6.3.4
Entirely wood, paper, natural fibers, or Group C plastics None, corrugated cartons, wooden crates, or wood
boxes
None, metal, or wood Class III
Entirely wood, paper, natural fibers, or Group C plastics Corrugated cartons, wooden crates, or wood boxes,
with plastic packing
None, metal, or wood See Figure 5.6.3.4
Wood, paper, natural fibers, or Group C plastics, with Group A
plastic components
None, corrugated cartons, wooden crates, or wood
boxes, with or without plastic packing
None, metal, or wood See Figure 5.6.3.4
Wood, paper, natural fibers, or Group C plastics, with or
without Group A plastic components
Any type Plastic See Figure 5.6.3.4
Entirely Group B plastics or free-flowing plastic materials None, corrugated cartons, wooden crates, or wood
boxes
None, metal, or wood Class IV
Entirely Group B plastics or free-flowing plastic materials Corrugated cartons, wooden crates, or wood boxes,
with plastic packing
None, metal, or wood See Figure 5.6.3.4
Group B plastics with Group A plastic components None, corrugated cartons, wooden crates, or wood
boxes, with or without plastic packing
None, metal, or wood See Figure 5.6.3.4
Entirely Group B plastics or free-flowing plastic materials, or
Group B plastics with Group A plastic components
Any type Plastic See 5.6.2 and See Figure 5.6.3.4
Entirely unexpanded Group A plastic Corrugated cartons, wooden crates, or wood boxes,
without expanded Group A plastic packing
None, metal, wood, or
plastic
Cartoned unexpanded Group A plastic
Entirely unexpanded Group A plastic None None, metal, wood, or
plastic
Exposed unexpanded Group A plastic
Entirely unexpanded Group A plastic Corrugated cartons, wooden crates, or wood boxes,
with expanded Group A plastic packing
None, metal, wood, or
plastic
See 5.6.4.4.1
Unexpanded Group A plastic with expanded Group A plastic
components
Corrugated cartons, wooden crates, or wood boxes,
with or without expanded Group A plastic packing
None, metal, wood, or
plastic
See 5.6.4.4.1
Unexpanded Group A plastic with expanded Group A plastic
components
None None, metal, wood, or
plastic
See 5.6.4.4.2
Expanded Group A plastic Corrugated cartons, wooden crates, or wood boxes,
with or without expanded Group A plastic packing
None, metal, wood, or
plastic
Cartoned expanded Group A plastic
Expanded Group A plastic None None, metal, wood, or
plastic
Exposed expanded Group A plastic
Table A.5.6.1.1 General Guide to Identifying the Commodity Class for Solid Combustibles
Characteristics of Unit Load
Commodity Class1
Note:1 This table provides guidance for the general characteristics to be considered in classifying a commodity. The additional commodity classifcation information included in this standard as
well as any relevant test data that is available should be considered in identifying the appropriate classification.
Second Revision No. 136-NFPA 13-2014 [ Section No. A.5.6.3 ]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
231 of 301 10/9/2014 8:39 AM
A.5.6.3
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
232 of 301 10/9/2014 8:39 AM
See Table A.5.6.3.
Table A.5.6.3(b) Alphabetized Listing of Commodity Classes
CommodityCommodity
Class
Aerosols
Cartoned or exposed — Level 1 Class III
Alcoholic Beverages
Cartoned or exposed
- Up to 20 percent alcohol in metal, glass, or ceramic containers Class I
- Up to 20 percent alcohol in wood containers Class II
Ammunition
Small arms, shotgun — packaged, cartoned Class IV
Appliances, Major (e.g., stoves, refrigerators)
- Not packaged, no appreciable plastic exterior trim Class I
- Corrugated, cartoned (no appreciable plastic trim) Class II
Baked Goods
Cookies, cakes, pies
- Frozen, packaged in cartons a Class II
- Packaged, in cartons Class III
Batteries
Dry cells (nonlithium or similar exotic metals)
- Packaged in cartons Class I
- Blister-packed in cartons Class II
Automobile — filled b Class I
Truck or larger — empty or filled b Group A plastics
Beans
Dried — packaged, cartoned Class III
Boat Storage
- Stored in racks See Table A.5.6
Bottles, Jars
Empty, cartoned
- Glass Class I
- Plastic PET (polyethylene terephthalate) Class IV
Filled noncombustible powders
- Plastic PET Class II
- Glass, cartoned Class I
- Plastic, cartoned [less than 1 gal (3.8 L)] Class IV
- Plastic, exposed (other than PET), any size Group A plastics
- Plastic, cartoned or exposed [greater than 1 gal (3.8 L)] Group A plastics
- Plastic, solid plastic crates Group A plastics
- Plastic, open plastic crates Group A plastics
Filled noncombustible liquids
- Glass, cartoned Class I
- Plastic, cartoned [less than 5 gal (18.9 L)] Class I
- Plastic, open or solid plastic crates c Group A plastics
- Plastic, PET Class I
Boxes, Crates
- Empty, wood, solid walls Class II
- Empty, wood, slatted See Table A.5.6
Bread
Wrapped cartoned Class III
Butter
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
233 of 301 10/9/2014 8:39 AM
CommodityCommodity
Class
Whipped spread Class III
Candles
Packaged, cartoned
- Treat as expanded plastic Group A plastics
Candy
Packaged, cartoned Class III
Canned Foods
In ordinary cartons Class I
Cans
Metal — empty Class I
Carpet Tiles
Cartoned Group A plastics
Cartons
Corrugated
- Unassembled (neat piles) Class III
- Partially assembled Class IV
Wax coated, single walled Group A plastics
Cement
Bagged Class I
Cereals
Packaged, cartoned Class III
Charcoal
Bagged — standard Class III
Cheese
- Packaged, cartoned Class III
- Wheels, cartoned Class III
Chewing Gum
Packaged, cartoned Class III
Chocolate
Packaged, cartoned Class III
Cloth
Cartoned and not cartoned
- Natural fiber, viscose Class III
- Synthetic d Class IV
Cocoa Products
Packaged, cartoned Class III
Coffee
- Canned, cartoned Class I
- Packaged, cartoned Class III
Coffee Beans
Bagged Class III
Cotton
Packaged, cartoned Class III
Diapers
- Cotton, linen Class III
- Disposable with plastics and nonwoven fabric (in cartons) Class IV
- Disposable with plastics and nonwoven fabric (exposed), plastic wrapped Group A plastics
Dried Foods
Packaged, cartoned Class III
Fertilizers
Bagged
- Phosphates Class I
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
234 of 301 10/9/2014 8:39 AM
CommodityCommodity
Class
- Nitrates Class II
Fiberglass Insulation
- Paper-backed rolls, bagged or unbagged Class IV
File Cabinets
Metal
- Cardboard box or shroud Class I
Fish or Fish Products
Frozen
- Nonwaxed, nonplastic packaging Class I
- Waxed-paper containers, cartoned Class II
- Boxed or barreled Class II
- Plastic trays, cartoned Class III
Canned
- Cartoned Class I
Frozen Foods
Nonwaxed, nonplastic packaging Class I
- Waxed-paper containers, cartoned Class II
- Plastic trays Class III
Fruit
Fresh
- Nonplastic trays or containers Class I
- With wood spacers Class I
Furniture
Wood
- No plastic coverings or foam plastic cushioning Class III
- With plastic coverings Class IV
- With foam plastic cushioning Group A plastics
Grains — Packaged in Cartons
- Barley Class III
- Rice Class III
- Oats Class III
Ice Cream Class I
Leather Goods Class III
Leather Hides
Baled Class II
Light Fixtures
Nonplastic — cartoned Class II
Lighters
Butane
- Blister-packed, cartoned Group A plastics
- Loose and in large containers (Level 3 aerosol) See Table A.5.6
Liquor
100 proof or less, 1 gal (3.8 L) or less, cartoned
- Glass (palletized) e Class IV
- Plastic bottles Class IV
Marble
Artificial sinks, countertops
- Cartoned, crated Class II
Margarine
- Up to 50 percent oil (in paper or plastic containers) Class III
- Between 50 percent and 80 percent oil (in any packaging) Group A plastics
Matches
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
235 of 301 10/9/2014 8:39 AM
CommodityCommodity
Class
Packaged, cartoned
- Paper Class IV
- Wood Group A plastics
Mattresses
- Standard (box spring) Class III
- Foam (in finished form) Group A plastics
Meat, Meat Products
- Bulk Class I
- Canned, cartoned Class I
- Frozen, nonwaxed, nonplastic containers Class I
- Frozen, waxed-paper containers Class II
- Frozen, expanded plastic trays Class II
Metal Desks
- With plastic tops and trim Class I
Milk
- Nonwaxed-paper containers Class I
- Waxed-paper containers Class I
- Plastic containers Class I
- Containers in plastic crates Group A plastics
Motors
- Electric Class I
Nail Polish
- 1 oz to 2 oz (29.6 ml to 59.1 ml) glass, cartoned Class IV
- 1 oz to 2 oz (29.6 ml to 59.1 ml) plastic bottles, cartoned Group A plastics
- Tissue products, exposed and plastic wrapped Group A plastics
Paper, Rolled
In racks or on side Class III
- Medium- or heavyweight
In racks Class IV
- Lightweight
Paper, Waxed
Packaged in cartons Class IV
Pharmaceuticals
Pills, powders
- Glass bottles, cartoned Class II
- Plastic bottles, cartoned Class IV
Nonflammable liquids
- Glass bottles, cartoned Class II
Photographic Film
- Motion picture or bulk rolls of film in polycarbonate, polyethylene, or metal cans; polyethylene bagged incardboard boxes
Class II
- 35 mm in metal film cartridges in polyethylene cans in cardboard boxes Class III
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
236 of 301 10/9/2014 8:39 AM
CommodityCommodity
Class
- Paper, in sheets, bagged in polyethylene, in cardboard boxes Class III
- Rolls in polycarbonate plastic cassettes, bulk wrapped in cardboard boxes Class IV
