THE UNIVERSITY OF NEW SOUTH WALES SCHOOL OF PHOTOVOLTAIC AND RENEWABLE ENERGY ENGINEERING Thermal analysis of a prefabricated building model Naman Uppal Bachelor of Engineering in Renewable Energy Engineering Course Code: SOLA4911 Thesis Part B Submission Date: June 2015 Supervisor: Associate Professor Alistair Sproul Assessor: Dr. Santosh Shrestha
This document is posted to help you gain knowledge. Please leave a comment to let me know what you think about it! Share it to your friends and learn new things together.
Transcript
THE UNIVERSITY OF NEW SOUTH WALES
SCHOOL OF PHOTOVOLTAIC AND RENEWABLE ENERGY
ENGINEERING
Thermal analysis of a prefabricated building model
Naman Uppal
Bachelor of Engineering in Renewable Energy Engineering
Course Code: SOLA4911 Thesis Part B
Submission Date: June 2015
Supervisor: Associate Professor Alistair Sproul
Assessor: Dr. Santosh Shrestha
! II!
Certificate of originality
I declare that this assessment item is my own work, except where acknowledged, and
has not been submitted for academic credit elsewhere, and acknowledge that the
assessor of this item may, for the purpose of assessing this item:
Reproduce this assessment item and provide a copy to another member of the
University; and/or,
Communicate a copy of this assessment item to a plagiarism checking service (which
may then retain a copy of the assessment item on its database for the purpose of future
plagiarism checking).
I certify that I have read and understood the University Rules in respect of Student
Academic Misconduct.
Signed:
Date: 02/06/15
! III!
I. Abstract
This thesis conducts a thermal analysis on the Hadrian Villa, an architecturally
designed two-bedroom residence that uses the Origination &U system. The &U
system is a prefabricated modular building model. The skeletal structure for the &U
design is made using lightweight fiber reinforced plastic. Heat transfer is a common
issue and concern for lightweight prefabricated housing, as is explored further in this
thesis. The main objective of this thesis is to understand how the Hadrian Villa will
perform in Australian climatic conditions and how low energy building techniques
can be implemented to reduce the thermal energy requirements for the design.
The analysis for this thesis is conducted in two sections. Firstly, preliminary
calculations are conducted to determine the thermal resistance of the wall panels.
These calculations indicate that the wall panels have an R-Value of 2.25m2K/W to
2.57m2K/W, varying according to the design choices of each face of the building.
Secondly, these values along with material and construction data are applied to the
AccuRate building software, to calculate the total thermal energy load of the building.
It is found that the basic Above Ground design has a base thermal energy load of
70.4MJ/m2.annum, which is classified as below thermal performance standard
established by the BASIX thermal comfort protocol. Improvements are implemented
to increase the thermal efficiency of the design. Using low energy building
techniques, the building is improved to a minimum thermal energy load of
30.3MJ/m2.annum. This brings the building clearly within thermal protocol
requirements of 39MJ/m2.annum.
To determine where this model is applicable, the Hadrian Villa simulations are tested
across different cities of Australia using the AccuRate software. It is found that design
performs best in Sydney, Brisbane and Wollongong, with a minimum thermal energy
load achieved in Sydney, as a subtropical climate. The Hadrian Villa is found to
perform worst in Darwin.
! IV!
II. Acknowledgements
The author would like to acknowledge some of the people without whom this thesis
would not have been possible.
Firstly, the author would like to extend his sincere gratitude to the supervisor of this
thesis, Associate Professor Alistair Sproul (Lecturer and Postgraduate Coordinator,
University of New South Wales). His lectures on Low Energy Buildings are what
sparked the author’s interest in this area of study. Alistair’s readiness to work with
students and industry are what allowed the author to find a thesis that related to a real
world project. His consistent reminders for meetings, encouragement to explore new
and different ideas, vast theoretical and industry knowledge, combine with unending
humour and relaxed attitude are what pushed the author to carry on through each
stage of the thesis.
Secondly, the author would like to thank the team at Pidcock and Origination.
Caroline Pidcock (Director of Pidcock Sustainability + Architecture and Origination
Pty. Ltd.) and Fergal White (Associate Director of Pidcock Sustainability +
Architecture) were an immense help throughout the thesis. The author truly
appreciates them offering their office space and resources, regular time for meetings,
consistent feedback and inclusion of the author in office festivities. It was a pleasure
for the author to be a part of the &U project, and he wishes the greater team
maximum success in this venture.