Plastic Containers (except PET)
- Noncombustible liquids or semiliquids in plastic containers less than 5 gal (18.9 L) capacity Class I
- Noncombustible liquids or semiliquids (such as ketchup) in plastic containers with nominal wall thicknessof 1 ⁄4 in. (6.4 mm) or less and larger than 5 gal (18.9) capacity
Class II
- Noncombustible liquids or semiliquids (such as ketchup) in plastic containers with nominal wall thicknessgreater than 1 ⁄4 in. (6.4 mm) and larger than 5 gal (18.9 L) capacity
Group A plastics
Polyurethane
- Cartoned or exposed expanded Group A plastics
Poultry Products
- Canned, cartoned Class I
- Frozen, nonwaxed, nonplastic containers Class I
- Frozen (on paper or expanded plastic trays) Class II
Powders
Ordinary combustibles — free flowing
- In paper bags (e.g., flour, sugar) Class II
PVA (polyvinyl alcohol) Resins
PVC (polyvinyl chloride)
- Flexible (e.g., cable jackets, plasticized sheets) Class III
- Rigid (e.g., pipe, pipe fittings) Class III
- Bagged resins Class III
Rags
Baled
- Natural fibers Class III
- Synthetic fibers Class IV
Rubber
- Natural, blocks in cartons Class IV
- Synthetic Group A plastics
Salt
- Bagged Class I
- Packaged, cartoned Class II
Shingles
- Asphalt-coated fiberglass Class III
- Asphalt-impregnated felt Class IV
Shock Absorbers
- Metal dust cover Class II
- Plastic dust cover Class III
Signatures
Books, magazines
- Solid array on pallet Class II
Skis
- Wood Class III
- Foam core Class IV
Stuffed Toys
Foam or synthetic Group A plastics
Storage Container
- Large container storage of household goods See Table A.5.6
Syrup
- Drummed (metal containers) Class I
- Barreled, wood Class II
Textiles
Natural fiber clothing or textile products Class III
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
237 of 301 10/9/2014 8:39 AM
CommodityCommodity
Class
Synthetics (except rayon and nylon) — 50/50 blend or less
- Thread, yarn on wood or paper spools Class III
- Fabrics Class III
- Thread, yarn on plastic spools Class IV
- Baled fiber Group A plastics
Synthetics (except rayon and nylon) — greater than 50/50 blend
- Thread, yarn on wood or paper spools Class IV
- Fabrics Class IV
- Baled fiber Group A plastics
- Thread, yarn on plastic spools Group A plastics
Rayon and nylon
- Baled fiber Class IV
- Thread, yarn on wood or paper spools Class IV
- Fabrics Class IV
- Thread, yarn on plastic spools Group A plastics
Tobacco Products
In paperboard cartons Class III
Transformers
Dry and oil filled Class I
Vinyl-Coated Fabric
Cartoned Group A plastics
Vinyl Floor Coverings
- Tiles in cartons Class IV
- Rolled Group A plastics
Wax-Coated Paper
Cups, plates
- Boxed or packaged inside cartons (emphasis on packaging) Class IV
- Loose inside large cartons Group A plastics
Wax
Paraffin/petroleum wax, blocks, cartoned Group A plastics
Wire
- Bare wire on metal spools on wood skids Class I
- Bare wire on wood or cardboard spools on wood skids Class II
- Bare wire on metal, wood, or cardboard spools in cardboard boxes on wood skids Class II
- Single- or multiple-layer PVC-covered wire on metal spools on wood skids Class II
- Insulated (PVC) cable on large wood or metal spools on wood skids Class II
- Bare wire on plastic spools in cardboard boxes on wood skids Class IV
- Single- or multiple-layer PVC-covered wire on plastic spools in cardboard boxes on wood skids Class IV
- Single, multiple, or power cables (PVC) on large plastic spools Class IV
- Bulk storage of empty plastic spools Group A plastics
Wood Products
- Solid piles — lumber, plywood, particleboard, pressboard (smooth ends and edges) Class II
- Spools (empty) Class III
- Toothpicks, clothespins, hangers in cartons Class III
- Doors, windows, wood cabinets, and furniture Class III
- Patterns Class IV
a The product is presumed to be in a plastic-coated package in a corrugated carton. If packaged in a metal foil, it can beconsidered Class I.
b Most batteries have a polypropylene case and, if stored empty, should be treated as a Group A plastic. Truck batteries,even where filled, should be considered a Group A plastic because of their thicker walls.
c As the openings in plastic crates become larger, the product behaves more like a Class III commodity. Conversely, as theopenings become smaller, the product behaves more like a plastic.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
238 of 301 10/9/2014 8:39 AM
d Tests clearly indicate that a synthetic or synthetic blend is considered greater than Class III.
e When liquor is stored in glass containers in racks, it should be considered a Class III commodity; where it is palletized, itshould be considered a Class IV commodity.
Table A.5.6.3 Examples of Class I Commodities
Product Heading Product NFPA 13
BatteriesDry cells (excludes lithium, lithium-ion, and other similar exotic metals orcombustible electrolyte); without blister packing (if blister packed refer tocommodity classification definitions)
Class 1
Dry cells (non-lithium or similar exotic metals; in blister packing; cartoned Class 2
Vehicle; any size (e.g. automobile or truck); empty plastic casingGroup A
Nonexpanded
Vehicle; large (e.g. truck or larger); dry or wet (excludes lithium-ion and othercells containing combustible electrolyte) cells
Group A
Nonexpanded
Vehicle; small (e.g. automobile); wet (excludes lithium-ion and other cellscontaining combustible electrolyte) cells
Class 1
Empty Containers Noncombustible Class 1
PET, bottles or jars Class 4
Rigid plastic (not including PET)Group A
Nonexpanded
Wood; solid sided (e.g. crates, boxes) Class 2
Film Rolls, IncludingPhotographic
Film (polypropylene, polyesther, polyethylene); rolled on any reel typeGroup A
Nonexpanded
Film; 35 mm metal film cartridges in polyethylene cans; cartoned Class 3
Film; motion picture or bulk rolls in polycarbonate, polyethylene or in metalcans; polyethylene bagged; cartoned
Class 2
Film; rolls in polycarbonate plastic cassettes; cartoned Class 4
Photographic paper; sheets; bagged in polyethylene; cartoned Class 3
Flammable /Combustible Liquids
Aerosol; Level 1 Class 3
Lighters; butane; blister-packed; cartonedGroup A
Nonexpanded
Liquids; over 20 and up to 50 percent alcohol (e.g. alcoholic beverages, hairspray); up to 1 gallon (3.8 L) glass bottles or jars; in racks; cartoned
Class 3
Liquids; over 20 and up to 50 percent alcohol (e.g. alcoholic beverages, hairspray); up to 1 gallon (3.8 L) glass bottles or jars; palletized; cartoned
Class 4
Liquids; over 20 and up to 50 percent alcohol (e.g. alcoholic beverages, hairspray); up to 1 gallon (3.8 L) plastic bottles or jars; cartoned
Class 4
Liquids; up to 20 percent alcohol (e.g. alcoholic beverages, flavoring extracts);greater than 5 gallon (18.9 L) plastic containers with wall thickness greaterthan 1 ⁄4 in. (6 mm)
Group A
Nonexpanded
Liquids; up to 20 percent alcohol (e.g. alcoholic beverages, flavoring extracts);metal, glass or ceramic containers
Class 1
Liquids; up to 20 percent alcohol (e.g. alcoholic beverages, flavoring extracts);plastic containers greater than 5 gallons (18.9 L) and wall thickness up to 1 ⁄4in. (6 mm)
Class 2
Liquids; up to 20 percent alcohol (e.g. alcoholic beverages, flavoring extracts);up to 5 gallons (18.9 L) plastic bottles or jars
Class 1
Liquids; up to 20 percent alcohol (e.g. alcoholic beverages, flavoring extracts);wood containers
Class 2
Nail polish; up to 2 oz (59 ml) glass bottles or jars; cartoned Class 4
Nail polish; up to 2 oz (59 ml) plastic bottles or jars; cartonedGroup A
Nonexpanded
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
239 of 301 10/9/2014 8:39 AM
Product Heading Product NFPA 13
Food Products -Frozen
Frozen foods; nonwaxed or nonplastic packaging Class 1
Frozen foods; plastic trays Class 3
Frozen foods; waxed or plastic-coated paper packaging Class 2
Food Products -Non-Frozen
Butter (stick or whipped spread) or margarine (up to 50 percent oil) Class 3
Butter; whipped spread Class 3
Dry foods (such as baked goods, candy, cereals, cheese, chocolate, cocoa,coffee, grains, granular sugar, nuts, etc.); bagged or cartoned
Skis; composite materials (plastic, fiberglass, foam, etc.) Class 4
Tobacco products; cartoned Class 3
Toys; stuffed; foam or syntheticGroup A
Expanded
Transformer; dry or empty (i.e. void of oil)-filled Class 1
NoncombustibleLiquids
Liquids or semi liquids; PET containers greater than 5 gallon (18.9 L) having anominal wall thickness greater than 0.25 in (6 mm)
Class 4
Liquids or semi liquids; PET containers up to 5 gallon (18.9 L) or greater than5 gallon (18.9 L) having a nominal wall thickness up to 0.25 in (6 mm)
Class 1
Liquids or semi-liquids (e.g. crushed fruits and vegetables); plastic containersup to 5 gallon (18.9 L) capacity
Class 1
Liquids or semi-liquids; plastic (except PET) containers greater than 5 gallon(18.9 L) capacity having a nominal wall thickness greater than 0.25 in. (6 mm)
Group A
Nonexpanded
Liquids or semi-liquids; plastic (except PET) containers greater than 5 gallon(18.9 L) capacity having a nominal wall thickness up to 0.25 in. (6 mm)
Class 2
Liquids; cardboard drink boxes, plastic-coated, wax-coated, and/or aluminum-lined; uncartoned or on corrugated carton trays with plastic sheeting.
Liquids; less than 5 gallon (18.9 L) plastic containers Class 1
Liquids; pharmaceuticals (nonflammable); glass bottles or jars; cartoned Class 2
Liquids; plastic bottles or jars; stored in open or solid plastic cratesGroup A
Nonexpanded
Paper Products Book signatures (paper part of book without hard cover) Class 2
Cartons (i.e. cardboard flats); corrugated; partially assembled Class 4
Cartons (i.e. cardboard flats); corrugated; unassembled in neat piles Class 3
Cartons; wax-coated, single-walled corrugatedGroup A
Nonexpanded
Cellulosic paper products; nonwax-coated (e.g. books, cardboard games,cartoned tissue products, magazines, newspapers, paper cups, paper plates, Class 3
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
241 of 301 10/9/2014 8:39 AM
Product Heading Product NFPA 13
paper towels, plastic-coated paper food containers, stationary)
Cellulosic paper products; wax-coated (e.g. paper plates, cups, etc.); looselypacked; cartoned
Group A
Nonexpanded
Cellulosic paper products; wax-coated (e.g. paper plates, cups, etc.); nested;cartoned
Class 4
Matches; paper-type; cartoned Class 4
Matches; wooden; cartonedGroup A
Nonexpanded
Rolled; lightweight; in storage racks Class 4
Rolled; medium or heavyweight; in storage racks or on-side Class 3
Tissue products; plastic-wrapped; cartoned Class 3
Tissue products; plastic-wrapped; uncartonedGroup A
Nonexpanded
Plastic / Rubber ABS (Acrylonitrile-butadiene-styrene copolymer)Group A
Nonexpanded
Acetal (polyformaldehyde)Group A
Nonexpanded
Acrylic (polymethyl methacrylate)Group A
Nonexpanded
Automobile bumpers and dashboardsGroup A
Expanded
Butyl rubberGroup A
Nonexpanded
Cellulose Acetate Class 4
Cellulose Acetate ButyrateGroup A
Nonexpanded
Chloroprene rubber Class 4
Containers; nonexpanded plastic gridded or solid; collapsed or nested with noair spaces
Group A
Nonexpanded
ECTFE (ethylene-chlorotrifluoro-ethylene copolymer) Class 4
EPDM (ethylene-propylene rubber)Group A
Nonexpanded
ETFE (ethylene-tetrafluoroethylene copolymer) Class 4
Ethyl CelluloseGroup A
Nonexpanded
FEP (fluorinated ethylene-propylene copolymer) Class 4
FRP (fiberglass-reinforced polyester)Group A
Nonexpanded
Melamine (melamine formaldehyde) Class 3
Nitrile Rubber (acrylonitrile-butadiene rubber)Group A
Nonexpanded
Nylon (nylon 6, nylon 6/6)Group A
Nonexpanded
PCTFE (polychlorotrifluoroethylene) Class 3
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
242 of 301 10/9/2014 8:39 AM
Product Heading Product NFPA 13
PET (Polyethylene Terephthalate - thermoplastic polyester)Group A
Nonexpanded
Phenolic Class 3
Plastics; stored in fully closed and solid (no openings), metal containers Class 1
PolybutadieneGroup A
Nonexpanded
PolycarbonateGroup A
Nonexpanded
Polyester elastomerGroup A
Nonexpanded
PolyethyleneGroup A
Nonexpanded
PolypropyleneGroup A
Nonexpanded
Polystyrene; foam products (e.g. plates, cups, etc.)Group A
Expanded
Polystyrene; rigid productsGroup A
Nonexpanded
PolyurethaneGroup A
Expanded
PTFE (polytetrafluoroethylene) Class 3
PVC (polyvinyl chloride) products Class 3
PVC resins; bagged Class 3
PVDC (polyvinylidene chloride) Class 3
PVDF (polyvinylidene fluoride) Class 3
PVF (polyvinyl fluoride)Group A
Nonexpanded
Rubber; natural in blocks; cartonedGroup A
Nonexpanded
Rubber; natural; expandedGroup A
Expanded
Rubber; natural; nonexpandedGroup A
Nonexpanded
Rubber; synthetic (santoprene)Group A
Nonexpanded
SAN (styrene acrylonitrile)Group A
Nonexpanded
SBR (styrene-butadiene rubber)Group A
Nonexpanded
Silicone rubber Class 4
Urea (urea formaldehyde) Class 3
Plastic ContainersBottles or jars (except PET) greater than 1 gallon (3.8 L) containingnoncombustible solids
Group A
Nonexpanded
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
243 of 301 10/9/2014 8:39 AM
Product Heading Product NFPA 13
Bottles or jars (except PET) up to 1 gallon (3.8 L) containing noncombustiblesolids
Group A, cartoned (treatas cartoned even ifuncartoned)
Nonexpanded
Powders / Pills Pharmaceutical pills; glass bottles or jars; cartoned Class 2
Pharmaceuticals pills; plastic bottles or jars; cartoned Class 4
Polyvinyl Alcohol (PVA) resins; bagged Class 4
Powders; combustible (ordinary - such as sugar or flour); free-flowing; bagged Class 2
Powders; noncombustible free-flowing powdered or granular materials (e.g.cement, calcium chloride, clay, iron oxide, sodium chloride, sodium silicate,etc.)
Class 1
Powders; noncombustible; glass bottles or jars; cartoned Class 1
Powders; noncombustible; PET bottles or jars Class 2
Powders; noncombustible; plastic (other than PET) bottles or jars; uncartonedGroup A
Nonexpanded
Powders; noncombustible; plastic bottles or jars greater than 1 gallon (3.8 L)capacity
Group A
Nonexpanded
Powders; noncombustible; plastic bottles or jars up to 1 gallon (3.8 L)capacity; cartoned
Class 4
Textile Materials /Products
Cloth; natural fibers; baled Class 3
Cloth; synthetic cloth Class 4
Clothing; natural fibers (e.g. wool, cotton) and viscose Class 3
Cotton; cartoned Class 3
Diapers; cotton or linen Class 3
Diapers; plastic or nonwoven fabric; cartoned Class 4
Diapers; plastic or nonwoven fabric; plastic-wrapped; uncartonedGroup A
Nonexpanded
Fabric; rayon and nylon Class 4
Fabric; synthetic (except rayon and nylon); greater than 50/50 blend Class 4
Fabric; synthetic (except rayon and nylon); up to 50/50 blend Class 3
Fabric; vinyl-coated (e.g. tablecloth); cartonedGroup A
Nonexpanded
Fibers; rayon and nylon; baled Class 4
Fibers; synthetic (except rayon and nylon); baledGroup A
Nonexpanded
Fibers; synthetic; baled Class 4
Thread or yarn; rayon and nylon; wood or paper spools Class 4
Thread or yarn; rayon or nylon; plastic spoolsGroup A
Nonexpanded
Thread or yarn; synthetic (except rayon and nylon); greater than 50/50 blend;paper or wood spools
Class 4
Thread or yarn; synthetic (except rayon and nylon); greater than 50/50 blend;plastic spools
Group A
Nonexpanded
Thread or yarn; synthetic (except rayon and nylon); up to 50/50 blend; plasticspools
Class 4
Thread or yarn; synthetic (except rayon and nylon); up to 50/50 blend; woodor paper spools
Class 3
Wax Products CandlesGroup A
Expanded
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
Changes to Table A.5.6.3 and Other Commodity Classification Tables
(1) Proposing the addition of a new heading entitled “Product Heading”
(2) Establishing a consistent format for listing commodity based on:
• Main description of commodity linked to Product Heading
• Any description specific to commodity (e.g. percent alcohol content)
• Description of bottles, jars or packaging external to the commodity is provided in, if applicable (e.g. glass bottles orjars)
• Description of container, if applicable (e.g. uncartoned, plastic container, etc.)
Note, if the commodity classification is the same cartoned or uncartoned, the description of the container will not beprovided. Also, the term “cartoned” means placed within a cardboard container.
(3) Under Commodity column, Group A plastics to be designated whether they should be treated as either expanded orunexpanded, regardless of the physical state of the plastic. If no designation is provided after the term “Group A”, thiswill mean that the designation is based on its actual physical state.
(4) All commodities are being reviewed to determine if they should be retained within the table
(5) Commodities listed within FM Global, XL and IFC standards are being reviewed to determine if they should beincluded within NFPA 13
(6) Add horizontal lines separating commodity listings as well as Product Heading
Other Considerations that are considered as part of this CI include:
(7) Table A.5.6 and its associated language should be moved to a new Section 5.7 entitled “Commodities Outside theScope of NFPA 13”
(8) Identify the term “bagged” as presently meaning “paper”; identify the effect of commodity classification if “bag” isplastic
ResponseMessage:
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
347 Wax Products Candles; cartoned Group A Expanded
349 Wax ProductsParaffin or petroleum wax;
blocks; cartoned
Group A Expanded
356Wire / Cable /
Spools
Spools; plastic; empty Group A Nonexpanded
357Wire / Cable /
Spools
Spools; wood; empty Class 3
360Wire / Cable /
Spools
Wire or cable; PVC insulated;
metal or wood spools
Class 2
361Wire / Cable /
Spools
Wire or cable; PVC insulated;
plastic spools
Class 4
365Wire / Cable /
Spools
Wire; bare; metal spools, on
wood skids, uncartoned
Class 1
366Wire / Cable /
Spools
Wire; bare; metal spools;
cartoned
Class 2
367Wire / Cable /
Spools
Wire; bare; plastic spools; on
wood skids, cartoned
Class 4
368Wire / Cable /
Spools
Wire; bare; plastic spools;
uncartoned
Group A Nonexpanded
369Wire / Cable /
Spools
Wire; bare; wood or cardboard
spools
Class 2
376 Wood Products Wood patterns Class 4
374 Wood Products
Wood products (e.g. fiberboard,
lumber, particle board, plywood,
pressboard with smooth ends and
edges); bundled solid blocks
piles
Class 2
377 Wood Products
Wood products (e.g. fiberboard,
lumber, particle board, plywood,
pressboard with smooth ends and
edges); unbundled or non-solid
blocks
Class 3
375 Wood Products
Wood products (e.g. toothpicks,
clothespins and hangers);
cartoned
Class 3
Second Revision No. 152-NFPA 13-2014 [ Section No. A.5.6.3.1 ]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
246 of 301 10/9/2014 8:39 AM
A.5.6.3.1
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
247 of 301 10/9/2014 8:39 AM
See Table A.5.6.3.1.