Lastly but importantly, the author would like to extend a hearty appreciation to his
mentors, friends and family. To each of them who spent the time to understand the
thesis work, ensured the author kept calm and balanced and provided their love and
Table 8-10: Fractional calculations for hook sections
Resistance R20 R21 R22
Total R 0.390333333 0.826656863 0.390333333
Thickness (mm) 13.25 103.5 13.25
Fraction 0.073611111 0.575 0.073611111
Fraction*U 0.188585255 0.695572765 0.188585255
Table 8-11: Fractional calculation of the square post section
East face
Area (m2)
R-Value
(m2K/W) Fraction
Fraction * U
(W/m2K)
Overall R Value
(m2K/W)
Wall 19.600 2.977 0.772 0.259
Window 2.000
Post 2.196 1.161 0.086 0.074
Beam 3.600 1.829 0.142 0.078
Sum 25.396 0.411 2.432
Table 8-12: East Wall R-Value Calculations
South face
Area (m2)
R-Value
(m2K/W) Fraction
Fraction * U
(W/m2K)
Overall R Value
(m2K/W)
! 81!
Wall 34.800 2.977 0.847 0.285
Window 7.400
Post 2.664 1.161 0.065 0.056
Beam 3.600 1.829 0.088 0.048
Sum 41.064 0.388 2.574
Table 8-13: South Wall R-Value Calculations
West face
Area (m2)
R-Value
(m2K/W) Fraction
Fraction * U
(W/m2K)
Overall R Value
(m2K/W)
Wall 14.800 2.977 0.753 0.253
Window 6.800
Post 2.664 1.161 0.136 0.117
Beam 2.196 1.829 0.112 0.061
Sum 19.660 0.431 2.322
Table 8-14: West Face R-Value Calculations
!Figure 8-1: North Face scale drawing
! 82!
!Figure 8-2: East Face scale drawing
!Figure 8-3: West Face scale drawing
!
! 83!
!Figure 8-4: South Face scale drawing
!The final section of the appendices compiles the summaries of all AccuRate run
simulations. They are ordered chronologically.
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: AG and column insD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
14.7 50.8 10.9 76.5 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
12.4 42.7 9.2 64.3 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
4.2 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 4:53 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: AG beam insulatedD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
15.6 50.9 11.0 77.5 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
13.1 42.8 9.3 65.2 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
4.1 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 4:52 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: AG Beam Post InsulationD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
14.8 51.4 11.0 77.2 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
12.5 43.2 9.2 64.9 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
4.2 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 4:57 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: double glaz AGD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
15.6 25.0 6.0 46.6 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
13.1 21.0 5.0 39.1 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
5.9 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 5:04 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: Best AG more GlazingD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
15.0 22.0 5.7 42.8 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
12.6 18.5 4.8 35.9 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.4 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 5:02 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: Improved floor BattsD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
15.4 18.7 5.3 39.3 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
12.9 15.7 4.4 33.0 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.7 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 4:58 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: Improved InsulationD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
15.3 18.3 5.2 38.8 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
12.9 15.3 4.4 32.6 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.7 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 4:58 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: Improved Windows OnlyD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
16.5 15.4 4.8 36.8 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
13.9 13.0 4.0 30.9 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.9 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 4:58 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: more Pcm AGD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
14.8 16.6 4.9 36.4 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
12.4 14.0 4.2 30.6 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.9 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 6:14 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: Improved north windowsD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
16.3 16.9 5.1 38.2 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
13.7 14.2 4.3 32.1 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.8 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 4:59 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: Reduced Floor BattsD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
17.5 18.6 5.3 41.4 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
14.7 15.6 4.4 34.8 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.5 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 4:59 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: Reduced High Level GlazD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
16.5 18.4 5.2 40.1 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
13.8 15.5 4.4 33.7 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.6 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 4:57 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: AG 0.3 Resin 1D e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
15.5 18.4 5.2 39.2 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
13.0 15.5 4.4 32.9 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.7 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 5:00 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: AG 0.3 Resin 2D e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
15.2 17.1 5.0 37.3 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
12.8 14.3 4.2 31.3 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.9 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 5:00 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: Base Design Above GrounD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
20.3 52.6 10.8 83.7 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
17.1 44.2 9.1 70.4 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
3.9 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 4:50 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: Best with Concrete flooD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
10.4 14.9 4.7 30.1 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
8.8 12.6 4.0 25.3 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
7.6 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 5:00 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: Best Conc more GlazD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