Table A.5.6.3.1 Examples of Class I Commodities
Product Heading Product
BatteriesDry cells (excludes lithium, lithium-ion, and other similar exotic metals or combustible electrolyte);without blister packing (if blister packed refer to commodity classification definitions)
Vehicle; small (e.g. automobile); wet (excludes lithium-ion and other cells containing combustibleelectrolyte) cells
Empty Containers Noncombustible
Flammable /Combustible Liquids
Liquids; up to 20 percent alcohol (e.g. alcoholic beverages, flavoring extracts); metal, glass orceramic containers
Liquids; up to 20 percent alcohol (e.g. alcoholic beverages, flavoring extracts); up to 5 gallons (18.9L) plastic bottles or jars
Food Products - Frozen Frozen foods; nonwaxed or nonplastic packaging
Food Products -Non-Frozen
Foods (e.g. coffee, fish products, fruit, meat products, nuts, poultry, etc.); metal cans
Fruits and vegetables (noncombustible semi-liquids); crushed; plastic containers up to 5 gallons(18.9 L)
Fruits and vegetables; fresh; wood spacers, non-plastic trays or containers
Meat; fresh; no plastic packaging; uncartoned
Milk; paper containers, or plastic bottles or jars up to 5 gallons (18.9 L) plastic bottles or jars
Salt; bagged
Furniture and Bedding Furniture; metal (e.g. file cabinets or desks with plastic trim); cartoned
Housing Materials /Appliances
Appliances; major (e.g. stoves, refrigerators); no appreciable plastic interior or exterior trim; cartoned
Gypsum board
Paint; water-based (latex); friction-top metal containers; cartoned
Miscellaneous Fertilizers; phosphates; bagged
Motors; electric
Transformer; dry or empty (i.e. void of oil)
Noncombustible LiquidsLiquids or semi liquids; PET containers greater than 5 gallon (18.9 L) having a nominal wallthickness greater than 0.25 in (6 mm)
Liquids or semi-liquids (e.g. crushed fruits and vegetables); plastic containers up to 5 gallon (18.9 L)capacity
Powders; noncombustible; glass bottles or jars; cartoned
Wire / Cable / Spools Wire; bare; metal spools, uncartoned
Table A.5.6.3.1 Examples of Class I Commodities
Alcoholic Beverages
Cartoned or exposed
- Up to 20 percent alcohol in metal, glass, or ceramic containers
Appliances, Major (e.g., stoves, refrigerators)
- Not packaged, no appreciable plastic exterior trim
Batteries
Dry cells (nonlithium or similar exotic metals)
- Packaged in cartons
Automobile
- Filled*
Bottles, Jars
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
248 of 301 10/9/2014 8:39 AM
Empty, cartoned
- Glass
Filled noncombustible liquids
- Glass, cartoned
- Plastic, cartoned [less than 5 gal (18.9 L)]
- Plastic, PET
Filled noncombustible powders
- Glass, cartoned
Canned Foods
In ordinary cartons
Cans
Metal
- Empty
Cement
Bagged
Coffee
Canned, cartoned
Fertilizers
Bagged
- Phosphates
File Cabinets
Metal
- Cardboard box or shroud
Fish or Fish Products
Frozen
- Nonwaxed, nonplastic packaging
Canned
- Cartoned
Frozen Foods
Nonwaxed, nonplastic packaging
Fruit
Fresh
- Nonplastic trays or containers
- With wood spacers
Ice Cream
Meat, Meat Products
- Bulk
- Canned, cartoned
- Frozen, nonwaxed, nonplastic containers
Metal Desks
- With plastic tops and trim
Milk
- Nonwaxed-paper containers
- Waxed-paper containers
- Plastic containers
Motors
- Electric
Nuts
- Canned, cartoned
Paints
Friction-top cans, cartoned
- Water-based (latex)
Plastic Containers
- Noncombustible liquids or semiliquids in plastic containers less than 5 gal (18.9 L) capacity
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
249 of 301 10/9/2014 8:39 AM
Poultry Products
- Canned, cartoned
- Frozen, nonwaxed, nonplastic containers
Salt
Bagged
Syrup
Drummed (metal containers)
Transformers
Dry and oil filled
Wire
Bare wire on metal spools on wood skids
*Most batteries have a polypropylene case and, if stored empty, should be treated as a Group A plastic. Truck batteries, evenwhere filled, should be considered a Group A plastic because of their thicker walls.
Supplemental Information
File Name Description
Table_A.5.6.3.1_rev_1_.xlsx
Submitter Information Verification
Submitter Full Name: Matthew Klaus
Organization: National Fire Protection Assoc
Street Address:
City:
State:
Zip:
Submittal Date: Wed Jul 02 07:27:42 EDT 2014
Committee Statement
CommitteeStatement:
As part of the commodity classification task groups review of the table A.5.6.3, all of the individual commodity tablesare being updated as well. This table is intended to correlate with the revised Table A.5.6.3.
ResponseMessage:
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
250 of 301 10/9/2014 8:39 AM
Product Heading Product
Batteries
Dry cells (excludes lithium,
lithium-ion, and other similar
exotic metals or combustible
electrolyte); without blister
packing cartoned (if blister
packed refer to commodity
classification definitions)
Batteries
Vehicle; small (e.g.
automobile); wet (excludes
lithium-ion and other cells
containing combustible
electrolyte) cells
Empty ContainersNoncombustible Metal
Flammable /
Combustible
Liquids
Liquids; up to 20 percent
alcohol (e.g. alcoholic
beverages, flavoring extracts);
metal, glass or ceramic
containers
Flammable /
Combustible
Liquids
Liquids; up to 20 percent
alcohol (e.g. alcoholic
beverages, flavoring extracts);
up to 5 gallons (18.9 L) plastic
bottles or jars
Food Products -
Frozen
Frozen foods; nonwaxed or
nonplastic packaging
Food Products -
Non-Frozen
Foods (e.g. coffee, fish
products, fruit, meat products,
nuts, poultry, etc.); metal cans
Food Products -
Non-Frozen
Fruits and vegetables
(noncombustible semi-liquids);
crushed; plastic containers up
to 5 gallons (18.9 L)
Food Products -
Non-Frozen
Fruits and vegetables; fresh;
wood spacers, non-plastic trays
or containers
Food Products -
Non-Frozen
Meat; bulk; fresh; no plastic
packaging; uncartoned
Food Products -
Non-Frozen
Milk; paper containers, or
plastic bottles or jars up to 5
gallons (18.9 L) plastic bottles
or jars
Food Products -
Non-Frozen
Salt; bagged
Furniture and
Bedding
Furniture; metal (e.g. file
cabinets or desks with plastic
tops and trim); cartoned or
shrouded
Housing
Materials /
Appliances
Appliances; major (e.g. stoves,
refrigerators); no appreciable
plastic interior or exterior
trim; uncartoned
Housing
Materials /
Appliances
Gypsum board
Housing
Materials /
Appliances
Paint; water-based (latex);
friction-top metal containers;
cartoned
MiscellaneousFertilizers; phosphates; bagged
Miscellaneous Motors; electric
MiscellaneousTransformer; dry or empty (i.e.
void of oil)-filled
Noncombustible
Liquids
Liquids or semi liquids; PET
containers up to 5 gallon (18.9
L) or greater than 5 gallon
(18.9 L) having a nominal wall
thickness up to 0.25 in (6 mm)
Noncombustible
Liquids
Liquids or semi-liquids (e.g.
crushed fruits and vegetables);
plastic containers up to 5
gallon (18.9 L) capacity
Noncombustible
Liquids
Liquids; cardboard drink boxes,
plastic-coated, wax-coated,
and/or aluminum-lined;
uncartoned or on corrugated
carton trays with plastic
sheeting.
Noncombustible
Liquids
Liquids; glass bottles or jars;
cartoned
Noncombustible
Liquids
Liquids; less than 5 gallon
(18.9 L) plastic containers
Plastic / Rubber
Plastics; stored in fully closed
and solid (no openings), metal
containers
Powders / Pills
Powders; noncombustible free-
flowing powdered or granular
materials (e.g. cement, calcium
chloride, clay, iron oxide,
sodium chloride, sodium
silicate, etc.); bagged Cement,
bagged
Powders / Pills
Powders; noncombustible; glass
bottles or jars; cartoned
Wire / Cable /
Spools
Wire; bare; metal spools, on
wood skids, uncartoned
Second Revision No. 153-NFPA 13-2014 [ Section No. A.5.6.3.2 ]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
251 of 301 10/9/2014 8:39 AM
A.5.6.3.2
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
252 of 301 10/9/2014 8:39 AM
See Table A.5.6.3.2.
Table A.5.6.3.2 Examples of Class II Commodities
Product Heading Product
Batteries Dry cells (non-lithium or similar exotic metals; in blister packing; cartoned
Film; motion picture or bulk rolls in polycarbonate, polyethylene or in metal cans; polyethylenebagged; cartoned
Flammable / CombustibleLiquids
Liquids; up to 20 percent alcohol (e.g. alcoholic beverages, flavoring extracts); plastic containersgreater than 5 gallons (18.9 L) and wall thickness up to 1 ⁄4 in. (6 mm)
Liquids; up to 20 percent alcohol (e.g. alcoholic beverages, flavoring extracts); wood containers
Food Products - Frozen Frozen foods; waxed or plastic-coated paper packaging
Food Products -Non-Frozen
Meat; fresh; no plastic packaging; cartoned
Salt; cartoned
Syrup; wooden container
Housing Materials /Appliances
Appliances; major (e.g. stoves, refrigerators); no appreciable plastic interior or exterior trim;cartoned
Light fixtures; nonplastic; cartoned
Housing materials (such as sinks, countertops, etc.); noncombustible, cartoned or crated
Miscellaneous Fertilizers; nitrates; bagged
Leather hides; baled
Shock absorbers; metal dust cover
Noncombustible Liquids Liquids or semi-liquids; plastic (except PET) containers greater than 5 gallon (18.9 L) capacityhaving a nominal wall thickness up to 0.25 in. (6 mm)
Liquids; pharmaceuticals (nonflammable); glass bottles or jars; cartoned
Paper Products Book signatures (paper part of book without hard cover)
Powders / Pills Pharmaceutical pills; glass bottles or jars; cartoned
Powders; combustible (ordinary - such as sugar or flour); free-flowing; bagged
Powders; noncombustible; PET bottles or jars
Wire / Cable / Spools Wire or cable; PVC insulated; metal or wood spools
Table A.5.6.3.2(b) Examples of Class II Commodities
Alcoholic Beverages
Up to 20 percent alcohol in wood containers
Appliances, Major (e.g., stoves)
Corrugated, cartoned (no appreciable plastic trim)
Baked Goods
Cookies, cakes, pies
- Frozen, packaged in cartons*
Batteries
Dry cells (nonlithium or similar exotic metals) in blister pack in cartons
Bottles, Jars
Filled noncombustible powders
- Plastic PET
Boxes, Crates
Empty, wood, solid walls
Fertilizers
Bagged
- Nitrates
Fish or Fish Products
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
253 of 301 10/9/2014 8:39 AM
Frozen
- Waxed-paper containers, cartoned
- Boxed or barreled
Frozen Foods
Waxed-paper containers, cartoned
Leather Hides
Baled
Light Fixtures
Nonplastic
- Cartoned
Marble
Artificial sinks, countertops
- Cartoned, crated
Meat, Meat Products
- Frozen, waxed-paper containers
- Frozen, expanded plastic trays
Pharmaceuticals
Pills, powders
- Glass bottles, cartoned
Nonflammable liquids
- Glass bottles, cartoned
Photographic Film
- Motion picture or bulk rolls of film in polycarbonate, polyethylene, or metal cans; polyethylene bagged in cardboard boxes
Plastic Containers
Noncombustible liquids or semiliquids (such as ketchup) in plastic containers with nominal wall thickness of 1 ⁄4 in. (6.4mm) or less and larger than 5 gal (18.9 L) capacity
Poultry Products
Frozen (on paper or expanded plastic trays)
Powders (ordinary combustibles — free flowing)
In paper bags (e.g., flour, sugar)
Salt
Packaged, cartoned
Shock Absorbers
Metal dust cover
Signatures
Book, magazines
- Solid array on pallet
Syrup
Barreled, wood
Wire
- Bare wire on wood or cardboard spools on wood skids
- Bare wire on metal, wood, or cardboard spools in cardboard boxes on wood skids
- Single- or multiple-layer PVC-covered wire on metal spools on wood skids
- Insulated (PVC) cable on large wood or metal spools on wood skids
Wood Products
Solid piles
- Lumber, plywood, particle board, pressboard (smooth ends and edges)
*The product is in a plastic-coated package in a corrugated carton. If packaged in a metal foil, it can be considered Class I.
Supplemental Information
File Name Description
Table_A.5.6.3.2_rev1_.xlsx
Submitter Information Verification
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
254 of 301 10/9/2014 8:39 AM
Submitter Full Name: Matthew Klaus
Organization: National Fire Protection Assoc
Street Address:
City:
State:
Zip:
Submittal Date: Wed Jul 02 07:30:09 EDT 2014
Committee Statement
CommitteeStatement:
As part of the commodity classification task groups review of the table A.5.6.3, all of the individual commodity tablesare being updated as well. This table is intended to correlate with the revised Table A.5.6.3.
ResponseMessage:
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
255 of 301 10/9/2014 8:39 AM
Product Heading
Product
Batteries
Dry cells (non-lithium or
similar exotic metals; in
blister packing; cartoned
Empty ContainersWood; solid sided (e.g. crates,
boxes)
Film Rolls,
Including
Photographic
Film; motion picture or bulk
rolls in polycarbonate,
polyethylene or in metal cans;
polyethylene bagged; cartoned
Flammable /
Combustible
Liquids
Liquids; up to 20 percent
alcohol (e.g. alcoholic
beverages, flavoring extracts);
plastic containers greater than
5 gallons (18.9 L) and wall
thickness up to ¼ in. (6 mm)
Flammable /
Combustible
Liquids
Liquids; up to 20 percent
alcohol (e.g. alcoholic
beverages, flavoring extracts);
wood containers
Food Products -
Frozen
Frozen foods; waxed or plastic-
coated paper packaging
Food Products -
Non-Frozen
Meat; fresh; no plastic
packaging; cartoned
Food Products -
Non-Frozen
Salt; cartoned
Food Products -
Non-Frozen
Syrup; wooden container
Housing
Materials /
Appliances
Appliances; major (e.g. stoves,
refrigerators); no appreciable
plastic interior or exterior
trim; cartoned
Housing
Materials /
Appliances
Light fixtures; nonplastic;
cartoned
Housing
Materials /
Appliances
Marble; artificial sinks,
countertops; cartoned or crated
Housing materials (such as
sinks, countertops, etc.);
noncombustible, cartoned or
crated
Miscellaneous Fertilizers; nitrates; bagged
Miscellaneous Leather hides; baled
MiscellaneousShock absorbers; metal dust
cover
Noncombustible
Liquids
Liquids or semi-liquids; plastic
(except PET) containers greater
than 5 gallon (18.9 L) capacity
having a nominal wall thickness
up to 0.25 in. (6 mm)
Noncombustible
Liquids
Liquids; pharmaceuticals
(nonflammable); glass bottles or
jars; cartoned
Paper ProductsBook signatures (paper part of
book without hard cover)
Powders / PillsPharmaceutical pills; glass
bottles or jars; cartoned
Powders / Pills
Powders; combustible (ordinary -
such as sugar or flour); free-
flowing; bagged
Powders / PillsPowders; noncombustible; PET
bottles or jars
Wire / Cable /
Spools
Wire or cable; PVC insulated;
metal or wood spools
Wire / Cable /
Spools
Wire; bare; metal spools;
cartoned
Wire / Cable /
Spools
Wire; bare; wood or cardboard
spools
Wood Products
Wood products (e.g. fiberboard,
lumber, particle board, plywood,
pressboard with smooth ends and
edges); bundled solid blocks
piles
Second Revision No. 154-NFPA 13-2014 [ Section No. A.5.6.3.3 ]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
256 of 301 10/9/2014 8:39 AM
A.5.6.3.3
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
257 of 301 10/9/2014 8:39 AM
See Table A.5.6.3.3.
Table A.5.6.3.3 Examples of Class III Commodities
Product Heading Product
Film Rolls, IncludingPhotographic
Film; 35 mm metal film cartridges in polyethylene cans; cartoned
Photographic paper; sheets; bagged in polyethylene; cartoned
Flammable /Combustible Liquids
Aerosol; Level 1
Liquids; over 20 and up to 50 percent alcohol (e.g. alcoholic beverages, hair spray); up to 1 gallon (3.8L) glass bottles or jars; in racks; cartoned
Food Products -Frozen
Frozen foods; plastic trays
Food Products -Non-Frozen
Butter (stick or whipped spread) or margarine (up to 50 percent oil)
Butter; whipped spread
Dry foods (such as baked goods, candy, cereals, cheese, chocolate, cocoa, coffee, grains, granularsugar, nuts, etc.); bagged or cartoned
Meat; fresh; plastic trays
Furniture andBedding
Furniture; wood (e.g. doors, windows, cabinets, etc.); no plastic coverings or foam cushioning
Box spring; standard (minimal plastic materials)
Housing Materials /Appliances
Appliances; no appreciable plastic exterior trim (interior of unit can have appreciable plastic)
Roofing shingles; asphalt-coated fiberglass
Miscellaneous Charcoal; standard (non-mineral spirit impregnated); bagged
Paper Products Cartons (i.e. cardboard flats); corrugated; unassembled in neat piles
Cellulosic paper products; nonwax-coated (e.g. books, cardboard games, cartoned tissue products,magazines, newspapers, paper cups, paper plates, paper towels, plastic-coated paper food containers,stationary)
Rolled; medium or heavyweight; in storage racks or on-side
Tissue products; plastic-wrapped; cartoned
Plastic / Rubber Melamine (melamine formaldehyde)
PCTFE (polychlorotrifluoroethylene)
Phenolic
PTFE (polytetrafluoroethylene)
PVC (polyvinyl chloride) products
PVC resins; bagged
PVDC (polyvinylidene chloride)
PVDF (polyvinylidene fluoride)
Urea (urea formaldehyde)
Textile Materials /Products
Cloth; natural fibers; baled
Clothing; natural fibers (e.g. wool, cotton) and viscose
Cotton; cartoned
Diapers; cotton or linen
Fabric; synthetic (except rayon and nylon); up to 50/50 blend
Thread or yarn; synthetic (except rayon and nylon); up to 50/50 blend; wood or paper spools
Wire / Cable / Spools Spools; wood; empty
Wood Products Wood products (e.g. fiberboard, lumber, particle board, plywood, pressboard with smooth ends andedges); unbundled or non-solid blocks
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
258 of 301 10/9/2014 8:39 AM
Product Heading Product
Wood products (e.g. toothpicks, clothespins and hangers)
Table A.5.6.3.3 Examples of Class III Commodities
Aerosols
Cartoned or exposed
- Level 1
Baked Goods
Cookies, cakes, pies
- Packaged, in cartons
Beans
Dried
- Packaged, cartoned
Bread
Wrapped, cartoned
Butter
Whipped spread
Candy
Packaged, cartoned
Cartons
Corrugated
- Unassembled (neat piles)
Cereals
Packaged, cartoned
Charcoal
Bagged
- Standard
Cheese
- Packaged, cartoned
- Wheels, cartoned
Chewing Gum
Packaged, cartoned
Chocolate
Packaged, cartoned
Cloth
Cartoned and not cartoned
- Natural fiber, viscose
Cocoa Products
Packaged, cartoned
Coffee
Packaged, cartoned
Coffee Beans
Bagged
Cotton
Packaged, cartoned
Diapers
Cotton, linen
Dried Foods
Packaged, cartoned
Fish or Fish Products
Frozen
- Plastic trays, cartoned
Frozen Foods
Plastic trays
Furniture
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
259 of 301 10/9/2014 8:39 AM
Wood
- No plastic coverings or foam plastic cushioning
Grains — Packaged in Cartons
- Barley
- Rice
- Oats
Margarine
Up to 50 percent oil (in paper or plastic containers)
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
260 of 301 10/9/2014 8:39 AM
Organization: National Fire Protection Assoc
Street Address:
City:
State:
Zip:
Submittal Date: Wed Jul 02 07:31:37 EDT 2014
Committee Statement
CommitteeStatement:
As part of the commodity classification task groups review of the table A.5.6.3, all of the individual commodity tablesare being updated as well. This table is intended to correlate with the revised Table A.5.6.3.