4.2 10.1 3.5 17.8 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
3.5 8.5 3.0 15.0 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
8.7 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 5:03 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: Best Conc floor no insuD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
3.6 6.5 2.7 12.8 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
3.0 5.5 2.2 10.8 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
9.3 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 5:01 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: 0.3 resinD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
3.3 5.8 2.6 11.7 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
2.8 4.9 2.2 9.8 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
9.4 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 4:56 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: Basic conc floorD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
5.8 25.4 7.5 38.7 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
4.9 21.4 6.3 32.6 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.7 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 5:02 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: CONS beam col insD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
10.6 23.7 6.2 40.4 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
8.9 20.0 5.2 34.1 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.6 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 4:53 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: Best 100mm conc floor D e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
4.6 6.9 2.6 14.1 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
3.9 5.8 2.2 11.9 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
9.1 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 5:01 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: Reduced Glaz best conccD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
4.3 6.9 2.6 13.9 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
3.6 5.8 2.2 11.7 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
9.2 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 5:01 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: half water wallD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
3.6 6.1 2.7 12.5 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
3.0 5.2 2.3 10.5 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
9.3 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 4:56 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: improved floor insulatiD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
3.3 5.7 2.6 11.6 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
2.7 4.8 2.2 9.8 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
9.4 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 4:55 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: improved wall insulatioD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
3.3 5.7 2.6 11.6 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
2.7 4.8 2.2 9.8 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
9.4 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 4:55 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: improved windowsD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
3.7 6.0 2.7 12.4 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
3.1 5.1 2.3 10.5 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
9.3 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 4:54 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: reduced glazingD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
4.0 7.1 2.9 13.9 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
3.4 6.0 2.4 11.7 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
9.2 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 4:54 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: Concrete floor 1stD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
7.0 27.5 7.6 42.1 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
5.9 23.2 6.4 35.5 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.4 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 4:51 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: concrete floor 2ndD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
15.7 26.7 6.5 48.8 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
13.2 22.5 5.5 41.1 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
5.8 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 4:51 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: concrete floor 3rdD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
15.7 26.7 6.5 48.8 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
13.2 22.5 5.5 41.1 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
5.8 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 4:52 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: concrete floor 4thD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
6.7 11.5 4.1 22.4 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
5.6 9.7 3.5 18.9 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
8.3 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 4:52 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: fixed louvreD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
16.5 15.8 4.8 37.2 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
13.9 13.3 4.0 31.2 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.9 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 5:04 am, 02/06/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 5000 Climate Zone: 16Design Option: Concrete floor 1stD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
42.6 43.7 2.0 88.3 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
35.9 36.8 1.7 74.4 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.8 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
480 325 227 165 125 96 70 46 22 3
Page 1 of 1Printed 12:12 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 4000 Climate Zone: 10Design Option: Concrete floor 1stD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
2.9 27.8 10.4 41.1 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
2.4 23.2 8.6 34.2 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.9 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
203 139 97 71 55 43 34 25 17 10
Page 1 of 1Printed 12:20 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 4870 Climate Zone: 32Design Option: Concrete floor 1stD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
0.0 125.5 65.7 191.2 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
0.0 109.1 57.1 166.2 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
4.5 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
302 253 214 181 153 128 105 84 64 48
Page 1 of 1Printed 12:29 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 800 Climate Zone: 1Design Option: Concrete floor 1stD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
0.0 366.1 154.0 520.1 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
0.0 327.2 137.6 464.8 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
4.2 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