ResponseMessage:
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
261 of 301 10/9/2014 8:39 AM
Product Heading Product
Film Rolls,
Including
Photographic
Film; 35 mm metal film
cartridges in polyethylene cans;
cartoned
Film Rolls,
Including
Photographic
Photographic paper; sheets;
bagged in polyethylene; cartoned
Flammable /
Combustible
Liquids
Aerosol; Level 1
Flammable /
Combustible
Liquids
Liquids; over 20 and up to 50
percent alcohol (e.g. alcoholic
beverages, hair spray); up to 1
gallon (3.8 L) glass bottles or
jars; in racks; cartoned
Food Products -
Frozen
Frozen foods; plastic trays
Food Products -
Non-Frozen
Butter (stick or whipped spread)
or margarine (up to 50 percent
oil)
Food Products -
Non-Frozen
Butter; whipped spread
Food Products -
Non-Frozen
Dry foods (such as baked goods,
candy, cereals, cheese,
chocolate, cocoa, coffee,
grains, granular sugar, nuts,
etc.); bagged or cartoned
Food Products -
Non-Frozen
Meat; fresh; plastic trays
Furniture and
Bedding
Furniture; wood (e.g. doors,
windows, cabinets, etc.); no
plastic coverings or foam
cushioning
Furniture and
Bedding
Mattress, Standard box spring
Box spring; standard (minimal
plastic materials)
Housing
Materials /
Appliances
Appliances; no appreciable
plastic exterior trim (interior
of unit can have appreciable
plastic)
Housing
Materials /
Appliances
Roofing shingles; asphalt-coated
fiberglass
Miscellaneous
Charcoal; standard (non-mineral
spirit impregnated); bagged
Miscellaneous
Leather; finished products (e.g.
shoes, jackets, gloves, bags,
luggage, belts)
MiscellaneousShock absorbers; plastic dust
cover
Miscellaneous Skis, wood
Miscellaneous Tobacco products; cartoned
Paper Products
Cartons (i.e. cardboard flats);
corrugated; unassembled in neat
piles
Paper Products
Cellulosic paper products;
nonwax-coated (e.g. books,
cardboard games, cartoned tissue
products, magazines, newspapers,
paper cups, paper plates, paper
towels, plastic-coated paper
food containers, stationary)
Paper Products
Rolled; medium or heavyweight;
in storage racks or on-side
Paper ProductsTissue products; plastic-
wrapped; cartoned
Plastic / RubberMelamine (melamine formaldehyde)
Plastic / RubberPCTFE
(polychlorotrifluoroethylene)
Plastic / RubberPhenolic
Plastic / RubberPTFE (polytetrafluoroethylene)
Plastic / RubberPVC (polyvinyl chloride)
products
Plastic / RubberPVC resins; bagged
Plastic / RubberPVDC (polyvinylidene chloride)
Plastic / RubberPVDF (polyvinylidene fluoride)
Plastic / RubberUrea (urea formaldehyde)
Textile
Materials /
Products
Cloth; natural fibers; baled
Textile
Materials /
Products
Clothing; natural fibers (e.g.
wool, cotton) and viscose
Textile
Materials /
Products
Cotton; cartoned
Textile
Materials /
Products
Diapers; cotton or linen
Textile
Materials /
Products
Fabric; synthetic (except rayon
and nylon); up to 50/50 blend
Textile
Materials /
Products
Thread or yarn; synthetic
(except rayon and nylon); up to
50/50 blend; wood or paper
spools
Wire / Cable /
Spools
Spools; wood; empty
Wood Products
Wood products (e.g. fiberboard,
lumber, particle board, plywood,
pressboard with smooth ends and
edges); unbundled or non-solid
blocks
Wood Products
Wood products (e.g. toothpicks,
clothespins and hangers);
cartoned
Second Revision No. 155-NFPA 13-2014 [ Section No. A.5.6.3.4 ]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
262 of 301 10/9/2014 8:39 AM
A.5.6.3.4
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
263 of 301 10/9/2014 8:39 AM
See Table A.5.6.3.4.
Table A.5.6.3.4 Examples of Class IV Commodities
Product Heading Product
Empty Containers PET, bottles or jars
Film Rolls, Including Photographic Film; rolls in polycarbonate plastic cassettes; cartoned
Flammable / Combustible Liquids Liquids; over 20 and up to 50 percent alcohol (e.g. alcoholic beverages, hair spray);up to 1 gallon (3.8 L) glass bottles or jars; palletized; cartoned
Liquids; over 20 and up to 50 percent alcohol (e.g. alcoholic beverages, hair spray);up to 1 gallon (3.8 L) plastic bottles or jars; cartoned
Nail polish; up to 2 oz (59 ml) glass bottles or jars; cartoned
Furniture and Bedding Furniture; wood; plastic coverings nonexpanded plastic trim
Noncombustible LiquidsLiquids or semi liquids; PET containers greater than 5 gallon (18.9 L) having anominal wall thickness greater than 0.25 in (6 mm)
Paper Products Cartons (i.e. cardboard flats); corrugated; partially assembled
Cellulosic paper products; wax-coated (e.g. paper plates, cups, etc.); nested;cartoned
Table A.5.6.3.4(b) Examples of Class IV Commodities
Ammunition
Small arms, shotgun
- Packaged, cartoned
Bottles, Jars
Empty, cartoned
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
264 of 301 10/9/2014 8:39 AM
- Plastic PET (polyethylene terephthalate)
Filled noncombustible powders
- Plastic, cartoned [less than 1 gal (3.8 L)]
Cartons
Corrugated
- Partially assembled
Cloth
Cartoned and not cartoned
- Synthetic a
Diapers
Disposable with plastics and nonwoven fabric (in cartons)
Fiberglass Insulation
- Paper-backed rolls, bagged or unbagged
Furniture
Wood
- With plastic coverings
Liquor
100 proof or less, 1 gal (3.8 L) or less, cartoned
- Glass (palletized) b
- Plastic bottles
Matches
Packaged, cartoned
- Paper
Nail Polish
1 oz to 2 oz (29.6 mL to 59.1 mL) glass, cartoned
Paints
Friction-top cans, cartoned
- Oil based
Paper, Rolled
In racks
- Lightweight
Paper, Waxed
Packaged in cartons
Pharmaceuticals
Pills, powders
- Plastic bottles, cartoned
Photographic Film
- Rolls in polycarbonate plastic cassettes, bulk wrapped in cardboard boxes
PVA (polyvinyl alcohol) Resins
Bagged
Rags
Baled
- Synthetic fibers
Rubber
Natural, blocks in cartons
Shingles
Asphalt-impregnated felt
Skis
Foam core
Textiles
Synthetics (except rayon and nylon) —
50/50 blend or less
- Thread, yarn on plastic spools
Synthetics (except rayon and nylon) — greater than 50/50 blend
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
265 of 301 10/9/2014 8:39 AM
- Thread, yarn on wood or paper spools
- Fabrics
Rayon and nylon
- Baled fiber
- Thread, yarn on wood or paper spools
- Fabrics
Vinyl Floor Coverings
Tiles in cartons
Wax-Coated Paper
Cups, plates
- Boxed or packaged inside cartons (emphasis is on packaging)
Wire
- Bare wire on plastic spools in cardboard boxes on wood skids
- Single- or multiple-layer PVC-covered wire on plastic spools in cardboard boxes on wood skids
- Single, multiple, or power cables (PVC) on large plastic spools
Wood Products
Patterns
a Tests clearly indicate that a synthetic or synthetic blend is considered greater than Class III.
b Where liquor is stored in glass containers in racks, it should be considered a Class III commodity; where it is palletized, itshould be considered a Class IV commodity.
Supplemental Information
File Name Description
Table_A.5.6.3.4_rev_1_.xlsx
Submitter Information Verification
Submitter Full Name: Matthew Klaus
Organization: National Fire Protection Assoc
Street Address:
City:
State:
Zip:
Submittal Date: Wed Jul 02 07:33:29 EDT 2014
Committee Statement
CommitteeStatement:
As part of the commodity classification task groups review of the table A.5.6.3, all of the individual commodity tablesare being updated as well. This table is intended to correlate with the revised Table A.5.6.3.
ResponseMessage:
Public Comment No. 308-NFPA 13-2014 [Section No. A.5.6.3.4]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
266 of 301 10/9/2014 8:39 AM
Product Heading Product
Empty ContainersPET, bottles or jars
Film Rolls,
Including
Photographic
Film; rolls in polycarbonate
plastic cassettes; cartoned
Flammable /
Combustible
Liquids
Liquids; over 20 and up to 50
percent alcohol (e.g. alcoholic
beverages, hair spray); up to 1
gallon (3.8 L) glass bottles or
jars; palletized; cartoned
Flammable /
Combustible
Liquids
Liquids; over 20 and up to 50
percent alcohol (e.g. alcoholic
beverages, hair spray); up to 1
gallon (3.8 L) plastic bottles
or jars; cartoned
Flammable /
Combustible
Liquids
Nail polish; up to 2 oz (59 ml)
glass bottles or jars; cartoned
Furniture and
Bedding
Furniture; wood; plastic
coverings nonexpanded plastic
trim
Furniture and
Bedding
Mattress, Standard box spring
Box spring; wrapped in plastic
cover
Housing
Materials /
Appliances
Fiberglass insulation; paper-
backed rolls; bagged or unbagged
Housing
Materials /
Appliances
Floor coverings; tiles, vinyl,
stacked tiles
Housing
Materials /
Appliances
Paint; oil-based; friction-top
metal containers; cartoned
Housing
Materials /
Appliances
Roofing shingles; asphalt-
impregnated felt
MiscellaneousAmmunition; small arms and
shotgun; cartoned
Miscellaneous
Skis; composite materials
(plastic, fiberglass, foam,
etc.)
Noncombustible
Liquids
Liquids or semi liquids; PET
containers greater than 5 gallon
(18.9 L) having a nominal wall
thickness greater than 0.25 in
(6 mm)
Paper Products
Cartons (i.e. cardboard flats);
corrugated; partially assembled
Paper Products
Cellulosic paper products; wax-
coated (e.g. paper plates, cups,
etc.); nested; cartoned
Paper Products Matches; paper-type; cartoned
Paper ProductsRolled; lightweight; in storage
racks
Plastic / RubberCellulose Acetate
Plastic / RubberChloroprene rubber
Plastic / Rubber
ECTFE (ethylene-chlorotrifluoro-
ethylene copolymer)
Plastic / Rubber
ETFE (ethylene-
tetrafluoroethylene copolymer)
Plastic / RubberFEP (fluorinated ethylene-
propylene copolymer)
Plastic / RubberSilicone rubber
Powders / Pills
Pharmaceuticals pills; plastic
bottles or jars; cartoned
Powders / PillsPolyvinyl Alcohol (PVA) resins;
bagged
Powders / Pills
Powders; noncombustible; plastic
bottles or jars up to 1 gallon
(3.8 L) capacity; cartoned
Textile
Materials /
Products
Cloth; synthetic cloth
Textile
Materials /
Products
Diapers; plastic or nonwoven
fabric; cartoned
Textile
Materials /
Products
Fabric; rayon and nylon
Textile
Materials /
Products
Fabric; synthetic (except rayon
and nylon); greater than 50/50
blend
Textile
Materials /
Products
Fibers; rayon and nylon; baled
Textile
Materials /
Products
Fibers; synthetic; baled
Textile
Materials /
Products
Thread or yarn; rayon and nylon;
wood or paper spools
Textile
Materials /
Products
Thread or yarn; synthetic
(except rayon and nylon);
greater than 50/50 blend; paper
or wood spools
Textile
Materials /
Products
Thread or yarn; synthetic
(except rayon and nylon); up to
50/50 blend; plastic spools
Wire / Cable /
Spools
Wire or cable; PVC insulated;
plastic spools
Wire / Cable /
Spools
Wire; bare; plastic spools; on
wood skids, cartoned
Wood Products Wood patterns
Second Revision No. 156-NFPA 13-2014 [ Section No. A.5.6.4.1 ]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
267 of 301 10/9/2014 8:39 AM
A.5.6.4.1
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
268 of 301 10/9/2014 8:39 AM
See Table A.5.6.4.1.
Table A.5.6.4.1 Examples of Group A Plastic Commodities
Product Heading Product Expanded / Nonexpanded
BatteriesVehicle; any size (e.g. automobile or truck);empty plastic casing
Nonexpanded
Vehicle; large (e.g. truck or larger); dry or wet(excludes lithium-ion and other cellscontaining combustible electrolyte) cells
Nonexpanded
Empty Containers Rigid plastic (not including PET) Nonexpanded
Film Rolls, IncludingPhotographic
Film (polypropylene, polyesther,polyethylene); rolled on any reel type
Liquids; up to 20 percent alcohol (e.g.alcoholic beverages, flavoring extracts);greater than 5 gallon (18.9 L) plasticcontainers with wall thickness greater than1 ⁄4 in. (6 mm)
Nonexpanded
Nail polish; up to 2 oz (59 ml) plastic bottlesor jars; cartoned
Nonexpanded
Food Products - Non-Frozen Margarine; over 50 and up to 80 percent oil Nonexpanded
Milk; any container; stored in solid plasticcrates
Furniture and Bedding Furniture and bedding; with foam cushioning Expanded
Mattress; foam (in finished form) Expanded
Housing Materials /Appliances
Carpet tiles; cartoned Nonexpanded
Floor coverings; vinyl; rolled Nonexpanded
Miscellaneous Charcoal; mineral spirit impregnated; bagged Expanded
Toys; stuffed; foam or synthetic Expanded
Noncombustible Liquids Liquids or semi-liquids; plastic (except PET)containers greater than 5 gallon (18.9 L)capacity having a nominal wall thicknessgreater than 0.25 in. (6 mm)
Table A.5.6.4.1(b) Examples of Group A Plastic Commodities
Batteries
Truck or larger
- Empty or filled a
Bottles, Jars
Empty, cartoned
- Plastic (other than PET), any size
Filled noncombustible liquids
- Plastic, open or solid plastic crates b
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
270 of 301 10/9/2014 8:39 AM
Filled noncombustible powders
- Plastic, cartoned or exposed [greater than 1 gal (3.8 L)]
- Plastic, solid plastic crates
- Plastic, open plastic crates
Candles
Packaged, cartoned
- Treat as expanded plastic
Carpet Tiles
Cartoned
Cartons
Wax coated, single walled
Diapers
Disposable with plastics and nonwoven fabric (exposed), plastic wrapped
Furniture
Wood
- With foam plastic cushioning
Lighters
Butane
- Blister-packed, cartoned
Margarine
Between 50 percent and 80 percent oil (in any packaging)
Matches
Packaged, cartoned
- Wood
Mattresses
Foam (in finished form)
Milk
Containers in plastic crates
Nail Polish
1 oz to 2 oz (29.6 mL to 59.1 mL) plastic bottles, cartoned
Paper Products
Tissue products, exposed and plastic wrapped
Plastic Containers
- Combustible or noncombustible solids in plastic containers and empty plastic containers
- Noncombustible liquids or semiliquids (such as ketchup) in plastic containers with nominal wall thickness greater than 1 ⁄4in. (6.4 mm) and larger than 5 gal (18.9 L) capacity
Polyurethane
Cartoned or exposed expanded
Rubber
Synthetic
Stuffed Toys
Foam or synthetic
Textiles
Synthetics (except rayon and nylon) —
50/50 blend or less
- Baled fiber
Synthetics (except rayon and nylon) — greater than 50/50 blend
- Baled fiber
- Thread, yarn on plastic spools
Rayon and nylon
- Thread, yarn on plastic spools
Vinyl-Coated Fabric
Cartoned
Vinyl Floor Coverings
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
271 of 301 10/9/2014 8:39 AM
Rolled
Wax-Coated Paper
Cups, plates
- Loose inside large cartons
Wax
Paraffin/petroleum wax, blocks, cartoned
Wire
Bulk storage of empty plastic spools
a Most batteries have a polypropylene case and, if stored empty, should be treated as a Group A plastic. Truck batteries, evenwhere filled, should be considered a Group A plastic because of their thicker walls.
b As the openings in plastic crates become larger, the product behaves more like Class III. Conversely, as the openingsbecome smaller, the product makeup behaves more like a plastic.
Supplemental Information
File Name Description
Table_A.5.6.4.1_rev1_.xlsx
Submitter Information Verification
Submitter Full Name: Matthew Klaus
Organization: National Fire Protection Assoc
Street Address:
City:
State:
Zip:
Submittal Date: Wed Jul 02 07:34:55 EDT 2014
Committee Statement
CommitteeStatement:
As part of the commodity classification task groups review of the table A.5.6.3, all of the individual commodity tablesare being updated as well. This table is intended to correlate with the revised Table A.5.6.3.