773 648 555 480 413 349 285 222 164 119
Page 1 of 1Printed 12:28 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 7000 Climate Zone: 26Design Option: Concrete floor 1stD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
171.9 0.5 0.0 172.5 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
145.1 0.4 0.0 145.6 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.2 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
723 498 354 262 202 155 113 71 31 0
Page 1 of 1Printed 12:25 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 3000 Climate Zone: 21Design Option: Concrete floor 1stD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
96.8 13.7 1.2 111.6 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
80.6 11.4 1.0 93.0 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.7 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
559 384 271 198 149 114 83 54 25 2
Page 1 of 1Printed 12:24 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 6000 Climate Zone: 13Design Option: Concrete floor 1stD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
17.0 43.3 3.7 64.1 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
14.4 36.6 3.2 54.1 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.9 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
387 251 167 118 89 70 52 34 17 4
Page 1 of 1Printed 12:15 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: Concrete floor 1stD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
7.0 27.5 7.6 42.1 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
5.9 23.2 6.4 35.5 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.4 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 12:23 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2500 Climate Zone: 56Design Option: Concrete floor 1stD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
18.3 11.3 3.5 33.1 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
15.3 9.5 2.9 27.7 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
7.9 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
284 186 125 88 66 51 39 26 14 5
Page 1 of 1Printed 12:22 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 5000 Climate Zone: 16Design Option: AG 0.3 Resin 2D e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
53.1 55.6 2.7 111.5 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
44.7 46.8 2.3 93.7 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.1 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
480 325 227 165 125 96 70 46 22 3
Page 1 of 1Printed 1:05 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 4000 Climate Zone: 10Design Option: AG 0.3 Resin 2D e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
9.7 20.7 9.6 39.9 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
8.0 17.2 7.9 33.2 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
7.1 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
203 139 97 71 55 43 34 25 17 10
Page 1 of 1Printed 1:10 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 4870 Climate Zone: 32Design Option: AG 0.3 Resin 2D e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
0.0 95.0 56.0 151.1 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
0.0 82.4 48.6 130.9 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
5.9 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
302 253 214 181 153 128 105 84 64 48
Page 1 of 1Printed 1:09 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 800 Climate Zone: 1Design Option: AG 0.3 Resin 2D e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
0.0 267.8 137.7 405.5 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
0.0 238.8 122.9 361.7 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
5.8 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
773 648 555 480 413 349 285 222 164 119
Page 1 of 1Printed 1:07 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 7000 Climate Zone: 26Design Option: AG 0.3 Resin 2D e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
144.3 2.6 0.2 147.1 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
121.4 2.2 0.2 123.8 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.7 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
723 498 354 262 202 155 113 71 31 0
Page 1 of 1Printed 1:04 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 3000 Climate Zone: 21Design Option: AG 0.3 Resin 2D e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
90.3 23.9 2.3 116.5 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
75.0 19.9 1.9 96.7 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.5 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
559 384 271 198 149 114 83 54 25 2
Page 1 of 1Printed 1:01 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 6000 Climate Zone: 13Design Option: AG 0.3 Resin 2D e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
29.5 52.9 4.1 86.5 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
24.9 44.6 3.4 72.9 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
5.8 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
387 251 167 118 89 70 52 34 17 4
Page 1 of 1Printed 1:06 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: AG 0.3 Resin 2D e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
15.2 17.1 5.0 37.3 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
12.8 14.3 4.2 31.3 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.9 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 12:56 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2500 Climate Zone: 56Design Option: AG 0.3 Resin 2D e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
28.3 14.4 3.5 46.3 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
23.6 12.0 2.9 38.5 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
7.0 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
284 186 125 88 66 51 39 26 14 5
Page 1 of 1Printed 1:11 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 5000 Climate Zone: 16Design Option: improved wall insulatioD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
31.8 16.9 1.4 50.1 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
26.8 14.2 1.2 42.3 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
8.1 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
480 325 227 165 125 96 70 46 22 3
Page 1 of 1Printed 12:36 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 4000 Climate Zone: 10Design Option: improved wall insulatioD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
1.4 8.1 4.9 14.4 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
1.2 6.7 4.1 12.0 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
9.7 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
203 139 97 71 55 43 34 25 17 10
Page 1 of 1Printed 12:38 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 4870 Climate Zone: 32Design Option: improved wall insulatioD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
0.0 65.6 48.8 114.4 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
0.0 57.0 42.4 99.4 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
7.3 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
302 253 214 181 153 128 105 84 64 48
Page 1 of 1Printed 12:30 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 800 Climate Zone: 1Design Option: improved wall insulatioD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
0.0 216.6 133.1 349.7 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
0.0 193.6 118.9 312.5 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.6 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
773 648 555 480 413 349 285 222 164 119
Page 1 of 1Printed 12:37 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 7000 Climate Zone: 26Design Option: improved wall insulatioD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
145.9 0.1 0.0 146.0 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
123.1 0.1 0.0 123.2 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.8 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
723 498 354 262 202 155 113 71 31 0
Page 1 of 1Printed 12:33 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 3000 Climate Zone: 21Design Option: improved wall insulatioD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
80.3 3.7 0.6 84.6 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
66.9 3.1 0.5 70.5 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
7.4 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
559 384 271 198 149 114 83 54 25 2
Page 1 of 1Printed 12:32 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 6000 Climate Zone: 13Design Option: improved wall insulatioD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
10.0 12.2 1.8 23.9 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
8.4 10.3 1.5 20.2 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
8.8 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
387 251 167 118 89 70 52 34 17 4
Page 1 of 1Printed 12:35 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: improved wall insulatioD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
3.3 5.7 2.6 11.6 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
2.7 4.8 2.2 9.8 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
9.4 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 12:32 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2500 Climate Zone: 56Design Option: improved wall insulatioD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
12.7 3.1 1.3 17.1 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
10.6 2.6 1.1 14.3 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
8.9 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
284 186 125 88 66 51 39 26 14 5
Page 1 of 1Printed 12:40 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 5000 Climate Zone: 16Design Option: Reduced High Level GlazD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
55.9 59.0 2.7 117.6 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
47.0 49.6 2.3 98.8 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
5.9 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
480 325 227 165 125 96 70 46 22 3
Page 1 of 1Printed 12:47 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 4000 Climate Zone: 10Design Option: Reduced High Level GlazD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
10.3 23.2 10.1 43.6 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
8.5 19.3 8.4 36.2 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.7 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
203 139 97 71 55 43 34 25 17 10
Page 1 of 1Printed 12:52 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 4870 Climate Zone: 32Design Option: Reduced High Level GlazD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
0.0 101.4 57.3 158.7 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
0.0 87.9 49.7 137.5 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
5.6 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
302 253 214 181 153 128 105 84 64 48
Page 1 of 1Printed 12:52 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 800 Climate Zone: 1Design Option: Reduced High Level GlazD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
0.0 281.1 139.3 420.4 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
0.0 250.7 124.2 375.0 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
5.6 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
773 648 555 480 413 349 285 222 164 119
Page 1 of 1Printed 12:49 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 7000 Climate Zone: 26Design Option: Reduced High Level GlazD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
150.4 3.1 0.2 153.8 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
126.6 2.6 0.2 129.4 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.6 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
723 498 354 262 202 155 113 71 31 0
Page 1 of 1Printed 12:45 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 3000 Climate Zone: 21Design Option: Reduced High Level GlazD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
94.4 25.6 2.4 122.3 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
78.3 21.2 2.0 101.5 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.4 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
559 384 271 198 149 114 83 54 25 2
Page 1 of 1Printed 12:44 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 6000 Climate Zone: 13Design Option: Reduced High Level GlazD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
31.6 57.5 4.1 93.2 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
26.6 48.4 3.5 78.5 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
5.5 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
387 251 167 118 89 70 52 34 17 4
Page 1 of 1Printed 12:50 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2000 Climate Zone: 17Design Option: Reduced High Level GlazD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
16.5 18.4 5.2 40.1 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
13.8 15.5 4.4 33.7 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.6 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars
230 148 98 68 50 39 30 22 13 6
Page 1 of 1Printed 12:41 am, 25/05/2015
AccuRate V1.1.4.1
Nationwide House EnergyRating Scheme
Project DetailsProject Name: Hadrian VillaFile Name: C:\Users\Naman Uppal\Desktop\hadrian house new.PROP o s t c o d e : 2500 Climate Zone: 56Design Option: Reduced High Level GlazD e s c r i p t i o n :
Client DetailsClient Name:Origination &UPhone:0000000000 Fax: Email:Postal Address:Site Address:Council submitted to (if known by assessor):
CALCULATED ENERGY REQUIREMENTS*Heating Cooling (sensible) Cooling (latent) Total Energy Units
30.0 15.8 3.6 49.5 MJ/m².annum* These energy requirements have been calculated using a standard set of occupant behaviours and so do not necessarily represent the usage pattern or lifestyleof the intended occupants. They should be used solely for the purposes of rating the building. They should not be used to infer actual energy consumption orrunning costs. The settings used for the simulation are shown in the building data report.
AREA-ADJUSTED ENERGY REQUIREMENTSHeating Cooling (sensible) Cooling (latent) Total Energy Units
25.0 13.2 3.0 41.2 MJ/m².annumConditioned floor area 90.9 m²
Star Rating
6.8 STARS
Area-adjusted star band score thresholds1 Star 2 Stars 3 Stars 4 Stars 5 Stars 6 Stars 7 Stars 8 Stars 9 Stars 10 Stars