ResponseMessage:
Public Comment No. 309-NFPA 13-2014 [Section No. A.5.6.4.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
272 of 301 10/9/2014 8:39 AM
Product Heading
Product Nonexpa
nded or
Expande
d
Batteries
Vehicle; any size (e.g.
automobile or truck); empty
plastic casing
Nonexpa
nded
Batteries
Vehicle; large (e.g. truck or
larger); dry or wet (excludes
lithium-ion and other cells
containing combustible
electrolyte) cells
Nonexpa
nded
Empty ContainersRigid plastic (not including
PET)
Nonexpa
nded
Film Rolls,
Including
Photographic
Film (polypropylene, polyesther,
polyethylene); rolled on any
reel type
Nonexpa
nded
Flammable /
Combustible
Liquids
Lighters; butane; blister-
packed; cartoned
Nonexpa
nded
Flammable /
Combustible
Liquids
Liquids; up to 20 percent
alcohol (e.g. alcoholic
beverages, flavoring extracts);
greater than 5 gallon (18.9 L)
plastic containers with wall
thickness greater than ¼ in. (6
mm)
Nonexpa
nded
Flammable /
Combustible
Liquids
Nail polish; up to 2 oz (59 ml)
plastic bottles or jars;
cartoned
Nonexpa
nded
Food Products -
Non-Frozen
Margarine; over 50 and up to 80
percent oil
Nonexpa
nded
Food Products -
Non-Frozen
Milk; any container; stored in
solid plastic crates
Nonexpa
nded
Food Products -
Non-Frozen
Snack foods (e.g. potato chips);
plasticized aluminum bags;
cartoned
Nonexpa
nded
Furniture and
Bedding
Furniture and bedding; wood,
with foam cushioning
Expande
d
Furniture and
Bedding
Mattress; foam (in finished
form)
Expande
d
Housing
Materials /
Appliances
Carpet tiles; cartoned Nonexpa
nded
Housing
Materials /
Appliances
Floor coverings; vinyl; rolled Nonexpa
nded
MiscellaneousCharcoal; mineral spirit
impregnated; bagged
Expande
d
MiscellaneousToys; stuffed; foam or synthetic Expande
Second Revision No. 80-NFPA 13-2014 [ New Section after A.12.1.3 ]
A.12.1.3.1.4
In the example shown in Figure A.12.1.3.1.4 , the maximum ceiling height shown is 30 ft (9.1 m). Sprinkler protection underthe highest part of the ceiling must be designed for that height to a point at least 15 ft (4.6 m) beyond where the ceiling heightdrops to 25 ft (7.6 m). Sprinkler protection beyond that point can be designed for a 25 ft (7.6 m) ceiling.
Figure A.12.1.3.1.4 Extended Sprinkler Coverage Under Sloped Ceilings.
Supplemental Information
File Name Description
Fig_A.12.1.3.1.4_SR_.jpg New Figure
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 12:51:11 EDT 2014
Committee Statement
CommitteeStatement:
This revision clarifies the proper design height requirements for sprinklers under a roof with a pitch of 2:12 orless.
Response Message:
Public Comment No. 332-NFPA 13-2014 [New Section after A.12.1.3]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
288 of 301 10/9/2014 8:39 AM
Second Revision No. 107-NFPA 13-2014 [ New Section after A.16.1.4.1 ]
A.16.1.6.7
The adjustments in 16.2.1.3.4 apply to solid shelves where the minimum required level of in-rack sprinklers from an openrack option is exceeded.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 18:03:46 EDT 2014
Committee Statement
CommitteeStatement:
This clarifies that although additional sprinklers are required due to the solid shelving, the reduction to ceiling densityallowed in 16.2.1.3.4 for additional in-rack sprinklers still applies.
ResponseMessage:
Public Comment No. 83-NFPA 13-2014 [New Section after A.16.1.4.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
289 of 301 10/9/2014 8:39 AM
Second Revision No. 108-NFPA 13-2014 [ Section No. A.16.2.1.3.4.6 ]
A.16.2.1.3.4.6
It is not the intent that an in-rack sprinkler be installed above the top-tier of storage when utilizing “in-rack sprinklers in everytier.”
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Thu Jun 26 18:04:18 EDT 2014
Committee Statement
CommitteeStatement:
The annex note makes clear that the intent of the committee to require in rack sprinklers in every tier does not includean in-rack sprinkler above the top tier of storage, which is protected by the ceiling sprinklers. As an annex note cannotoverride the body of the standard, this wording should be in the body of the standard
ResponseMessage:
Public Comment No. 305-NFPA 13-2014 [Section No. A.16.2.1.3.4.6]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
290 of 301 10/9/2014 8:39 AM
Second Revision No. 130-NFPA 13-2014 [ Section No. A.23.3.2 ]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
291 of 301 10/9/2014 8:39 AM
A.23.3.2
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
292 of 301 10/9/2014 8:39 AM
See Figure A.23.3.2(a) through Figure A.23.3.2(d).
Figure A.23.3.2(a) Summary Sheet.
Figure A.23.3.2(b) Hydraulic Calculation Example (Plan View and Elevation View).
Figure A.23.3.2(c) Hydraulic Calculations.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
293 of 301 10/9/2014 8:39 AM
Figure A.23.3.2(d) Hydraulic Graph.
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
294 of 301 10/9/2014 8:39 AM
Node 4 includes tee at top and bottom of riser nipple included with branch line due to consistent pipe size from the perviousnode.
Supplemental Information
File Name Description
Figure23_3_2c.xlsx Note to art - do not include logo from Sprinkler Academy in the standard.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Jun 27 19:29:40 EDT 2014
Committee Statement
CommitteeStatement:
In lieu of providing the note at the bottom of the figures as was provided during the first draft meeting, FigureA.23.3.2(C) was revised to more accurately outline the calculations for the system shown in Fig A.23.3.2(b) anddescribed in Fig A.23.3.2(a).
ResponseMessage:
Public Comment No. 186-NFPA 13-2014 [Section No. A.23.3.2]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...
295 of 301 10/9/2014 8:39 AM
Pipe Analysis Hydraulic Calculation Forms
Node
1Elev 1
K
factor
flow added -
this step (q)Nominal ID fittings -
qty and
equiv
length
L ft C Pt total
notesF ft Pf per
foot
Pe elev
ft Pf frictT
1 16.0 q 19.5Nom
ID1
Node
2Elev 2 total flow (Q) Actual ID
F 00.124
Pe 0.0
L 13 C=120 Pt 12.1
13 Pf 1.62 16.0 Q 19.5
Act
ID
2 16.0 5.60 q 20.7Nom
ID
1.049T
13.7
Q = 5.6 x sq rt 13.7 = 20.7gpmF 00.125
Pe
1 1/4L 13 C=120 Pt
13 Pf 1.61.38
T
Q= 130sq ft x 0.15dens =19.5gpm
P = (19.5/5.6)2 = 12.1
3 16.0 Q 40.2Act
ID
3 16.0 5.60 q 21.9Nom
ID15.3
Q = 5.6 x sq rt 15.3 = 21.9gpmF 00.131
Pe
1 1/2L 13 C=120 Pt
13 Pf 1.71.61
T4 16.0 Q 62.1
Act
ID
4 16.0 5.60 q 23.1Nom
ID17.0
Q = 5.6 x sq rt 15.7 = 23.1gpm
Pe = 1 ft x .433 = 0.4 psi2T = 16 F 16
0.236Pe 0.4
1 1/2L 20.5 C=120 Pt
36.5 Pf 8.61.61
TCM1 15.0 Q 85.2
Act
ID
CM1 15.0 -- q --Nom
ID26.0
Keq = 85.2gpm / sq rt 26psi
Branchline Keq = 16.71F 0
0.070Pe 0.0
2L 10 C=120 Pt
10 Pf 0.72.067
TCM2 15.0 Q 85.2
Act
ID
CM2 15.0 16.71 q 86.3Nom
ID26.7
Q = 16.71 x sq rt 26.7 = 86.3gpm
in Branchline #2F 0
0.107Pe 0.0
2.5L 10 C=120 Pt
10 Pf 1.12.469
TCM3 15.0 Q 171.5
Act
ID
CM3 15.0 16.71 q 88.1Nom
ID27.8
Q = 16.71 x sq rt 27.8 = 88.1gpm
in Branchline #3
AV = 15
F 00.231
Pe 0.0
2.5L 70 C=120 Pt
70 Pf 16.22.469
T
44.0
Pe = 15 ft x 0.433psi = 6.5psiF 21
CM4 15.0 Q 259.6Act
ID
CM4 15.0 -- q --Nom
ID
0.081Pe 6.5
3E = 5 L 119 C=120 Pt
140 Pf 11.23.068
GV = 1 TBOR 1.0 Q 259.6
Act
ID
BOR 1.0 -- q __Nom
ID61.7 C=150Adj F x 1.51 = 31.7ft
Sch40 Adj F x (Act ID/ S40 ID)4.87
31.7 x (2.98/3.068)4.87
=
31.7ft x 0.869 = 27.5ft
GV = 1 F 27.50.061
Pe 0.0
3E = 5 L 50 C=150 Pt
77.5 Pf 4.73.395
T = 15 TSRC 0.0 Q 259.6
Act
ID
qNom
ID66.4
F Pe
L C Pt
PfT
Pf
QAct
ID
qNom
ID
QAct
ID
F Pe
L C Pt
T
Second Revision No. 117-NFPA 13-2014 [ New Section after A.23.4.1 ]
A.23.4.1.4
NFPA 13 does not provide a specific velocity limitation for the use of the Hazen-Williams formula. This is, in part, due to anexpectation that excessive friction loss values will result in increasing pipe sizes, thereby serving as an inherent limit onvelocity. However, the fact that NFPA 13 does not provide a specific limit should not be taken as an endorsement that theformula can be used for any velocity of water flow. The formula was empirically determined using "normal" conditions. Whenthe velocity in the pipe exceeds that which was used to determine the formula, the formula might no longer be valid. Therehas been some research performed (Huggins 1996) in which results using the Hazen-Williams formula and the Darcy-Weisbach formula were compared, and the conclusion was that a specific velocity limit applied to all pipe sizes is notappropriate.
Submitter Information Verification
Submitter Full Name: [ Not Specified ]
Organization: [ Not Specified ]
Street Address:
City:
State:
Zip:
Submittal Date: Fri Jun 27 14:34:13 EDT 2014
Committee Statement
CommitteeStatement:
The current text could be read to say that there is no reason to limit the velocity when using the Hazen-Williamsformula.
Response Message:
Public Comment No. 341-NFPA 13-2014 [New Section after A.23.4.1]
National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentPara...